You are on page 1of 52
(?) MITSUBISHI ELECTRIC CORPORATION | PROJECT : MEW PREVENTIVE MAINTENANCE pate: 18/71/08 SUBSTATION: MINA ABDULLA 'C’ 432/11kV_ TEST REPORT No: 110C O/ | sT REPORT FOR OVERCURRENT & EARTH FAULT RELAYS Voltage Level: 11k Panel No. : / Circuit Name S/,- aS OIG Relay Type: MOC-7B-G Make Mitsubishi Setting Range: O-S ~ A 0 IF Relay Type : MOC-78-G Make : Mitsubishi Setting Range: C-L - OG Mounting Semifush OC Voltage: 220V Rating > tame. cto: yoojra T OIC Red ¢ Plug | Time } Creep | Reset Operating Time (See) settiig | Mutter |_Amps._| Amps. Sef. Na ZRIRL tax x 8X] 10x syle = 135) 0-gs| 1-88 [rag] 1-91 3-99] -87 [7-97 CRITERIA Yoo/ | 0 -YS| ¥ 1007 |< Re NP BALBS-G-H/IS-2.0f 26-7.) Tore Blue > T pug | time | creep | Reset Operating Time (Sec.) Setting | Wuliplier | Amps._| Amps. Set.No: FR/RG 19x [2x 8X | _ 10x Style - [AAS] 0-48 | 7-APX| LAS -R-Y Y/Y] 1-891 SE CRITERIA (reo7| 0-95 | 300%. | Rai F/Bd Par) tenes RET fers pug | Time | Creep | Reset | ‘Operating Time (Sec.) ] setting | Muttisier | Amps. | Amps. Ser.No.: PR O69 13x | 2x 8X] 10x ‘syle = 0810-40 \0 2/|0-RojR| 9-66] 8 |7 RZ CRITERIA | eT] O-Go [760% ey, |8 AI 364: 5E-1-#| 0-126] RS er RLS Flag Operation & Resetting Wiring Tightness CP/RP, Switchgear, v_ |v) v_| Relay Terminais and Components viv iv { Insulation Check AC to Earth v| v] 7 _| Magnet Gap vi vie Insulation Check DC toEanh_| v | v|_~ | Mechanical Resetting viele Insulation Check ACtoDG | v | v| 7 | Hair Spring Assembly vi viv | Trip Contact v | v|_v | setting Pointer viviv Intertip Contactor v |v |_7 [Earth Wire Check intemal & extemal [7 | | ha | Alarm Local & Remote v, x Load Current Amps.) | Relay Current on oad | Rex ra The: (mA) | Comments MELCO ENGINEER MEW ENGINEER ae £ ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: 18/7/08 SUBSTATION: MINA ABDULLA ‘C" 432/146 TEST REPORT No: 11S0L 9, ‘TEST REPORT FOR SOLKOR RELAY Voltage Level Atkv Panel No.: / CircuitName : C/s- RS Relay Type Solkor B Ser.No. :AYEY7y Make: Reyrolle DC Voltage 220 At. No. 2850430010 Rating 4Amp CT Ratio : 400/18 ‘SECONDARY PILOT. TRIPPING PILOT | CURRENT ciRcuIT CURRENT TERMINAL RELAY | PHASE | AMPS] CONDITION De VOLTAGE OPERATION mA AC VOLTS RN | o-vs | OPEN 18-8 oP-2 (OPERATED (yn [To 76 OPEN 10 &2. Yor eae B-N ORY OPEN 1082 GoD OPERATED R-Y | 6-73 OPEN to 82 Ye-7 or Y-B O73 OPEN 1a 87 Yet OPERATED {-r-e [| 4-36 OPEN 10 8% Ws OPERATED RN | 7-00 ‘OPEN 2656, 95-5 OPERATED R-N | 7-s/ | SHORTED 10 Fo = NOT OPERATED STANDARD OPEN 99-121 OPERATED 1 7 ‘Aux. Contact Operation Y | Trip Circuit v Intertrip Retay 7 __| indication Local & Remote s Ingulation AC to Earth /__| beat Contact Motion “ Insulation DC to Earth VY _ | Contact Cleaning Insulation DC to AC /__ | Gheck Reset Device e Flag Operation & Reset /__| Plugin after Test y Spill Current [Coad Curent (amps)- | Relay Currentonload Ra | Yo Ba Ne (ma) Comments WELCO ENGINEER MEW ENGINEER ae x a MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: 16/1 /o@ SUBSTATION: MINA ABDULLA °C" 132/44kY TEST REPORTNo: 1106 02 I OR OVERCURRENT & EARTH FAULT RELAYS Voltage Level 44k PanelNo. : 2 Circuit Name 8/5 -RY O/C Relay Type : MOC-78-G Make Mitsubishi Setting Range : 0° ~ 2-0 G/F Relay Type : MOC-7B-G Make Misubish) Setting Range :0-A- 0 Mounting ‘Semifiush DC Voltage 220 Rating 4Amp. CT Ratio Yoon ore Rea 6 Plug | Time | Creep | Reset ‘Operating Time (See) Setting | Mutter |_Amps._| Amps Se.No.: $2099 13x [2X 8x] _ 10x ‘Style 725] 0-¢5| 1 80 [a5] BY ay) 1-92] 1-38 CRITERIA Toot| O-Y$|> 7007, |< PeP|F- HA 8 C0! YP. o] OT T l OIC Blue d Plug } Time Creep | Reset ‘Operating Time (Sec.), Setting | Mutiplier | Amps. | Amps. Ser.No.: £2 /oo tax] 2 | 8x | 10x ‘Style A eee CRITERIA toos | 0 - Ye [F004 120 119-19 4S B VB I 162.0] 7REIM EF o Plug Time Creep | Reset Operating Time (Sec.) Seting | Multiplier | Amps. | Amps Ser.No.: BROEE tax] ax | ox | 1x ‘syle: 02 |0-yolo aileroloy 3%] v7 | ORS CRITERIA, [oe 7] Oa [> 1007 |x Ro 1| O=1 FSV 3-06-74 [1 19-F eg] @ [SEF Re EF Flag Operation & Resetting Wiring Tightness CPIRP, Switchgear, vv |_| Relay Terminals and Components viviv Insulation Check AC toEarth | 7 | 7] 7 | Magnet Gap “vl Insulation Check DC to Earth | / ~~ | Mechanical Resetting Yiviy Insulation Check AC tC | “| ¥|_~/| Halr Spring Assembly Yi Trip Contact Z| VA | Seting Poirter AT Interrip Contactor ‘| | / [Earth Wire Check internal &Extemal_— | | vi ‘Alarm Local & Remote Load Current (Amps.)— ] Relay Current on toad | Ro- Yo Bo ‘Ne 18 Aany ma) | Yysad|USanA| GSana| 2-OmA Comments = MELCO wroneer [ents (MEW ENGINEER : ae= ¢ a MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE SUBSTATION: MINA ABDULLA ‘C’ 432/41kV DATE TESTRI 76/0/08 EPORT No: 11S0L 0.2 ‘TEST REPORT FOR SOLKOR RELAY. Panel No. :2. Voltage Level: 11kV CircuitName : S/g- RY Relay Type ‘Sokor Ser.No. :RY6Y G7 Make DCVolage 220 At. No 2650H30010 Rating CT Ratio ; 400/14 [SECONDARY PILOT TRIPPING PILOT CURRENT, ciRcuIT CURRENT TERMINAL RELAY ‘PHASE AMPS: CONDITION Dc VOLTAGE OPERATICN mA AC VOLTS, RN | 0-73 OPEN 10-49 Sy OPERATED Y-N OG OPEN 10-¥Y 88-0 OPERATED B-N ORR OPEN 70 -ty PF.2 OPERATED R-Y O66 ‘OPEN 10-48 Yo-R ‘OPERATED y-8 | 066 OPEN 1078 voy OPERATED (oR: [os | OPEN 10-8 Vo.s | OPERATED R-N /-00 OPEN AP ER 93-0 OPERATED R-N LST ‘SHORTED 10-66 : NOT OPERATED ‘STANDARD ‘OPEN 99-121 ~[ OPERATED ‘Aux, Contact Operation J | Trip Circuit v Intertrip Relay | Indication Local & Remote e, Insulation AC to Earth 7 | beaf Contact Motion v Insulation DC to Earth 7} Sentact Cleaning Z Insulation DC to AC 7 | Check Reset Device “ Flag Operation & Reset v Plug in after Test v Spill Current OSL, [leseGoren@imes)- | Relay urentonieas]R2 [ve [Be [Wa 1 b anys (mA) | 4Sana| HS x00] Ama] 2 Yooh Conuments MELCO croneen: Same MEW ENGINEER aS ¢ a MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: 76/11/08 SUBSTATION: MINA ABDULLA 'C'132/14KV TEST REPORT No: 1106 0g Te Votiage Level 1hKy Circuit Name o/s POR VERCURRENT & EARTH FAULT RE! - RB OIC Relay Type: MOC-TB.G Make Mitsubishi Panel No. :-3 Setting Range: 0.5 - 2-0 E/F Relay Type MOC-7B-G Make Mitsubishi Setting Range: 0-2 - O-€ Mounting Semifush De Voltage: 220V Rating : Amp, CT Ratio, Yoofa T OIC Red é Plug Time | Creep | Reset Operating Time (Sec.) Setting | Multiplier |_Amps._| Amps. 13x | x 8x 10x Ser. No.: FROGS style 7 25 | 0-5 |7- 90 7as |12-2| 9-% | %o|t Yo CRITERIA Too7| O95 >7007 4/201 7-13 AF EFA] Te 2.0f 2ET T Foc Blues Plug | Time | Creep | Reset Operating Time (See. Setting | Multiplier | Amps._| Amps. 13x] 2x x 10x, Ser. No. FROFR ‘Sie 7 asl a-us|/-Re vas a-o| 3-3¢ | 7-92 |t Yo CRITERIA 7ao7| 0 -ts [> 1007, |AO7|9 8A? BF -U BAP ROT] PLP) EF @ Pug | Time | Creep | Reset Operating Time (See) Setting | Muttiptiee | Amps._| Amps. Ser, No. : 820-72 13x] 2x ox | 10K Style OR | -Yo|d R/|0-20\/03| 7 ¥a|!' 