Sizing wire-type EGCs for parallel runs

There are specific rules for wire-type EGCs or equipment-bonding jumpers installed with parallel runs for
feeders or branch circuits. Section 250.122(F) states that, when conductors are run in parallel in
separate raceways or cables, any wire-type EGCs also are required to be run in parallel in their
respective raceway or cable. If wire-type EGCs are installed with the paralleled feeder conductors, the
EGCs must also be installed in parallel, but they can be smaller than 1/0. This is because multiple EGCs
are not being installed to share ground-fault current in the occurrence of a ground-fault event but to
provide a low-impedance path regardless of where the fault occurs. They are already fully sized
according to Section 250.122, as required.

When parallel arrangements of conductors are installed in separate raceways, such as in multiple
conduits, and the NEC requires wire-type EGCs, an EGC must be installed in each of the separate
raceways. In this type of installation, each EGC installed in parallel is required to be sized using Table
250.122 based on the rating of the fuse or circuit breaker protecting the entire parallel set.

It is important to remember that Section 300.3(B) generally requires all conductors of the circuit,
including the EGCs, to be installed in the same raceway, cable or trench. One reason for the requirement
to include an EGC in each of the raceways is that the full-sized EGC prevents overloading and possible
damage of a smaller, inadequately sized EGC should a ground fault occur in one of the parallel branches.
Another reason is that it keeps impedance levels low during normal operation and during ground-fault
events. Installing an EGC in only one of the raceways separates the EGC from its associated ungrounded
conductors of the same circuit and is a violation of Sections 250.122(F), 300.3(B) and 310.10(H). Keeping
the impedance in the effective ground-fault current path as low as possible ensures fast, effective
operation of fuses or circuit breakers in the case of a ground fault.

Example 1: A 4,000-ampere (A) feeder is installed in 10 PVC conduits in a parallel arrangement, each
containing four 750 copper conductors. What is the minimum size copper EGC required in each conduit?

Answer: The NEC requires a 500 kcmil copper EGC in each raceway based on the 4,000A overcurrent
device in accordance with Table 250.122.

Example 2: If an 800A feeder is installed in (2) raceways in a parallel arrangement, each containing (4)
750 copper conductors, what is the minimum size wire-type EGC in each raceway of this circuit?

Answer: The NEC requires a 1/0 AWG copper EGC in each raceway.
Sizing wire-type equipment- bonding jumpers in parallel runs
Where wire-type equipment-bonding jumpers (supply side or load side) are installed with parallel runs,
the NEC requires them to be installed according to 310.10(H) and sized according to 250.102. Section
250.102(C) includes sizing rules for supply--side bonding jumpers and equipment--bonding jumpers
installed on the load side of an overcurrent device. They must be sized according to 250.102(D).

The difference is simple. Supply-side bonding jumpers are sized using Table 250.66 or the 12.5 percent
rule where the largest ungrounded conductor exceeds the sizes provided in Table 250.66. Load-side
equipment-bonding jumpers are sized based on the rating of the overcurrent device using Table
250.122. Good examples of supply-side bonding jumpers are those installed with parallel secondary
conductors from separately derived systems or parallel service-entrance conductors.

Example 1: A 2,000A service is installed in six rigid metal conduits in a parallel arrangement, each
containing four 600 kcmil copper conductors. The conduits rise into the bottom of a service
switchboard. What is the minimum size copper supply-side bonding jumper from each conduit busing to
the equipment-grounding terminal bar in the service equipment?

Answer: The NEC requires a 1/0 copper equipment-bonding jumper from each raceway based on the
values in Table 250.66. Note that if the equipment-bonding jumper was installed in a “daisy-chain”
fashion, connecting all the conduits together and to the equipment-grounding terminal bar with a single
bonding jumper through lay-in lugs, the equipment-bonding jumper must be a minimum of 450 kcmil or
the next higher size in Table 8, which is 500 kcmil. Note: 6 600 kcmil = 3,600 kcmil 12.5% = 450 kcmil.

Example 2: If an 800A service is installed in two raceways in a parallel arrangement, each containing
four 750 copper conductors, what is the minimum size equipment-bonding jumper required?

Answer: The NEC requires a 4/0 AWG copper equipment-bonding jumper from each raceway to the
enclosure. Note: 750 kcmil 2 = 1,500 kcmil 12.5% = 187,500 cm and round up to the next higher size in
Table 8, Chapter 9.
Cable assemblies installed in parallel arrangements
Cable assemblies, such as metal-clad cable (Type MC), are manufactured in standard conductor size
configurations unless they are a special-order item. The EGC in a standard cable is typically sized
adequately for single circuit use and might not be adequate for all parallel circuit installations.

If cable assemblies are installed in large-capacity parallel circuits, it is necessary to verify that each EGC
is sized as Table 250.122 requires, based on the size of the fuse or circuit breaker protecting the entire
parallel circuit. Installing cable assemblies in parallel arrangements may necessitate a special order that
includes sizing the EGC in each cable large enough to allow the cable to be Code-compliant in a parallel
installation.

Some cable manufacturers produce cable assemblies with larger EGCs when parallel arrangements are
included in the project design. Section 250.122(A) indicates that EGCs never have to be larger than the
ungrounded conductors of the circuit. Remember, in a paralleled feeder run, the ungrounded
conductors of the circuit include all of the conductors in parallel that are added together to make a
single conductor.

Summary
Section 250.118 of the NEC specifies EGC types. Wire-type EGCs must be sized according to Section
250.122 based on the rating of the overcurrent device protecting the circuit. When circuits are installed
in parallel arrangements in multiple raceways of cable assemblies, the NEC requires a separate EGC in
each raceway or cable assembly. The minimum size required for each EGC must not be smaller than the
sizes Table 250.122 specifies. Where equipment-bonding jumpers are installed with circuits in parallel,
they must meet the sizing requirements contained in Sections 250.102(C) for supply-side bonding
jumpers and 250.102(D) for load-side bonding jumpers. The note following Table 250.122 is not
optional. EGCs must provide an effective ground-fault current path as described in Section 250.4. The
requirements in the NEC are the minimum.