VKM-GM Series VKM-G Series: DX-coil and Humidifier DX-coil

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

PCH0439

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
NEW
For any inquiries, contact your local distributor. DX-coil and humidifier VKM–GM series
DX-coil VKM–G series

H e a t R e cla im V e n tila tio n


V K M -G (M ) s e r ie s

Combined Air Conditioning and Ventilation


for Energy Efficiency and Comfort
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an
outdoor unit with anti-corrosion treatment.

The air conditioners manufactured All Daikin Industries locations About ISO 14001
by Daikin Industries have and subsidiaries in Japan have ISO 14001 is the standard defined by the
received ISO 9001 certification for received environmental International Organization for Standardization (ISO)
quality assurance. management system standard relating to environmental management systems.
ISO 14001 certification. Our group has been acknowledged by an
Certificate Number. JMI-0107
JQA-0495 internationally accredited compliance organisation
Daikin Industries, Ltd.
JQA-1452 Domestic Group as having an appropriate programme of
Certificate Number. EC99J2044 environmental protection procedures and activities
to meet the requirements of ISO 14001.

Dealer
Head Office:
Umeda Center Bldg., 4-12, Nakazaki-Nishi
2-chome, Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 18-1, Konan
2-chome, Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c All rights reserved
Printed in Japan 12/04/000

The specifications, designs, and information in this brochure are subject to change without notice.
The new HRV lineup features the DX-coil in response to
recently diversifying outdoor air introduction requirements.
Efficient outdoor air introduction and temperature adjustment to suit
conditions indoors. This is realized by heat exchanger and energy
saving technology unique to Daikin. The lineup now includes models
with a humidifier, responding to diversifying customer requirements. During
The features you expect from Daikin are there. The DX-coil contributes Efficient outdoor air introduction is possible simultaneous
to the prevention of cold airflow hitting people directly during heating HRV (VKM) introduces fresh outdoor air with heating and
minimum heat losses, while a wide variety of features
operation. High static pressure enhances design flexibility. All these respond to customer requirements.
humidifying
operation.
cutting-edge technologies are packed in an integrated compact body.
Daikin, the top provider of high quality indoor air, offers even more
comfortable environment.
atu res
New fe

Components of Indoor Air Quality


Humidifier
The lineup now includes models with a humidifier, in respone to diversifying
customer requirements.

DX-coil
Ventilation Humidification The HRV features DX-coil that contributes to the prevention of cold airflow
hitting people directly during heating operation, due to the after-cool, after-heat
HRV operations done beforehand.

(VKM)
High static pressure
Airflow Higher external static pressure means enhanced design flexibility.

Lineup
Type 500 800 1000
DX-Coil & Humidifier VKM50GMV1 VKM80GMV1 VKM100GMV1
DX-Coil VKM50GV1 VKM80GV1 VKM100GV1

1 2
A compact unit packed with
Daikin’s cutting-edge technologies
Exhaust Fan NEW Design flexibility
Heat Exchanger
Elements Efficient fan performance produces a high static pressure
Damper Motor
Improvements to the fan, including the Dramatically higher static pressure is
EA Damper use of multi-arc blades, a thinner scroll achieved due to improved fan
(Exhaust air to outdoors) and optimized fan scroll angle, help to performance. This reduces limitations
OA NEW DX-coil boost efficiency. on unit placement and allows more
(Direct expansion coil) flexibility in duct design.
(Fresh air from
outdoors) RA Higher static pressure Exchange efficiency
(Return air and reduced noise
Multi-arc blades
90 (%)
from room) The use of multiple, VKM50GMV1 Tempe
Operating air flow rate range

overlapping arc-shaped rature


400 excha 80
fan blades makes it Enth nge eff
alpy icienc
possible to optimize the exch y
chord length and blade- Enth ange
350 alpy efficie 70
outlet angle. This results ex c ncy (
in higher static pressure han heatin
ge e g )

External static pressure (Pa)


and quieter operation over ffici
the entire usage range. 300 enc
y (c 60 ø200
ooli Pipe
ng) length
Rotating currents
for reduced loss 250 80m

