Introduction
Recent changes have been made to IEEE 519. These revisions add clarity to the 1992 document as well
as present new definitions, methods and recommendations. This brief summary of changes to IEEE 519
as it pertains to low voltage adjustable frequency drives (AFD’s) is further expanded on in the following
pages. This paper is not an exhaustive analysis of the differences between the 1992 version and the
2014 version. Rather, it attempts to highlight the differences as they affect the practice of specifying, ap-
plying and installing low voltage adjustable frequency drives.
1. The Point of Common Coupling (PCC) is specifically defined as the point of connection to the
utility.
2. Total Demand Distortion (TDD) is redefined. TDD is the critical base which determines how %
harmonics are to be limited. The new definition attempts to clearly establish what had previously
been open to interpretation.
3. A new statistical method of measuring and recording harmonic content is described with a greater
emphasis on statistical sampling and almost no mention of instrumentation.
5. No changes were made to the current distortion limits, however the new table ignores harmonics
th
above the 50 .
6. The recommendations for increasing harmonic current limits put active and passive filters on an
equal footing with phase shifted multipulse drives.
Application Note AP040094EN The Effects of Changes to IEEE 519-1992 to 2014
Effective November 2014
“Total demand distortion “The ratio of the root mean TDD is the critical
(RSS), harmonic current dis- square of the harmonic con- base which deter-
tortion in % of maximum de- tent, considering harmonic mines how % harmon-
Total mand load current (15 or 30 components up to the 50th ics are to be limited.
(3)
Demand min demand)” order and specifically exclud- The new definition
Distortion ing interharmonics, ex- attempts to clearly
(TDD) pressed as a percent of the articulate what had
Definition maximum demand current. previously been open
Harmonic components of or- to interpretation.
der greater than 50 may be
(4)
included when necessary.”
“9.2 Basic Equipment Used The new requirement for The 2014 recommen-
for the Analysis of Nonsinus- Harmonic Measurements dation emphasizes
oidal Voltages and Current” Methods include well defined statistical analysis
Harmonic This section describes the “very short time harmonic over instrumentation.
Measurement instrumentation and tech- measurements”, “short time This will have little
Methods niques required to accurately harmonic measurements”, effect on the planning
measure industrial harmon- and “statistical evaluation of new AFD’s but will
(5)
ics. techniques.” These tech- impact on site meas-
niques reduce the effect of urements.
(6)
outlier data points.
For low voltage and medium For low voltage and The two tables have
voltage drives use “Table medium voltage drives identical entries,
10.3 - Current Distortion use “Table 2 – Current however 1992
Limits for General distortion limits for specifies harmonic
Distribution Systems (120 V systems rated 120V numbers > 35th while
Maximum Through 69,000 V)”
(9)
through 69kV”
(10)
2014 specifies 35 ≤ h
Harmonic Current ≤ 50. The 2014 table
Distortion in makes it clear that
Percent of IL harmonics greater
th
than the 50 are not
addressed by this
recommendation.
“However, when phase shift “It is recommended that This change puts
transformers or converters the values given in Table alternate mitigation
with pulse number (q) higher 2, Table 3, and Table 4 techniques (passive
than six are used, the limits be increased by a filters, active filters) on
for the characteristic multiplying factor when an equal footing with
Recommendations harmonic orders are actions are taken by a phase shift
for Increasing increased by a factor equal user to reduce lower- transformers with
Harmonic Current to √𝑞/6 provided that the order harmonics. The higher pulse
Limits amplitudes of the multipliers given in table converters.
noncharacteristic harmonic 5 are applicable when
orders are less than 25% of steps are taken to reduce
the limits specified in the the harmonic orders
tables.”
(11) given in the first column.”
(12)
References
[1]
Section 10.1 – Pg. 75 of IEEE 519-1992
[2]
Section 1.2 – Pg. 2 of IEEE 519-2014
[3]
Section 3.1 – Pg. 11 of IEEE 519-1992
[4]
Section 3 – Pg. 4 of IEEE 519-2014
[5]
Section 9 – Pgs. 68-74 of IEEE 519-1992
[6]
Section 4 – Pg. 4-5 of IEEE 519-2014
[7]
Section 10.3 – Pg. 77 of IEEE 519-1992
[8]
Section 5.1 – Pg. 6 of IEEE 519-2014
[9]
Section 10.3 – Pg. 78 of IEEE 519-1992
[10]
Section 5.2 – Pg. 7 of IEEE 519-2014
[11]
Section 10.4 – Pgs. 78 of IEEE 519-1992
[12]
Section 5.5 – Pg. 9 of IEEE 519-2014