Key Plan:

TYPICAL ITEM OF DUCTWORK C'


SYSTEM REQUIRING ACCESS N Red Line
(FD, MFSD & MD)

(MAKKAH)
MHV_AG_+0.00_F.F.L._AT GRADE LEVEL Green Line
°
.90 Blue Line
300x400
300x400 0 252
450x450

ISOMETRIC VIEW OF EAF-CL-1A


TYPICAL ACCESS 450x450

450x450
0 DOOR LOCATION
15MM

450x450
EAF-CL-1B
ACCESS DOOR ON THE UNDERSIDE 450x450
350x350 350x350
OF DUCT WHERE POSSIBLE Gold Line
(OR SIDE OF DUCT WHERE NOT)
Note MHV_AG_+0.00_F.F.L._AT GRADE LEVEL Legends:
EAF-CL-2A LEGENDS
Access door to be located opposite of 0 FD FIRE DAMPER ELB ELBOW FIRE RATED (FR)
EAF-CL-2B M MSFD MOTORISED SMOKE FIRE DAMPER

4875
airflow direction for Fire Damper and on the M MD MOTORISED DAMPER F/T/A/B FROM/TO/ABOVE/BELOW

3825
VOLUME CONTROL DAMPER

3725

3725
450x450 VCD
side of actuator motor for the MSFD/ MD NON RETURN DAMPER

3450
NRD
SUPPLY GRILL RETURN GRILL EXHAUST GRILL

2975
2925

2925
(SAG) (RAG) (EAG)
AIR/ FRESH AIR HANDLING UNIT (AHU/FAHU)

Duct Access Door COMPUTER ROOM AIR CONDITIONING (CRAC/ CRAH)

FAN COIL UNITS (DXFCU/CHFCU)


1 : 80 FAN FAG FRESH AIR GRILL WM WIREMESH
SILENCER
COLOR CODE DESCRIPTION
PRE-COOLED FRESH AIR DUCT (PAD)
MHV_CL_-5.00_F.F.L._CONCOURSE LEVEL
SUPPLY AIR DUCT (SAD)
-5000 EAF-CL-3A RETURN AIR DUCT (RAD)
EXHAUST AIR DUCT (EAD)
EAF-CL-3B TOILET EXHAUST DUCT (TED)
MECHANICAL EQUIPMENT

400x700
175

400x700
1580
825 650 900 780 1655 1840 950 400 650 Notes:
1400x900 RAD 1. All dimensions are in MM unless otherwise indicated.

400x700
2 Nos. FAN STACKED BOD: 2600 2. All levels are referred from CONCOURSE FFL (-5.00 M) unless otherwise indicated.
5782
250x250 EAD Section EAF CL 400x700 400x700 3. All supply air, return air, tempered fresh air & exhaust ducts routed through heat recovery units shall be insulated as per project specifications
7 8
EAF-CL-3A
700x400 EAD
BOD: 3650
S3 1 : 50
and approved material submittal.
4. Ducts having FD, MD & MFSD shall be provided with access doors in ducts & ceilings

480
BOD: 480 EAF-CL-3B 700x300 TED
650x400 RAD BOD: 3650 MHV_CL_-5.00_F.F.L._CONCOURSE LEVEL 5. Duct sizes mentioned on plans are clear sizes, excluding the thickness of insulation or lining.
BOD: 3550 1250x900 SAD 6. All ducts passing through slab shall be provided with fire dampers.
300x500 EAD BOD: 3025 700x400 EAD 1100x900 RAD -5000 7. Provide 6 MM square mesh screen on all free duct and wall openings.
BOD: 480 BOD: 2600 8. Flexible duct connections to any air outlet shall not exceed a length of 1.50 meters and should be straightened as much as possible to achieve
BOD: 1915 600x500 PAD
1400x900 SAD 400x300 TED minimum resistance to air flow.
500x300 EAD BOD: 3400 9. Integrate flexible connections or rollers supports for MEP services which run through the structural expansion joints.
BOD: 3650 BOD: 3025 BOD: 3650
Section EAF 10. For Schedule and details of supports refer to standard detail drawings M0..-AA-36750, 51 & 52.
11. All Fire Dampers are curtain type with blades outside the air stream. For installation details,sizes of curtain etc, Refer to the respective material
S4 1 : 50
submittal.
12. Shop drawings along with Manufacturer/Supplier Fabrication drawings that includes tags, elbow, radius and flanges shall be referred for site
installation.
7
672
1002
100