Air Supply Fan SA Resin scroll


Ultra High

(Supply air to room) The use of a thinner


scroll makes it possible
200
60m
Electronics Box to rectify the rotating
currents within the scroll.
(Control box) 150
Higher static pressure 40m
Higher static and reduced pressure loss High
pressure 100
NEW Double suction
The fan diameter
Fan scroll angle
In addition to increasing Low
20m
Humidifier element has been α
the scroll wrap angle θ
and boosting the static
50
Float switch increased and the pressure, the outflow
Utilizing the principle of capillary action, blade width angle α has been
Solenoid optimized to suit, optimized to reduce
0
water is permeated throughout the resulting in higher
θ 100 200 300 400 500 600 700
valve static pressure.
pressure loss in the
Air flow rate (m3/h)
humidifier element. The heated air from the outflow area.

DX-coil goes through the humidifier and


absorbs the moisture. water NEW Unique control system
AIRFLOW SA
Independent operation possible
The VRV II
outdoor unit
Independent operation of HRV (VKM) type
indoor unit is possible (on/off control only) by
Drain pan Drain connecting an optional remote controller. HRV (VKM)
Indoor unit
HRV (VKM)
Indoor unit
HRV (VKM)
Indoor unit
remote control remote control remote control

NEW Design flexibility


Operable outdoor temperature down to –15°C
Proprietary Developed HEP Element If the outdoor air suction temperature falls below –10°C, the unit changes to
The heat exchange element uses a High Operation of intermittent operation to prevent freezing of the heat exchanger element and dew
the heat exchanger element condensation within the unit.
Efficiency Paper (HEP) that has superior
moisture-absorption and humidifying
Outdoor Indoor
Intermittent operation
properties and doubles the current 30.6°C
62% RH
SA
27.4°C
A thermistor (standard equipment) within the unit detects the outdoor air
efficiency of moisture absorption. 63% RH temperature. Unit operation varies according to the detected temperature.
The heat exchange unit speedily recovers NEW
heat contained as latent heat (vapor).
SA

Quiet operation
Temperature Integrally-
The element is made of a material with RA and humidity formed liner
RA
superior flame-resistant properties and is 26°C
Structure

Features
50% RH
treated with an anti-molding agent. Reduced pressure loss and quieter operation internally lowers the noise output of the
32°C
70% RH Integrally-formed liner VKM50GMV1 system to 35/36 dB (220–240 V, 50 Hz).

3 4
NEW Design flexibility Easy installation + Space saving
Indoor unit connectable to up to 130% of the capacity Integrated system includes ventilation and
of the outdoor units humidifying operations
NEW Energy saving Rather than using separate
ventilation and humidifying
Night Purge Operation components, the system
● Conventional
system Outdoor
unit
HRV Humidifier
(Field supply)

incorporating HRV (VKM) integrates


Night purge is an energy-conserving function that works all functions, reducing
Standard indoor unit

at night when air conditioners are off. By ventilating the total number of indoor units
rooms containing office equipment that raises the room and facilitating a far simpler system. Ventilation, air conditioning,
and humidifying in a single system
temperature, night purge reduces the cooling load when The installation space becomes ● New system
air conditioners are turned on in the morning. smaller and the labor required for
The VRV II
outdoor unit

• Night purge only works to cool and if connected to Heat


Purge
installation and maintenance is Standard indoor unit
HRV (VKM)
Building Multi or VRV systems. sources
reduced significantly. One fewer
unit!

• Night purge is set to “off” in the factory settings, so if


you wish to use it, request your dealer to turn it on.
Easy operation
NEW Energy saving Ventilation, cooling/heating and humidifying
Automatic changeover to efficient operation patterns are possible with one remote controller.
Operation automatically changes to the optimum pattern to suit conditions.
Various air conditioner
Cooling In between (bypass ventilation) Heating functions can be managed
Exhaust fan Damper
Heat exchanger element
(heat recovery)
Heat exchanger element
(heat recovery) using a single remote The VRV II
control. This makes it easy outdoor unit

EA RA EA RA EA RA
to obtain high-quality and
Automatic Automatic
changeover changeover energy-efficient outdoor air HRV (VKM)
OA SA OA SA OA SA treatment. Link connection

Air supply fan DX-coil (cooling) DX-coil (heating) Humidifying


Indoor unit During group control operation,
remote control the unit has a capacity equivalent
to two standard indoor units. Up
to 16 standard indoor units can
NEW Energy saving
be connected at once.

