Professional Documents
Culture Documents
Heat Transfer and Exergy Analysis of A Spiral Heat Exchanger
Heat Transfer and Exergy Analysis of A Spiral Heat Exchanger
net/publication/283070484
CITATIONS READS
6 1,448
2 authors, including:
duc-khuyen Nguyen
Nong Lam University
8 PUBLICATIONS 21 CITATIONS
SEE PROFILE
All content following this page was uploaded by duc-khuyen Nguyen on 05 June 2016.
To cite this article: Duc-Khuyen Nguyen & Jung-Yang San (2016) Heat Transfer and Exergy
Analysis of a Spiral Heat Exchanger, Heat Transfer Engineering, 37:12, 1013-1026, DOI:
10.1080/01457632.2015.1104159
Article views: 77
Download by: [University of Tennessee, Knoxville] Date: 31 March 2016, At: 21:31
Heat Transfer Engineering, 37(12):1013–1026, 2016
Copyright
C Taylor and Francis Group, LLC
ISSN: 0145-7632 print / 1521-0537 online
DOI: 10.1080/01457632.2015.1104159
The heat transfer effectiveness of a countercurrent spiral heat exchanger is expressed as a function of number of transfer units,
ratio of flow capacity rates, number of spiral turns, and dimensionless start-point angle of spiral (dimensionless angular
angle of the start point of a spiral curve constituting the solid wall of the heat exchanger). The heat transfer effectiveness is
weakly dependent on the dimensionless start-point angle of spiral, but moderately increases with the number of spiral turns.
As the number of spiral turns is larger than 20, the heat transfer effectiveness of the spiral heat exchanger approaches that
of a counterflow heat exchanger. The heat transfer effectiveness of the spiral heat exchanger has a maximum. The optimum
number of transfer units at the maximum heat transfer effectiveness increases with the number of spiral turns, whereas it
increases with a decrease of the ratio of flow capacity rates. In the second-law analysis, an optimum hot flow-to-cold flow
capacity-rate ratio is found. For obtaining a large net recovered exergy rate, the spiral heat exchanger needs to possess
a large number of transfer units (greater than 2.0) and operate at a near balanced-flow condition. In addition, a small
consumed mechanical power is demanded.
INTRODUCTION et al. [9] and Wijeysundera et al. [10] investigated heat transfer
performance of a compact spiral-coil heat exchanger. Bes [11]
The spiral heat exchanger is a compact-type heat exchanger. used the Laplace transformation method to solve fluid temper-
Its flow pattern can be arranged to be countercurrent, which is ature distribution in a spiral heat exchanger. Bes and Roetzel
similar to that in a counterflow heat exchanger. In addition, the [12–14] proposed a set of formulas using for determining the
spiral channel in the heat exchanger provides the flow with a heat transfer performance of a spiral heat exchanger. Burmeister
high convective heat transfer coefficient. These reasons make it [15] examined the effect of number of heat transfer units (NTU)
possess a high heat transfer performance. on the heat transfer effectiveness of a spiral-plate heat exchanger.
The concept of a spiral heat exchanger was first proposed in Adamski [16] measured heat transfer and pressure drop data for
the late 19th century. During the 1930s, this device was rein- a spiral recuperator in a ventilation system. Rennie and Ragha-
vented in Sweden [1]. Since then, much work on spiral-type van [17] analyzed heat transfer performance of a double-pipe
heat exchangers has been done by different researchers. Wil- helical heat exchanger. San et al. [18] investigated heat trans-
helmsson [2] introduced applications of spiral heat exchangers. fer characteristics of a serpentine heat exchanger. Salem et al.
Sterger et al. [3] analyzed the optimum characteristic parame- [19] obtained a closed-form solution of the ε-NTU relation for
ters for a double-spiral heat exchanger. Wu [4] showed a cal- a counterflow heat exchanger. Martin [20] presented empirical
culation procedure for constructing the geometric shape of a correlations of fluid friction data and Nusselt number for a spiral
spiral heat exchanger. Picón-Núñez et al. [5, 6] proposed a de- heat exchanger.
sign methodology for a spiral heat exchanger. Targett et al. [7] The heat transfer effectiveness of a heat exchanger (ε) is
presented fluid temperature distribution in a double-spiral heat defined as the actual heat transfer rate of the heat exchanger di-
exchanger. Naphon and Wongwises [8] measured average in- vided by the maximum possible heat transfer rate. In the indus-
tube heat transfer coefficients in a spiral-coil heat exchanger. Ho try, this performance factor is widely used to evaluate thermal
performance of heat exchangers. The heat transfer effective-
ness reflects the amount of thermal energy involved in a heat
exchanger. Nevertheless, due to a lack of consideration of the
Address correspondence to Professor Jung-Yang San, Mechanical Engi-
neering Department, National Chung Hsing University, 250 Kuo-Kuang Road, consumed pumping power for driving the working fluids, it can-
Taichung, Taiwan. E-mail: jysan@dragon.nchu.edu.tw not be solely used to determine the overall performance of the
1013
1014 D.-K. NGUYEN AND J.-Y. SAN
with axial thermal dispersion in one fluid. San and Pai [24] eval-
uated the second-law efficiency of a serpentine heat exchanger.
