REX 521 Protection Relay: Operator's Manual
REX 521 Protection Relay: Operator's Manual
Protection Relay
Operator’s Manual
Industrial IT enabled products from ABB are the building blocks for greater
productivity, featuring all the tools necessary for lifecycle product support in
consistent electronic form.
1MRS 751107-MUM Protection Relay REX 521
Issued: 29.11.2001
Version: D/17.11.2003 Operator’s Manual
Contents
1. Safety information .....................................................................6
2. Introduction ...............................................................................7
2.1. REX 521 protection relay ..............................................................7
3. Instructions ................................................................................8
3.1. HMI features ..................................................................................8
3.1.1. Push-button functions ......................................................10
3.1.2. Selecting language ..........................................................11
3.1.3. Passwords .......................................................................12
3.1.4. Display backlight ..............................................................12
3.1.5. Display contrast ...............................................................12
3.1.6. Display test ......................................................................13
3.1.7. Selecting primary values ..................................................13
3.1.8. Optically isolated serial communication port ....................13
3.2. Menu chart ..................................................................................14
3.2.1. Measurement menu .........................................................15
3.2.2. Event menu ......................................................................16
3.2.3. Manual control .................................................................17
3.2.3.1. Local/Remote position selection ........................17
3.2.3.2. Controlling breaker .............................................17
3.2.4. Setting parameter ............................................................19
3.2.5. Setting bit masks ..............................................................19
3.3. Indication messages ...................................................................20
3.3.1. Protection indications .......................................................20
3.3.2. Self-supervision ...............................................................21
3.3.3. Condition monitoring indication ........................................22
3.4. LED indicators .............................................................................23
3.4.1. Green indication LED (READY) .......................................23
3.4.2. Yellow indication LED (START) .......................................23
3.4.3. Red indication LED (TRIP) ...............................................23
3.5. Alarm LEDs .................................................................................24
3.5.1. Alarm LED 1-8 .................................................................24
4. Test mode ................................................................................25
4.1. I/O test .........................................................................................25
4.2. IRF test ........................................................................................25
4.3. Function block test ......................................................................26
3
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
5. References .............................................................................. 27
6. Index ........................................................................................ 28
7. Appendix A: Abbreviations ................................................... 31
4
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
Revision history
Version D/17.11.2003:
-Changes in chapters 3.1., 3.2.3.1. and 5.
-Changes in Table 3.1.1-1, “Push-button functions,” on page 10, Table 3.2.1-1, “Measurement view,”
on page 15, Table 3.2.1-1, “Measurement view,” on page 15.
-Changes in Fig. 3.2.-1.
5
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
1. Safety information
6
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
2. Introduction
The purpose of this manual is to provide the user with the basic information on the
protection relay REX 521 Revision C, and to especially focus on explaining the use
of the human-machine interface (HMI). You find information about the new features
of the relay in REX 521 Technical Reference Manual, General (see “References” on
page 27).
7
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
3. Instructions
8
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
REX 521
2
3
4 READY START TRIP
C 8
6
E 9
REX 521_face_a
7
Fig. 3.1.-1 HMI front view
1. Alarm LEDs
2. LED indicator: Trip, CBFP
3. LED indicator: Start, Block
4. LED indicator: Ready, IRF, Test mode
5. LCD
6. Optical PC connector
7. Navigation buttons
8. Clear/Cancel
9. Enter
9
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
C clear/cancel
left right
E enter
down
Nav_Butt
Fig. 3.1.1.-1 Push-buttons
The table below gives a short explanation of the push-buttons and their functions.
10
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
Display
Control General
Cond. monit.
Measurements
Power Quality
Tests
Configuration
LangSel
Fig. 3.1.2.-1 Selecting language
1. Select with [↓] and [→ ] buttons Configuration in the main menu,
General in the group menu, Software in the subgroup menu and
Active language in the parameter menu.
2. Press the [E] button until the second row of the display starts flashing. Then
select the wanted language with [↓] and [↑] buttons.
3. Confirm the selection by pressing the [E] button once more or cancel the
selection by pressing the [C] button.
After altering the language, the display menus are shown in the new language and
the selection is restored after disconnection of power supply.
11
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
3.1.3. Passwords
ABB
Protection
Control
Configuration
Tests Analog scales
Communication
Digital Inputs Password MMI
Display = 999
Configuration
PWmenu_a
Fig. 3.1.3.-1 Password menus
Setting values are protected by passwords. There are two different passwords, one
for protecting the HMI setting values and another for protecting settings through
serial communication.
