Professional Documents
Culture Documents
Kiln Heat and Mass Balance September 2010
Kiln Heat and Mass Balance September 2010
Kiln Heat and Mass Balance September 2010
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 1/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
Table of Contents
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 1/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
1.1 Calculation of neutral waste gas out of fuel elemental analysis (as fired
basis)
Nm 3 ⎛ %C %H %S %O ⎞ 22.414
=⎜ + + − ⎟*
kgfuel ⎝ 12.001 4.032 32.064 32 ⎠ %OXYair
Nm 3 ⎛ %C % N ⎞ 22.414 %OXYair ⎞
+ (1 −
% H % H 2O %S
=⎜ + + + + ⎟* ⎟ * N .C. A
kgfuel ⎝ 12.001 2.016 18.015 32.064 28.01 ⎠ 100 100 ⎠
Definition:
o Neutral Combustion (Waste) Gas:
Combustion gas of a fuel or fuel mix under stoechiometric condition (0% Oxygen in the waste
gas).
o Neutral Combustion Air: Air required for complete stoechiometric combustion of the fuel.
Sulphur is typically not remaining as SO2 in the waste gas as calculated in the formula above.
All or most of it is trapped in the kiln system and finally present in clinker as SO3. For final exit
gas calculation this effect is considered in the division heat balance tool.
1.2 Calculation of CO2 and H2O from material and water spraying
In calciner and preheater kilns only a part of CO2 is present in the kiln exit; most of it is
released in the calciner / preheater.
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 2/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
Excess Air
KEGN * OXYki ln
• EA =
OXYair − OXYki ln
KEGN: Neutral Kiln Exit Gas including material CO2 and H2O [Nm³/kg]
Definition:
o Excess Air Kiln:
Amount of air in addition to neutral combustion air kiln to achieve the Oxygen at kiln inlet (for
benchmark the defined analyzer position is inside kiln = kiln inlet seal false air excluded!).
o Total Combustion Air Kiln:
Neutral Combustion Air Kiln + Excess Air Kiln.
o Excess Air Kiln Line (preheater / calciner kilns):
Amount of air in addition to neutral combustion air kiln line to achieve the Oxygen at preheater
exit.
o Total Combustion Air Kiln Line (preheater / calciner kilns):
Neutral Combustion Air Kiln Line + Excess Air Kiln Line.
Kiln and Preheater exit (waste) gas is the sum of neutral combustion gas from fuel, CO2 and H2O from
raw material, H2O out of water spraying and the excess air.
Further impacts like a gas bypass, CO in exit gas and combustibles in raw material are considered in the
division heat balance tool.
In case of preheater / calciner kilns the calculation is done separately for kiln exit gas and preheater exit
gas.
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 3/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
Kiln exit gas for wet and long dry is considered inside kiln, without false air at settling chamber
and without water injection.
Values are with 100% petcoke firing under optimized conditions (see chapter kiln simulated
optimum parameters)..
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 4/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
Evaporation of volatiles overlaps the exothermic reaction in the sintering zone and transfer heat to colder
areas.
The final exothermic reaction of the clinker phases is estimated on clinker Bogue results:
3. Cooler Efficiency
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 5/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
• Design Criteria:
Grate Loading < 45 tpd/m²
Total specific cooling air > 2.1 Nm³/kg cl
Target: clinker temperature 70°C + ambient ; k- factor > 1.6
• Blowing Density:
Expressed in Nm³/m²/s. Calculate the blowing density for every compartment using the effective
area (covered by clinker) and the cooling air blown in the compartment. Take care to consider
the grate area covered by horse shoe.
Rule of thumb for blowing density of the static grate or first chamber:
1.6 – 1.8 Nm³/m²/s for conventional grate cooler and old Fuller cooler
1.5 for IKN fixed inlet (some plants will need up to 2)
1.3-1,4 for FLS ABC inlet
Higher airflow might be required to avoid static areas of clinker that could result in snowman
formation. The objective of a fixed inlet is to ensure a good distribution of clinker on the moving
grate. The blowing density of the following chambers should show a constant decrease. Use the
Lafarge cooling air distribution spread sheet for a first assessment.
