DRW180855AA

Model Connections Dimensions (unit: mm)


(-) 2-Ø4 Operation indicator (blue)
Number of Varistor INPUT 1
1 POINT RELAY TERMINAL BLOCK (5A) Model Terminal side Controller side Relay type Input logic

12.6
relay points installation 2
(+)

ABS Series ABS-S01PQ-CN MATSUSHITA 82


Screw Screw 1 (Panasonic) PQ COM None Not installed
ABS-S01R6-CN OMRON G6B
INSTRUCTION MANUAL RY1

33.2
Terminal Specifications
B B
A A OUTPUT 3 35.2
72
4
88.5

D
C
C
D
<Spade terminal> <Ring terminal> (unit: mm)
Installation
A B C D Applicable wires
1. Mounting and Removal at DIN rail. DIN Rail
Spade terminal ≥4.1 ≤16.0 ≥3.3 ≤7.0 AWG19-14 ● Mounting connection part
Ring terminal ≥4.1 ≤16.0 ≥3.3 ≤7.0 (0.65 to 2.0mm2) 1) Push the rail lock towards direction ①. DIN Rail
※Please use the UL certified terminals. 2) Attach the DIN rail connection hook onto the DIN rail.
3) Push the unit towards direction ②, then push the rail
lock in to lock into position.
Thank you for choosing our Autonics product. Specifications ● Removal ①
Rail lock

① ②
Please read the following safety considerations before use. Model ABS-S01PQ-CN ABS-S01R6-CN 1) Insert a screwdriver into the rail lock hole and pull it
Power supply 24VDC ±10% towards direction ①.
Rated load voltage & current※1 250VAC 5A, 30VDC 5A 2) Remove the unit by pulling the unit towards direction ②.
Safety Considerations Current consumption※2
Output type
≤20mA
1a contact relay output
2. Mounting with screws ①
1) This unit can be mounted on panels using the rear rail locks.
※Please observe all safety considerations for safe and proper product operation to avoid hazards. Applicable relay PQ1a-24V[MATSUSHITA (Panasonic)] G6B-1174P-FD-US[OMRON]
2) Push rail locks to the directions ①, ②.
No. of relay points 1-point
※ symbol represents caution due to special circumstances in which hazards may occur. 3) M4×15mm spring washer screws are recommended for installation. ②
Indicator Operation indicator: blue LED
When using flat washers, use Ø6mm diameter washers. The tightening torque Rail lock
Applicable wire AWG19-14 (0.65 to 2.0mm2)
Warning Failure to follow these instructions may result in serious injury or death. should be between 0.7 and 1.0 N.m.
Insulation resistance ≥1,000MΩ (at 500VDC megger)
Between 3. Connecting multiple units
Caution Failure to follow these instructions may result in personal injury or product damage. 4,000VAC 50/60Hz for 1 minute Connect multiple units by locking the socket ( ) and peg ( ) together in direction ①.
Dielectric coil-contact
strength Between
Warning same contacts※3
1,000VAC 50/60Hz for 1 minute ②
1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial Mechanical 1.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours
economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion Vibration
Malfunction 1.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 minute ①
apparatus, safety equipment, crime/disaster prevention devices, etc.) Mechanical 1000m/s2 (approx. 100G) in each X, Y, Z directions for 3 times
Failure to follow this instruction may result in personal injury, economic loss or fire. Shock
Malfunction 100m/s2 (approx. 10G) in each X, Y, Z directions for 3 times
2. Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant
heat, vibration, impact, or salinity may be present. Environ- Ambient temp. -15 to 55℃, storage: -25 to 65℃
Failure to follow this instruction may result in explosion or fire. ment Ambient humi. 35 to 85%RH, storage: 35 to 85%RH Example of connection
3. Do not connect, repair, or inspect the unit, remove connector or change relay while connected to a power source. Material CASE, BASE: polyamide 6, TERMINAL PIN: brass
Failure to follow this instruction may result in fire or electric shock. Tightening torque 0.7 to 0.8 N.m
4. Do not disassemble or modify the unit.
Failure to follow this instruction may result in fire or electric shock.
Approval ※4
Replacing Relay ①
Protection
② Operation indicator ③
Weight※5 Approx. 430g (approx. 31g) Approx. 416g (approx. 30g) 1) Pull the protection cover to the direction ①. cover guide