Wu et al. [25] proposed a second-law-based effectiveness for
evaluating exergy transfer in heat exchangers. Ruan et al. [26] Figure 1 An Archimedes spiral.
investigated exergy transfer in a three-fluid heat exchanger. San
[27] defined an exergy recovery index for evaluating the second-
law performance of heat exchangers. Hadi et al. [28] analyzed
entropy generation induced by free convection in an inclined and ending at ϕo (Figure 1) [30–32] can be expressed as
cavity filled with a porous medium.
In this work, heat transfer characteristics and exergy recovery φo φo 2
dr
performance of a spiral heat exchanger are analyzed. Firstly, the L= ds= r2 + dφ
φi φi dφ
ε-NTU relationship of the heat exchanger is established. In the
literature [3, 7, 11–15, 20], much work on evaluating the heat
1
transfer effectiveness of spiral heat exchangers can be found. = a φo φ2o + 1 − φi φi2 + 1
However, in those works, the core regions in the heat exchangers 2
were considered to be completely insulated. In this work, this ⎛
⎞⎤
part of heat transfer is considered in the mathematical model φo +
φ2o + 1
for establishing the ε-NTU relationship. Second, in the previous + ln ⎝ ⎠⎦ (2)
work [3, 7, 11–15], at the ratio of flow capacity rates of 1.0 (C φi + φi2 + 1
= 1, balanced-flow condition), a maximum value of the heat
transfer effectiveness was found. In this study, it is intended to The considered spiral heat exchanger is constructed by two
obtain the maximum values of the heat transfer effectiveness Archimedes spirals. The two spirals originate from the same
at various C values. Third, it is also intended to acquire an center point, but they have a phase difference of π. In addition,
optimum operating condition for the heat exchanger used in the numbers of turns (Nt ) of the two spirals are the same. A spiral
waste heat recovery. At this optimum operating condition, the heat exchanger of this type with Nt = 3.0 is shown in Figure 2.
heat exchanger is capable of recovering a maximum amount of In Figure 2, the two spirals constructing the heat exchanger cor-
exergy from the waste heat source. respond to two independent curvilinear coordinates, φh and φc ,
respectively. The two coordinates also have a phase difference
of π. As shown in the figure, the angles at the start points of
the two spirals are the same (φh,i = φc,i ) and the angles at the
THE ARCHIMEDES SPIRAL end points are also the same (φh,o +π = φc,o +π). Hence, in
Figure 2, after the spiral represented by a solid line rotates with
The trajectory of an Archimedes spiral (Figure 1) can be an angle of π, it will overlap with the spiral represented by a
expressed as [29] dashed line.
Equation (2) can be used to evaluate the heat transfer area in
r = aφ (1) the spiral heat exchanger as [4]
where r and ϕ are the radius and angular angle of a point on At = (L inner + L outer ) H = 2L H
the spiral respectively; a is a constant that represents the rate of
change of radius.
= (H a) φo φ2o + 1 − φi φi2 + 1
Using Eq. (1), the arc length of the spiral starting from ϕi
heat transfer engineering vol. 37 no. 12 2016
D.-K. NGUYEN AND J.-Y. SAN 1015
Downloaded by [University of Tennessee, Knoxville] at 21:31 31 March 2016
⎛
⎞⎤
φo +
φ2o + 1
+ ln ⎝ ⎠⎦ (3)
φi + φi2 + 1 Figure 3 Control volume for hot flow.
be a half turn of the channel (innermost half turn). In addition, = a (φh + π)2 + 1dφh
2L
the central partition between the hot and cold flows is assumed
to be insulated, while the outermost half turns of the two walls After arrangement, Eq. (5) can be expressed as
a
are also considered to be insulated. If so, either the hot flow or
dTh,φh
the cold flow can be divided into three different heat transfer re- = NTUh φ2h + 1 Tc,φc −π − Th,φh
gions (i.e., innermost half turn, intermittent turns, and outermost dφh 2L
half turn).