7R|/ Ro CRITERIA Rot] @- Yo |>/a07 |< R07] P-/2|758-Y 4ISET-E| 19-1 RS] EF RIS [EF Flag Operation & Resetting Wiring Tightness CP/RP, Switchgear, ¥ | v| | Relay Terminals and Components vlely Insulation Check AC toEarth | | v| / | Magnet Gap viviv Insulation Check DC toEarth | v | y| /_| Mechanical Resetting AAS Insulation Check ACtoDc | ¥| v|_v_| Hair Spring Assembly PAA Z Trip Contact lv “7 | Setting Pointer vive Intertrip Contactor vv] 7 | Earth Wire Check intemal & extemal |] vy ‘Alarm Local & Remote vi[vfv ‘oad Curent (Amps) | Relay Current on oad | Rox (ma) Ye [ee [me I Comments = MELCO ENGINEER MEW ENGINEER 0 S a MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: 46/1// 08 SUBSTATION: MINA ABDULLA*G'132/41K¥ TEST REPORT No: 1180L. 0 2 TEST REPORT FOR SOLKOR RELAY Voltage Level dtkv Panel No. : 3 Cireut Name; S/s > RA Relay Type Solkor R Ser.No. :RYY8 IF Make Reyrolle DE Voltage 220 Ari.No, : 2850830010 Rating: 1Amp CT Ratio : 40014 SECONDARY PILOT TRIPPING PILOT CURRENT CIRCUIT CURRENT TERMINAL RELAY PHASE | AMPS CONDITION oc VOLTAGE OPERATION mA AC VOLTS, R-N Oe OPEN 12-97 GF OPERATED Y-N Org OPEN 1O- Fo 2-8 OPERATED B-N C2 OPEN 10-34 U3-# OPERATED R-v_ | 0 -¥2 | OPEN 70 FO Os ‘OPERATED Y-8 0: 2 OPEN 10° %) UY -6 OPERATED R-8 | 0-3 OPEN 70-72 Uy 2 OPERATED R-N 700 ‘OPEN RY. 8D Go 7 OPERATED R-N | 7-&% | SHORTED 70-95 : NOT OPERATED STANDARD OPEN 99-124 OPERATED ‘Aux. Contact Operation Y__| Trip Cireut v ‘intertip Relay /_| Indication Local & Remote Y Insulation AC to Earth /_| beat Contact Mation v Insulation OC to Earth / | Contact Cleaning Vv Insulation DC to AC Vv ‘Check Reset Device “2 Flag Operation & Reset | J Plug in after Test J | Spill Current Lead Curent (Amps) | Relay Current on load | Roe Ye [Be Ne | (mA) Comments Pilot CP'S ave Skotted at Uo Relogy Case MELCO cree: enent > MEW ENGINEER a ¢ a MITSUBISHI ELECTRIC CORPORATION [rrouecr MEW PREVENTIVE MAINTENANCE pate: 73///08 SUBSTATION: Ml ILLA 'C" 432/44KV TEST REPORT No: 1100 O¢/ ‘TEST REPORT FOR OVERCURRENT & EARTH Fi LAY: Voltage Level: 14kV PanelNo. : CrcuitName : C/s - 6 O/C Relay Type: MOC-7B-G Make Mitsubishi Setting Range: O-5§ — 20 EJF Relay Type > MOG-7B:G Make Mitsubishi Setting Range: 0-2 ~ O-€ Mounting ‘Semifush DeVoltage ; 220V Rating Amp. CT Ratio Yoofra I~ 1 OIC Red @ Plug ] Time | Creep } Reset Operating Time (Sec.) Setting | Muttipier | Amps. _| Amps. Set. No: PRIA 13x [x x] 10K Style 1,25) O-uS| 4 RG\7-As|-9| 8 -93| 6 8F| SF CRITERIA 4oo S| O GS|>l007\4 Rot \9-18-OE 85-0844 18 0? of (IES Torc Bues pug | time | creep | Reset Operating Time (Sec) Setting | mutter | Amps. | Amps. Ser. No.: BRAB/ 13x [2x 8x | 10x Style ras] 0-95 | 1 So] 726|w- Y 8) THLE OT ‘CRITERIA 7e07.| O- 75 [3/007 [RO FBG YH Wea 1G EF @ rug | time | creep | Reset | Operating Time (Sec) Setting | Muttipier | Amps. | Amps. Ser.No GROVE 13x] 5x 10x Style 0-2) 0 - vel O-R/| 0 -Ro 1-6] 2 17-78 [7 ‘CRITERIA Bot] 0 Yol> Toot AoE =! 42 BH) 156-1 172-124) R18] EF RIB EF Flag Operation & Resetting Wiring Tightness CPIRP, Switchgear, J | J) | Relay Terminals and Components. J % Insulation Check ACto€arh | ¥| |. | Magnet Gap aa Insulation Check DC taarth | | v| | Mechanical Resetting viv ~ insulation Check AC to DG ¥|_4\_7 | Haic Soring Assembly vvv Trip Contact | ¥|_v|_v_ [Setting Pointer YL 4 Vv Intertip Contactor [Lv | | ~ | Earth Wire Check internal & Extemal Y|viZ { “| [Alarm Local & Remote vive toad Curent Amps) ] Relay Gurenton oad | [= Bo Comments = nee crneen: Saar MEW ENGINEER a if a MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: 7/11/08 SUBSTATION: MINA ABDULLA ‘C'432/11kV TEST REPORT No: 11S0L Oy ‘TEST REPORT FOR SOLKOR RELAY Voltage Level: 41KV Panel No.: cireutName : S/¢ - 76 Relay Type ‘Solkor R Ser.No. :AYEY 26 Make Reyroile, DC Vottage 220V Att. No. 2650H30010 Rating tAmp CT Ratio : 40044 ‘SECONDARY PILOT TRIPPING PILOT CURRENT ciRcuIT CURRENT TERMINAL RELAY PHASE | AMPS | CONDITION oc VOLTAGE OPERATION mA AC VOLTS R-N Ow OPEN 10.82 S76 OPERATED YN | 6-7 (OPEN 70 BY LF ‘OPERATED B-N | 0-23| OPEN 70-68 FR ‘OPERATED R-Y | 0-68 OPEN 70 G2 Vo @ ‘OPERATED Y-B | 0-68 OPEN 10 82. Yo 3 Ceeeae, R-B O-8y OPEN 10-83 POF OPERATED R-N ft 00 ‘OPEN AIST 89-9 Coenen, R-N [| /- 67 | SHORTED 10-?o E NOT OPERATED ‘STANDARD OPEN 99-124 ‘OPERATED ‘Aux. Contact Operation Y | Trip Circuit Y Intertrip Relay J_| Indication Local & Remote v Insulation AC to Earth | beat Contact Motion v Insulation DC to Earth Y__ |Contact Cleaning 4 Insulation DC to AC JS _| Check Reset Device Flag Operation & Reset Plug in ater Test v4 Spill Current Load Current (Amps.)- | Relay Current on load | Rx “Tee No (mA) Comments :- MELCO woe Roa MEW ENGINEER ae ( ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE vate: 74/7/08 SUBSTATION: MINA ABDULLA ‘C”132/11KV. TEST REPORT No: 1106 O5 ‘TEST REPORT FOR OVERCURRENT & EARTH FAULT RELAYS Voltage Level atky PanelNo. : 5 CirevitName : &/g - 3 ‘OC Relay Type: MOG-75-G Make Misubishi Setting Range: 0-5 - 2-0 EF Relay Type: MOC-7B:G Make Mitsubishi Setting Range 0 2- 0° Mounting ‘Semifush De Voltage: 220V Rating : 4Amp. CT Ratio Yoo }ia 1G Red ¢ Plug | Time | Creep | Reset Operating Time (Sec) | Setting | Multipier |_Amps. | Amps. Ser.No.: F211 ¥ | 43x | 2x 8x 10X Style PRS] O-YS| 1-86 | AF IAVU YY | 1-91 | 88 CRITERIA 007.1 0-05 [> 00/0 |F1E AEE Te RG, OIC Blue ¢ Plug | Time | Creep | Reset (Operating Time (Sec) | Setting | mutipier |_Amps._| Amps. Ser.No.: BRA*SF 13x | 2x 8x, 10x. [sve FASO Us| 7-30] 7 as] 4-7] F-90[ 7-90 | Go CRITERIA Fo07| 0: Os [> 10a [ROY I13 BIH UBT AM F267 Uy) EF § T Pug | time | creep | Reset ‘Operating Time (Sec) Setting | mutiplie |_Amps._| Amps. Ser.No.: FROLO 13x] 2K x | 10x Style OR] OVO RIOR YT) Z-Jo|l #7 | RR (oemrenn ReT| © Vo [> 700 7| 4/20) |B - A 288-9 7 S618 179-724 RS EF RIS [er Flag Operation & Resetting Wiring Tightness CP/RP, Switchgear, Y || ~_| Relay Terminals and Components vyivi v Insulation Check AC to arth | VV) | Magnet Gap alee Insulation Check DC toEarth | /| 7] | Mechanical Resetting wv le Insulation Check ACto0G | | v|_¥_| Hair Spring Assembly mele Trip Contact ¥\ 7) v7 | Setting Pointer vi viv Intertip Contactor wv | v7 _| Earth Wire Check Internal & External Aas | ‘Alarm Local & Remote wv [oad Current (amps) = Rey Cureton ioad | Rex Yo Bo: No 1b Bamps (| Gaal Yamn| ¢2ma | 1-Pma] Comments = MELCO ENGINEER MEW ENGINEER Ss ie a MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE vate: 7¥ (108 SUBSTATION: MINA ABDULLA ''C' 432/14kV TEST REPORT No: 1180 O5 ‘TEST REPORT FOR SOLKOR RELAY Voltage Level ttkv Panel No.: 5 CircutName —: S/g - 8 Relay Type ‘Solkor R Ser.No. :24Y9B8 Ff Make Reyrolle De Voltage 220 ‘Art.No. : 2680H30010 Rating > 1Amp CT Ratio 4400/1 SECONDARY T PILOT TRIPPING PILOT CURRENT ciRcUIT CURRENT TERMINAL RELAY PHASE | AMPS | CONDITION oc vouTace | OPERATION \ ma AC VOLTS R-N O73 OPEN 70 -8/ SF -s— OPERATED Y-N 0-16 ‘OPEN 10 -&3 Gy OPERATED B-N CRA ‘OPEN 70-83 R.A OPERATED RY | o-65| OPEN 10 62, 7S am Cee, y-8 | 0-65] OPEN 70 83 Ged OPERATED r-8 | o-g2] OPEN 70° 8R GS) ‘OPERATED R-N | 7-00 OPEN RB Ob 98 ae R-N | ¢ 57 | SHORTED 70°93 - NOT OPERATED STANDARD OPEN 99-124 (OPERATED ‘Aux. Contact Operation lv Trip Circuit v 4 Interttp Relay Y__| Indication Local & Remote 7 Te Ty “} Insulation AC to Earth VY _ | Leaf Contact Motion SY Vingulaton DC to Earth VY | Contact Cleaning - Insulation DC to AC J | Gheck Reset Device v Flag Operation & Reset | 4 Plug in after Test ve Spill Current "Teed Gurent(Amps)- | RelayGurentoniad]Ra (Ya [ea [Aa (ma) | Pilot