Symmetricom NTS-200 GPS Network Time Server Approved for Use with DeltaV
Systems
Affected Products:
Product Line Category Device Version
DeltaV Alliance Products Symmetricom Time Server 200 & DeltaV
The Symmetricom NTS-200 GPS Network Time Server (NTS) with software build 182-9004v008 has been tested with
DeltaV and was found acceptable for use. Furthermore, the NTS-200, which is part of the Emerson Process Management
Alliance program, has replaced the Datum/Symmetricom TymServe 2100, which is no longer available.
Refer to the NTS-200-GPS User's Manual for general installation and configuration information. Refer to the next sections
of this article for the specific network settings required for configuring a Network Time Server to be used with DeltaV
systems.
After establishing an initial IP configuration using the front panel, use a web browser, such as Microsoft Internet Explorer,
to configure the required network and timing parameters. Use the IP addresses and subnet mask described in the
following sections to set up the time server for broadcast mode.
IP Addresses
The DeltaV system supports both a primary and an optional backup Network Time Server on the control network. The
Network Time Servers can be attached to either the primary or the secondary control network. It is recommended that the
primary Network Time Server be attached to the primary control network and the backup Network Time Server be
attached to the secondary control network in a redundant control network system. If the system is simplex (has only a
primary control network), attach both Network Time Servers to the primary control network.
For the primary Network Time Server, use the following IP addresses:
Subnet Mask
The subnet mask for the Network Time Servers attached to the control network is 255.254.0.0.
The subnet mask for the Network Time Servers attached to the remote network(s) must be assigned by your network
administrator.
The route (default gateway for the devices on a different subnet) is required and can be left blank or assigned all zeros.
Broadcast Mode
To work with the DeltaV System, the Network Time Server must be set up for broadcast mode and the broadcast interval
must be set to 16 seconds. Establish a web browser session between the setup computer and the Network Time Server.
In the NTP settings page, uncomment and modify the broadcast line to appear as follows:
Broadcast 255.255.255.255 minpoll 4
See section 3.1.7 of the NTS-200 Users Manual for details of this setting.
Note NTS-200 is no longer available for purchase. New systems installing Time Server must use the recently
qualified Network Time Server Symmetricom NTS-250. See details in KBA NA-0600-0065: Symmetricom
SyncServer S250 GPS Network Time Server Is Approved for Use with DeltaV Systems
Alliance Program Product Technical Support: Hardware and Software tested by Emerson, but found in Emerson's Price
List or Complimentary Products List is categorized as "non-standard". Alliance Program products are not Emerson
products and fall in the non-standard category. Specific Alliance Program products are tested for compatibility with
specific DeltaV system versions. Emerson supports the interoperability of Alliance Program non-standard hardware and
software with DeltaV systems, but with constraints. If the Emerson Process Management Global Service Center or other
support organization determines the site issues are with the non-standard tested software or hardware, the user will be
requested to contact the third party vendor for further support. Alternatively, Emerson will use reasonable commercial
efforts to provide fee based support services upon the user’s request. Standard Foundation Support Technical Support
rd
covers system issues related to standard product only. Under the Alliance Program, specific versions of the 3 party
product as well as that of DeltaV are absolutely required. If the requirements expand beyond the constraints specified for
the specific Alliance Product, incremental testing, which is chargeable to the customer, will be required to re-qualify.
Disclaimer of Warranties: THERE ARE NO REPRESENTATIONS OR WARRANTIES OF ANY KIND, EXPRESS OR
IMPLIED, AS TO MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSE, OR ANY OTHER MATTER WITH
RESPECT TO ANY OF THE SERVICES OFFERED HEREUNDER.
Limitation of Liability: IN NO EVENT, REGARDLESS OF THE FORM OF THE CLAIM OR CAUSE OF ACTION
(WHETHER BASED IN CONTRACT, INFRINGEMENT, NEGLIGENCE, STRICT LIABILITY, OTHER TORT OR
OTHERWISE), SHALL EMERSON PROCESS MANAGEMENT'S LIABILITY TO CUSTOMER EXCEED THE PRICE TO
CUSTOMER OF THE SPECIFIC SERVICES PROVIDED BY EMERSON PROCESS MANAGMENT GIVING RISE TO
THE CLAIM OR CAUSE OF ACTION. CUSTOMER AGREES THAT IN NO EVENT SHALL EMERSON PROCESS
MANAGEMENT'S LIABILITY TO CUSTOMER EXTEND TO INCLUDE INCIDENTAL, CONSEQUENTIAL OR PUNITIVE
DAMAGES. THE TERM "CONSEQUENTIAL DAMAGES" SHALL INCLUDE, BUT NOT BE LIMITED TO, LOSS OF
ANTICIPATED PROFITS, LOSS OF USE, LOSS OF REVENUE AND COST OF CAPITAL.
©Emerson Automation Solutions 2009-2016. All rights reserved. For Emerson Automation Solutions trademarks and service marks, click this link to
see trademarks. All other marks are properties of their respective owners. The contents of this publication are presented for informational p urposes
only, and while every effort has been made to ensure their accuracy, they are not to be construed as warrantees or guarantees, express or implied,
regarding the products or services described herein or their use or applicability. All sales are governed by our terms and co nditions, which are
available on request. We reserve the right to modify or improve the de sign or specification of such products at any time without notice.
View Emerson Products and Services: Click This Link