Iran. J. Environ. Health. Sci. Eng., 2007, Vol. 4, No. 4, pp.

235-242

A NEW EXHAUST VENTILATION SYSTEM DESIGN SOFTWARE


*
H. Asilian Mahabady, M. Omidvar, A. Rezaee, A. Khavanin, S. B. Mortazavi
Department of occupational and Environmental Health, Medical faculty, Tarbiat Modares University, Tehran, Iran

Received 14 August 2007; revised 2 September 2007; accepted 23 September 2007


ABSTRACT
A Microsoft Windows based ventilation software package is developed to reduce time-consuming and
boring procedure of exhaust ventilation system design. This program Assure accurate and reliable air
pollution control related calculations. Herein, package is tentatively named Exhaust Ventilation Design
Software which is developed in VB6 programming environment. Most important features of Exhaust
Ventilation Design Software that are ignored in formerly developed packages are Collector design and fan
dimension data calculations. Automatic system balance is another feature of this package. Exhaust
Ventilation Design Software algorithm for design is based on two methods: Balance by design (Static
pressure balance) and design by Blast gate. The most important section of software is a spreadsheet that is
designed based on American Conference of Governmental Industrial Hygienists calculation sheets.
Exhaust Ventilation Design Software is developed so that engineers familiar with American Conference
of Governmental Industrial Hygienists datasheet can easily employ it for ventilation systems design.
Other sections include Collector design section (settling chamber, cyclone, and packed tower), fan
geometry and dimension data section, a unit converter section (that helps engineers to deal with units), a
hood design section and a Persian HTML help. Psychometric correction is also considered in Exhaust
Ventilation Design Software. In Exhaust Ventilation Design Software design process, efforts are focused
on improving GUI (graphical user interface) and use of programming standards in software design.
Reliability of software has been evaluated and results show acceptable accuracy.

Key words: Industrial ventilation, Balance method, gate method, software, VB6

INTRODUCTION
By industries development, the amount of air are not installed according to plans, leading to
contaminants that are released in workplace has tremendous loss as a result of inefficiency. All
grown increasingly. To reduce these contaminants, ventilation systems must be designed so perform
there are several methods that, one of which is adequately for all conditions. (William et al., 2004).
control at source. Industrial ventilation is perhaps If designer is not very experienced in system
the most powerful tool available for environmental balance or is not familiar with air flow behavior in
professionals to control workplace pollution. Exhaust ducts, branch entrances, and fittings, an error in
ventilation can capture contaminants at source, loss coefficient selection and manual calculations
refine and eliminate them, and as a result reduces may cause system to be unbalanced and as a result
workplace pollution and work related diseases be inefficient.
caused by them (ACGIH, 2001; Burton, 1994). As computers are getting faster, powerful, more
It is estimated that tens thousand of new industrial reliable, cheaper and more accessible, their areas
exhaust ventilation systems are installed annually. of application are also becoming widespread.
If we assume that the average capacity is 1000cfm According to above mentioned advantages,
with installation costs of 5$ per cfm and yearly software developing in exhaust ventilation field
expense of 2$ per cfm, it is apparent that this seems to be necessary.
presents a considerable investment. However, Although Manual Design of exhaust ventilation
many of these systems are improperly designed, systems is useful for occasional design (often a
*Corresponding author-Email: Asilia_h@modares.ac.ir single branch system), the manual calculation
Tel: +98 21 8801 1001, Fax: +98 21 8801 3030 method is time consuming and increase probability