CFS ave Skeoted af Ihe Reloy Cese « Comments = MELCO ENGINEER : MEW ENGINEER, Se ¢ 4 ae MITSUBISHI ELECTRIC CORPORATION f= + MEW PREVENTIVE MAINTENANCE DATE: “4/02 SUBSTATION: MINA ABDULLA ‘C’ 32/t1hY S/S TEST REPORT No: DIFF 06 TEST REPORT FOR DIFFERE! x Voltage Level : s4kV Panel No.: 6 CireutName : 3OMVA Transformer No. / Relay Type: HUB-2-G Ser.No. :/3920, /892Y, Make Mitsubishi (3925 Rating : 1Amp DC Voltage: 220 Mounting : Semiftush Syle + S42BJA HV Side CT Ratio - 200/58 LVSide CT Rato~ 1600018 ‘Tap Seng; HV-1.0Amp.LV-4 SECONDARY miccraa | DER | “Gpem® | operate | eveMenr TerwiNaL | "AMPs COI | YESNO | * 1000% R-N S68 SB | $6 | Yee | 7H Hv YON 35. gat | 39 Yes_| 7009 sive BON Soy 2% | 9-39| ves |? \ RON $73 Bho 2 SE eb Ww Yon vot 333 |. Yo Yes SIDE BON 03s vio_| 2.29 | Yer whew [ow sTaBILITY [R-N[R-N| 10 | 137 | 9.6 By Ato werrario [¥-n]¥-N| 10 [197 | w-7 | G7@ | to samma_[B-N|B-N] 10 | 137 | 7o-¥ yo 8 Ao R[Y|e R|y[8 IGS Operation Vv Lv Magnet ii Tap Bridge Lv | Contacts AAS [Insulation Gheck AC to Earth Vz} | Wie and Terminal Check External AZ Insulation Check DC to Earth ¥| |v Wire and Terminal Check intemal] /| | / Tripping Vv A] [Replace Cover Yaw Check Cover Seal CL 7 instantaneous Device viadv Diferential AC Vote on Load Load Current (Amn 140 -BAemps Ro ye Bo : BY bay 19 Sav |S fanv. HV Side LV Side Relay Curent on Load (mA) na | vw | eo | N | Ro | vo | Be YooasA| loom A\FooanAl ~ — |/6¥ anf 0%mal Ova A Comments: MELCO ENGINEER MEW ENGINEER A MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE DATE: 43/7/08 SUBSTATION: MINA ABDULLA ‘c" 432/114 TEST REPORT No: 11REF Of ‘TEST REPORT FOR RESTRICTED EARTH FAULT RELAY Voltage Level : 11kV Panel No. Circuit Name : SOMVATransformerNo. / Relay Type: ARE-3-G Ser.No. Make — : Mitubishi Range 04-048 DCVoltage: 220v Mounting : Semiflush Tap Setting : 0.158 Rating Amps Sie + 843A SECONDARY serine | PICK-UP |DROPOFF Amps] Remarks INJECTION ‘Amps ‘Amps REF Bus Side 0.15 0-152 O ./R3 REF Neutral Side os | 2-753 | 0.8 Flag Operation Y | Wiring Tightness v Tap Setting S| Contact Cleaning 4 Fingulation Cheek AC to Earth Y _| Replace Cover v | Insulation Check DC to Earth J | Reset Device 4 | insuiaton Check DC 10 AC 17 | pping i Load Current Relay Current on load Comments = wncomonetn: Saeti= uewenanecr: 2 OF a MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE vate: /8/1// 08 SUBSTATION: MINA ABDULLA‘C” 422/4KV S/S TEST REPORT No: 11AVR 06 TEST REPORT FOR AUTOMATIC VOLTAGE REGULATOR Voltage Level: 11kV Panel No.: 6 CircuitName : 30MVA Transformer No, / Relay Type: LAA-4-G Ser.No, : 4393) Make Mitsubishi Rating ‘ov Mounting ; Semifiush Dc Voltage: 220V Style B40PJA REFERENCE | DEAD] SECOND INPUT REGULATING INDICATION, INPUT ZONE | (WrefDZ%#Vief) [STANDARD VOLTAGE |__ RAISE LOWER (oLTs) | SETTING VOLTS SECOND INPUT!1% [TR | IND.| TR ] IND |» VOLTS | 108.395 1434-10645 | vss) | — | = 107 16 108.605 107.52-109.69 = [= foes) | UNDERVOLTAGE | MEASURED AVR | STANDARD Lock by O.BVret + 3% DEAD ZONE | TIME DIAL | % VARIATION | REGULATOR OPERATING | INDICATION SETTING | SETTING ‘OF INPUT “TIME (SECS) % 5% 10% MEASURED 100.13 7% R 15 2 94.86 Sor R T1404 @ 05 L 1.5 2 119.47 Sow c Operation indicator Vv | Dials vw ‘Veet. Setting Board Y | Rearrelays v Wire and Terminal Check External Y__| Reset Device ¥v Wire and Terminal Check Internal | Replace Cover v Check Cover Seal | v Comments :- MELCO svoneer: SSa2> MEW ENGINEER : =< ¢ an MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE oat: 18/7/08 SUBSTATION: MINA ABDULLA ‘0 132/14V. TEST REPORT No: 1100 O¥ TEST REPORT FOR OVERCURRENT & EARTH FAULT RELAYS: Vottage Level Ky PanelNo. : 7 Circuit Name Puc Sle-0 ©rG Relay Type : MOC-7B.G Make : Mitsubishi Setting Range: ©. — 2.0 EF Relay Type : MOC-7B-G Make : Misubishi Setting Range: 0 2 — 0-24 Mounting semifush De Voltage: 2200 Rating Amp. CTRatio 9: YOO//A OIC Red @ Plug Time | Greep | Reset Operating Time (Sec.) Setting | Muttipier_|_Amps._| Amps. Se.No.: GRIGE 13x] 2x 8X | 10x ‘Style - 10s | O-ys | 130) 7:26 | 4-1] 3 FY) f- 9G¢| HG [crITeRIa 7eat| O- YS| lool |\ OB). |T1207 | F754 3 B-V-85 1 2-054 46-1 OIC Blue ¢ Plug | Time | Creep | Reset Operating Time (Sec.) Setting | Multiplier | Amps. | Amps Ser. No. : 2/6 13x | 2K 8x 10X. Style 1-9S| © -9S| 7 -R8|7-RY|NA| Y-08| 7-99 | 7 Yo CRITERIA Foo? | © - Us [> 7007 | <1R0F |9-73 68 0-V GY I5- 2-05] [1 EF 4 Pug | time | creep | Reset Operating Time (Sec.) Seting | Multiplier | Amps. | Amps. Ser.No.: 89 OXF 1.3K | 2X 8x 10X syle: 0 20| 0-yo |o Ka |0-a/\oi|9-s0|7-6/| 7-79 CRITERIA Rot [0-Go [> 1007 |X 7R0% [B-72]250-V BN) 5-1 A PTH RISE RTS TEF Flag Operation & Resetting Wiring Tightness GPIRP, Switchgear, | AL | Relay Terminals and Components Y\nie Insulation Check AG toEarh | v| |__| Magnet Gap Vie Insulation Gheck 0G to Earth | /'| y|_./ | Mechanical Reseting PA Insulation Check AC to DC vw Y | Hair Spring Assembly viviZ7 Trip Contact |r| v | Setting Pointer _ viviy Intertrip Contactor “| v/_/ | Earth Wire Check intemal Extemal || v| ~ Alarm Local & Remote ole le Load Current (Amps.)- | Relay Current on load | Ro- Yo Bo No IA bsangs mA) | Gyan Al YY ans] %Y¥-m4 | 1 Sa Comments = MELCO ENGINEER MEW ENGINEER : BS of ae MITSUBISHI ELECTRIC CORPORATION | Proucr + MEW PREVENTIVE MAINTENANCE vate: “7/1/08 SUBSTATION: MINA ABDULLA ‘CG 132/11kV. TEST REPORT No: 11S0L 0g ‘TEST REPORT FOR SOLKOR RELAY Voltage Level: 11kV Panel No.: 8 CreutName ; PAL S/g~/2 Relay Type ‘Sokor R Ser.No. : RYGPI2 Make Reyrolle DeVolage : 220V At. No. 2650130010 Rating ©: 4Amp CT Ratio : 400/14 f SECONDARY PILOT TRIPPING PILOT —) GURRENT cicurr CURRENT TERMINAL RELAY PHASE | AMPS | CONDITION Dc VouTace | OPERATION mA ACVOLTS R-N | 0-79 ‘OPEN 40-97 G75 | operated | (yew 0-6 PEN 70-77 PIE OPERATED | B-N 0-22 | OPEN 10-6 S73 OPERATED _ | R-Y | 0.66 | OPEN 70-6, You OPERATED y-8 0-66 OPEN 10-77 Yo-3 OPERATED RB | 043 ‘OPEN 70-¥6, 9-9 OPERATED RN | 7-00 OPEN 27-18 £99 OPERATED RN | 7 6g | SHORTED 70 V8. [NOT OPERATED STANDARD | _OPEN. | 99-127 | | OPERATED { ux. Gontact Operation er [ie Grout v_| Intertip Relay /_| Indtation Local & Remote Insulation AC to Earth | teat Contact Motion FA | Insulation DC to Earth 4 Contact Cleaning wv r Insulation Oc to AC | Check Reset Device z 1 Flag Operation & Reset V___| Plugin after Test eB | Spill Current | Load Current Amps)- | Relay Currentontoad | Re Tye laa Ne (ma) comments. 2¢lof C7'S are Sherlep od thy Leb CaSe MELCO ENGINEER MEW ENGINEER 7 rE § ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: 79 /“/08 SUBSTATION: MINA LAC 132/14kV TEST REPORT No: 1106 9 ‘TEST REPORT FOR OVERCURRENT & EARTH FAULT RELAYS Voltage Level dikv PanelNo. : CircuitName — : S/g - 5 OIC Relay Type : MOC-7B-G Make Mitsubishi Setting Range: O-S — R-o E/F Relay Type MOC-7B-G Make Mitsubishi Setting Range: CR - O-F Mounting Semiflush DC Voltage: 220 Rating : tam, CT Ratio Yoo! OIC Red § Pug | Time | Creep | Reset | Operating Time (Sec.) Seting | Mutter | Amps. | Amps. Set. No.: PAZ /F 13x] 2x EB 10x. Style = 7-25| 0: YS| 137 | 7-29 |8-3 Y-00 | 7-83 | 130 CRITERIA 7o07.