Control of the HRV (VKM) type

Efficient outdoor air introduction with heat exchanger indoor unit is managed using the
remote controller of the standard

and cooling/heating operation


indoor units connected.
100 80
60
■ Indoor unit with outdoor air treatment
Using outdoor air, the temperature Outdoor air temperature Design flexibility
Heating and cooling in summer
Effect of full heat exchange
can be brought near room + Slim design
Relative humidity (%)

Effect of cooling
temperature with minimal cooling 40
heat recovery
capacity through the use of
outdoor air. + The slim design of only 387 mm in height
humidifying Indoor temperature during cooling enables installation inside ceilings with
Effect of
Indoor temperature during heating humidification
20 less than 407 mm of clearance.
Outdoor air temperature 387 mm
in winter Effect of heating
Effect of full heat exchange
Features

Features
–5 0 5 10 15 20 25 30 35 40
Dry bulb temperature (°CDB)

5 6
Model Line Up

Clean DX-Coil & Humidifier (VKM50GMV1, VKM80GMV1, VKM100GMV1)

Fresh-up Operation
The user can select between two fresh-up modes using the remote controller.

S upply F re s h-up: E x ha us t F re s h-up:


Raising the air supply maintains proper room pressure to Raising exhaust air decreases room pressure to
prevent back-flow of toilet/kitchen odors or moisture inflow. prevent the leaking of odors or floating bacteria into
other rooms.
Portion of fresh-up Air exhaust VKM50GMV1 VKM80GMV1 VKM100GMV1
operation HRV (VKM) Normal HRV (VKM)
ventilation fan
Air exhaust Air supply Exchange efficiency Exchange efficiency Exchange efficiency
90 (%) 90 (%) 90 (%)
Operating air flow rate range
VKM50GMV1 Temper VKM80GMV1 Operating air flow rate range
VKM100GMV1 Operating air flow rate range
400 ature ex 80 Tem
chang pera
Enth e effici Tempe 80 t 80
alpy e ency rature Ent ure
x ch a excha ha exc
Enth nge e Enth nge eff lpy han
350 alpy fficie 70 alpy icienc e
xch ge e
exc ncy (h e xch y fficie
han eatin ange En ang ncy
Sick room Floor area ge e g) 500 Enth effic 70 500 tha ee 70
alpy ffic

External static pressure (Pa)

External static pressure (Pa)

External static pressure (Pa)


fficie exch ienc lpy ien
300 ncy 60 ø200 ange y (he ex cy
Air supply Portion of (coo
ling Pipe effic
ienc
ating
) ch
an
(he
atin
) length y (co ge g)
exhaust 250 80m 400 oling 60
)
400 eff
ici 60
operation Ultra High en
cy ø250
(co
oli Pipe
200 300 300 ng
60m Ultra High 50 ) length
ø250 Ultra High
Pipe 100m
150
length
40m 200 200 80m
High 100m
100 High 80m 60m
High
ex. Office ex. Hospital Low 60m 40m
20m 100 100 Low
50 Low 40m
20m
20m
0 0 0
100 200 300 400 500 600 700 200 400 600 800 1000 200 400 600 800 1000 1200
Air flow rate (m3/h) Air flow rate (m3/h) Air flow rate (m3/h)

Preventing Dust from Falling with Directly Mounted Ducts

DX-Coil (VKM50GV1, VKM80GV1, VKM100GV1)

OFF Dust Blowing mode No dust is blown out.

