Calculation of Seismic Forces: REF: I.S. 1893 (Part 1) - 2002. As Per Clause 7.5 V A W
Calculation of Seismic Forces: REF: I.S. 1893 (Part 1) - 2002. As Per Clause 7.5 V A W
VB = A hW
As per clause 6.4.2 of IS 1893 (Part 1) : 2002, The design horizontal seismic coefficient A h ,
Sa/g = 2.50 depending upon T. [From Clause 6.4.5 for Type III soil]
Z I Sa
Hence, Ahy =
2Rg
= 0.067
= 3.92
DETAILED CALCULATION FOR OF SEISMIC FORCES
Roof Load
DEAD = 13.4 T
SDL = 4.2 T
TOTAL DEAD LOAD = 17.61 T
STORE Wihi^2
Y
Wi (T) hi (m) Wihi^2 Qi=DxVB Vi
(∑Wihi^2)
Roof 17.61 9.2 1490.40 0.650 2.55 2.55
1 Floor
st
31.93 5 798.21 0.348 1.36 3.91
Plinth 9.30 0.8 5.95 0.003 0.01 3.92
TOTAL 2294.56