| O- os [seo |XiROL |F-BAS EY A 2-04] UT He) OIC Blue Plug | Time | Creep | Reset Operating Time (Sec.) setting | Mutipier | Amps. | Amps Set. No.:B27 09 13x] 2x | 8x 10X Sie: = 1-8 0-07-30 |7-26|72-8| YT] 7 Fo[ TOF CRITERIA Too7, | 0-06 | > Zo0y |5 20/919. 6|301Y Bh AAT |-R Fe f EF > Plug Time Creep | Reset Operating Time (Sec.) Setting | Mutipior | Amps. | Amps. Ser. No. : 89.0 ¥5- tax] 2% | 8K | 10x [sve - 0 -A|O-Yo| 0-2/0 20/1 | P88 | 1-7 \1-22 CRITERIA Aos| © - Yo |> 1007) 1/201) F 19) 9 30-VIN! S61 T 194-98. RIE LEF RTS EF Flag Operation & Resetting Wiring Tightness CPIRP, Switchgear, V| A) | Relay Terminals ané Components Yi7l< Insulation Check AG toEarth | 7 | ¥| | Magnet Gap viviv Insulation Check DC to Earth ¥| ~_| Mechanical Resetting Vivvo Insulation Check AC to DC v_| | & | Hair Spring Assembly iv lvl Trip Contact | Y |v | ~_| Setting Pointer vivi[y Intertrip Contactor Y | v|v_| Earth Wire Check internal & External wiv le ‘Alarm Local & Remote vi viv oad Current (Amps.)— | Relay Current on toad | Ro- Yo Be Ne 8 Danps (mA) | Joana | SOaA| POapa| /- Oma] Comments = MELCO ENGINEER wewenoneer: SSE ( ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: (9/#/08 SUBSTATION: MINA ABDULLA‘C'132/11KV TEST REPORT No: 11SOLO9 EST REPORT FOR SOLKOR RELAY Votage Level: 11kV Panel Ho.: 7 CireuitName : /g-S RelayType Soko SenNo, OSG Make: ‘Reyrote DC Voltage 220 Att, No. 2650120010 Rating «©: Amp CT Ratio : 40014 ‘SECONDARY ] PILOT TRIPPING PILOT CURRENT crRcurr CURRENT TERMINAL RELAY PHASE [AMPS] CONDITION Dc VOLTAGE | OPERATION mk ACVONTS RN |O-"y| OPEN 70 -F¥ Y2-0 | OPERATED yen | O-7¥ | OPEN 70.98 OF-0 OPERATED BN | 0-29 OPEN 70-99, V2 eae R-Y O-%o | OPEN 10-98 Ys -7 OPERATED 8 | O-%o | __ OPEN 10.58 CS 1 | OPERATED RB | O35 OPEN 70-99 OU OPERATED TTR-N [¢- 00 ‘OPEN RE-RG %.2 ‘OPERATED RN | 7-99 | SHORTED 71-20, : NOT OPERATED STANDARD OPEN po-121 | | OPERATED ‘Aux, Contact Operation Ty [tip circuit v Interrip Relay | Indication Local & Remote v | Insulation AC to Earth _| beat Contact Motion | | insutation DC to Earth w_| Contact Clearing = 1 [sutton DG t9 AC V_| Check Reset Device vi! | Fea eran & Reset S| Plugin atter Test 1 Spill Current - Vani Caran ipa). | Rela Covetontas [Rar uae ee EAaps ()) Qoapa| Roan4| Poan4! /-Ea/) Comments = MELCO ENGINEER MEW ENGINEER ad a MITSUBISHI ELECTRIC CORPORATION PROJECT MEW PREVENTIVE MAINTENANCE pate: 30/77/08 SUBSTATION: MINA ABDULLA‘C" +32/14hV TEST REPORT No: 1106 /0 ‘TEST REPORT FOR OVERCURRENT & EARTH FAULT RELAYS: Voltage Level aky PanelNo. : / O CreutName : QSOKVA AY TAL / OIC Relay Type : MOC-78-G Make Mitsubishi Setting Range: 0.5 — Q:0A E/F Relay Type Mitsubishi Setting Range: @-/ — 0 Amp, CT Ratio 2000/14 i T 5 1c Red Piug | Time | creep | Reset Operating Time (Sec) Setting | Multiplier | Amps. | Amps. Ser.No: B2799 tax] 2x | ox | 1% Style_: 132PJA bol o-6 | pol ho rel 6-$s 19:42 | 8? Bipeced Vaue 07%] 0-6 |>reey leroy 2-1 log puslasun2 yl ea—/92 OIC Blue > Plug Time Creep | Reset Operating Time (Sec.) Setting | Multiplier_| Amps._| Amps. Ser.NO! BOE 13x | _2X x | 10x [sve_ssep Lio Loe [p02 [yo alse vlosy [1-3 Expected Value toox| 0-6 |>reoy kiz oy |i2 - Gl 507~Gunlezy 2-90 kb: EF 6 Plug | Time | creep | Reset Operating Time (Sec.) Setting | Multiplier |_Amps._| Amps. Ser. No.: 8203 13x | 2x ‘8X 40x Style: 133PJA -2 [0-6 lox lowe leg |5-88 [oz [1-88 Eapeced Vaue 22071 0-6 bpro0% kereo% bev |¢.02-6-F lp ay-2-2)-48-7- 92 R 8 &F RB EF Flag Operation &Reseting “Wiring Tightness CP/RP, Switchgear, Relay Terminals and Components nae Inuiation Check ACto Earth «= Magnet Gap Yvy \neulation Check DC toEarth = Mechanical Resetting vve Insulation Check AC to DC ~~ ¥ Hair Spring Assembly eee Trip Contact Y % % Setting Pointer yvivy Intertrip Contactor Y % % earth wire Check Internal & extemal YY Alarm Local & Remote ¥ a Load Current- - Relay Current onload = Ro Yo Bo No Comments = ; ees MELCO ENGINEER : MEW ENGINEER ; =? a MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE DaTE: 022/1.2/ 08 SUBSTATION: MINA ABDULLA ‘C'132/11kV TEST REPORT No: 110CF / «2 ‘TEST REPORT FOR OIC & E/F RELAYS Voltage Level: 11kV PanelNo. : /100y |<207. lara - Gtr} 2 su. 296)1-68-1-98 OVC Blue ¢ Pug | Time | Creep | Reset Operating Tine (See) | Setting | Mutiplier | Amps. | Amps. Set.No.: 82/15 tax] 2x | ox [10x Style: 132PJA re 102 10°99 |/6.515:53 19:54 | /. Ja | Bopeced Vahe [oor poo y, le2ov ba~re eed top o.30-2-D4za-1-92) EF > Plug Time ] Creep | Reset ‘Operating Time (Sec.) Setting | Multiplier_| Amps. _| Amps. Ser.No.: 89081 43K 2x 5x 10X Sle :133PJA__ | Oy 6 los pro |u| 5 DS6 | 189 Expected Value 2071] a6 [ror | eOf |KAFLF-L2 6) F-85841 -T5-2.05} 796-110) Or Bie § T creep | Reset Operating Time (See.) Ames. | Amps. Ser. NO: BP MIT 13x | 2x 8X 40X Style 7-5) 0-0 | Far | RG 10-9 P-9| 7-96] 7-78 CRITERIA 00%. | O-ys 1007 1267. PE APR -Y GF OM P56 lee e Pug | Time | Creep | Reset Operating Time (Sec.) Setting | Mutiplier Amps. | Amps. ‘Ser, No.: £0 OFF tax] 2k Xx 70x Style: OR | O- YO | ORS) O-Ro V-0| 2-69 1° FR| RE ‘CRITERIA Rol | O- Yo |>/07 |<7R07 |B= 19 |F B-GRY SE-1-G|/ 2-1 RIBTEF RIB | EF Flag Operation & Resetting Wiring Tightness CP/RP, Switchgear, M11 | 4 _| Relay Terminals and Components vitlv Insulation Check AG toEarth_ | J |v |¥_| Magnet Gap via wv Insulation Check DC toEarth | v |v |v _| Mechanical Resetting Pale\rze| | insutation Check AC to DC. ¥ |e) ¥ | Hair Spring Assembly Vivi Trip Contact V |v |~_| Setting Pointer Yiviv [tetertip Contactor v |v | Z| Earth Wire Check intemal & External Vi4~ i ‘Alarm Local & Remote Yiviv Load Current (Amps.) — Relay Current on load | Ry Yo Bo Ne Boat) Aanps (A) | 50- anh] 50-6 wh) S0-6a9A) /-Band | Comments : WMELCO ENGINEER MEW ENGINEER: Fo ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE vate: 23/1/08 SUBSTATION: MUN, LA‘ 132/14KV TEST REPORT No : 1180L /¢y TES} RT FOR SOL RELAY Votage Level atky Panel No.: ty Circuit Name 6fe-27 Relay Type Solkor R Ser.No. : QYEYYs Make —: Reytolle 0C Voltage 220 At. No 26501130010 Rating: 1Amp CT Ratio : 40018 SECONDARY PLOT TRIPPING PILOT CURRENT CIRCUIT CURRENT TERMINAL RELAY PHASE | AMPS | CONDITION oc VOLTAGE | OPERATION mA AC VOLTS [RN [Ow ‘OPEN 70-86. G2 ‘OPERATED yn | 6-77 ‘OPEN 16-85 SEF coe en | 0.22 OPEN 10-85 ra ‘OPERATED R-¥ | o. 6% OPEN 10 8S" vot oer Y-B | 0.67 ‘OPEN 10-8 wy OPERATED RB | Og ‘OPEN 70 8" V0.2 OPERATED R-N | /:@0 ‘OPEN 6-49 BU ‘OPERATED R-N | 4 60 SHORTED 40 8&6 : NOT OPERATED STANDARD | __ OPEN 99-124 | OPERATED r 1 ‘Aux. Contact Operation [ [rte cir v Intertrip Relay J | Indication Local & Remote v | insulation AC to Earth VV | Leat Contact Motion v I insulation DG to Earth VY _| Contact Cleaning - ' insulation DG to AC J | Check Reset Device Ta { Flag Operation & Reset J | Pluginafter Test a t Spill Current 0: USamp JLoad Curent (Amps)- | Relay Current on load Tye Ba ae Ro - MpArops (ma) &. bans, $0 baa] So- 60h) /- a4 Comments :- MELCO sroneen: | nes I> MEW ENGINEER = 100Y. [1207 |8-1a) 8-8-4 S| BTA 27 RIBTEF R[B IEF Flag Operation & Resetting Wiring Tightness CP/RP, Switchgear, more Ld) | Rey Terminal and Components way Insulation Check AC to Earth | J ¥ | Magnet Gap Si viv ‘insulation Check OC toEarth | V| ¥| | Mechanical Resetting viv insulation Check ACt0DC_| S| r| v_| Hair Spring Assembly “77 ] Trip Contact ¥ | A_7 | Setting Pointer Vivi~ Intertrip Contactor |<] VW | earth Wite Check internal & External Yivi7 ‘Alarm Local & Remote Yiv So [Load Current (Amps.)