W ith C om pe titors ' P roduc ts W ith the H R V (V K M )


When conventional total heat exchange units, which When the HRV (VKM) is operating independently, the fan
are independently operated using a dedicated remote in an interlocked indoor unit continues turning, so dust
controller, are directly connected by a duct, there is a does not fall from the air filter.
possibility of dust falling from the air filter of the indoor
unit when the air conditioner is OFF. VKM50GV1 VKM80GV1 VKM100GV1
Exchange efficiency Exchange efficiency Exchange efficiency
90 (%) 90 (%) 90 (%)
VKM50GV1 Operating air flow rate range
Temper VKM80GV1 Operating air flow rate range VKM100GV1 Operating air flow rate range
400 ature ex 80 Tem
A sign is displayed on the remote controller when the air filter needs cleaning.
Enth chang pera
alpy e effici Tempe 80 t 80
exch ency ra ture e Ent ure
ange xc ha exc
Enth effic Enth hange lpy han
350 alpy ienc 70 alpy e fficien e
xch ge e
exc y (he e xch cy fficie
han ating ange En ang ncy
g ef ) 500 Enth effic 70 500 tha e effi 70
alpy
External static pressure (Pa)

External static pressure (Pa)

External static pressure (Pa)


ficie exch ienc lpy cie
300 ncy
e (c 60 ø200 ange y (he ex nc y (h
ooli Pipe effic ating ch eat
ng) length ienc ) an ing
y (co ge )
250 80m 400 oling 60 400 eff 60
) ici
Ultra High en
cy ø250
(co
oli Pipe
200 300 300 ng
60m Ultra High 50 ) length
ø250 Ultra High
Pipe 100m
150
length
40m 200 200 80m
High 100m
100 High 80m 60m
Low
High

Model Line Up
20m 100 60m 100 40m
Low
50 Low 40m
20m
20m
0 0 0
100 200 300 400 500 600 700 200 400 600 800 1000 200 400 600 800 1000 1200
Air flow rate (m3/h) Air flow rate (m3/h) Air flow rate (m3/h)

7 8
Specifications
Type VKM50GMV1 VKM80GMV1 VKM100GMV1 VKM50GV1 VKM80GV1 VKM100GV1
Refrigerant R410A
Power Supply 1 phase, 220–240 V, 50 Hz
Dimensions Ultra-high
Air flow rate (m3/h) 500 750 950 500 750 950
Static pressure (Pa) 160 140 110 180 170 150
Air flow rate (m3/h) 500 750 950 500 750 950
VKM50G(M)V1 Air Flow Rate & Static High
Pressure (Note 7) Static pressure (Pa) 120 90 70 150 120 100
Supply air fan Damper plate Direct expansion coil Feed water tank *1 Hanger bracket
387
1688
4-14 x 40 oval hole Air flow rate (m3/h) 440 640 820 440 640 820
Exhaust air fan 160 Low
235 Static pressure (Pa) 110 70 60 110 80 70

20
Ultra-high (W) 560 620 670 560 620 670
Heat

164
248

RA exchange High (W) 490 560 570 490 560 570


EA Return air from room mode Low (W) 420 470 480 420 470 480
Exhaust air to outdoors 210 Power Consumption

420
832

878
Ultra-high (W) 560 620 670 560 620 670
431

Bypass
SA High (W) 490 560 570 490 560 570
mode
Supply air to room Low (W) 420 470 480 420 470 480