235
Iran. J. H.
Environ. Health.
Asilian, et al.,Sci. Eng.,EXHAUST
A NEW 2007, Vol. 4, No. 4, pp. 235-242
VENTILATION...

of errors. Since the mid 1970s a number of datasheet, selection of balance method
computer programs for the design of systems have (automatically or user selection), etc.
been introduced in the open literature and by Datasheet includes 41 rows that some of them
engineering consultants and manufactures. One are filled by the user, and others are automatically
type of design program has been developed for filled by the program, based on data which is
the programmable hand calculators (Barritt, 1978; entered by the user.
Malchaire, 1981; shotwell, 1984). These have the
merit of explicitly and are easily use in the field MATERIALS AND METHODS
but may not have advanced features, such as To develop new software, some steps must be
automatic balancing. More recently, Spreadsheet considered, including possibility, sketching,
program for personal computers have been applied compiling, debugging and providing installation
to ventilation design using the velocity pressure program (Stroo, 2001). In EVDS Design, pseudo
method (Rennix, 1987; Koshland and Yost, 1987; codes were prepared at first, and then variables
Temple systems 1999). Although these programs and algorithms were defined. Structure of algorithm
are powerful tools for design, but they haven’t for system design in EVDS was defined in Fig. 1.
ability to design collector and hood and may not After the algorithm definition step, software GUI
be able to take in to account psychometric was designed. In GUI design, it has been tried to
correction in design process. user interface be based on programming standards
This study presents Exhaust Ventilation Design and also be user- friendly. For this reason we have
Software (EVDS) as a computer-aided exhaust used dropdown menus and, and designed a toolbar
ventilation design software for fundamental for fast access to necessary options.
understanding of the principles underlying the system EVDS is developed in VB6 Programming
design. The software has been planned to facilitate environment. In EVDS design ActiveX and dll
complete exhaust ventilation system design. components have been used to accelerate
EVDS uses velocity pressure method for exhaust programming procedure and fascinate
ventilation system design (ACGIH, 2001). This programming user interface. Program debugging
method has been in widespread use for about 50 was performed in several steps to remove logical
years; its popularity results from the ease of initial and syntax errors.
calculation and ability to redesign system elements P.C. specifications for EVDS design summarized
when necessary. Previously an alternative design as below:
procedure called equivalent foot method was Windows edition: Microsoft Windows XP
published that fell further from favor in the interim, (professional)
and is no longer presented in the ventilation
System: AMD Athlon (tm) 64 processor 3200+3
publications (William et al., 2004). Since EVDS
GHZ, 512MB of RAM
employs a datasheet similar to ACGIH velocity
pressure calculation sheet, every designer can After program debugging, codes were compiled
easily employ it. Psychometric corrections have to a native code and optimized for fast coding.
been also considered in EVDS calculations Finally, all related files compiled to a setup program
(ASHRAE, 2001)). Altitude and temperature in order to distribute the program and its
deviations from standard condition are components to end user P.C.
automatically calculated as flow rate (KQ) and System requirements for EVDS including:
velocity pressure (KP) coefficients, taking into
Operating system: Windows 95/98/NT4/2000/ME/XP
account psychometric correction.
Processor: 486DX/66 MHz PC or higher
Intelligent structure of software makes aware user
Space usage: 15MB of free Space on hard disk
from errors accrued in design step. These
warnings include high pressure difference between Software GUI
branches, deviation from minimum transport EVDS has several sections which are explained
velocity in duct, incorrect data entering in as follows:

236
Iran. J. Environ. Health. Sci. Eng., 2007, Vol. 4, No. 4, pp. 235-242

Start

Balance by gate Balance by design

Branch 1 Branch 2 Branch 1 Branch 2

SP ratio between two branch SP ratio between two branch

SP ratio >1 SP ratio <1.2 SP ratio <1.2

Gate in duct with lower SP


Flow correction Redesign in branch
With lower sp
Sub main

Sub main
SP ratio <1.2 SP ratio <1.2

Fig. 1: EVDS system balance algorithm

Industrial ventilation system design main page: can see triple pressures in a chart. In design
This is the main section of the program that user process of EVDS psychometric corrections and
employ it to initialize a new project. Main sheet static pressure effect in fan inlet also has been
consists of a dropdown menu and a toolbar for considered (Fig. 2).
fast access to other sections. In this section user

Fig. 2: EVDS main sheet

237
Iran. J. Environ. Health.
H. Asilian, et al.,Sci. Eng.,EXHAUST
A NEW 2007, Vol.VENTILATION...
4, No. 4, pp. 235-242

Flow (KQin) and pressure (KPin) coefficients in fan where:


inlet can be calculated as below (ACGIH, 2001):
D 0 . 14 T
n = 1− ( ) 0 .3 (6)
2 .5 283
1
K Qin = (1)
Sp i In which:
1+
13.6( 29.92 + Δp) T: temperature (ÚK)
D: cyclone diameter (in.)
And:
Where in Equation (1):
SPi: Static pressure at fan inlet (in. WG) ⎧⎪ ⎡ ⎛ D 2⎤
⎞⎡ ⎛d⎞ ⎤ L
2 2 2
πD e ⎞ ⎛S H ⎞ 1 ⎛ S + k − Lb d ⎛D ⎞
ΔP: Pressure deviation from standard barometric c = ⎨ 2 ⎢1 − ⎜ ⎟ ⎥⎜ − ⎟+ ⎜ ⎟ ⎢1 + + ⎜ ⎟ ⎥ + b − ⎜ e ⎟
WH ⎪ ⎢ ⎝ D ⎠ ⎥⎦ ⎝ D 2 D ⎠ 3 ⎝ D ⎠ ⎢⎣ D ⎝D⎠ ⎥ D ⎝ D ⎠
⎩ ⎣ ⎦
condition (in. Hg)
KQin : flow coefficient at fan inlet
2 ⎧
πD ⎪ ⎡ ⎛ D e ⎞ ⎤⎛ S
2
H ⎞ 1 ⎛ S + k − L b ⎞⎡ d ⎛d ⎞ ⎤ Lb ⎛ De
2