Relay
Caution ※1: Relay contact capacity for resistive load. 2) Press the operation indicator guide to the
1. Use the unit within the rated specifications. ※2: The power consumption including LED current by one relay. direction ② and remove the relay to the
Failure to follow this instruction may result in fire or product damage. ※3: OMRON relay is 3,000VAC.
direction ③.
2. Use dry cloth to clean the unit, and do not use water or organic solvent. ※4: Except 30VDC of rated load voltage for .
Failure to follow this instruction may result in fire or electric shock.
3) Insert a new relay to the case.
※5: The weight of 1-point relays is per 10 units with packing and the weight of parentheses is per 1.
3. Keep the product away from metal chip, dust, and wire residue which flow into the unit. ※Environment resistance is rated at no freezing or condensation. ※Use the operation indicator guide for displaying
Failure to follow this instruction may result in fire or product damage. the power and removing the relay.
4. Do not use the product when a screw of terminal is loosened. Relay ※The values of PQ1a-24V relay are measured at 20ºC with a tolerance of ±10%.
Failure to follow this instruction may result in fire or product damage. 1) Coil specifications The values of G6B-1174P-FD-US relay are measured at 23ºC with a tolerance of ±10%.

Model Rated
voltage Must operate voltage Must release voltage Rated
current Coil resistance Power
consumption
Cautions during Use
Précautions pour la sécurité PQ1a-24V 24VDC ≥75% of rated voltage ≤5% of rated voltage 8.3mA 2,880Ω 200mW 1. Follow instructions in 'Cautions during Use'. Otherwise, it may cause unexpected accidents.
G6B-1174P-FD-US 24VDC ≥70% of rated voltage ≤10% of rated voltage 8.3mA 2,880Ω 200mW 2. Check the polarity of power or COMMON when connecting with PLC or other controllers.
※Après avoir lu ce guide, s'il vous plaît, placez-le dans un lieu où vous pouvez récemment le trouver.
3. While supplying power to the load or right after turning off the power of the load, do not touch the body.
※ symbol represents caution due to special circumstances in which hazards may occur. 2) Contact specifications Failure to follow this instruction may result in a burn due to the high temperature.
Manufacture MATSUSHITA (Panasonic) OMRON 4. Power supply should be insulated and limited voltage/current or Class 2, SELV power supply device.
Avertissement L'inaccomplissement des instructions peut provoquer des blessures graves. Model PQ1a-24V G6B-1174P-FD-US 5. Keep away from high voltage lines or power lines to prevent inductive noise.
Arrangement 1form A (SPST-1a) In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire
Précaution Le produit peut être endommagé ou de provoquer des blessures si les consignes ne sont pas respectées. Contact Material Au-clad AgNi type AgSnIn at input signal line.
Resistance (initial) ≤50mΩ (at 1A 6VDC ) ≤30mΩ (at 1A 5VDC ) Do not use near the equipment which generates strong magnetic force or high frequency noise.
Avertissement Rated load (resistive) 5A 250VAC 5A 30VDC 5A 250VAC 5A 30VDC
6. This unit may be used in the following environments.
1. Utilisez le produit seulement après avoir relié un double dispositif de sécurité pour les instruments qui ont un Max. switching capacity 1,250VA 150W 1,250VA 150W
grand effet pour le corps humain et la propriété, comme sont les dispositifs d'énergie atomique, mets en oeuvre Rating (resistive) ①Indoors (in the environment condition rated in 'Specifications')
Médecine, de véhicules, Rails, aéronefs, Brûleurs ou produits de sécurité. Max. switching voltage 250VAC 110VDC 380VAC 125VDC ②Altitude max. 2,000m
L'inaccomplissement peut causer des incendies, lésions personnelles ou dommages à la propriété. Max. switching current 5A ③Pollution degree 2