248
OA
153

34
42
Fresh air from outdoors
(Outdoor air) Fan Motor Type Sirroco Fan

130
20
0.280 × 2 0.280 × 2 0.280 × 2

60
Motor Output kW 0.280 × 2 0.280 × 2 0.280 × 2
More than 600

153 160 Solenoid valve *1 28


150– 250

Maintenance Cover Humidifier Ultra-high (dB) 37/37.5/38 38.5/39/40 39/39.5/40 38/38.5/39 40/41/41.5 40/40.5/41
(Natural evaporative type) *1 94 Heat
Control box exchange High (dB) 35/35.5/36 36/37/37.5 37/37.5/38 36/36.5/37 37.5/38/39 38/38.5/39
Inspection Inspection Maintenance cover 144
(For humidifier) *1 mode Low (dB) 33/34/35.5 34/34.5/35.5 33.5/34.5/35.5 34.5/36/37 35/36/36.5
hatch hatch 210 Sound Level (Note 5) 32/33/34
(220–240 V) Ultra-high (dB) 37/37.5/38 38.5/39/40 39/39.5/40 38/38.5/39 40/41/41.5 40/40.5/41
Maintenance space for the heat exchanger elements 360 (In case of ■450 inspection hatch)
the air filters, fans (and humidifier) 140 (In case of ■600 inspection hatch) Bypass
High (dB) 35/35.5/36 36/37/37.5 37/37.5/38 36/36.5/37 37.5/38/39 38/38.5/39
mode
Low (dB) 32/33/34 33/34/35.5 34/34.5/35.5 33.5/34.5/35.5 34.5/36/37 35/36/36.5
137 1764 137
10 515 Feed water connection port *1 Humidification Capacity (Note 4) (kg/h) 2.7 4.0 5.4 — — —
High efficiency filter (option) 322 (ø6.4C1220T)
102 Ultra-high (%) 76 78 74 76 78 74
Temp. Exchange 76 78 74
High (%) 76 78 74
ø196 Efficiency
ø250 Low (%) 77.5 79 76.5 77.5 79 76.5
Ultra-high (%) 64 66 62 64 66 62
* The specification subject to change without notice. Enthalpy Exchange High (%) 64 66 62 64 66 62
Heat exchanger elements Gas pipe
connection * Be sure to provide two inspection hatch. Efficiency (Cooling)
Air filters (ø12.7) (■450 or ■600) at the service side of filters and elements. Low (%) 67 68 66 67 68 66
* The high effciency filter (option) can be attached to the SA surface
Liquid pipe connection Drain outlet
(ø6.4) (PT3/4 male screw)
of the heat exchanger elements. Ultra-high (%) 67 71 65 67 71 65
Note *1. VKM50GMV1 only. Enthalpy Exchange High (%) 67 71 65 67 71 65
Efficiency (Heating)
Low (%) 69 73 69 69 73 69
VKM80/100G(M)V1
Casing Galvanized Steel Plate
Supply air fan Damper plate Direct expansion coil Feed water tank *2 Hanger bracket
387 4-14 x 40 oval hole Insulating Material Self-Extinguishable Urethane Foam
1688
160
235 Exhaust air fan Heat Exchanging System Air to Air Cross Flow Tot al Heat (Sensible + Latent Heat) Exchange
20

Heat Exchanger Element Specially Processed Nonflammable Paper


183

RA Air Filter Multidirectional Fibrous Fleeces


439

Return air from room DX-coil Cooling (Note 2) (kW) 2.8 4.5 5.6 2.8 4.5 5.6
Capacity Heating (Note 3) (kW) 3.2 5.0 6.3 3.2 5.0 6.3
EA
592

Exhaust air to outdoors Height (mm) 387 387 387 387 387 387
1214

1262

Dimensions Width (mm) 1764 1764 1764 1764 1764 1764


622

SA
Depth (mm) 832 1214 1214 832 1214 1214
Supply air to room
210 Connection Duct Diameter (mm) ø200 ø250 ø200 ø250
439

OA
Net (kg) 102 120 125 96 109 114
153

Fresh air from outdoors Machine Weight


34

42

(Outdoor air)
Gross (Note 8) (kg) 107 129 134 —
130
20
60

Around Unit 0°C–40°C DB, 80%RH or less


More than 600

153 160 Solenoid valve *2 28


150– 250

Maintenance Cover Humidifier Unit Ambient Condition OA (Note 9) -15°C–40°C DB, 80%RH or less
(Natural evaporative type) *2 94
Control box
Inspection Inspection Maintenance cover *2 RA (Note 9) 0°C–40°C DB, 80%RH or less
(For humidifier) 144
hatch hatch Connectable outdoor units RXYQ5–48MY1B, RXYQ5–48MAY1, REYQ8–48MY1B
210
Maintenance space for the heat exchanger elements 360 (In case of ■450 inspection hatch) Note: 1. Cooling and heating capacities are based on the following conditions. Fan is based 7. Air flow rate can be changed over to Low mode or High mode.
the air filters, fans (and humidifier) 140 (In case of ■600 inspection hatch) on High and Ultra-high. 8. In case of holding full water in humidifier.
The figures in the parenthesis indicate the heat reclaimed from the heat recovery 9. OA: fresh air from outdoor. RA: return air from room.
89 1764 89 ventilator. 10. Specifications, design and information here are subject to change without notice.
10 515 When calculating the capacity as indoor units, use the following figures: 11. Power consumption and efficiency depend on the above value of air flow rate.
Feed water connection port *2
322 VKM50GMV1/GV1: 3.5 kW, VKM80GMV1/GV1: 5.6 kW, VKM100GMV1/GV1: 7.0 kW 12. Temperature exchange efficiency is the mean value for Cooling and Heating.
High efficiency filter (option) (ø6.4C1220T)
102 2. Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB Efficiency is measured under the following condition: Ratio of rated external
3. Indoor temperature: 20°C DB, Outdoor temperature: 7°C DB, 6°C WB static pressure outdoor to indoor is kept constant at 7 to 1.
4. Humidifying capacity is based on the following conditions:
Feed clean water (city water, tap water or equivalent). Dirty water may clog the
ø246