+ (φh + π) + 1 Tc,φc +π − Th,φh
2
(6)
Energy Balance for Hot Flow
(ii) In the innermost half turn [(φh,i − π) ≤ φh < φh,i ]
The control volume for the hot flow in the hot-flow channel dTh,φh a
= NTUh
is shown in Figure 3. Based on the energy balance, the energy dφh 2L
heat transfer engineering vol. 37 no. 12 2016
1016 D.-K. NGUYEN AND J.-Y. SAN
Dimensionless Energy Equations for (ṁc p )h ≤ (ṁc p )c
× (φh + π)2 + 1 Tc,φc +π − Th,φh (7)
Hot Flow
with initial condition Th,φh (φh = φh,i − π) = Th,in .
(i) For (φ∗h,i − 1/2) ≤ φ∗h < φ∗h,i ,
(iii) In the outermost half turn [(φh,o − π) ≤ φh ≤ φh,o ],
dθh,φ∗h NTU
dTh,φh a =
= NTUh φ2h + 1 Tc,φc −π − Th,φh (8) dφ∗h L∗
dφh 2L
⎡ ⎤
2
1 1
×⎣ φ∗h + + θc,φ∗c +1/2 − θh,φ∗h ⎦
2 4π2
+ (φc + π)2 + 1(Th,φh +π − Tc,φc ) (9) (13)
(15)
DIMENSIONLESS ENERGY EQUATION
where C = (ṁc p )min /(ṁc p )max = (ṁc p )h /(ṁc p )c .
The energy equations for the hot and cold flows are con- (ii) For φ∗c,i ≤ φ∗c < (φ∗c,o − 1/2),
verted into dimensionless forms, respectively. For convenience
of the analysis, two different operations ((ṁc p )h ≤ (ṁc p )c and dθc,φ∗c NTU 2 1
= C φ∗c + θh,φ∗h −1/2 − θc,φ∗c
(ṁc p )c ≤ (ṁc p )h ) are separately considered. dφ∗c L∗ 4π2
heat transfer engineering vol. 37 no. 12 2016
D.-K. NGUYEN AND J.-Y. SAN 1017
⎤
2 Cold Flow
1 1
+ φ∗c + + θh,φ∗h +1/2 − θc,φ∗c ⎦ (16)
2 4π2 (i) For (φ∗c,i − 1/2) ≤ φ∗c < φ∗c,i ,
dθc,φ∗c NTU
(iii) For (φ∗c,o − 1/2) ≤ φ∗c ≤ φ∗c,o , =
dφ∗c L∗
dθc,φ∗c NTU ⎡ ⎤
= C 2
dφ∗c L∗ 1 1
×⎣ φ∗c + + θh,φ∗h +1/2 − θc,φ∗c ⎦
2 4π2
2 1
× φ∗c + θh,φ∗h −1/2 − θc,φ∗c (17)
4π2 (21)
(ii) For φ∗c,i ≤ φ∗c < (φ∗c,o − 1/2),
with initial condition θc,φ∗c φ∗c = φ∗c,o = 0.
Downloaded by [University of Tennessee, Knoxville] at 21:31 31 March 2016
dθc,φ∗c NTU 2 1
= φ∗c + θh,φ∗h −1/2 − θc,φ∗c
dφ∗c L∗ 4π2
Dimensionless Energy Equations for (ṁc p )h ≥ (ṁc p )c
⎤
2
1 1
Hot Flow + φ∗c + + θh,φ∗h +1/2 − θc,φ∗c ⎦
2 4π2
(i) For (φ∗h,i − 1/2) ≤ φ∗h < φ∗h,i ,
(22)
dθh,φ∗h NTU
= C
dφ∗h L∗ (iii) For (φ∗c,o − 1/2) ≤ φ∗c ≤ φ∗c,o ,
⎡ ⎤
2 dθc,φ∗c NTU
1 1 =
×⎣ φ∗h + + θc,φ∗c +1/2 − θh,φ∗h ⎦ dφ∗c L∗
2 4π2
2 1
(18) × φ∗c + θh,φ∗h −1/2 − θc,φ∗c (23)
4π2
with initial condition θh,φ∗h φ∗h = φ∗h,i − 1/2 = 1, where with initial condition θc,φ∗c (φ∗c = φ∗c,o ) = 0.