• The default value of the serial communication password is 001 and of the HMI
password 999.
• The HMI password is not active until it has been changed from the default value.
After changing it, the relay prompts for password whenever the [E] button is
pressed in the setting value menu. Once the right password has been given, it
stays active until the display is returned to idle state by time-out. To disable the
HMI password, change it back to the default value 999.
• In case a password is forgotten, the HMI password can be viewed and changed
via serial communication.
12
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
Increase
Push E and
Contr
Decrease
Fig. 3.1.5.-1 Adjusting display contrast
• The display contrast may be adjusted anywhere in the menu structure except in
the setting menus where the [E] button is used for entering setting mode.
• The selected contrast value is stored in a non-volatile memory and thus, after an
auxiliary power failure, the contrast is restored automatically.
13
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
Output relays
Protected unit
Self-supervision
Time
14
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
Meas_val
THD-% 0.0
Demand values
IL1-A 0025.0
IL2-A 0025.0
Dem_val
IL3-A 0025.0
Uo Uo (V)
Measured values
3U U1 (kV) Uo-V 00.00
U2 (kV) U1-kV 0.50
U3 (kV)
U2-kV 0.50
U3-kV 0.50
Meas_val_Uo
f f (Hz)
f-Hz 50.00
PQE P (kW)
Q (kVAr)
E (kWh, kvarh) Power
P-kW +0
Q-kvar +0
PF cos j +0.00
P demand +0
Q demand +0
Energy
kWh 0
kvarh 0
Reverse energy
Meas_val_PQE_a
kWh 0
kvarh 0
15
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
Meas_H07_a
Time to restart
only. s 0
Thermal level
% 40 *
* The calculated thermal level of the device, maximum from the stator and the rotor.
16
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
The selected control position remains the same during auxiliary power-off.
When the local mode is selected, the character “L” is shown in the bottom-right
corner of the HMI main view. However, if the language in the relay is other than
English, the character that is shown in the display depends on the selected language.
17
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
=L o c a l
Control CB Control CB
=O p e n. E=C l o s e =O p e n. E=O p e n
=C l o s e d. E=O p e n =C l o s e d. E=C l o s e
Control CB Control CB
=I n t e r l o c k e d =P r e p a r i n g ...
Control CB Control CB
=A b o r t e d =A r e Y o u S u r e ?
Control CB Control CB
=I n t e r l o c k e d =O p e n i n g ...
=C l o s i n g ...
ManCtrl
Fig. 3.2.3.-1 Manual control
18
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
Event mask 1
= E0 0:1
EvM
19
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
4. Once the password has been entered, press the [E] button to confirm. Now the
selected setting value starts flashing.
5. Enter the new setting value using the buttons [↑], [↓] and [→ ], [← ].
6. Press the [E] button to confirm.
When entering single bit values, the bit to be edited may be shifted by pressing the
[→ ] button when the cursor is located in the rightmost corner of the display. In that
way, the cursor does not have to be moved back and forth between the bit number
and the value during the setting period, thus simplifying the procedure.
To find the meaning of each event, refer to Event List for REX 521 on the CD-ROM
Technical Descriptions of Functions (see “References” on page 27).
3I> : START
L1 , L2 , L3
St_strt
Strt
20
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
If a started protection function is blocked, the name of the function and the text
BLOCK are displayed. Now, the yellow LED indicator is blinking.
3I>: BLOCK
Bl_blck
Blck
Fig. 3.3.1.-2 Indication of blocking
If a protection function trips, the name of the function and the text TRIP appear on
the display. The red LED indicator is lit. The faulted phases are displayed in this
case.
Should the protection function deliver a delayed trip for circuit-breaker failure
protection (CBFP), the red indicator starts blinking.
3I> : TRIP
L1 , L2 , L3
Trp
Bl_trp
3.3.2. Self-supervision
The protection relay is provided with an extensive self-supervision system. The self-
supervision system handles run-time fault situations and informs the user about
existing faults over the display and the serial communication.
When a fault has been detected, the green READY indicator starts blinking. At the
same time, the self-supervision (IRF) output relay is activated.
Additionally, a fault indication text INTERNAL FAULT appears on the display and
an event is generated.
INTERNAL FAULT
Relay Control
Bl_IRF
irf
21
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
TCS1: SUPERV
Trip Circuit Sup
TCS
Fig. 3.3.3.-1 Condition monitoring indication
22
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
Blinking LED: IRF or Internal relay fault (IRF) has occurred or the relay is in
TEST MODE test mode1). Internal faults are accompanied by an
indication message, provided the HMI panel is
operative.