ø263

Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB
5. The operating sound measured at the point 1.5 m below the center of the unit is valve or cause dirt deposits in the water container, resulting in poor humidifier
converted to that measured in an anechoic chambar built in accordance with the JIS performance. (Never use any cooling tower water and heating-purpose water.)

Specifications
C 1502 conditions. The actual operating sound varies depending on the surrounding Also, if the supply water is hard water, use a water softener because of short life.
Dimensions

* The specification subject to change without notice. conditions (near running unit’s sound, reflected sound and so on) and is normally * Life of humidifying element is about 3 years (4,000 hours) under the supply water
Heat exchanger elements Gas pipe
connection * Be sure to provide two inspection hatch. higher than this value. conditions of hardness: 150 mg/l. (Life of humidifying element is about 1 year
Air filters (ø12.7) (■450 or ■600) at the service side of filters and elements. For operation in a quiet room, it is required to take measures to lower the sound. (1,500 hours) under the supply water conditions of hardness: 400 mg/l.)
Liquid pipe connection Drain outlet
* The high effciency filter (option) can be attached to the SA surface For details, refer to the Engineering data. Annual operating hours: 10 hours/day x 26 days/month x 5 months = 1,300 hours
of the heat exchanger elements. 6. The noise level at the air discharge port is about 8–11 dB or higher than the unit’s
(ø6.4) (PT3/4 male screw)
Note *2. VKM80/100GMV1 only. operating sound.
For operation in a quiet room, it is required to take measures to lower the sound.

9 10
Centralized Control of Air Conditioning and Ventilation

Operation of the air conditioner using the remote controller is interlocked with
operation of the HRV, greatly simplifying overall system control. The same remote
Centr alized Contr ol System
controller completely centralizes air conditioning and ventilation operations, so no By combining the (optional) centralized control equipment below, the user can achieve a wide range of
HRV remote controller installation work is necessary. Using a centralized remote comprehensive centralized control systems for air conditioning and ventilation.
controller also frees the user to choose from a wide range of control systems that
integrate air conditioning and ventilation. By incorporating a variety of centralized
control equipment, the user can build a large, high-grade centralized control system. Centralized Controller (DCS302C61)
• 64 groups (zones) of indoor units can be
controlled individually same as LCD Remote controller.
Outdoor Unit • Max.64 groups (128 indoor units controllable)
• Max. 128 groups (128 indoor units) are controllable by using 2 central remote
controllers, which can control from 2 different places.
• Zone control
Indoor • Malfunction code display
Unit
• Max. wiring length 1,000 m (Total : 2,000 m)
• Combination with Unified ON/OFF controller, schedule timer and BMS system
• Airflow volume and direction can be controlled individually for indoor units in
HRV (VKM) each group operation.
• Ventilation volume and mode can be controlled for Heat Reclaim Ventilation
Remote Controller (VKM).
• Up to 4 Operation/Stop pairs can be set per day by connecting a schedule timer.

Oper ations and Contr ol with the Air Conditioning Remote Contr oller
Unified ON/OFF Controller (DCS301B61)
• Simultaneous ON/OFF of the HRV (VKM) and air conditioner • One unit can turn ON/OFF up to 16 groups (128 units) of HRV (VKM) and air
conditioner units individually or in a batch.
• Independent operation of the HRV (VKM)
• Lamps display operation and failure status of the connected HRV (VKM) and air
• Airflow rate switching (initial setting) conditioner units.
• Ventilation mode switching (initial setting)
• Up to 8 units can be linked to allow centralized control of up to 128 units.
• Self-diagnosis functions
• Filter sign display and reset
• Timer settings (simultaneous control with air conditioner)
• Fresh-up mode switching (Selectable: supply rich mode, exhaust
rich mode; Initial setting)