C = (ṁc p )min /(ṁc p )max = (ṁc p )c /(ṁc p )h Heat Transfer Effectiveness (ε)
(ii) For φ∗h,i ≤ φ∗h < (φ∗h,o − 1/2), The heat transfer effectiveness of the spiral heat exchanger is
defined as the actual heat transfer rate divided by the maximum
dθh,φ∗h NTU ∗ 2 1 possible heat transfer rate as [33]
= C φh + θc,φ∗c −1/2 − θh,φ∗h
dφ∗h L ∗ 4π 2
(ṁc p )c (Tc,out − Tc,in )
ε=
⎤ (ṁc p )min (Th,in − Tc,in )
2
1 1
+ φ∗h + + θc,φ∗c +1/2 − θh,φ∗h ⎦(19) (ṁc p )h (Th,in − Th,out )
2 4π2 = (24)
(ṁc p )min (Th,in − Tc,in )
(iii) For (φ∗h,o − 1/2) ≤ φ∗h ≤ φ∗h,o ,
i. For (ṁc p )min = (ṁc p )h ,
dθh,φ∗h NTU
= C ε = 1 − θh,out = θc,out /C (25)
dφ∗h L∗
ii. For (ṁc p )min = (ṁc p )c ,
∗ 2 1
× φh + θc,φ∗c −1/2 − θh,φ∗h (20) ε = θc,out = (1 − θh,out )/C (26)
4π2
In Eqs. (12)–(23), L ∗ denotes the dimensionless length of For ideal gas flow, c = c p ; for incompressible flow,
the wall. The L ∗ value can be calculated by using the φi∗ and c = cv .
Nt values. Hence, the NTU, C, φi∗ , and Nt are the characteristic The calculation of the exergy rate needs to be based on a
parameters determining the heat transfer performance of the common reference state at which the fluid is unable to do further
spiral heat exchanger. In the four parameters, the dimensionless work. The atmospheric condition is generally selected as the
start-point angle of spiral (φi∗ ) is found to be a weak factor reference state, which is also known as the dead state. In Eq.
affecting the heat transfer effectiveness (ε). As the φi∗ value (27), T0 denotes the dead-state temperature or the atmospheric
increases from 2 to 20, at Nt = 3 and NTU ≤ 10, the deviation temperature, while FP represents the pressure-drop factor of
in the ε value is less than 0.72%; at Nt = 20 and NTU ≤ 10, it the flow. For ideal gas flow, the FP can be expressed as FP =
is less than 0.38%. In this work, the φi∗ value is fixed at 2.0. [1 − (1/κ)][ln(1 + P/Pout )]; for incompressible flow, it can
be expressed as FP = P/(ρcv T0 ), where P stands for the
Numerical Analysis pressure drop of the flow (Pin − Pout ). In Eq. (27), the first term
on the right-hand side represents the thermal exergy change
rate in the flow, while the second term represents the consumed
The forward finite-difference scheme is used to discretize
Downloaded by [University of Tennessee, Knoxville] at 21:31 31 March 2016
where
SECOND-LAW ANALYSIS
FP,total ≡ FP,c C ∗ + FP,h
Exergy Change Rate in a Flow
C ∗ ≡ (ṁc)h /(ṁc)c
The heat exchange process in the spiral heat exchanger in-
volves a transfer of thermal energy from the hot flow to the and for ideal gas flow, c = c p ; for incompressible flow, c = cv .
.
cold flow and a consumption of mechanical energy (P) for Using Eqs. (25) and (26), the ( E X )net values at
driving the working fluids. For assessing the economic value of (ṁc)min = (ṁc)c and (ṁc)min = (ṁc)h are expressed respectively
the heat exchanger, the two different forms of energy (thermal as:
energy and mechanical energy) are converted into a common
basis: exergy. The exergy change rate in the hot/cold flow is the (i) At (ṁc)min = (ṁc)c ,
difference in the exergy rate of the fluid between the inlet and
.
the outlet. It is expressed as [27] ( E X )net
. ψnet ≡ = ψther mal − ψmech
( E X ) = E X .out − E X in
.
= ṁ (h − T0 s) (ṁc)h T0
∗
Tout − Tin Tout 1 ∗ ∗
θh
= (ṁc) T0 − ln = ε θh − θc − ln 1 + ε ∗ − 1
T0 Tin C∗ θc
−Fp,total (30)
where θ∗c ≡ Tc,in /T0 , θ∗h ≡ Th,in /T0 .
Nt
NTU C 3 6 10 20
Figure 9 ε-NTU relationship at Nt = 20. Figure 10 Comparison of ε values at φi∗ = 2.5 and Nt = 9.25.
Figure 12 ψnet at θ∗h = 1.8 and FP,h = FP,c = 0.0001. Figure 14 ψnet at θ∗h = 1.8 and FP,h = FP,c = 0.01.
that of the counterflow heat exchanger. The deviation in the ψnet (or Fp,c ) values (i.e., θ∗h = 1.2 and Fp,h = 0.01), the ψnet
value between the two heat exchangers increases with the NTUh value could turn into a negative value.