2
k S
⎫⎪ (7)
c = ⎨ 2 ⎢1 − ⎜ ⎟ ⎥⎜ − ⎟+ ⎜ ⎟ ⎢1 + + ⎜ ⎟ ⎥+ −⎜ ⎟ − ⎬
WH ⎪ ⎢ ⎥ ⎝ ⎠ ⎝D ⎠ ⎦⎥
⎩ ⎣ ⎝ ⎠ ⎦ ⎝ ⎠ ⎢⎣ ⎝ D ⎠
D D 2 D 3 D D D D D⎪
And: ⎭

where:
⎡ SPi ⎤ (2) D: cyclone diameter (ft)
K Pin = ⎢1 + ⎥ KP
⎣ 13.6 ( 29.92 + ΔP ) ⎦ W: width of inlet (ft)
H: height of inlet (ft)
KP =
1 (3)
KQ
S: length of vortex finder (ft)
Lb: length of body (ft)
KP 1 Lc: length of cone (ft)
K Pin = = (4)
K Qin K Q × K Qin De: diameter of gas exit (ft)
Dd: diameter of dust outlet (ft)
Where:
KP: Pressure coefficient for psychometric and:
1/ 3
correction ⎛ D2 ⎞
KQ: flow coefficient for psychometric correction k = 2.3D e ⎜ ⎟ (8)
⎜ WH ⎟
KPin: pressure correction coefficient at fan inlet ⎝ ⎠

d = D − [( D − D d )( S + k + L b ) / L c ] (9)
Fan Static Pressure can also calculated as below:
⎛ ρ p d 2p V g ⎞
FSP = SPOut − SPin − VPin + Z Ψ = ⎜ ( n + 1) ⎟ (10)
⎜ 18 μ g D ⎟
⎝ ⎠
Where:
FSP: Fan Static Pressure (in. WG) where:
SPout: Static Pressure at fan outlet (in. WG) ρp: Particle density (lb/ft3)
SPin: Static Pressure at fan inlet (in. WG) Dp: Particle diameter (ft)
VPin: Velocity Pressure at fan inlet (in. WG) Vg: gas velocity (fpm)
μg: gas viscosity (lb/ft.s)
Cyclone design section
This section is used for cyclone design with several Pressure loss in cyclones can be calculated as
standard configurations. The efficiency and below:
pressure drop in cyclone design is calculated as
below (Wane T.D., 2000): ΔP = 1 / 2ρ g V 2 g H v (11)
where:
1 /( 2 n + 2) (5) w h e r e :

η = 1 − exp(−2 (Cψ )
ΔP: pressure drop in cyclone (Pa)

238
Iran. J. Environ. Health. Sci. Eng., 2007, Vol. 4, No. 4, pp. 235-242

ρg: gas density (kg/m3) In Cyclone design section eight dimensions of


Vg: gas velocity (m/sec) cyclone can be determined; also efficiency and
And H v calculated as below (Dirgo, (1988); pressure drop can be calculated (Fig. 3).
Ramachandran et al., 1991): Settling chamber design
Although the cost and size of chambers would
make it impractical but they are most commonly
1/ 3
⎧ ⎛S⎞ ⎫ utilized as precleaners for other collection
⎛ HW ⎞⎪⎪ ⎜ ⎟ ⎪⎪
⎝ D⎠ (12) equipment where there are some large size
H v = 20⎜ ⎟⎨
⎜ D 2 ⎟ ⎛ L b + L c ⎞⎛ L b ⎞⎛ Dd ⎞ ⎬ particles (over 50μm in diameter) (William, 1997).
⎝ e ⎠⎪ ⎜ ⎟⎜ ⎟⎜ ⎟ ⎪
⎪⎩ ⎝ D ⎠⎝ D ⎠⎝ D ⎠ ⎪⎭ This section like cyclone design section has been
designed for settling chamber dimension’s
calculating (Fig. 4).

Fig. 3: Cyclone design section

Fig. 4: Settling chamber design section

239
Iran. J. Environ. Health.
H. Asilian, et al.,Sci. Eng.,EXHAUST
A NEW 2007, Vol.VENTILATION...
4, No. 4, pp. 235-242

User can calculate width and length of chamber D: minimum diameter of particles that remove by
as below: chamber (μ)
ρ0: particle density (lb/ft3)
a = Q /V that V ≤ 300 fpm (13) Ve: specific volume (ft3/lb)

