Cat 6 UTP Field Plug Termination

Slide on
Crimp tool optional
Flush Cutters boot if
(p/n: PT-908)
with 3-slot die: being used
(p/n: PT-DIE2-8)

Plug
Load Body
Pair Bar
Jacket Strip tool
Optional Isolator
(p/n: CPT-RGTP)
Boot or equivalent
Category 6 UTP Cable O.D. ≤ 0.25”
(6.4 mm)
23-26 AWG solid or stranded, conductor
insulation 0.037” – 0.042” (.94 – 1.07mm)
Tools 1

Orange Pair

Orange Pair
Brown Pair

Brown Pair
Green Pair

Green Pair
Blue Pair

Blue Pair
[T568B [T568A]
wiring
shown]

~ 2 in. (51 mm)


≤ 0.04”
(1mm)

Remove center spline if


Remove Jacket applicable
Insert Isolator (notched side away from jacket)
2 3 4

[T568B shown] [T568B shown]


[T568B] [T568A]

≤ 0.04” (1mm)
White-Orange
White-Orange

White-Brown
White-Brown

White-Green
White-Green

White-Blue
White-Blue

Orange
Orange

Brown
Brown

Green
Green

Blue
Blue

Brown conductor
(pin 8)

≤ 0.04”
(1mm)

Insert into load bar with


brown pair on right and lip Trim flush with load bar
Untwist and flatten pair
side of bar up as shown
down to isolator Trim ends clean
5 6 7 8
Cat 6 UTP Field Plug Termination
Optional Boot
Use 3-slot die
(p/n: PT-DIE2-8)
1

OR

(non-booted version)
Min. jacket depth:
0.2” (5.1mm)

Fully insert assembly into


crimp tool and squeeze
2
Insert fully into plug body ! If using boot, slide into handles until they release.
place prior to crimping
9 10 11

Pin#’s
1 2 3 4 5 6 7 8

Rev. B 03/19 100.26236.00


Finished Assembly
12

© 2019 Siemon

To assist safe installations, comply with the following:


A. Use caution when installing or modifying telecommunications circuits.
B. Never touch uninsulated wire terminals unless the circuit has been disconnected.
C. Never install this device in a wet location.
D. Never install wiring during a lightning storm.

Lors de l'installation, respectez les consignes de sécurité suivantes:


A. Utiliser avec prudence lors de l'installation ou de la modification circuits de
télécommunications.
B. Ne jamais toucher les bornes de fil métallique non isolés sauf si le circuit a été débranché.
C. Ne jamais installer cet appareil dans un endroit humide.
D. Ne jamais installer pendant un orage.

To ensure you have the latest


revision to this document, please visit: www.siemon.com

You might also like