Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

130

Chris R Hendy Design of cross-girders and


Head of Bridge Design
and Technology slabs in ladder deck bridges
Highways &
Transportation
Abstract
Atkins
Deck slabs in ladder decks span longitudinally between transverse cross-
Jessica Sandberg
girders and the primary function of these cross-girders is to support the deck
slab. The girders may however need to perform the secondary function of
Senior Engineer preventing the slab from buckling in compression. The concrete deck slab of
Highways & a ladder deck can have a very large transverse span between main girders.
Transportation This large unsupported width can lead to buckling of the slab in compression
Atkins unless it is prevented from doing so by transverse girders. Where transverse
girders are required to prevent buckling of the slab, they need to be designed
to be both stiff enough and strong enough to perform this function in
addition to resisting vertical loading. If the spacing of the cross-girders is
David Iles
large, it is still possible for second order bending moments to develop in the
Steel Construction slab under the effects of global compression. This paper sets out guidance on
Institute
the limiting spacing of main girders and cross-girders to avoid consideration of
second order effects and also the means of determining second order effects
in slab and cross-girders when this becomes necessary.

Introduction
In ladder deck bridges, such as those are rules that may be applied. The
illustrated in Figure 1, the deck slab purpose of this paper is to show how
performs two principal functions: the Eurocode rules may be applied
it carries permanent and variable to the design of cross-girder and slab
loads in plate bending, spanning and to provide simplified factors to
between the transverse cross-girders account for second order effects.
and between the main girders; and it
In hogging regions, the deck slab is
acts as the flanges of the composite
in tension and there are no buckling
main girders and cross girders. In
effects to consider; there are no
sagging regions, the deck slab is
second order effects in the slab and
in compression longitudinally and
no restraint forces imposed on the
its stability against plate buckling
cross girders. Nevertheless, the
needs to be verified. The cross
dimensions of the slab and the cross
girders provide regularly spaced
girders are generally chosen the same
out-of-plane restraint to the slab, in
as in the sagging regions and thus
addition to their role in supporting
the verification in the sagging regions
the deck slab between the main
determines the sizes for the whole
girders; the stiffness of the restraint
bridge.
that these cross girders provide must
be considered and any forces arising
from the restraint that they provide
must be included in their design.
Even when restrained by the cross
girders, the slab itself is relatively
Structures