- [Relay Current on load | Re- Yo. Bo bY Aanps (mA) | 60a | 60 4) “60a04| 1 Bank Comments : MELCO ENGINEER pfeil MEW ENGINEER Se2i ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE vate: 23/1/0F SUBSTATION: MM so 492111ky TEST REPORT No: 11S0L 65 ‘TEST REPORT FOR SOLKOR RELAY Voltage Level: 11kV Panel No. £5 CircuitName : Aese-G/e-F Relay Type SokerR —Se.No. = AGYGa Make: Rewolle DC Voltage za0v. Ar.No. : 2650490010 Rating: Amp CT Ratio : A008 [~— SECONDARY PILOT, TRIPPING PILOT CURRENT ciRcumt CURRENT TERMINAL RELAY ["BHASE | ANS] CONDITION oc VOLTAGE | OPERATION mA AG VOLTS R-N | O-"y ‘OPEN 10-80 SS OPERATED YN | Of | OPEN 10 SOG OPERATED BN | 0-A3 | OPEN 70.60 Vo.2 OPERATED R-¥ ©-68 OPEN 10 Bo We? OPERATED y-8 | 0-6g | OPEN 70 & Oh OPERATED R-B | O9y | OPEN 70-80 We OPERATED R-N_| 7-00 | OPEN PPB) 96-0 OPERATED R-N | 7-6/_|_ SHORTED 70-8) : NOT OPERATED ‘STANDARD ‘OPEN 99-121 |__OPERATED ‘Aux. Contact Operation Vy rep cieut Ty | Intertip Relay / | Indication Local & Remote v 4 "Ingulation AC to Earth | Leaf Contact Motion v ! insulation DC to Earth v7 Contact Cleaning Y 1 F insulation DC to AC _| Cheek Reset Device v t | Fag Operation & Reset v/_| Plugin ater Test V | Spill Current Load Gurrent (Amps.) = Relay Current on load | Ra [xe | i Comments: I Yo¢ C7°S ase Chote! ad thy Relosy Se. MELCO woneen eenaait= MEW ENGINEER AES ao MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: 86/1/08 SUBSTATION: MINA ABDULLA ‘C’ 132/11kV S/S. TEST REPORT No : 11DIFF 6 ‘TEST REPORT FOR DIFFERENTIAL RELAY Voltage Level : 44k Panel No.:/6 Cireut Name : 3OMVA Transformer No. 2 RelayType : HUB2G — SeNo. :/9724, /$9.22 Make; Mitsubishi 139A) Rating 1Amp DC Voltage: 220v, Mounting ; Semifush Style B42PJA HV Side CT Ratio - 200/14 LV Side CT Ratio - 1600/14 Tap Setting: HV-1.0Amp.LV-.0amp. 7 SECONDARY || ore. | “Geen” | operated | eLteir TERMINAL | AMPS Col YESNo | 100% RoW 330 see | eyo | ves | 0/6 WW YN GES 6 2-86 Yes pei i SIDE BON IE gov | avg | Yes 1072 R-N YS0 Gar 24 Yes w Y-N Y3P Su RG Yes SIDE B-N ee RIG. BRR yes wfilw lw fw stapiiTy [R-N|R-N| 10 | 137 | 8 Samad 66 -/my| Vo tveTRaTIO Y-N|Y-N| 10 | 137 | /S-fana| S39 Sav] Vo sama_[e-N[B-N| 40 | 137 | 77 Pana] ST-0mm| wo R]Y|8 R]Y |B) ICS Operation Y |Z | 7 | Magnet vias Tap Bridge S| /| 7 | Contacts 4 Az Insulation Check AC to Earth | 4 | Z| Wire and Terminal Check External 44 Insulation Check DC to Earth | 4 | 7 | Wire and Terminal Check Internal Via Tripping |r| /| Replace Cover vivflZ ‘Check Cover Seal | ¢| A Instantaneous Device vivi~] Diferenial AC Votaae on Load Load Curent (Amps) 91 -2.6m ps Ro we [a env | 18 -Gev | 1Q-onv Hv Side Lv side Relay Current on Load (mA) Ro | vo | po | N | RO) YO | F9mA|PamA| Foon, — | Canal Rana 183. Comments := ; MELCO ENGINEER psn MEW ENGINEER Ae iy ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE vate: 28/71/08 SUBSTATION: MINA ABDULLA 'C'132/11kV TEST REPORT No: 11REF 76, TEST REPORT FOR RESTRICTED EARTH FAULT RELAY Voltage Level : 11kV Panel No.: /6 Circuit Name : 30MVA Transformer No, 2 Relay Type > ARES-G SerNo. : 9939 Make Mitsubishi Range 01=0.48 DC Voltage: 220V Mounting: Semifush Tap Setting : 0.154 Rating samps Style: S43PUA ‘SECONDARY SETTING Pick-up | DROP OFF Amps Remarks INJECTION ‘Amps Amps REF Bus Side 0.45 0-15] O.1RE REF Neutral Side 0.15 0/52 ORF Flag Operation Y | Wiring Tightness v Tap Setting / | Contact Cleaning v Insulation Check AC to Earth VY _| Replace Cover aw Insulation Check DC to Earth JY | Reset Device v Insulation Check DC to AC J | Tripping S Load Current | -2-Séaupg| Relay Current on load Lémb, Comments :- MELCO ENGINEER : MEW ENGINEER aa" ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: 30/“//o & SUBSTATION: MINA ABDULLA 'C’ 132/41kv S/S TEST REPORT No: 11AVR 76 TEST REPORT FOR AUTOMATIC VOLTAGE REGULATOR Voltage Level: 411kV Panel No.: 1 6 Circuit Name; 30MVA Transformer No. Relay Type > LAAAG Se.No. : /3933 Make Mitsubishi Rating tov Mounting : Semifiysh De Voltage: 220V Style: S40PJA REFERENCE | DEAD | SECONDINPUT REGULATING INDICATION INPUT ZONE | (Vref*D2%eVret) [STANDARD VOLTAGE | _ RAISE LOWER, (voLTs) SETTING VOLTS SECOND INPUT+1% | TR | IND.| TR | IND % voLTs f 105.395 104.34-106.45, /05:3| R na oe 107 15 108.605 | ___‘107.52-10968 = [= Tost UNDERVOLTAGE | MEASURED AVR | STANDARD LOCK BE'Q 0.8Vref + 3% DEAD ZONE] TIME DIAL] % VARIATION | REGULATOR OPERATING | INDICATION SETTING | SETTING (OF INPUT TIME (SECS) % 5% 10% MEASURED f 100.13 *5 R 16 2 3406 4-7) R 114.04 7-8 t 18 2 119.47 5:02 L ‘Operation Indicator Y | Dials ¥ Viet. Setting Board | Rearrelays wa Wire and Terminal Check Extemal Y | Reset Device “ Wire and Terminal Check Internal v_| Replace Cover v Check Cover Seal “ Comments MELCO ENGINEER MEW ENGINEER SS i ae MITSUBISH! ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: 9/4 / OF ‘SUBSTATION: MINA ABDULLA ‘C" 432/114 TEST REPORT No: 1100 1 TEST REPORT FOR OVERCURRENT & EARTH FAULT RELAYS Voltage Level ty PanelNo. 1 GireuitName : Chg - J OIC Relay Type : | MOC-78-G Make Mitsubishi Setting Range: 0.5 ~ 2-0 EJF RelayType : MOC-TBG Make Mitsubishi Setting Range: O-2~ O-8 Mounting Semifush DC Voltage: 220M Rating amp. cT Ratio §—-: Goo/ra 1G Red § Pug | Time | creep | Reset Operating Time (Sec.) Setting | Multiplier | Amps. | Amps. Ser. No.: F270F 13x] 2x 6x | 40x Style 7 as | O-US | 1-36 | 7 26)I-9\ 3 -% \l- %_|7- 9 CRITERIA \root.| O- Gs [S007 |X 1207]7-18 G3 BF V-B) LAO | BH | orc Blue | eiug | time | creep | Reset ‘Operating Time (Sec.) Setting |_Muttiplier_|_Amps._| Amps. [Sen no %Q/RO Vaax[ 2x [ x | 1x Style: 4.95| O-Ysl 7:RE\FP-AG\4-G\ 8-97 GF | 7-97 (aren Tool | © tts 131007 |S10 D469 1-8 Hh 0m Hb Pe) fer» Pug | time | Creep | Reset ‘Operating Time (Sec.) Setting | Multipiier_| Amps. | Amps. [‘Ser.No.: F2O 66 13x] 2X 8X 10x syle: C2 | 0-Y0\C R004) ATW / V8 | 7-22 | | CRITERIA Rot] O° Yo |rle04 |X AOL 6 = 14] F FBV) 56-78 | 18-Fg R [BI EF RTS EF Flag Operation & Resetting Wiring Tightness CP/RP, Switchgear, I V |v) v | Relay Terminals and Components viviv insulation Check AC toEarth | | | v | Magnet Gap Vivv [insulation Check DC to arth | v | y| v/_| Mechanical Resetting viviv Tnstiation Check ACtoDC | v"| yw] v_| Hair Spring Assembly viv Trip Contact Ty] 7] | Setting Pointer viviv Intertrip Contactor v1 vi w_| Earth Wire Check Internal & External viviv i [Alarms Local & Remare av Lead Curent (amps) — | Relay Gurent on oad | Rex Yo Bo No 18 ovegs| (A) UomA | Wbma- \Pbma | ¢-beod Comments :- MeLco crn: saat 2 MEW ENGINEER an MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: PY///08 SUBSTATION: MINA ABDULLA ‘C" 432/14hy. TEST REPORT No: 1180L 7 | ‘TEST REPORT FOR SOLKOR RELAY. Voltage Level KV Panel No.: 77 CireutName —: SJ ~ 7 Relay Type 2 SolkorR Ser.No. :RVUYEPG Make Reyrolle DG Voltage z20v ‘ArtNo, : 2650H90010 Rating: 1Amp CT Retio : 400/14 | SECONDARY PILOT TRIPPING PILOT CURRENT. CIRCUIT CURRENT TERMINAL RELAY [PARSE T AlPS—| CONDITION De VOLTAGE | OPERATION A AC VOLTS R-N | O-/y | OPEN 10-73 CB6 OPERATED Yn | O-/7| OPEN 10-9 BIR OPERATED 8-N O 23 OPEN 10-92 vos OPERATED [ery |o-68 ‘OPEN 10 93 Ub OPERATED | \y-8 [0-68 OPEN 10-23 Ys OPERATED R-B OR ‘OPEN 70 FZ YULo OPERATED R-N | 7-00 ‘OPEN QF: IP O/ | OPERATED R-N | 7. 