∗
value, while the maximum deviation occurs at the Copt value. For using the spiral heat exchanger in a waste heat recovery
∗ ∗
The Copt and ψnet values at various θh , NTUh and Fp,h (or process, if the thermal energy recovered by the heat exchanger
∗
Fp,c ) values are presented in Table 2. The Copt value is slightly is intended to convert into work or a cooling effect, the ψnet
∗
affected by the θh and Fp,h (or Fp,c ) values, whereas it varies value needs to be positive and it should be designed to be as
∗
remarkably with the NTUh value. At NTUh < 2, the Copt value large as possible. From an economic viewpoint, a large ψnet
increases dramatically with a decrease of the NTUh value; at value implies a short payback period of the utility cost for the
NTUh ≥ 4, it is almost invariant with the NTUh value. In Ta- process. From Table 2, it can be known that for obtaining a large
ble 2, it is also shown that the maximum ψnet value significantly net recovered exergy rate (ψnet ), the NTUh value of the heat ex-
decreases with the θ∗h value. At small θ∗h values and large Fp,h changer needs to be larger than 2.0 and the heat exchanger needs
to operate at a near balanced-flow condition ((ṁc p )h ≈ (ṁc p )c
or NTUh ≈ NTU). In addition, for recovering low-grade ther-
mal energy (small θ∗h values), a small ψmech value is highly
demanded for avoiding the occurrence of a negative net recov-
ered exergy rate. A negative net recovered exergy rate means
the consumed mechanical exergy rate (i.e., power consumption
of fans or pumps) is larger than the recovered thermal exergy
rate.
In many engineering applications, both the hot-flow capacity
rate and the cold-flow capacity rate are specified. Under this
circumstance, the C∗ value is fixed and thus the heat exchange
∗
process won’t be able to operate at the Copt value. However,
in some engineering applications, the flow capacity rate of the
hot fluid (heat source) is specified, whereas the flow capacity
rate of the cold fluid can be selected. For instance, consider a
heat exchanger that is used to recover waste heat from a flue gas
that is exhausted from a thermal system. The thermal energy
recovered by the heat exchanger then is input into an engine
operating with the organic Rankine cycle (ORC) to produce
electricity. In this case, the hot-flow capacity rate (flow capacity
rate of the flue gas) is fixed whereas the size of the ORC engine
Figure 13 ψnet at θ∗h = 1.8 and FP,h = FP,c = 0.001. can be selected to meet the requirement for obtaining the Copt ∗
value (i.e., the size of the ORC engine determines the cold- 0.01 m and H = 0.11 m were obtained. The correlation of the
∗
flow capacity rate). Operating at the Copt value, more exergy heat transfer data was expressed in the following form:
can be extracted from the flue gas and thus more exergy can be
N u = 0.003025Re + 18.4 for 3209 ≤ Re ≤ 14932 (31)
delivered to the ORC engine. Consequently, a maximum amount
of electricity is produced in the process. Equation (31) is used to calculate the Nu values for the hot
and cold flows in the channels of the heat exchanger. It is worth
mentioning that the channel aspect ratio (H/W) in this exam-
ple is different from that established by Eq. (31). A different
NUMERICAL EXAMPLE channel aspect ratio could result in a deviation in the Nu value.
However, in these two cases, the channel aspect ratios are quite
A numerical example using the acquired ε-NTU relation- large, which could make the deviation in the Nu value be small.
ship to predict the heat transfer performance of a spiral heat
exchanger is illustrated. The number of turns of the spiral (Nt ) Table 3 Geometric parameters and operating conditions of a spiral heat
constructing the heat exchanger is 6 and the dimensionless start- exchanger
ing angle (φ∗h,i = φ∗c,i ) is 4. In addition, the channel width (W) is
Geometric Number of turns (Nt ) 6
0.011 m and the channel height (H) is 0.3 m. From a geometric
parameters Dimensionless starting angle (φi∗ ) 4
calculation, the length of the spiral wall (L) and the total heat Channel width (W) 0.011 m
transfer area of the heat exchanger (2LH) are estimated to be Channel height (H) 0.3 m
5.13 m and 3.08 m2, respectively. Length of the spiral wall (L) 5.13 m
The heat exchanger recovers waste heat from a flue gas at Total heat transfer area (At ) 3.08 m2
Channel hydraulic diameter (Dh ) 0.0212 m
temperature of 453.15 K and volumetric flow rate of 4 m3/min.