Schedule Timer (DST301B61)


• One unit can control the operation of up to 128 HRV (VKM) and air conditioner
A Var iety of Contr ol Systems That Can Be Contr olled Using Only the units on a weekly schedule.
• Can set two ON/OFF operations per day for a period of one week.
Air Conditioner Remote Contr oller
Centralized Control of Air Conditioning and Ventilation

Centralized Control of Air Conditioning and Ventilation


Group Control
Air conditioner
*1
Up to 16
One air conditioner remote controller simultaneously controls up to units
HRV
16 air conditioner and HRV (VKM) units. (VKM)
Air conditioner Up to 500 m
*1: Count HRV (VKM) unit as two air conditioners. For details, see Table 1 on page 13. remote controller

Air conditioner

2-Remote-Controller Control
Allows control of air conditioner and HRV units from two places by HRV Number of units that can
connecting two air conditioner remote controllers. (Group control Air conditioner Up to 500 m
(VKM)
be connected per system
possible) remote controller (No. 2)
Centralized controller 2 units
Air conditioner
remote controller (No. 1)
Unified ON/OFF controller 8 units
Air conditioner
Schedule timer 1 unit
Long-distance Remote Control
Operation control from afar, i.e., a distant control room, is possible HRV
(VKM)
thanks to wiring of up to 500 m. (2-remote-controller control Up to 500 m

possible) Air conditioner


remote controller
2-remote-controller control possible

11 12
Image of group
HRV (VKM) Control Systems control system

Various Control Systems According to Applications and Conditions


Standard
system

Combined
system

Independent
system

System Construction Necessary System Construction Necessary


System Characteristics Accessories System Characteristics Accessories
Independent

Batch/Individual Control System


Independent Operation System

Operation

[Unified ON/OFF Controller]


• Independent operation of
• One controller can control
HRV (VKM) HRV (VKM) is possible. VRV remote
ON/OFF the “ON/OFF” operation of
• VRV remote controller controller controller 16 groups of units
can be used. or schedule

Air Conditioning Interlocked Centralized Control System


Air conditioner
remote controller Indoor unit HRV (VKM) timer collectively or individually.
• Up to 8 controllers can be Unified ON/OFF
Air conditioner Air conditioner
remote controller remote controller installed in one centralized controller or
Simultaneous Operation

transmission line (in one schedule timer, VRV


HRV (VKM) HRV (VKM) system), which enables remote controller
• Operation is possible control of up to 128 groups.
of Multiple Units

using 2 remote When necessary,


(16 groups x 8 = 128
controllers. centralized controller
groups)
• Multiple HRV (VKM) units VRV remote Indoor unit HRV (VKM) [Schedule Timer]
can be simultaneously controller • One schedule timer can
Air conditioner Air conditioner remote controlled in batch. Air conditioner control the weekly schedule
remote controller
remote controller controller (No. 2) [Up to 8 HRV (VKM) units of up to 128 units.
(No. 1)
can be connected.]
Air Conditioning Interlocked Control (VRV, SkyAir) System

Zone Control System


Indoor unit HRV (VKM) [Centralized Controller]
• Multiple VRV indoor units

Zone 1
or HRV (VKM) units can Indoor unit HRV (VKM) Centralized • The centralized controller Centralized
controller provides setting and
be connected and controller, VRV
Air conditioner Air conditioner monitoring functions, and
controlled in batch, with remote controller remote controller remote controller
Standard System

interlocked operation of can control up to 128 VRV


and HRV (VKM) units When necessary,
Air conditioner HRV (VKM)s and air
remote controller collectively or individually. unified ON/OFF
conditioners by using the
controller or
air conditioner remote VRV remote • Multiple groups can be
Table 1 Connectable indoor units schedule timer
controller. controlled within the same

Zone 2
controller
HRV (VKM) 0 1 2 3 • The HRV (VKM) unit Indoor unit HRV (VKM) zone.
VRV Up to 16 Up to 14 Up to 12 Up to 10 can also be operated
independently using the Air conditioner
4 5 6 7 8 remote controller
remote controller for the
Up to 8 Up to 6 Up to 4 Up to 2 0 indoor unit, even if the
Note: The HRV (VKM) uses two remote control addresses per indoor unit is not in
unit, and the number of units that can be group controlled operation.
are shown above.
Major HRV Control Systems