6y- | SHORTED 10.98. : | NOT OPERATED ‘STANDARD oPen [99-124 OPERATED j r 1 ‘Aux. Contact Operation SY Trip Circuit v r Taman Intertrip Relay |__| Ineteaton Local & Remote 4. 4 | Insulation AC to Earth rA Leaf Contact Motion, am "insulation DC to Earth Y__| Contact Cleaning Pinsulation OC ta AC YS _ | Check Reset Device | a | Fag Operation & Reset J _| Plugin after Test vi | Spill urrent Load Current (Amps.)- | Relay Current on fad | Rez Ye Jez |e (mA) 4 conmens. 2ilok C7'S are Skooted af fhe Lelocy Cese. ; = £ MELCO ENGINEER, MEW ENGINEER a MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE SUBSTATION: MINA ABDULLA 'C'432/41kV DATE: RY/7/, /08 TEST REPORT No: 1100 48 ‘TEST REPORT FOR OVERCURRENT & EARTH FAULT RELAYS Voltage Level Athy PanelNo. :78 CircutName ; Dare She * ¥ OIC Relay Type: MOC-7B-G Make Mitsubishi Setting Range: O.5 — 2-0 EFF Relay Type : MOC-7B-G Make Mitsubishi Setting Range: 0-2 — OG Mounting 2 Semifush DC Voltage : 220V Rating stamp. cTRatio §— : Yoo lym, OIG Red ¢ Plug | Time | Creep | Reset Operating Time (Sec.) Setting | Multiplier | Amps. | Amps. Ser.No.: $2096 13x] 2x x 10x syle: /32 pa |/ AS| O- YS |7-RB |PRE- ADC. 16 | 7-96 |7- Go CRITERIA 007) O- US| $1007, |C207 P19 65 BY 65! 5-2 OF Al -4) OIC Blue ¢ Plug | Time | Creep | Reset Operating Time (Sec.) Setting | Muttipier | Amps._| Amps. Ser.No.: 82176 13x] 2% ex__| 10x Style: J 2PGH|*- as| o-Y¥s |7-8o [7-26 Fo] Y-12 | 7- %| 7-Go CRITERIA FooT| 2 -Ys| + lao L| RON P86 EV-E| BRC HG) EF 6 Plug | Time | Creep | Reset Operating Time (Sec.) Setting | Multiplier | Amps. | Amps. Ser.No 92087 13x [2x x | _10x Style =/33 pga C 210-Yo|0-24 |O-Ro 0-6| 7°98) 0. xf) 7:-RI CRITERIA Rot | © Yo leer |A7a0/ B-7I EV HM IE-7 GIT RS [EF R[ 8 [EF Flag Operation & Resetti CPIRP, Switchgear, “er mi Y nd Components viviv Insulation Check AC to Earth | J | | Magnet Gap Yiviv Insulation Check OC to Earth | /| / J | Mechanical Resetting Vis wv insulation Check ACtODG | V| ¥| | Hal Spring Assembly 47 ‘Trip Contact v |v | o [setting Pointer viv Intertrip Contactor Liv Earth Wire Check Internal & External Y{4v ‘Alarm Local & Remate Yo Load Current (Amps) | Relay Current on oad | Ro- Ye Bo Ne Re. branps (MA) | Aan | FRapnA| $2294 | / Seon Comments :- MELCO ENGINEER : MEW ENGINEER BER C a MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: &Y/7//08 SUBSTATION: MINA ABDULLA ‘C' 432/11KV TEST REPORT No: 11SOL /Q ‘TEST REPORT FOR SOLKOR RELAY Voltage Level: 41KV Panel No.: / 2 a Circuit Name Pare Ye* ¥ Relay Type : SolkorR Ser.No, : PYEOS6 — Make Reyrolle DC Voltage: —-220V Att. No. 265030010 Rating «; 1Amp CT Ratio : 400/14 ‘SECONDARY PILOT TRIPPING PILOT CURRENT CIRCUIT CURRENT TERMINAL RELAY PHASE | AMPS] CONDITION Dc VOLTAGE | OPERATION MA ACVOLTS R-N | O-*9 ‘OPEN 70-81 SOS— OPERATION YN [0-46 OPEN 10-8 ory OPERATION BN | O-a/ OPEN 70 &3 b-0 OPERATION RY | 0 -6$" OPEN 10 -8/ Go OPERATION y-B | 0-65 OPEN 10 8S 89-9 OPERATION R-B | 0.32 OPEN to $f PBS OPERATION RIN 17.2 ‘OPEN EGE 7 OPERATION R-N 1S ‘SHORTED 10 86 - OPERATION ‘STANDARD ‘OPEN 99-121 ‘OPERATION ‘Aux. Contact Operation v Trp Circuit v Intertip Relay Z Inication Local & Remote Insulation AC to Earth J Leaf Contact Motion v Insulation DC to Earth i Contact Cleaning va Insulation DC to AC Sf Check Reset Device a Flag Operation & Reset J Plug in after Test 4 Spill Current Load Current-= Relay Current onload Rox Ye bo Ne comments» Pilot CFP's are Skooted of Me Rehey Gse. MELCO ENGINEER wewenawerr: —_ 25ARE ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE vate: 26/08 SUBSTATION: MINA ABDULLA ‘C' 432/1tkv TEST REPORT No: 1100 77 ‘TEST REPORT FOR OVERCURRENT & EARTH FAULT RELAYS. Voltage Level ‘Ky Panel No. : 79 CircuitName : Se - O/C Relay Type: MOC-7B-S Make Mitsubishi Setting Range : 0. - 2-0 EJF Relay Type: MOC-7BG Make Mitsubishi Setting Range : 0-42 ~ O-F Mounting Semiflush Dc Voltage: 220V Rating Amp, CT Ratio yoo fia OIC Redo Plug Time ‘Creep 1 Reset Operating Time (Sec.) Setting | Multiplier_| Amps. | Amps. Ser. No. ZROMY 13x [2x x] MK swe: /32PGa|7-a5 10-45 |7-R8 |7-24|7.6| Y-02| 1-9 [797 CRITERIA 7007 | O- US [> T0oT\T Re (PIPL SEO EF 2-0 TG) ! orc Blue e Plug | Time | Creep | Reset Operating Time (Sec.) Setting |_Multiplier_| Amps. _| Amps. Ser. No.: PROF E 13x | 2x 8X 10x. Sye 1 /78RPIa|7-RS| O- GE] Go [726 | 2-6] P-93|7- B® |7-Go CRITERIA WOT | FOS |S7007 |< ROY |O-14-4g- GH I PY I EF o Plug Time Creep Reset Operating Time (Sec.) setting | Multiplier | Amps. | Amps. Ser.No.: FAOYO 13x | 2X x | _ 10x, Syle 3493 2501 0-2 | O-Go |O'R/ [0 RO|N-2| 8°76 | 1% | RY CRITERIA R07 | O- Yo [S007 | TROL, 8 -79\3 8-4 Be S678 | 172-14 RS EF eF Fea reraion Aeseing | | | Wear emai ana components x insulation Check AC toEarth || /| “ | Magnet Gap / Insulation Check DC to Earth, Y_| Mechanical Resetting Jf Insulation Check AC to DC VY AZ | Hair Spring Assembly f ‘Trip Contact Jf | Setting Pointer /| Intertrip Contactor V1 v¥|_~_| Earth Wire Check intemal & External |__| Atarm Local & Remote v Load Current (Amps.)- | Relay Current on load | Ro: ‘Yo. Teo (ma) | Comments ‘MELCO ENGINEER MEW ENGINEER SER f ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: 2640/08 SUBSTATION: MINA ABDULLA ‘C" 132/t1KV TEST REPORT No: 1180L / TEST R REI Voltage Level: 1nKv Panel No.: 79 cretName : O/y -Y Relay Type SokacR —Ser.No. :RYOYY/ Make: Beyrolle DC Voltage 220V Art. No. 2650! Rating Amp CT Ratio : 40014 SECONDARY PILOT TRIPPING PILOT CURRENT circu CURRENT TERMINAL RELAY PHASE | AMPS~| CONDITION De vouTaGe | OPERATION MA AG VOLTS, R-N O78 ‘OPEN 7O 3 G62 OPERATION YN | 0-76 | OPEN 70-82, GED OPERATION B-N | 6-22 ‘OPEN 70 -f2 | oF ‘OPERATION R-Y | 2-67 ‘OPEN 10 G2 Yet OPERATION. y-8 | c.67| OPEN 10-82 7 OPERATION RB | 033 | OPEN 10 2 wk OPERATION R-N 7-00 ‘OPEN RO FE. Fou OPERATION [UR-N | 7-66 | SHORTED 70 -8Y. : OPERATION STANDARD OPEN 9.9-12.1 OPERATION ‘Aux. Contact Operation Trip Circuit v Inertip Relay v Indication Local & Remote. 7 Inston ACI Eat Leat Conactioion Insulation Dc toEath Contact Clearing Y Insulation DC fo AC vy Check Reset Device = Flag Operation Reset Plug in after Test Lf ‘Spill Current Load Current- Relay Current onload Ro Yor Be Ne comments Pi/af CP's ave CShosted af ty Leloey Case MELCO ENGINEER MEW ENGINEER SEP ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE DATE: 2 5/11/08 SUBSTATION: MINA ABDULLA ‘G" 132/11kV ‘TEST REPORT No: 1106 90 ‘TEST REPORT FOR OVERCURRENT & EARTH FAULT RELAYS, Voltage Level: 11KV PanelNo. : 20 Circuit Name S/s-18 O1G Relay Type: MOC-7B-G Make Mitsubishi Setting Range: 0.5 — 0-04 EIF Relay Type: MOC-7B-G Make Mitsubishi Setting Range : 0-2 —0.