• Cooling Air:
Expressed in Nm³/kg cl. While optimizing the air in the recuperation zone often requires an
increase at the first fans, the total cooling air should be minimized to reduce power cost. Decide
on a clinker target temperature required for cement quality but do not go below this temperature.
An optimized cooler can achieve low clinker temperature with low total cooling air.
Typical figures: 1.8 to 2.2 Nm³/kg cl, old grate coolers without fixed inlet up to 2.4 Nm³/kg cl.
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 6/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
The calculation in the division heat balance tool is considering the exact enthalpy of the cooling air in the
recuperation zone, which is typically higher compared to the average enthalpy of the cooling air.
• This efficiency depends highly on the quantity of secondary and tertiary air. It is higher for wet kilns
(∼85%) than for dry kilns (∼70%).
The k-factor is the main indicator for cooler performance benchmark. The k-factor is independent from
the amount of secondary and tertiary air and therefore shows cooler performance independent from the
kiln system or fuel used.
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 7/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
Cooling Efficiency
Cooler Loss
• Cooler loss = all heat not recovered by combustion air.
Cooler loss = heat content of clinker leaving cooler ( hck ,out ) + heat content of vent air including
dust + heat content of any mid air extraction including dust + cooler wall losses
4. Wall Losses
The total heat loss from a surface is the sum of both the radiation and convection losses
QTotal = Qradiation + Qconvection
It is recommended to use the Division calculaltion tool to calculate Wall Losses, it can be found on the
Cement Portal.
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 8/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
The emissivity is a property of the material and its surface condition (see below).
Emissivity e:
Material Emissivity ∈
Bricks 0.8
Steel 0.95
Oxidized steel ∈ =0.996-2.88*10-4.(tp-100)
Dusty kiln shell ∈ =0.96-5.2*10-4.(tp-100)
Silica bricks ∈ =0.81-6.08*10-4.(tp-200)
Other data Tp ∈ tp ∈
Iron oxide 500C 0.78 Steel oxidised 40C 0.94
Zinc galvanized sheet bright 28C 0.23 Steel oxidised 370C 0.97
Iron polished 425C 0.144 Steel polished 770C 0.52
Steel dense shiny oxide layer 25C 0.82 Steel pipe 200 0.8
It is important to take care to use the correct value since an incorrect emissivity value will create a
significant error in the “measured temperature” and hence the calculated heat loss, see example.
Emissivity can be checked on static surfaces by first measuring the temperature with a contact pyrometer
and then pointing the infra-red pyrometer at the same point and adjusting the emissivity until the
temperature reads the same as that measured by the contact thermometer.
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 9/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
The individual formula for convection losses are too numerous depending on the flow type to be
presented here. The general formula is :
Qconvection= h x A x ( Tshell – Tambient)
e
With h = hnat * (1+0.57 v)
hnat is the natural convection coefficient which depend of the surface orientation, and the type
of flow : laminar or turbulent For calculating hnat you need a characteristic dimension of the surface
considered: for Duct = the Diameter,
Vertical plane shell = the height,
Horizontal plane shell = the length
For example for a horizontal pipe and laminar flow:
v is the speed of the air surrounding the surface (including wind, kiln speed, fans…) (m/s)
e is the exponent reflecting the impact of wind (varying from 0.5 to 0.8)
Σ heatin = Σ heatout
Σ massin = Σ massout
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 10/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
• A clear definition of the balance border around the pyro line is essential, all mass and energy flows
passing this envelope need to be considered.