Operating (i) Hot-flow (flue gas) side
The inlet temperature and volumetric flow rate of the cold flow conditions Inlet temperature 453.15 K
(air) are 298.15 K (environmental temperature) and 2.5 m3/min, Volumetric flow rate at inlet 4.0 m3/min
respectively. The thermal energy acquired by the cold flow is Density at inlet (ρ f ) 0.8 kg/m3
intended to regenerate a desiccant wheel, which is incorporated Mass flow rate (ṁ f ) 0.0533 kg/s
Average specific heat (c p, f ) 1122 J/kg-K
with a vapor-compression type air conditioner to form a hybrid
Average thermal conductivity (k f ) 0.0343 W/m-K
air-conditioning system (using the desiccant wheel for dehumid- Average kinematic viscosity (μ f ) 2.5 × 10−5 kg/m-s
ification and using the vapor-compression type air conditioner (ii) Cold-flow (air) side
for cooling). A detailed specification of the geometric parame- Inlet temperature 298.15 K
ters and operating conditions of the heat exchanger is listed in Volumetric flow rate at inlet 2.5 m3/min
Density at inlet (ρa ) 1.18 kg/m3
Table 3.
Mass flow rate (ṁ a ) 0.0492 kg/s
In order to calculate the NTU value, the average convective Average specific heat (c p,a ) 1007 J/kg-K
heat transfer coefficients for the hot and cold flows (hf and ha ) Average thermal conductivity (ka ) 0.0317 W/m-K
need to be known. In an earlier experimental work [34], the Average kinematic viscosity (μa ) 2.21 × 10−5 kg/m-s
heat transfer data for an airflow in a spiral channel with W =
heat transfer engineering vol. 37 no. 12 2016
1024 D.-K. NGUYEN AND J.-Y. SAN
Hence, the Nu value evaluated by using Eq. (31) should be still 13719, it is 0.0263. Using the data, the pressure drops of the
valid for roughly predicting the heat transfer performance of airflow and flue-gas flow are estimated to be
the heat exchanger. For accurately predicting the heat transfer
performance, the Nu value needs to be calculated by using a L ρa u a2
(P)a = f a = 591Pa = 60.3mm − H2 O
correlation equation not only with the Re, but also with the di- Dh 2
mensionless channel geometry as the characteristic parameters.
Using the specified values shown in Table 3, the convective (P) f = 1038Pa = 105.8mm − H2 O
heat transfer coefficients on the air side (ha ) and flue gas side
Following these, the FP,a and FP, f values are calculated
(hf ) are evaluated as:
to be 0.00166 and 0.00291, respectively. These two values yield
an overall pressure drop factor (FP,total ) of 0.0043. Then using
(i) Cold-flow (air) side: Eq. (29), the dimensionless net recovered exergy rate (ψnet )
and the net recovered exergy rate input into the hybrid air-
ρa u a Dh ṁ a Dh conditioner system are found to be 0.0496 and 884.6 W, respec-
Rea = = = 14307, N u a = 61.68
μa μa (W H ) tively.
Downloaded by [University of Tennessee, Knoxville] at 21:31 31 March 2016
N u a ka
ha = = 92.1W m 2 −K
Dh CONCLUSIONS
(ii) Hot-flow (flue gas) side:
From the result of the analysis, it is known that the φi∗ value
is a weak factor affecting the ε value. At C = 0, the ε value
ṁ f Dh
Re f = = 13719, N u f = 60 increases with the Nt value; at C = 0, despite the Nt value, the
μ f (W H ) ε value is the same as that of a condenser or an evaporator.
The deviation in the ε value between the spiral heat exchanger
Nu f k f
hf = = 96.8W/m2 −K and a counterflow heat exchanger decreases with an increase of
Dh the Nt value. At Nt ≥ 10, the deviation is small. In addition
to the Nt value, the deviation also increases with the C and
The overall heat transfer coefficient (U) between the cold NTU values. At Nt ≥ 3 and NTU ≤ 8.0, the maximum devi-
flow and the hot flow is estimated by using the hf and ha values. ation in the ε value is 12.9%. The maximum deviation occurs
Neglecting the solid-conduction (wall) effect, the U value is at C = 1.
equal to For a set of C and Nt values, the spiral heat exchanger has
a maximum ε value. The optimum NTU value at the maximum
1 ε value moderately increases with a decrease of the C value,
U≈ = 47.2W/m2 −K
(1 h a ) + (1 h f ) whereas it significantly increases with the Nt value. At Nt > 3,
the optimum NTU value is larger than 6.9.
Then the NTU, C, and C∗ values of the heat exchanger are In a waste heat recovery process, as the thermal energy re-
evaluated as covered by the heat exchanger is intended to convert into work
U At U At or a cooling effect, the dimensionless recovered thermal exergy
NTU ≡ = = 2.93,
(ṁc p )min (ṁc p )a rate (ψther mal ) needs to be larger than the dimensionless con-
sumed mechanical exergy rate (ψmech ). Subtracting the ψmech
(ṁc p )min (ṁc p )a value from the ψther mal value yields the dimensionless net re-
C≡ = = 0.827 covered exergy rate (ψnet ). The ψnet value can be used to assess
(ṁc p )max (ṁc p ) f
the economic value of the heat exchanger used in the waste heat
(ṁc p )h (ṁc p ) f recovery process. A larger ψnet value implies a shorter payback
C∗ ≡ = = 1.21 period of the utility cost for the process.