L'inaccomplissement peut causer des incendies, lésions personnelles ou dommages à la propriété. Insulation resistance ≥1,000MΩ (at 500VDC megger) ④Installation category II
2. Ne pas réparer ou vérifier le produit tout alimenté. Dielectric Coil and contacts
4,000VAC 50/60Hz for 1 minute 3,000VAC 50/60Hz for 1 minute
L'inaccomplissement peut provoquer un incendie ou des décharges électriques. Electrical
strength Open contacts 1,000VAC 50/60Hz for 1 minute 1000VAC 50/60Hz for 1 minute
3. Utilisez le produit avec l'environnement comme il est décrit dans le manuel. Évitez le lieu d'émission de gaz
corrosifs, gaz inflammables, incorporation température, haute humidité, vibrations, choc, etc.
character-
istics
Surge voltage 8,000V 6,000V Major Products
L'inaccomplissement peut provoquer un incendie ou une explosion. Operate time ≤20ms ≤10ms Photoelectric sensors Temperature controllers
4. Ne pas démonter et modifier cet appareil. S'il vous plaît nous contacter si cela est nécessaire. Release time ≤10ms Fiber optic sensors Temperature/Humidity transducers
L'inaccomplissement pourrait causer des décharges électriques, incendies, lésions personnelles ou dommages à le 3.5mm amplitude at frequency of 10 to 55Hz 1.5mm amplitude at frequency of 10 to 55Hz Door sensors SSRs/Power controllers
Mechanical Door side sensors Counters
produit. (for 1 min) in each X, Y, Z direction for 1 hour (for 1 min) in each X, Y, Z direction for 1 hour
Vibration Area sensors Timers
2.0mm amplitude at frequency of 10 to 55Hz 1.5mm amplitude at frequency of 10 to 55Hz
Précaution Mechanical Malfunction Proximity sensors Panel meters
(for 1 min) in each X, Y, Z direction for 10 min (for 1 min) in each X, Y, Z direction for 10 min
character- Pressure sensors Tachometer/Pulse(Rate)meters
1. Cette unité ne doit pas être utilisé à l'extérieur. 980m/s2 (approx. 100G) in each X, Y, Z 1000m/s2 (approx. 100G) in each X, Y, Z
istics Mechanical Rotary encoders Display units
Peut raccourcir le cycle de vie du produit ou causer un choc électrique. direction for 3 times direction for 3 times
Shock Connectors/Sockets Sensor controllers
2. S'il vous plaît respecter les spécifications nominales. 2
294m/s (approx. 30G) in each X, Y, Z 100m/s2 (approx. 10G) in each X, Y, Z
Malfunction Switching mode power supplies
L'inaccomplissement peut raccourcir le cycle de vie du produit et provoquer un incendie. direction for 3 times direction for 3 times
3. Dans nettoyer l'appareil, n'utilisez pas d'eau ou de solvants organiques. Et utiliser un chiffon sec.
Control switches/Lamps/Buzzers http://www.autonics.com
Expected Mechanical ≥20,000,000 operations (at 180 times/min) ≥50,000,000 operations (at 18,000 times/hour) I/O Terminal Blocks & Cables
L'inaccomplissement peut donner lieu des décharges électriques ou des dommages au produit. life Electrical
※1
≥100,000 operations (5A 250VAC , 30VDC resistive load) HEADQUARTERS:
Stepper motors/drivers/motion controllers
4. Ne pas laisser de poussière pénétrer l'unité. 18, Bansong-ro 513 beon-gil, Haeundae-gu, Busan, South
Ambient temperature -40 to 70℃ -25 to 70℃ Graphic/Logic panels
Cela pourrait provoquer un incendie ou un dysfonctionnement. Environment Korea, 48002
Ambient humidity 5 to 85%RH Field network devices
※The above specifications are subject to change and some models may be discontinued without notice. Laser marking system(Fiber, CO₂, Nd:YAG) TEL: 82-51-519-3232
Unit weight Approx. 7g Approx. 5g E-mail: sales@autonics.com
※Be sure to follow cautions written in the instruction manual and the technical descriptions (catalog, Laser welding/cutting system
※1: Panasonic relay is 20 times per 1 minute and OMRON relay is 1,800 times per 1 hour.
homepage). ※Environment resistance is rated at no freezing or condensation. DRW180855AA