A typical balance border and Heat In - Output Table of a calciner line is shown below:
gas analysor
A
new
314TC0
5 CY19 CY21
CY23 CY25
ID fan CA3
CY27 CY31
3
oil oil
burner burner
gas gas
burner burner
gas analysor
• Heat Inputs
o Kiln feed (sensible + latent)
o Fuel main burner (sensible + latent)
o Fuel calciner (sensible + latent)
o Primary air and transport air main burner
o Primary air and transport air calciner
o Cooling air
o False air
o Exothermic Heat of clinkerization
• Heat Outputs
o Clinker
o Preheater exit gas
o Preheater exit dust
o Cooler exhaust gas and dust
o Endothermic Heat of clinkerization including decarbonatization
o Heat of Water vaporization
o Wall losses
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 11/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
• Additional to the over all heat balance of the pyro line a sub balance is carried out for the cooler and
other areas of interest (conditioning tower, bypass,…).
5.2 Measurements
• A 24 hour truck weighing is recommended for clinker.
• To determine the preheater exit dust, truck weighing of the kiln filter dust is recommended. The raw
mill needs to be stopped one hour before and during the weighing. Coal mill should be stopped in
parallel or the amount of preheater exit gas and dust towards coal mill needs to be estimated. Any
dust source (example gas conditioning tower) should be covered by truck weighing.
• Further truck weighing is recommended for fuel if dosing is not reliable or cannot be calibrated
properly.
• The table below shows typical recommended process measurements and their frequency:
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 12/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
• Typical sampling frequency is shown in the next table for materials and fuels. Standard analysis like
XRF should be carried out on every hourly sample in the plant.
The recommended additional analysis to be carried out in the TC lab like CO2, H, S2-, TOC in kiln
feed, ultimate fuel analyse, fuel ash analyse, ect are described in the kiln audit analyse template
(Pyro 2 / Kiln Audit training).
• Material Sampling:
Filter DUST (mill
Material: KILN FEED HOT MEAL (dry) HOT MEAL (wet) CLINKER BYPASS DUST
stopped)
2 samples during
Recommended sampling frequency once per hour twice per shift twice per shift once per hour once per shift
mill stopped
1 to 3 typical 1 to 6 typical
1 average sample 1 average sample average sample
sample (dry sample - same
Sample to TC: out of all hourly out of all hourly averge sample out of all audit
sampling, no air time as dry
audit samples audit samples samples
contact) sampling
• Fuel Sampling
solid shredded
Material: coal or coke liquid fuel solid biomass fuel
waste (plastic,…)
Recommended sampling
twice per shift twice per shift twice per shift twice per shift
frequency
1 average 1 average sample 1 average sample 1 average sample
Sample to TC lab: sample out of all out of all audit out of all audit out of all audit
audit samples samples samples samples
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 13/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
The example below shows the kiln audit result of Volos kiln 5, a 4 stage calciner line. The
division heat balance tool is used for calculation.
KILN AUDIT HEAT BALANCE TOOL - COOLER BALANCE AND PERFORMANCE SHEET
Cooler input Cooler output
kg/h T°C Nm3/kgck kJ/kgck % kg/h T°C Nm3/kgck kJ/kgck %
Cooling fans 350100 27 2,14 73,86 4,1 Secondary air 73329 999 0,45 632,58 34,8
Hot Clinker 127000 1445 1605,06 88,4 Tertiary air 66303 999 0,41 572,21 31,5
Exhaust air water injection 0 0 0,00 0,00 0,0 Mill take off #1 0 0 0,00 0,00 0,0
False air 0 0,00 0,00 0,0 Mill take off #2 0 0 0,00 0,00 0,0
Clinker Dust return (SA) 5684 1445 71,84 4,0 Exhaust air 210468 245 1,29 414,13 22,8
Clinker Dust return (TA) 5140 1445 64,96 3,6 Cold clinker 122105 101,5 76,92 4,2
Wall losses 27,39 1,5
Vap. Heat 0,00 0,0
Dust secondary air 5684 999 44,36 2,4
Dust tertiary air 5140 999 40,11 2,2
Dust exhaust air 4895 245 8,01 0,4
Dust Mill take off 1 0 0 0,00 0,0
Dust MIll take off 2 0 0 0,00 0,0
Air leakage 0 0,00 0,00 0,0
Total 487924 2,14 1815,72 100 Total 487924 4587 2,14 1815,72 100
Out - In 0 0,00 0,00
Cooler Load, tday/m2 37,6
Recovery Efficiency, ρ 72,65% Air Load, Nm3/kgck 2,14
Cooling Efficiency, η 95,21% Average Blowing Density, Nm3/s/m2 0,93
Recovery Factor, k 1,52 excellent cooler Cooler Loss, kJ/kgck 526,45
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 14/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
The complete and actualized database is available on the portal – pyroprocessing domain for benchmark.
