7SR102 Rho-MOTOR PROTECTION RELAY-UPDATED
7SR102 Rho-MOTOR PROTECTION RELAY-UPDATED
7SR102 Rho-MOTOR PROTECTION RELAY-UPDATED
Location
AL-SHARIF GROUP
Contractor Contract No.
HOLDING
Sheet No.
Site Test MOTOR PROTECTION
Record RELAY Page 1 of
1. GENERAL DETAILS
Panel Ref CT Ratio 100/1
Relay Type ARGUS-7SR1102 In 1
Manufacturer REYROLLE VT Ratio 2.
Serial No. BF1912506976 Vn
No. of contacts: 3BI+5BO Drawing/Sheet No
Order - No. 7SR1702-3NA87-1CAO-Z 100-250 VDC
Auxiliary Voltage
Software Revision 2436H80012R4f-2b#671c 100-230 V 50/60 Hz
88V DC Threshold
Opto-coupler supply: Frequency (fn) 60 Hz
(Rated 110-250VDC)
VISUAL INPECTION:
3. ELECTRICAL TESTS:
Location
AL-SHARIF GROUP
Contractor Contract No.
HOLDING
Sheet No.
Site Test MOTOR PROTECTION
Record RELAY Page 2 of
4. MEASUREMENTS:
4.1 CURRENT MEASUREMENT:
Location
AL-SHARIF GROUP
Contractor Contract No.
HOLDING
Sheet No.
Site Test MOTOR PROTECTION
Record RELAY Page 3 of
R-Y-B 75%
R-Y-B 100%
Sequence Components at 3Φ Currents:
Positive Sequence Current I1 : 1.00 x In
Negative Sequence Current I2 : 0.00 x In
Zero Sequence Current I0 : 0.00 x In
5. OVERCURRENT PROTECTION:
Location
AL-SHARIF GROUP
Contractor Contract No.
HOLDING
Sheet No.
Site Test MOTOR PROTECTION
Record RELAY Page 4 of
Y
B
RYB
5.2 TIME DELAYED OVER CURRENT(51-1):
Location
AL-SHARIF GROUP
Contractor Contract No.
HOLDING
Sheet No.
Site Test MOTOR PROTECTION
Record RELAY Page 5 of
600*ln { 12-(1-0.5)*0
-1.05*1.05
7. STALL PROTECTION(14):
Stage-1: 14-1
Settings:
Gn-14-1 Setting 2.0 x In
Gn-14-1Control Running
Gn-14-1 delay 5.0 Sec
Location
AL-SHARIF GROUP
Contractor Contract No.
HOLDING
Sheet No.
Site Test MOTOR PROTECTION
Record RELAY Page 6 of
0.6∟240° 2.5∟240°
0.6∟120° 2.5∟120°
Location
AL-SHARIF GROUP
Contractor Contract No.
HOLDING
Sheet No.
Site Test MOTOR PROTECTION
Record RELAY Page 7 of
Operating Remarks
Applied Set Current Pickup Drop Off
Phase Time @ 0.125
Current (A) Current Current
x In (Sec)
R 5∟0° 1.25
Y 5∟240° 1.25
B 5∟120° 1.25
Pickup Tolerance: 100% Is, ±5% or ±1% of In
Operation Time Tolerance: ± 1% or ±10ms + Element basic operating time 50 ms @ 0.5xIs, ±10ms
Procedure:
Apply 3Φ Nominal current in all phases.
Reduce the 3Φ current gradually to below set value until relay trip.
Measure the time at 50% of set current value
U/C Guard setting reference is Motor Stop current = 0.1 x Itheta (Thermal Protection)
Maximum Start 66-Start Counter Reset to Maximum Number of Start Measured max number
Period zero with in max Start Period of start
Test Performed by: Test Witnessed by: Date of Test
Name:
Signature:
Client SWCC
Location
AL-SHARIF GROUP
Contractor Contract No.
HOLDING
Sheet No.
Site Test MOTOR PROTECTION
Record RELAY Page 8 of