Major HRV Control Systems


13 14
Option

Installation of Optional Pr oducts (For VKM50G (M) V1, VKM80G (M) V1, VKM100G (M) V1)
PC board adaptor for heater control kit (BRP4A50)
When the installation of an electric heater is required in a cold region, this adaptor with an internal timer function eliminates the
Air suction/discharge grille (Option) complicated timer connecting work that was necessary with conventional heaters.
Notes when installing
Flexible duct Indoor Outdoor
Examine fully the installation place and
(Option) specification for using the electric heater based on
RA the standard and regulation of each country.
High efficient filter RA EA
Supply the electric heater and safety production
(Option) HRV
(VKM) devices such as a relay and a thermostat, etc., of
SA SA
Heater
control kit OA which qualities satisfy the standerd and regulation
(Field supply)
Temperature thermo.
of each country at site.
(Field supply) Use a non-inflammable connecting duct to the
BRP4A50 (ON when the temperature
Round hood is at or below -10°C) electric heater. Be sure to allow 2 m or more
Branch duct between the electric heater and HRV (VKM) for
(Field supply) Temperature thermo. (Field supply)
safety.
(Field supply) (OFF when the temperature is at or more than 5°C) Power supply (Field supply)
Relay box For the HRV (VKM) units, use a different power
Silencer (Option) supply from that of the electric heater and install a
SA circuit breaker for each.
Duct
(Field supply)

Thermal insulation material (Field supply)


EA
OA
Applicable model VKM50/80/100G(M)V1
Member
Remote controller BRC1A62 *1
Centralized Central remote controller DCS302C61
controlling Unified ON/OFF controller DCS301B61
device Schedule timer DST301B61
Wiring adaptor for electrical
Controlling device

KRP2A61
appendices
For humidifier running ON signal output KRP50-2
PC Board Adaptor

Installation box for adaptor PCB KRP50-2A90 (Mounted electric component assy of HRV)
For heater control kit BRP4A50

Type FXLQ-M
For wiring (indoor unit of VRV) FXCQ-M FXFQ-M FXKQ-M FXSQ-M FXMQ-M FXHQ-M FXAQ-M FXDQ-N FXNQ-M FXZQ-M

KRP1B61 KRP1B59 KRP1B61 KRP1B3 — KRP1B56 KRP1B61 KRP1B57


Installation box for adaptor PCB Notes 2, 3 Notes 2, 3 — Note 5 — Note 3 Notes 2, 3 Notes 4, 6 — Notes 4, 6
KRP1B96 KRP1D98 KRP4A91 KRP1C93 KRP4A93 KRP1B101 KRP1B101
Note: 1. Installation box is necessary for each adaptor marked . 5. Installation box is necessary for second adaptor.
2. Up to 2 adaptors can be fixed for each installation box. 6. Installation box is necessary for each adaptor.
3. Only one installation box can be installed for each indoor unit. 7. *1 Necessary when operating HRV (VKM) independently. When operating interlocked
4. Up to 2 installation boxes can be installed for each indoor unit. with other air conditioners, use the remote controllers of the air conditioners.

Applicable model VKM50G(M)V1 VKM80G(M)V1 VKM100G(M)V1


Member
— K-DDM24B100
Additional function

Silencer
Nominal pipe diameter (mm) — 250 mm
Air suction/ White K-DGL200B K-DGL250B
Discharge grille Nominal pipe diameter (mm) 200 250
High efficiency filter YAFF241G80M YAFF241G100M
Air filter for replacement YAFF242G80M YAFF241G100M
Flexible duct (1 m) K-FDS201C K-FDS251C
Flexible duct (2 m) K-FDS202B K-FDS252C
— YDFA25A1
Duct adaptor
Nominal pipe diameter (mm) — 250

Remote Controller Centralized controller Unified ON/OFF controller Schedule timer

Silencer Air suction/discharge grille Flexible duct Duct adaptor


(Noise suppression type) (Noise suppression type)

15 16