The overview below will be updated yearly.
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 15/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 16/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
Heat Loss
Distribution
Heat of Clinker kJ/kg 1800 1800 1800 1800 1800 1800
Formation (%) (32) (44) (51) (51) (51) (54)
Kiln / kJ/kg 940 1220 360 810 800 675
PreheaterExit (%) (17) (30) (10) (23) (23) (21)
Gas
Cooler Exhaust kJ/kg 110 240 316 295 350 370
Air (%) (2) (6) (9) (9) (10) (11)
Wall Loss kJ/kg 700 470 300 340 250 275
(%) (12) (12) (9) (10) (7) (8)
Vaporization kJ/kg 2050 20 630 20 20 20
Feed Moisture (%) (36) (0.5) (18) (0.6) (0.6) (0.6)
Kiln / Preheater kJ/kg 20 250 20 35 35 25
Exit Dust Loss (%) (0.4) (6.2) (0.6) (1.0) (1.0) (0.8)
Clinker after kJ/kg 70 80 70 90 90 90
Cooler (%) (1.1) (1.9) (2.0) (2.7) (2.7) (2.7)
Cooler
Secondary Air Nm³/k 1.49 1.13 0.99 0.99 0.38 0.38
Volume g
Secondary Air °C 716 832 913 916 965 980
Temperature
Tertiary Air Nm³/k - - - - 0.53 0.50
Volume g
Tertiary Air °C - - - - 965 980
Temperature
Exhaust Air Nm³/k 0.61 0.97 1.11 1.11 1.17 1.21
Volume g
Exhaust Air °C 141 188 217 204 224 233
Temperature
Cold Clinker °C 90 100 90 120 120 120
Temperature
Hot Clinker °C 1390 1400 1435 1435 1450 1450
Temperature
Cooling Air Nm³/k 2.1 2.1 2.1 2.1 2.1 2.1
g
Recovery % 89 82 77 77 75 73
Efficiency
K Factor 1.5 1.5 1.5 1.5 1.5 1.5
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 17/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
The next graphic shows the impact of different fuel, bypass and kiln size. Baseline is the optimized 3000
tpd 5 stage calciner line shown above – last column.
3600
kJ / kg
clinker
Influcence on specific heat consumption
3500
3200
3200
3100
3000
Baseline
1 Fuel Impact
2 Bypass
3 Kiln 4Size
+ 120 kJ / kg + 60 kJ / kg + 50 kJ / kg
- 120 kJ / kg - 50 kJ / kg
9. References
Cement Portal
• How to Perform a Kiln Audit
• How to Optimise a Clinker Cooler
• Lafarge Cooler Air Distribution Calculation Tool
• Calciner / Preheater Heat Balance Tool
• Wet and Lond Dry Heat Balance Tool
• Pyro-Process I & II Division Training
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 18/20
INTERNAL USE ONLY Version September 2010
CEMENT PROCESS ENGINEERING VADE-MECUM
CHAPTER 3-1 – KILN HEAT & MASS BALANCE
My notes:
© Copyright 2010, Lafarge SA. All rights reserved. KILN HEAT & MASS BALANCE – Page 19/20
INTERNAL USE ONLY Version September 2010