(ṁc p )c (ṁc p )a
The ψnet value significantly decreases with the θ∗h value. At
Using the NTU and C values, the heat transfer effectiveness small θ∗h values, as the ψmech value is large, the ψnet value could
(ε) of the heat exchanger is found to be 0.78 (Figure 7). Next, turn into a negative value. This would make the heat recovery
the exit temperatures of the air and flue gas are calculated to be process become meaningless.
419.05 K and 353.12 K, respectively. From the exit temperature A maximum ψnet is found. The optimum C∗ value (Copt ∗
)
∗
of the air, it can be known that the thermal energy recovered by at the maximum ψnet decreases with an increase of the θh and
∗
the heat exchanger is 5990 W. NTUh values. At NTUh > 2, the Copt value is close to 1.0. For
The pressure drops of the hot and cold flows can also be obtaining a large net recovered exergy rate, the NTUh value
calculated using previously acquired fluid friction data [34]. At of the spiral heat exchanger needs to be greater than 2.0 and
Rea = 14307, the Darcy friction factor (f) is 0.026; at Ref = the spiral heat exchanger needs to operate at a near balanced-
heat transfer engineering vol. 37 no. 12 2016
D.-K. NGUYEN AND J.-Y. SAN 1025
flow condition. In addition, at small θ∗h values, a low consumed θ∗h Th,in /T0
mechanical power is highly demanded. κ specific heat ratio, c p /cv
μ kinematic viscosity, kg/m-s
ρ density, kg/m3
FUNDING φ spiral-direction coordinate, radians
φ∗ dimensionless spiral-direction coordinate, φ/2π
The authors thank the National Science Council of the Re- ψmech dimensionless total consumed mechanical exergy rate
public of China for financial support of this research (NSC-100- ψnet dimensionless net recovered exergy rate
2221-E-005-077). ψther mal dimensionless recovered thermal exergy rate
NOMENCLATURE Subscripts
Industrial and Engineering Chemistry Research, vol. 31, [23] Gupta, A., and Das, S. K., Second Law Analysis of Cross-
no. 3, pp. 658–669, 1992. flow Heat Exchanger in the Presence of Axial Dispersion
[8] Naphon, P., and Wongwises, S., An Experimental Study on in One Fluid, Energy, vol. 32, no. 5, pp. 664–672, 2007.
the In-Tube Convective Heat Transfer Coefficient in a Spi- [24] San, J. Y., and Pai, K. L., Performance of a Serpentine
ral Coil Heat Exchanger, International Communications in Heat Exchanger: Part II—Second-Law Efficiency, Applied
Heat and Mass Transfer, vol. 29, no. 6, pp. 797–809, 2002. Thermal Engineering, vol. 29, no. 14–45, pp. 3088–3093,
[9] Ho, J. C., Wijeysundera, N. E., Rajasekar, S., and Chan- 2009.
dratilleke, T. T., Performance of a Compact, Spiral-Coil [25] Wu, S. Y., Yuan, X. F., Li, Y. R., and Xiao, L., Energy
Heat Exchanger, Heat Recovery Systems & CHP, vol. 15, Transfer Effectiveness on Heat Exchanger for Finite Pres-
no. 5, pp. 457–468, 1995. sure Drop, Energy, vol. 32, no. 11, pp. 2110–2120, 2007.
[10] Wijeysundera, N. E., Ho, J. C., and Rajasekar, S., The Ef- [26] Ruan, D. F., Yuan, X. F., Wu, S. Y., and Li, Y. R., Exergy Ef-
fectiveness of a Spiral Coil Heat Exchanger, International fectiveness Analysis of Three-Fluid Heat Exchanger, Jour-
Communications in Heat and Mass Transfer, vol. 23, no. nal of Superconductivity and Novel Magnetism, vol. 23, no.
5, pp. 623–631, 1996. 6, pp. 1127–1131, 2010.
Downloaded by [University of Tennessee, Knoxville] at 21:31 31 March 2016
[11] Bes, T., Eine Methode der Thermischen Berechnung [27] San, J.Y., Second-Law Performance of Heat Exchang-
von Gegen-und Gleichstrom-Spiralwärmeaustauschern, ers for Waste Heat Recovery, Energy, vol. 35, no. 5, pp.
Wärme-und Stoffübertragung, vol. 21, no. 5, pp. 301–309, 1936–1945, 2010.
