CALCULATION OF SEISMIC FORCES

REF: I.S. 1893 (Part 1) - 2002.

As per Clause 7.5

VB = A hW

As per clause 6.4.2 of IS 1893 (Part 1) : 2002, The design horizontal seismic coefficient A h ,

Z I Sa [ Zone factor, Z = 0.16 ] From Table-2


= 2Rg [ Zone III ]
[ Importance factor,I = 1.00 ] From Table-6
[ Response reduction factor,R = 3.00 ] From Table-7

Height of building h = 9.2 m

Base dimensions of building d = 16.725 m


7.9 m
W = Seismic weight of the building as per clause 7.4.2

T= (0.09h)/(d^1/2) = 0.29 second [As per Clause 7.6.2]

Sa/g = 2.50 depending upon T. [From Clause 6.4.5 for Type III soil]

Z I Sa
Hence, Ahy =
2Rg

= 0.067

Total design lateral force VB = AhW

= 3.92
DETAILED CALCULATION FOR OF SEISMIC FORCES

Plinth Level Load


DEAD = 1.29 T
BKW = 8.0 T
TOTAL DEAD LOAD = 9.30 T

SEISMIC WEIGHT AT PLINTH LEVEL = 9.30 T

First Floor Load


DEAD = 13.9 T
SDL = 3.8 T
BKW = 9.01 T
TOTAL DEAD LOAD = 26.75 T

LIVE LOAD = 5.18 T


SEISMIC WEIGHT AT 1ST FLOOR = 31.93 T

Roof Load
DEAD = 13.4 T
SDL = 4.2 T
TOTAL DEAD LOAD = 17.61 T

Live Load not to be included as per clause 7.3.2 IS 1893(2002)


SEISMIC WEIGHT AT ROOF = 17.61 T

Distribution of Total Horizontal Load to Different Floor Levels

STORE Wihi^2
Y
Wi (T) hi (m) Wihi^2 Qi=DxVB Vi
(∑Wihi^2)
Roof 17.61 9.2 1490.40 0.650 2.55 2.55
1 Floor
st
31.93 5 798.21 0.348 1.36 3.91
Plinth 9.30 0.8 5.95 0.003 0.01 3.92
TOTAL 2294.56