13. For access door Location on the Duct follow standard installation detail adjust where necessary in line with site condition. Location of access
door for reflected ceiling (RC) will be provided under the respective Architectural Layout drawings.
D D 14. For schedule of MD & MFSD refer to M0…-AA-26643, 44 & 45.
15. Install opposed blade volume dampers on all duct branches and branch take-offs and wherever required for proper balancing of air.
S4 16. Bellmouth openings for return air shall be sized at a maximum velocity of 2.5 meters per second, unless noted otherwise.
36662_1 17. Wall openings for return air shall be sized at a maximum velocity of 1.25 meters per second, unless noted otherwise.
500x750 PAD 500x800 PAD 18. Wall and roof openings shall be 13 MM larger all around than duct or fire damper sleeve passing through wall or slab and the void shall be filled with
250x250 EAD

1795
BOD: 4650 BOD: 4425 non-combustible material as per approved material submittal
BOD: 2225 400x700 EAD 19. Provide sleeves where pipes/ducts penetrate walls and slabs.
650x400 RAD BOD: 1750
BOD: 2850 250x250 EAD MHV_AG_+0.00_F.F.L._AT GRADE LEVEL 20. The room thermostats/ temperature sensor shall be mounted on the wall @ 1.5 meters from finished floor or as indicated in Architectural drawings.
21. Provide access panels in the ceiling for all FD, MD, MFSD, VAV boxes, FCU control valves and other concealed equipment.
600x500 PAD BOD: 4075 0 22. Fresh air intake shall be provided with sand trap louver with face velocity not exceeding 1 m/s or as per manufacturer recommendation to achieve
1137

BOD: 3400 the stipulated efficiency.


3770

444
300x400 RAD 400x300 EAD Reference Documents:
700x300 TED BOD: 4375 BOD: 4150
BOD: 4875
751

2000x700 SED FR

1014
750x450 EAD
1490

BOD: 4550 1100x900 RAD


BOD: 3450
500x800 PAD 200x300 EAD
900x1250 SAD
BOD: 3600 BOD: 3900
BOD: 885 CHFCU-CL-HVAC-1 0 5 [m]
1 2 3 4
450x450 TED 150x150 PAD 550x700 RAD

4425
BOD: 4875 BOD: 3550 BOD: 1863 Scale: 1:100
310 1725

4650

4650
400x300 TED

4597

4425
Drawing Revision History:

4375
BOD: 4875

3600
2738

3550
2000x700 SED FR 350x350 TED 500x800 PAD
700x400 EAD 400x300 TED FAHU-CL-1 0.3 ISSUED FOR APPROVAL JKU 25/11/2017

3900
BOD: 4000 BOD: 3825 BOD: 1735
BOD: 4425 BOD: 4875 0.2 ISSUED FOR APPROVAL 15/07/2017
400x650 RAD 2 Nos. FAN STACKED JKU
1400x900 RAD
0.1 ISSUED FOR APPROVAL 03/07/2017

1863
BOD: 2725 EAF-CL-1A JKU

1735
BOD: 2360
450x450 TED T/A Rev Description App Date
EAF-CL-1B
500x450 EAD T/A Purpose of Issue:
700x400 EAD T/A 750x450 EAD

674
500x800 PAD
03 - ISSUED FOR APPROVAL

549
450x450 TED BOD: 549
BOD: 4375 MHV_CL_-5.00_F.F.L._CONCOURSE LEVEL BOD: 674
AHU-PL-1 400x300 TED
AHU-CL-1 -5000 Design Validation:
BOD: 4875
350x350 TED SONO Reference: Date:
400x650 RAD
BOD: 3075
400x400 EAD FR T/A BOD: 3825
FAHU-CL-1 DVE Reference: Date:
700x400 EAD T/A
750x450 EAD T/A
400x400 EAD FR
BOD: 4900 S1 1 : 50
Client:
3400