slender, in terms the ratio of cross


girder spacing to slab thickness,
and second order effects need to be
considered in its design verification.
The rules in Eurocodes 2, 3 and 4
do not explicitly deal with these Figure 1. Typical ladder deck geometry
design considerations, although there (prior to casting deck slab)
93
Plate buckling action of
the deck slab
For the concrete slab to buckle under
longitudinal compression, it must
bend out of plane both longitudinally
and transversely. If there were no
cross-girders, the behaviour would
be like that of a plate – see Figure 2.
Schlaich et al1 recommend that, to
prevent any significant second order
effects from occurring in the slab due
to such buckling, the transverse span Figure 3. Slab buckling between cross-girders
to depth ratio should not exceed 30;
the authors of this paper consider,
based on precedent, this to be a
Where a wide slab is stiffened by the Second order effects in
cross girders, the mode of buckling
reasonably pragmatic limit for typical tends toward that of simple strut deck slab
concrete grades up to C40/50 but buckling – the greater the aspect
this limiting ratio might be a little too ratio, the closer the buckling is to Where second order effects in the
large for higher strength concrete strut-like behaviour – see Figure 3. compressive region of the deck slab
grades. To consider whether second order need to be accounted for, this can by
effects in the slab are significant achieved using EN 1992-1-1, treating
and, if they are, to evaluate the the slab as a simple compression
design effects, it is conservative to member. Three methods are given
ignore plate action (i.e. buckling of for determining second order effects
a rectangular plate supported on in reinforced concrete compression
four sides) and to treat the slab as a members, in clauses 5.8.6, 5.8.7
column, with a half wavelength of and 5.8.8. The clause 5.8.6 method
buckling equal to the span between requires non-linear analysis and is
cross girders. thus not readily applicable; the clause
5.8.8 method is not suitable for
Limit on cross-girder spacing members with transverse load, such
to avoid considering second as the deck slabs; thus the clause
Figure 2. Slab buckling without restraint 5.8.7 method is used.
from cross-girders (plate-like behaviour)
order effects in the slab
In PD6687-22, clause 6.1 provides a The clause 5.8.7 method uses a
simple rule for externally prestressed nominal stiffness of the compression
When the slab transverse span/ members that second order effects member that takes account of
thickness ratio is within the above need not be checked when the the level of stress in the member,
limit, it is sufficiently stable without spacing between deviators does the concrete strength and the
any additional restraint from the not exceed 10 times the section member slenderness. In doing so,
cross girders. Consequently, the depth. This simple rule is considered it is important to use the actual
design of the cross-girders does not appropriate for the slab of a ladder design compression force in the
need to include any restraint forces. deck in the sagging region. The slab (to avoid over-conservatism)
However, in practice, when the rule is less conservative than the and the eccentricity of that force
slab thickness is typically 250mm, simple rule for isolated compression from the centre of the slab (as this
the above limit is equivalent to a members in clause 5.8.3.1 of EN causes slab moment and curvature
limiting spacing of the main girders 1992-1 but even so, in practice, which will also be amplified by the
of 7.5m (slightly less if the concrete is with a 250mm slab thickness the compression). Generally, the slab
stronger than C40/50). Most ladder consequent limit of 2.5m on cross force is unlikely to be at the level of
deck construction places the main girder spacing is much lower than its design compression resistance,
girders at greater spacing than this the preferred spacing of between as the design situation will be
(up to about 18m) and then the slab 3m and 4m. In practice, therefore, with combined longitudinal and
will need to be stiffened transversely second order effects in the slab will transverse loading on the slab (and
by cross-girders. need to be considered. thus there will be significant local

94
130 Design of cross-girders and slabs in ladder deck bridges

bending moments to be considered).


Additionally, Eurocode 4 requires
shear lag to be considered at ULS
and this will normally mean that the
design compression resistance is not
that of the gross slab. Even if the full
width of the slab can be mobilised,
its large width makes it unlikely that
it will be fully utilised in compression.
The clause 5.8.7 method derives a
magnification factor that is applied to
the first order moments. The factor is
expressed in clause 5.8.7.3 as:

b Figure 4. Eccentricity of slab force


MEd = M0Ed 1+
( NB /NEd ) - 1
noted above, the value of NEd should B equal to the main girder spacing
be based on the actual slab force and length L between cross girders.
Where
calculated allowing for shear lag and
M0Ed is the first order moment, the crushing resistance Acfcd should ksp 2Et 3 ksp 2EI
Ncr,p = =
which should be taken as be based on the whole gross width 12(1-v 2)B (1-v 2)B 2
Mslab +NEd(e+w0) of slab ignoring shear lag.
NEd is the design value of the (Note that fcd should be calculated in
in which ks = (B/L + L/B)2
axial force in the slab, accordance with EN 1992-2 rather
coexisting with MEd than EN 1994-2). The effective creep and v = 0 for cracked concrete.
ratio jef is determined in accordance
NB is the buckling load, given by In this case, EI will not be constant
with clause 5.8.4(2) of EN 1992- in the two directions, even if the
NB =p 2EI/L2
1-1. A value of zero implies all the reinforcement provision is the same,
Mslab is the moment in the slab slab moment is due to non-quasi- because the transverse direction
due to transverse loading permanent loading. typically has zero compressive force.
Values of the magnification factor A conservative approach would be to
e is the eccentricity of the axial
for a range of n values are given in take the smaller value of the cracked
force relative to the centroid
Figure 5, for a 250mm thick slab stiffness derived in accordance
of the slab
spanning 3.0 and 4.0m. It will be with clause 5.8.7.2 in either the
w0 is the geometric imperfection noted that the curves for 4m spacing longitudinal or transverse direction.
in the slab (= slab span/400, have been curtailed at n = 0.6; This is, however, likely to be overly
based on the value of θo = beyond this point the curve changes conservative since, for normal slab
1/200 in EN 1992-2, clause gradient according to clause 5.8.7 support aspect ratios, the behaviour
105 and the UK NA) because the parameter k2 reaches a is dominated by the stiffness in the
limiting value of 0.2. Clearly there longitudinal direction, so the slightly
EI is the nominal stiffness,
would be no step change in reality unconservative approach of basing
given by clause 5.8.7.2.
and calculations beyond this value EI solely on the longitudinal direction
Second order effects may be ignored of n could either be conservatively will be acceptable. In addition, the
if they are less than 10% of the first performed to clause 5.8.7 or non- moment amplification method itself
order effects, according to clause linear analysis used. becomes more conservative the more
5.8.2(6). plate-like the behaviour becomes as,
The situation where the main
The calculation of stiffness EI for plate-like behaviour, the elastic
beam spacing is not large relative
critical buckling force is not an upper
Structures