1) - Relay
- Function block
23
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
Non-active LED: OFF Normal operation. All the alarms are OFF.
a. Valid only if the LED is not activated by the parameter Alarm LED States.
b. The alarm can also be OFF if an auxiliary supply break has occurred. The state of the LED is then
preserved and has to be acknowledged (cleared) from the main view.
24
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
4. Test mode
Digital inputs, output relays and IRF relay may be tested by setting the parameter
Test mode to Testing in the menu Main menu\Tests\General.
When test mode is activated, the green READY indicator is blinking. Refer to
Technical Reference Manual, General (see “References” on page 27) for further
information.
Test mode can be cancelled by setting the parameter to No test or by
disconnecting the power supply.
If the user does not cancel the test mode, it remains active and the Ready LED
remains blinking.
Input states
= 000000000
InpSt
D9 ... D1
Fig. 4.1.-1 Digital input testing
The following picture shows the menu used for output relay testing
Tests\Outputs. Observe that the self-supervision relay is activated in another
menu and is thus not included in this menu. The relays are activated in the order: SO,
PO and HSPO, starting from the right side.
Output states
= 000000
OutpSt
25
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
26
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
5. References
Manuals for the REX 521
Tool-specific manuals
27
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
6. Index
A
Alarm LEDs ........................................................................................... 8, 24
1-8 ........................................................................................................ 24
Modes ................................................................................................... 24
B
Bit masks .................................................................................................... 19
Altering contents .................................................................................. 19
Breaker ....................................................................................................... 17
Buttons ....................................................................................................... 10
D
Digital inputs
Testing .................................................................................................. 25
Display
Adjusting Contrast ............................................................................... 12
Backlight .............................................................................................. 12
Contrast ................................................................................................ 12
Display test ........................................................................................... 13
Language .............................................................................................. 11
E
Event view .................................................................................................. 16
H
H07 configuration
Measurement view ............................................................................... 16
HMI features ................................................................................................ 8
I
Indication messages
Condition monitoring ........................................................................... 22
Green LED ........................................................................................... 23
Help messages ...................................................................................... 20
Internal fault ......................................................................................... 20
Protection indication ............................................................................ 20
Self-supervision .................................................................................... 21
Start, Block ........................................................................................... 20
Trip, CBFP ........................................................................................... 20
IRF relay
Testing .................................................................................................. 25
J
Jump ........................................................................................................... 16
28
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
L
Latched output relays
Resetting ...............................................................................................10
LED indicators ........................................................................................8, 23
READY ................................................................................................23
START .................................................................................................23
TRIP .....................................................................................................23
Local control ...............................................................................................17
Local/Remote position ................................................................................17
Changing control position ....................................................................17
Control positions .................................................................................. 17
M
Manual control ............................................................................................ 17
Messages ...............................................................................................18
Measurement menu ....................................................................................15
Measurement view ......................................................................................15
Menu chart ..................................................................................................14
O
Object control menu ................................................................................... 17
Optically isolated serial communication port .............................................13
Output relays
Testing ..................................................................................................25
P
Parameters ..................................................................................................19
Setting ...................................................................................................19
Passwords ...................................................................................................12
Disabling HMI password ......................................................................12
HMI password ......................................................................................12
Serial communication password ...........................................................12
Primary values ............................................................................................ 13
Push-buttons ...............................................................................................10
Arrow button ........................................................................................10
Functions .............................................................................................. 10
Operating the relay ...............................................................................10
R
Remote control ........................................................................................... 17
REX 521 protection relay features ...............................................................7
S
Safety Information ........................................................................................ 8
Safety information ........................................................................................ 6
Selecting language ......................................................................................11
29
REX 521 Protection Relay 1MRS 751107-MUM
Operator’s Manual
T
Test
Display ................................................................................................. 13
Function block ...................................................................................... 26
I/O ........................................................................................................ 25
IRF ........................................................................................................ 25
Test mode ................................................................................................... 25
Cancelling ............................................................................................ 25
Timeout ...................................................................................................... 17
30
1MRS 751107-MUM Protection Relay REX 521
Operator’s Manual
7. Appendix A: Abbreviations
CT Current transformer
HMI Human-machine interface
HSPO High-speed power output
IRF Internal relay fault
LCD Liquid chrystal display
PO Power output
SO Signalling output
VT Voltage transformer
CBFP Circuit-breaker failure protection'
VD Voltage detector
31