700x400 EAD
450x450 TED T/A
750x450 EAD
BOD: 4900
BOD: 4900 7
Qatar Railways Company
325 450x450 TED
325 868 450x450 TED 600x500 PAD 700x2000 SED FR
P.O. Box 29988
BOD: 4428 BOD: 3775 700x2000 SED FR
400x300 TED BOD: 4750
BOD: 4000
BOD: 4550 Doha - Qatar
450
BOD: 4875
775 575 535 615 1610
1171

110 2 Nos. FAN STACKED MHV_AG_+0.00_F.F.L._AT GRADE LEVEL


400x400 EAD FR 500x450 EAD
BOD: 4048 790
BOD: 4900 EAF-CL-2A 0 Contractor Name & Logo:
S2 700x400 EAD 385 200x200 PAD
700x400 PAD EAF-CL-2B BOD: 4115
BOD: 4900

RnR
BOD: 2113 36662_1
620

300x200 EAD
400x650 RAD BOD: 4525 450x450 TED
BOD: 3075 BOD: 4800
FD 3306 750x450 EAD 450x500 EAD
450x450 TED
500x450 EAD BOD: 4900 BOD: 4048
BOD: 3775 700x2000 SED FR
400x400 EAD FR BOD: 4325 400x700 EAD Project:
BOD: 4900 400x300 EAD BOD: 3650
750x500 PAD BOD: 3658 BOD: 4875
HIA T1 - METRO STATION
1852
1820

700x400 PAD 300x200 EAD BOD: 1778 800x500 PAD


BOD: 4750 750x450 EAD
BOD: 3900 BOD: 1735
AND SWITCHBOX
4642

150x150 PAD
HVAC Room BOD: 4900
BOD: 3825

4550
750x500 PAD S3 Discipline:
4000 HVAC SERVICES
BOD: 4650 450x750 EAD
50

3650

36662_1
BOD: 549
891

800x500 PAD
BOD: 3600 T 400x300 EAD Drawing Title:
SHOP DRAWING
1413

FAHU-CL-1 BOD: 4150


150x150 PAD
BOD: 3550 AHU-PL-1 MHV DUCT LAYOUT
1000

400x300 RAD 340 S1 1224


640

BOD: 4375 125 36662_1 AHU-CL-1 CONCOURSE LEVEL PLANT ROOM


337

852 CHFCU-CL-HVAC-1
C C
420

MHV_CL_-5.00_F.F.L._CONCOURSE LEVEL
1000

400x400 EAD FR Originator: Contractor:


BOD: 4200 -5000 Drawn I.A. 03/07/2017 Checked ESC
1903 FD FD FD FD
Checked M.A. 03/07/2017
700x550 RAD 750x500 PAD 400x300 EAD
BOD: 1863 800x500 PAD Approved J.H. 03/07/2017 Approved PSE
BOD: 4150
700x400 PAD BOD: 4450 BOD: 4425 CL_100_Plant Room_HVAC 1 As indicated
BOD: 4550
1 AHU-CL-1ww
Scale: Sheet Size: A1
7 1 :850
2119 988 2613 2231
900 3606 2170 170
0 2035 S2 1 : 50
Drawing No.

M013-RnR-MHV-DWG-REST020-CL-36662_1
Rev:

0.3
THE DRAWING AND ANY INFORMATION OR DESCRIPTIVE MATTER SET OUT HERE ON IS LICENSED TO THE QATAR RAILWAYS COMPANY AND IS CONFIDENTIAL AND SUBJECT TO COPYRIGHT.IT MUST NOT BE DISLOSAED,LOANED,COPIED OR USED FOR MANUFACTURING,TENDERING OR FOR ANY OTHER PURPOSE WITHOUT WRITTEN PERMISSION.© QATAR RAILWAYS COMPANY.