FOR THE SINGLE LINE DIAGRAM
Basic Assumptions:
1. Vp= 7.62 KV
2. Conductor to be used is stranded copper conductor
3. Allowabke ACVD= 5% of Vp
=150% of safe ACVD
4. Conductor is spaced 44 incges measured on center
5. Conductors are arranged in horizontal configuration(Parallel Spacing)
6. Demand factor for commercial,institutional and industrial load (3- Ø) is 1.
I. SUMMATION OF LOADS
A. Residential Loads
B. COMMERCIAL/INSTITUTIONAL/INDUSTRIAL (THREE-PHASE)
Xd= 0.187-((0.187-0.185)*(56-55.437)/(56-55))
Xd = 0.186Ω/mi
1.39 0.58
1207.5 [ * 1 + * 0 ]
7 1
= = 2.905 %
10 * (7.62)2
I. SUMMATION OF LOADS
A. Residential Loads
DT NO. POLE NO. KVA RATING PHASE
2 64 50 1-F
4 70 100 1-F
7 77 75 1-F
11 85 75 1-F
14 121 125 1-F
18 156 100 1-F
TOAL 525 KVA
B. COMMERCIAL/INSTITUTIONAL/INDUSTRIAL (THREE-PHASE)
CHURCH, INSTITUTIONAL : POST NO. 78
AVERAGE CONNECTED LOAD = 12 * 0.917 = 11.004 KVA
TRANSFORMER SAFETY FACTOR = 1.25 * AVERAGE CONNECTED LOAD = 13.755 KVA
USE 1 PC 15 KVA , 3-Ø DT
PARK, INSTITUTIONAL : POST NO. 80
AVERAGE CONNECTED LOAD = 25 * 1 = 25.000 KVA
TRANSFORMER SAFETY FACTOR = 1.25 * AVERAGE CONNECTED LOAD = 31.250 KVA
USE 1 PC 45 KVA, 3-Ø DT
HOSPITAL, INSTITUTIONAL : POST NO. 82
AVERAGE CONNECTED LOAD = 45 * 0.994 = 44.730 KVA
TRANSFORMER SAFETY FACTOR = 1.25 * AVERAGE CONNECTED LOAD = 55.913 KVA
USE 1 PC 75 KVA, 3-Ø DT
SUPERMARKET, COMMERCIAL : POST NO. 113
AVERAGE CONNECTED LOAD = 50 * 0.95 = 47.500 KVA
TRANSFORMER SAFETY FACTOR = 1.25 * AVERAGE CONNECTED LOAD = 59.375 KVA
USE 1 PC 75 KVA, 3-Ø DT
ARCADE, COMMERCIAL : POST NO. 119
AVERAGE CONNECTED LOAD = 30 * 0.666 = 19.980 KVA
TRANSFORMER SAFETY FACTOR = 1.25 * AVERAGE CONNECTED LOAD = 24.975 KVA
USE 1 PC 30 KVA, 3-Ø DT
COCKPIT AREA, COMMERCIAL : POST NO.157
AVERAGE CONNECTED LOAD = 30 * 0.917 = 27.510 KVA
TRANSFORMER SAFETY FACTOR = 1.25 * AVERAGE CONNECTED LOAD = 34.388 KVA
USE 1 PC 45 KVA, 3-Ø DT
4 64 50 560 28000
14 77 75 1960 147000
15 78 15 2100 31500
16 80 45 2240 100800
18 82 75 2520 189000
19 85 75 2660 199500
Xd= 0.187-((0.187-0.185)*(56-55.437)/(56-55))
Xd = 0.186Ω/mi
Thus,
0.46
810 [ 2.089 * 1 + * 0 ]
9
%VD
= 2.914 %
=
10 * (7.62)2
1 31 75 1-F
3 15 75 1-F
6 20 75 1-F
10 52 100 1-F
12 88 75 1-F
B. COMMERCIAL/INSTITUTIONAL/INDUSTRIAL (THREE-PHASE)
COMMERCIAL CENTER ,COMMERCIAL : POST NO.14
AVERAGE CONNECTED LOAD = 30 * 0.666 = 19.980 KVA
TRANSFORMER SAFETY FACTOR = 1.25 * AVERAGE CONNECTED LOAD = 24.975 KVA
USE 1 PC 30 KVA, 3-Ø DT
RADIO STATION,COMMERCIAL : POST NO.93
AVERAGE CONNECTED LOAD = 45 * 0.944 = 42.480 KVA
TRANSFORMER SAFETY FACTOR = 1.25 * AVERAGE CONNECTED LOAD = 53.100 KVA
USE 1 PC 75 KVA, 3-Ø DT
II.TOTAL KVA BROUGHT FORWARD
III.TOTAL KVA-SPAN
29 93 75 4060 304500
28 88 75 3920 294000
6 31 75 840 63000
18 20 75 2520 189000
13 15 75 1820 136500
14 14 30 1960 58800
ΣKVA-SPAN = 1882300 KVA-FT
METHOD 3
%VD =
10(KV)2
Rt= Rad’= (3.79* 2987.778)/5280= 2.145 Ω
Since,
Xt= [(Xa+Xd)d’]/5280
Xt= [(.665+.186)* 2987.778]/5280= 0.481 Ω
Thus,
= = 2.327 %
10 * (7.62)2
METHOD 4:
Using IEEE Exact Voltage Drop Formula
VD= V + I R cos θ + I X sin θ - √(V2 -(I X cos θ - I R sin θ)2))
Since, Rt=2.145 Ω
Xt= 0.481 Ω
Thus,
VD= 7.62*10^3+(47.734*2.145 *1)+( 47.734*0.481 *0)-√7.62*10^3-
(47.734*0.481 *1)-( 47.734*2.145 0)
VD= 102.391 Volts
ACTUAL ACVD = √3 VD = √3 * 102.391 = 177.346 V
%VD = 177.346 / 7.62*10^3 = 2.327 %
2.327 % is less than the Allowable Voltage Drop of 5.00%.
Therefore, load is SAFE!