€A Mounting Semiflush DC Voltage: 220V Rating : 1amp. CT Ratio (eosin O16 Red § Plug | Time | Creep | Reset Operating Time (Sec.) Setting |_Muttipier | Amps. | Amps. Ser. No.: bod //F 13x [2x 5x 10x Syle_ 122 pya| p-as| 0-5| 1.99 | raslig.ul oF |o-o/|/ ‘CRITERIA 2007] 0-05 | rroy. |r0e7 lero lez |s-30- e356 -rep|/2= 126 R[S [EF RIS [oF Flag Operation & Resetting Wiring Tightness CPIRP, Switchgear, ~ | Relay Terminals and Components viv“ly ‘neulation Check AC toEarth | | v| v7 | Magnet Gap vivly Insulation Check DC to Earth v | _¥ | Mechanical Resetting v\v i Insulation Check AC to DC v | <1 [Hair spring Assembly Yiv|¥ ‘Trip Contact Y|~| [| Setting Pointer viv Intertrip Contactor v¥ | /|_ J | Earth Wire Check Internal & Extemal v| 4 ¥ ‘Alarm Local & Remote vialv Load Current (Amps.)— | Relay Current on load | Rox Yo Bo Ne (ma) Comments MELCO ENGINEER, MEW ENGINEER Be \ ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: 5/1/08 SUBSTATION: MINA ABDULLA ‘6’ 132/11kV TEST REPORT No : 11SOL 20 | TEST RE! Fi ELAY Voltage Level ttky Panel No.: o? 0 GireutName > S/S 78 Relay Type ‘Solkor R ‘Ser. No. 240552 Make > Reyrolle DC Voltage z20y ‘ArtNo. : 2650H30010 Rating: 1Amp CT Ratio : 400/18 ‘SECONDARY PILOT TRIPPING PILOT CURRENT, circuit CURRENT TERMINAL RELAY “PHASE | AMPS} CONDITION pc VOLTAGE ‘OPERATION mA AC VOLTS an | ove ‘OPEN 10-82 @o-F ‘OPERATION YN | O/F OPEN 10-82 : OPERATION | B-N O23 OPEN D-82 GQ>5 OPERATION Rey | o-%7 ‘OPEN 10-83 5-5 | OPERATION Y-8 Ort OPEN 10-83 US b ‘OPERATION RB | 0.35 (OPEN 10-82 oe. ‘OPERATION R-N_ | 7-00 OPEN 25.09 89-5 OPERATION RN | 7-@9_| SHORTED 70-92 | : OPERATION ‘STANDARD OPEN | 99-124 ‘|_ OPERATION ‘Aux. Contact Operation v Trip Circuit v ‘ntertip Relay v \ndication Local & Remote “ Insulation AC to Earth v Leaf Contact Motion v Insulation DC to Earth v Contact Cleaning v Insulation DC 1 AC. v heck Reset Device v Flag Operation & Reset Y Plug in after Test v Spill Current a Load Current. Relay Current onload Re Yer Bo No Comments = MELCO ENGINEER MEWENGINEER: ke ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: 20/7/08 SUBSTATION: MINA ABDULLA 'C’432/11kV TEST REPORT No: 1100 #2/ TEST REPORT FOR OVERGURRENT & EARTH FAULT RELAYS Voltage Level sv Panel No. : 02/ CiretName : Gg - RO OIC Relay Type: MOC-7B-G Make Mitsubishi Setting Range :O0.5 - 2-0 E/F Relay Type : MOC-7B-G Make : Mitsubishi Setting Range: 0-2 — O'S Mounting Semnifush Dc Vollage : 220v Rating amp. CT Ratio Yools OIC Red 6 Plug | Time | Creep | Reset Operating Time (Sec.) Setting | Mutipier | Amps._| Amps. Ser. No. : f2/ OL) tax] 8X 10x ‘Style F-AS| O-Os-| 7-20 [7-26 |/8-F| VIG FOS [EU CRITERIA 7007 | O- Us [> lool Kee? 919-B3S FRAT IS 2.07| 7387 Soc anes Plug | Time | Creep | Reset Operating Time (Sec.) Setting | Multiplier_| Amps._| Amps. Ser.No.: $2 /o8 43x | 2x 8X 10x | Stile 7-25| 0-Uy| 7-3) |7-26|2-9| 4-08] 99 [1-88 ‘CRITERIA F007 | O- GS | TOOL | K 1o26h 9-18-48 65-Y- OF] I6 92-07 7-6-7) EF ¢ Plug | Time | Creep | Reset Operating Time (Sec.) Setting |_Multiplier_|_ Amps. _| Amps. Ser.No.: ROG 2 13x] 2X 8X 40x | sole CR|0-Yo |o Rolo 9/4 8° [7 77[ RZ CRITERIA 07 | 0-Yo |) 1007. [#1207 | B- 19] 7.36-y B|75b-18[ 72-128 R18 (EF, [RLS [EF Fas cpwaten aResetng | Z| v| 7 | Reayreminais ana Componente”) || insulation Check AC to Earth | v | y|_y_| Magnet Gap YAS Insulation Check DC to Earth | ¥ |v | v | Mechanical Resetting Yviv Insulation Check AG to DC ¥ | v/v | Hair Spring Assembly viviv ‘Trip Contact |v) | v_| Setting Pointer vinyv Intertrip Contactor v Ly | ~ | Earth Wire Check internal & External viv ‘Alarm Local & Remote vide Load Gurent(Amps) = [Rely Curerton oad) Re Yo Be Ne im Comments :- MELCO ENGINEER MEW ENGINEER : _ 5 ae MITSUBISHI ELECTRIC CORPORATION | PROVECT : MEW PREVENTIVE MAINTENANCE vate: 20/1 /ok SUBSTATION: MINA ABDULLA ‘CG’ 432/41kV. TEST REPORT No: 11SOL #/ ‘TEST REPORT FOR SOLKOR RELAY Voltage Level tik Panel No. :@/ Circuit Name Og -Re Relay Type Solkor R Ser.No. : QAYY92Y Make : Reyfolle DeVotage =: AO Art No. 2650H30010 Rating «> Amp CT Ratio: 400A ‘SECONDARY PILOT TRIPPING PILOT GURRENT cIRCUIT CURRENT TERMINAL RELAY PHASE | AMPS | CONDITION pe VOLTAGE (OPERATION mA AG VOLTS R-N | O-/¢ ‘OPEN 70-8 | oF ‘OPERATED Yn | ovy7 ‘OPEN 10-80 G26 ‘OPERATED B-N | 029 OPEN 1081 GS. 6 aie Ry | 0-¥o OPEN 10 81. wet OPERATED Y-8_ | 0-40 OPEN 108) vod OPERATED R-B OSS OPEN 10 80 oy-8 OPERATED R-N | 7-00 ‘OPEN RE FE 97-0 ose R-N | 7.85 | SHORTED 70-92 7 NOT OPERATED [__ STANDARD open | 99-121 OPERATED ‘Aux. Contact Operation vy | Trp circuit v Intertip Relay V/__ | indication Local & Remote v i Insulation AC to Earth /_| beaf Contact Motion y Insulation DC to Earth Y | Contact Cleaning Y Insulation DC to AC | Check Reset Device v "Flag Operation & Reset I Plug in after Test Vv | Spil Curent I'Load Current (amps.)- | Relay Current on load | Ra: | Yo Too ‘No (may | EI \ ‘Comments MELCO ENGINEER : MEW ENGINEER : MEW ENGINEER na MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW ENTIVE MAINTENANCE pate: 32/7//0 & SUBSTATION: MINA ABDULLA 'C' 132/11kV TEST REPORT No: 110C 23 REPORT FOR OVERCURRENT & EAR! YS Voltage Level 11k PanelNo. : 3 Circuit Name S70RE CO: Owe OIC Relay type: MOC-7B-G Make Mitsubishi Setting Range: 0. — 0 E/F Relay Type MOC-7B-G Make Mitsubishi Setting Range : &°.2 — 0-84 Mounting Semiflush De Voltage: 220V Rating amp. CT Ratio oe oo/1A ole Redd Plug | Time | creep | Reset Operating Time (See:) Setting | Multiplier |_Amps._| Amps. Ser.No.: 89/02 43x | 2x 8x 10x. Sve: /32e7A|/-00l o-e | s-oy| nos |nclz62| /-70| Pao | CaITERIA 100) -& [rrooxleroyle-2 le 29 pal 86-3]? -/28) O'C Blue § Plug | time | creep | Reset ‘Operating Time (Sec.) Setting | Mutter |_Ames. | Amps. ‘Set.No.: 8207 tax [x 5X | 10x Syle_: /320VA| pro | ow | 0%! noo |e pol n67| 7 CRITERIA zoox| o-ty |>roy \creoy le-72 [23.9-waelise —7-8\-72 72. aro Plug Time } Creep | Reset Operating Time (Sec.) Setting | Multiplier | Amps. | Amps. Ser. No.: 9.20 ¥6 43x] 2x Style: /33PGA | 0-9 | © © -9/ | O-90\1)-9| 3°74 CRITERIA ex) O° [Proo 4 (K/20Y |p. |7-38— YJol RIS oF RIS [oF Flag Operation & Resetting Wiring Tightness CPIRP, Switchgear, v | ~|_~ | Relay Terminals and Components de |< Insulation Check AC to Earth |u| | Magnet Gap viele Insulation Check DC toEarth | v || -~ | Mechanical Resetting Yi insulation Check AC 1D | |v] v7 | Hair Spring Assembly viv| 7 ‘Trip Contact vl | | Setting Pointer “Aw Intertrip Contactor v |v] | Earth Wire Check internal & External Vivi ‘Alarm Local & Remote vv Load Gurrent (Amps.)