1987. [28] Hadi, H., Mohsen, P., and Mahmoud, D., Control of Free
[12] Bes, T., and Roetzel, W., Thermal Theory of the Spiral Convection and Entropy Generation in Inclined Porous
Heat Exchanger, International Journal of Heat and Mass Media, Heat Transfer Engineering, vol. 33, no. 6, pp.
Transfer, vol. 36, no. 3, pp. 765–773, 1993. 565–573, 2012.
[13] Bes, T., and Roetzel, W., Approximate Theory of Spi- [29] Lawrence, J. D., A Catalog of Special Plane Curves, Dover
ral Heat Exchanger, Design and Operation of Heat Ex- Publications, New York, NY, p. 186, 1972.
changers, Proceedings of the EUROTHERM Seminars No. [30] Thomas, G. B., Weir, M. D., and Hass, J., Thomas’ Calcu-
18, February 27–March 1, 1991, Hamburg, Germany, pp. lus, 12th ed., Addison Wesley, Boston, MA, p. 637, 2009.
223–232, Springer-Verlag, Berlin, Germany, 1991. [31] Weisstein, E. W., Archimedes’ Spiral, MathWorld—A
[14] Bes, T., and Roetzel, W., Distribution of Heat Flux Density Wolfram Web Resource, http://mathworld.wolfram.com/
in Spiral Heat Exchangers, International Journal of Heat ArchimedesSpiral.html, April 2014.
and Mass Transfer, vol. 35, no. 6, pp. 1331–1347, 1992. [32] Nguyen, D. K., Heat Transfer Effectiveness and Exergy
[15] Burmeister, L. C., Effectiveness of a Spiral-Plate Heat Ex- Recovery Effectiveness of a Spiral Heat Exchanger, M.Sc.
changer With Equal Capacitance Rates, ASME Journal of Thesis, National Chung Hsing University, Taiwan, ROC,
Heat Transfer, vol. 128, no. 3, pp. 295–301, 2006. 2011.
[16] Adamski, M., Heat Transfer Correlations and NTU Num- [33] Incropera, F. P., Dewitt, D. P., Bergman, T. L., and Lavine,
ber for the Longitudinal Flow Spiral Recuperators, Applied A. S., Foundations of Heat Transfer, 6th ed., John Wiley &
Thermal Engineering, vol. 29, no. 2–3, pp. 591–596, 2009. Sons, Singapore, pp. 688–692, 2013.
[17] Rennie, T. J., and Raghavan, V. G. S., Numerical Studies of [34] San, J. Y., Heat Transfer Performance of a Spiral Heat
a Double-Pipe Helical Heat Exchanger, Applied Thermal Exchanger, NSC Project Number NSC-100-2212-E-005-
Engineering, vol. 26, no. 11–12, pp. 1266–1273, 2006. 077, Taiwan, ROC, 2011.
[18] San, J. Y., Lin, G. S., and Pai, K. L., Performance of
a Serpentine Heat Exchanger: Part I—Effectiveness and Duc-Khuyen Nguyen is a Ph.D. student in the Me-
chanical Engineering Department of National Chung
Heat Transfer Characteristics, Applied Thermal Engineer-
Hsing University, Taiwan. He received the B.S. de-
ing, vol. 29, no. 14–15, pp. 3081–3087, 2009. gree in mechanical engineering from Nong Lam Uni-
[19] Salem, A. A., Awad, B. S. A., and Syed, M. Z., versity, Vietnam, and the M.S. degree in heat transfer
Effectiveness–NTU Relations for Counterflow Heat Ex- from National Chung Hsing University, Taiwan. His
changers: The Effect of Kinetic Energy Variation and Heat research interests include heat transfer enhancement,
drying technology, and postharvest technology.
Leak From Outside, Heat Transfer Engineering, vol. 34,
no. 10, pp. 810–827, 2013.
Jung-Yang San is a professor in the Mechanical En-
[20] Martin, H., Heat Exchangers, Hemisphere, Washington
gineering Department of National Chung Hsing Uni-
DC, pp. 73–82, 1992. versity, Taiwan. He received his master’s degree from
[21] San, J. Y., Worek, W. M., and Lavan, Z., Second-Law Stanford University and Ph.D. degree from the Illi-
Analysis of a Two- Dimensional Regenerator, Energy, vol. nois Institute of Technology. His research interests
12, no. 6, pp. 485–496, 1987. include waste heat recovery, adsorption heat pump,
heat transfer enhancement, and jet impingement
[22] San, J. Y., and Jan, C.L., Second-Law Analysis of a Wet
cooling.
Cross Flow Heat Exchanger, Energy, vol. 25, no. 10,
pp. 939–955, 2000.
heat transfer engineering vol. 37 no. 12 2016