Fan geometry section


⎛ K (1 + W ) VQ
+7
⎞ (14) After project design, user can utilize this section
b = 1.44e ⎜ ⎟⎟
⎜ D 2 ρ 0Ve to calculate impeller diameter, impeller width, and
⎝ ⎠
casing dimensions (Ralph, 2001). At this stage user
⎛ K (1 + W ) VQ ⎞ can obtain 9 fan dimensions (Fig. 5).
b = 1.44e + 7 ⎜ ⎟ (15)
⎜ D 2
ρ V ⎟ Hood design section
⎝ o e ⎠ If user wants to calculate flow rate, hood dimension,
Where in Equations (13) and (15): or see standard ventilation designs, this section can
a : chamber width (ft) help him/her to design hood. This section has been
b : chamber length (ft) designed based on Ventilation standards manual
K: kinematics viscosity of gas (ft2/min) which helps user to design miscellaneous hood
W: Humidity ratio (lb/lb) configurations including slot, flanged slot, plain
V: Air velocity in chamber (fpm) opening, flanged opening, booth, canopy and plain
Q: air flow (cfm) multiple slot opening hoods (Fig. 6).

Fig. 5: Fan geometry data section

Fig. 6: Hood design section

240
Iran. J. Environ. Health. Sci. Eng., 2007, Vol. 4, No. 4, pp. 235-242

Collector selection guide Contraction and Expansion loss


This section presents useful information about most This section has been designed to present
collectors that are widely used in industrial contraction and expansion coefficient losses in
ventilation system design. This information includes ducts. User can also calculate losses due to
max loading, collection efficiency, pressure loss, contractions and expansions, in this section
and energy consumption of collector (Fig. 7). (Fig. 8).

Fig. 7: Collector selection guide section

Fig. 8: Contraction and Expansion loss section

241
Iran. J. H.
Environ.
Asilian,
Health.
et al.,Sci. Eng.,EXHAUST
A NEW 2007, Vol. 4, No. 4, pp. 235-242
VENTILATION...

RESULTS Printing, United Stats of America.


Dirgo, J., (1988). Relationship between cyclone dimension
After EVDS design and compiling, validity of
and performance, Sc. D. Thesis, Harvard University,
software was examined by the following methods: Cambridge, Mass.
First, output of software was compared with Koshland, C. P., Yost, M. G., (1987). Use of a Spreadsheet
manually calculated results. Then software results in the design of an Industrial Ventilation Systems, Appl.
were compared with output of projects that have Ind. Hjg., 2: 204.
Malchaire, J. B., (1981). Design of Industrial Exhaust
been published by authorized organizations in Systems Using a Programmable Calculator. Ann. Occup.
industrial ventilation field. Also, calculations were Hyg. 24 : 217.
performed in an excel worksheet and results Ralph, G .C., (2001). Fans Reference guide, Fourth Edition,
compared with EVDS output. Software outputs Ontario Power Generation, Canada.
Ramchandran, G., Leith, J., (1991). Cyclone optimization
show maximum error of 0.5% in boundary
based on a new empirical model for pressure drop, Aerosol
conditions. Sci. Technol., 15 :135-148.
Renix, C. P., (1984). Computer Assisted Ventilation Design
DISCUSSION and evaluation, Appl. Ind. Hyg., 2: 32.
Shotwell, H. P., (1984). A Ventilation Design Program for
With regard to EVDS validity examination, it seems
Hand-held Programmable Computers, Am. Ind. Hyg.
that some errors occurred in EVDS calculations, Assoc. J., 45 : 749.
are resulted from round-off error. Numbers are Stroo, E., (2001), Essential guide to Microsoft Visual Basic
rounded off to four digits in EVDS calculations. 6.0, Canada, Microsoft Press.
In spite of this round off error, EVDS provides an Wane, T. D., (2000). Air Pollution Engineering Manual, Wiley
and Sons Inc., Canada.
acceptable accuracy for ventilation system design. William, A. B., Michael J.E., Robert D.T., (2004). Ventilation
It has a user friendly environment and can be used for Control of the Work Environment, Wiley and Sons
as comprehensive exhaust ventilation software Inc., Canada.
that facilitates design process and prepare William, L. H., (1997). Industrial Ventilation Air pollution
Control Systems, United Stats of America, Mc Graw Hil.
whatever a user requires for design. EVDS can
design new exhaust ventilation system, check and
redesign previously improperly installed systems.
Another application is collector design for
contaminant elimination. For future software
development, it is suggested that a 3D drawing
environment such as AutoCAD can be added to
the software.

ACKNOWLEDGEMENTS
Authors thanks to the authorities of Tarbiat
Modares University (TMU) for providing facilities
and is highly indebted to the Dr. jafari , associated
professor of Shahid Beheshty University of
Medical Science, Department of Occupational
Health.

REFERENCES
American Conference of Governmental Industrial
Hygienists., (2001). Industrial ventilation, 24 th. Ed.,
ACGIH, Cincinatti.
Barritt, S. L., (1978). Duct design by Programmable
calculator. Heat, /Piping/Air cond. Dec.
Burton, J., (1994). Industrial Ventilation (A Self Study
Companion to the ACGIH Ventilation Manual), Carr