= | Relay Current on load | Rex Yo Be ‘No: mal 25 2Amps (| 63-mA| 63m | b3m4 | bmn Comments = MELCO ENGINEER MEW ENGINEER See ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE vate: 20/71/08 SUBSTATION: MINA ABDULLA'B" 132/11hV TEST REPORT No: 11S0L 23 ‘TEST REPORT FOR SOLKOR RELAY Voltage Level: 11KV Panel No: 23 CroutName > S70@E CO. CML Relay Type Solkor. Ser.No. : 2 YGY62 Make : Reyrolle DCVotage 220 Art. No, 2850430010 Rating: 1Amp CT Ratio: 400/14 ‘SECONDARY PILOT TRIPPING PILOT Bl CURRENT, CIRCUIT CURRENT TERMINAL RELAY PHASE | AMPS | CONDITION bc VOLTAGE OPERATION mA AC VOLTS RN | ov OPEN 70-82 Goh OPERATION YN | py ‘OPEN 10-83 | SG OPERATION B-N | pao OPEN 10-3, 96 OPERATION R-Y | 9.68 OPEN 10-82 YES OPERATION Y-8 | 049 ‘OPEN 10-82 oe OPERATION RB | p-3y OPEN 10.8. GoF ‘OPERATION R-N | ¢-p0 ‘OPEN 27-38 Ved OPERATION R-N_| 7.67 | SHORTED 10 -Fod 7 ‘OPERATION STANDARD ‘OPEN 99-124 OPERATION ‘Aux. Contact Operation “ Trip Circuit v Intertip Relay v Indication Local & Remote Y Ingulation AC to Earth v Leaf Contact Motion Y Insulation DC to Earth Y ‘Contact Cleaning v Ingulation DC to AC v Check Reset Device a Flag Operation & Reset v Plug in ater Test vy Spill Current ae Load Current. Relay Current onload Ret Yo Bo Ne Comments:= 1007 e778 ARE $itogFEO AT FYE RELA CASE MELCO ENGINEER New enowneer : === § a MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE pate: R#/"/08 SUBSTATION: MINA ABDULLA ‘C"132/11kV TEST REPORT No: 1106 cy ‘TEST REPORT FOR OVERCURRENT & EARTH FAULT RELAYS Voltage Level: 41KV Panel No. : ACy CircuitName —: O/s -75 OIC Relay Type : MOC-7B-G Make Mitsubishi Setting Range: OS — 2-0 E/F Relay Type : MOC-7B-G Make Mitsubishi Setting Range: O-& ~ O-€ Mounting 2 Semifush DC Voltage: 220V Rating : 1Amp. cTRatio —: Yao/A OIC Red 6 Plug | Time | Creep | Reset Operating Time (Sec.) Setting | Muttipier | Amps. | Amps. ‘Ser.No.: BA 777 13x [2x 8X | 10x sye 7392274 | 7-95] 0 -Ys | 7-26 [25 |7-9| ¥-72| 7-99 | EW CRITERIA real! 0-45 |*l007|l00°% | PROT |9-+9- (18 &-Y.b5 |1-75-2-F| 26-74) EF 6 Plug | Time | Creep | Reset Operating Time (Sec.) Setting | Multiplier |_Amps._| Amps. Ser.No: PROF) 13x | _2X 8x 10K Style :497 PI4 [0 P| C-Yo |O -Ro| o-/9\/0-/| F Ro | 7: P| 7 AI CRITERIA Ro7 | 0 - Go [P1077 |<120/ | 8-12 | 58-4 4] 7 56-1-§| A Tag [ R [BEF R[8 [er Flag Operation & Resetting Wiring Tightness CP/RP, Switchgear, V | 4_v | Relay Terminals and Components viv Insulation Check AC to Earth | V7 | Magnet Gap viv Insulation Check DC to Earth | /| v| ~ | Mechanical Resetting viv Insulation Check AC tC | | ¥\_¥_| Hair Spring Assembly Vivi Trip Contact ¥| A | Setting Pointer AAY Intertrip Contactor JY | J) ~ | Earth Wire Check internal & External vivit ‘Alarm Local & Remote Load Current Amps.) - | Relay Current on load | Ro- Yo Bo Ne (ma) Comments > MELCO conan) SaaalSs MEW ENGINEER ae c ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE vate: 24/1/08 SUBSTATION: MINA ABDULLA ‘C' 132/14kV TEST REPORT No: 11SOL AY TEST REPORT FOR SOLKOR RELAY Voltage Level: 11kv Panel No: cireutName —: S/g ~15 Relay Type SokorR ——Ser.No. :RYEUSY Make: Reyrolle DC Voltage 220v Att No, 2650H90010 Rating > 1Amp CT Ratio : 400/14 SECONDARY PILOT TRIPPING PILOT CURRENT, circu CURRENT TERMINAL RELAY PHASE | AMPS] CONDITION De VOLTAGE | OPERATION mA AC VOLTS: RN | Ow ‘OPEN 10-& 62-2 (OPERATED Yn | Ov? OPEN 70 bub Yok OPERATED BN | OA OPEN 10-& 3 OPERATED R-Y | 0-67 OPEN 70 By RG OPERATED y-8 | OG | OPEN 10 -By a. # | OPERATED R-8 | O93 OPEN 1083 YR.R OPERATED R-N_ | 7-¢0 ‘OPEN 28-12 100.6 Saeed R-N_ | 7.57 | SHORTED 70 8F : NOT OPERATED ‘STANDARD ‘OPEN 99-124 OPERATED ‘Aux. Contact Operation Trip Circuit Intertrip Relay Indication Local & Remote Insulation AC to Earth Leaf Contact Motion Ingulation DC to Earth Contact Cleaning Ingulation DC to AC Check Reset Device Flag Operation & Reset Plugin after Test Spill Curent Load Current (Amps.)- | Relay Current on load | Ro Ye Be Ne (ma) Comments :- ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE DATE: 2441/08 SUBSTATION: MINA ABDULLA ‘C" 432/11kV TEST REPORT No: 1100 25 TEST REPORT FOR OVERCURRENT T RELAYS Voltage Level stay PanelNo. : 25° CireuitName : O/g- 73 OIC Relay Type : MOC-7B-G Make Mitsubishi Setting Range: OS - 2-0 EIF Relay Type : MOC-78-G Make Mitsubishi SettingRange: 0 W- 0-8 Mounting : Semifush DC Voitage : 220V Rating Amp. CT Ratio: Yoo/sa OIC Red Plug | Time | Creep | Reset Operating Time (Sec.) Setting | Mutioler | Amps. | Amps. | ‘Ser. No.: G27 30 13x | 2x 8x | 10x Sle: (BR OGa |/ 9S | O Us | RF [7-26 |/2-R| Y-Ro | 7 -% | 7-89 CRITERIA 7007 | OS | ¥ICOT |e PIF 6a SY 8 FoR RET: 1c Blue § Piug | Time | creep | Reset Operating Time (See.) Setting | Muttiolier |_Amps._| Amps. Ser.No: BQIOR 13x[ 2x | 8x | 10x Sle: GR PTa | ASO US|! Rg | TRS | #| 8-95 | *-Fo|* Yo CRITERIA 1o07.| Os [2/007 | <0 |9-79-8)9 85 -V-br| / %-0-0r| 7 6-/) ER ¢ Plug | Time ] creep | Reset Operating Time (See.) Seting | Multiplier | Amps. | Amps Ser.Noi SROVF 13x [2x x _[_ 10x Siie = 798PIa|0-@ | O-Yo|O 27 | 0 mo|7-%| F Fo | 798 | TAG CRITERIA RoT| 0 Yo Slaal KRol. [8-133 YA 56-1 [PRT OB RIEL EF R[S [EF Fas operation anes [Vv [v/v [Rearramnae and components” | || v insulation Check AC to Earth | v"| v|_v | Magnet Gap vay insulation Check DC to Earth | /'| v| ~ | Mechanical Resetting Miia Insulation Check AC to DC. S| Z| o | Hair Spring Assembly J a Trip Contact | v| x | Setting Pointer viv[l% Intertip Contactor v [A [Earth wire Check internal a extemal | v| /| 7 ‘Alarm Local & Remote vivIy Load Current (Amps.)- | Relay oe Ro Yo Be ‘No mA 1 Comments MELCO ENGINEER pats MEW ENGINEER Ee a MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVEMAINTENANGE DATE: 2#/7//06 SUBSTATION: MINA ABDULLA ‘C’ 432/41kV TEST REPORT No: 11SOL_ 25 TEST REPORT FOR SOLKOR RELAY Votage Level atky Panel No.: 25° CircuitName : OJ -/3 Relay Type Solkor R Ser.No, = RYE Y YQ Make Reyrolle DC Voltage 220v Art. No. 2650H30010 = Rating 4Amp CT Ratio : 400/14 SECONDARY PILOT TRIPPING PILOT CURRENT ciRcuIT CURRENT TERMINAL RELAY PHASE “AMPS | CONDITION oc VOLTAGE OPERATION mA AC VOLTS R-N OW ‘OPEN 10-79 Ors ‘OPERATED Yn | 67¥ OPEN O49 S84 oma B-N | 0-22 ‘OPEN 10 -%P 89-9 OPERATED R-Y | 0-66 OPEN 10-80 Yo: s- Cee y-B | 0-68 OPEN 10-49 Go-& ‘OPERATED R-B | Oy OPEN t0-fo Yous OPERATED R-N | 7-00 OPEN RF 39 vO OPERATED R-N_|_ 7-52 | SHORTED 10-88 : NOT OPERATED ‘STANDARD OFEN 99-121 (OPERATED ‘Aux. Contact Operation VA Vv Intertrip Relay | Indication Local & Remote / Insulation AC to Earth \/__ | Leaf Contact Motion v Insulation DC to Earth af _| Sontact Cleaning a Insulation DC to AC /_| Check Reset Device 4 Flag Operation & Reset JY | Plugin after Test ey. Spill Current Load Current (Amps.)- | Relay Current on load | Ra Yo Tee Ne (mA) Comments - wacooonee | anal MEW ENGINEER eer ae MITSUBISHI ELECTRIC CORPORATION | PRovecr MEW PREVENTIVE MAINTENANCE [ SUBSTATION : MINA ABDULLA o-432/1tKY vate: 07/12/08 VEST REPORT Na: 11S8EF yT REPORT FOR STANDBY EARTH FAULT RE! Voltage Level: 11ky Panel No 44 Circuit Name Bus Coupler AnNo. : 4o5atso97 Relay Type: TJMBD Ser.No. : 252450. Make Reyrolle Rating 4Amp. DC Voltage: 220V Mounting : Semiflush (RELAY DATA actual | CREEP | RESET ‘OPERATING TIME "AMPS _|_ AMPS feeaterte ess cine, | an MITSUBISHI ELECTRIC CORPORATION PROJECT MEW PREVENTIVE MAINTENANCE pate: 07/12/08 SUBSTATION : TEST REPORT No EST REPORT FOR UNDER FREQUENCY RELAY Voltage level: 7 J eV [Panel No.) 5 Circuit name: S/8=7 Make Art No. . Under frequency ae Gis bee | we: 8 / Mounting ‘Semi Flush DC voltage: 220V, Rating :420V AIC 50HZ ‘Shunt Resistance:4.5KQ. | Relay Data Setting Operating Frequency | TimeDelay | frequency | Time oa Under (Hz) (Cycles) Hi: Frequency (Hz) Relay vs.) 1 48.09 | O-/4O ‘Wire check internal and extemal Flag operation and resetting Trip contact V7 Plugin after testing Calculated time in eycles: (T*F)-3 Allowable tolerance:+3/-2 Comments :- Longer delay setting was adopted to confirm basic relay operation Adopted relay setting: 20eycles ‘Time measured: ms Allowable tolerance range:420-520 ms Pe S368 MELCO ENGINEE! MEW ENGINEER aS v

You might also like