according to clause 5.8.7.2 depends to the cross girder spacing and the
on a number of parameters, bound on strength, whereas it is for
behaviour is partially plate-like, rather
including the area of reinforcement, column-like behaviour. The benefit
than solely column-like, could be
the effective creep ratio jef and the of using the plate critical force will
accommodated in the process of
relative axial force n. The relative be small but will increase as the ratio
determining NB by substituting the
axial force is a significant parameter: B/L reduces. Utilising this approach
buckling load for a plate, Ncr,p of side
its value is defined as NEd /Acfcd. As is likely only to be of benefit in the

95
(a)

(b)

Figure 5. Magnification factor, to allow for second order effects (250 mm slab, C40/50), (a) H20 bars at 150 mm centres, top and
bottom, (b) H16 bars at 150 mm centres, top and bottom

96
130 Design of cross-girders and slabs in ladder deck bridges

situation where a small overstress moments is parabolic, this gives a b considered in verifying the strength
was produced using the column value of 1.0. of the cross girder).
buckling approach.
The moment magnification factor is: The Designers’ Guide to EN 1993-
An example of the calculation of the b 1
23 gives a method of calculation to
magnifying factor, for both simple m= 1+ = 1+
(5237/1133)-1
=1.28 combine the destabilising effect of
(NB/NEd)-1
strut buckling and for plate panel the deck slab and the transverse
buckling is given below. Alternatively, NB can be replaced by moments acting on the transverse
Ncr,p members in the strength check.
Assume a slab thickness 250mm,
cross girder spacing 3500mm and ks= (B/L+L/B)2 = (3500/12000 + Stiffness requirement
main girder spacing 12000mm. The 12000/3500)2 = 13.84 Based on the requirement in EN
slab concrete is C40/50 and the
v = 0 for cracked concrete. 1993-1-5, 9.2.1 the stiffness
reinforcement is H16 bars at 150mm
requirement may be expressed as:
centres (take distance between
ksp2EI 13.84 x p2 x 6.50 x 1012
top and bottom bars = 160mm, Ncr,p = = x B
symmetrically placed abouththe slab (1-v 2)B2 120002 d +wEd <
300
centroid). Take jef = 0 and = 0.20 10-3 = 6166 kN
and fcd = acc fck / gm = 22.7 MPa with And then where
acc = 0.85 and gm = 1.5. wEd is the deflection of the cross
1 girder under transverse load
Properties per metre width of slab m= 1+
(6166/1133)-1
=1.23
Ic = 1.302 × 109 mm4 d is the extra deflection arising
Is = 17.2 × 106 mm4 This reduces the moment due to the compression
magnification factor. in the slab and, in the
Material properties
absence of transverse axial
Es = 200 000 MPa
force in the cross girder, is
Ecd = Ecm/gcE = 35 000/1.2 = 29 200 Destabilizing effects on given by:
MPa
transverse cross girders
The effective stiffness is given by -1
EIst
clause 5.8.7.2 of EN 1992-1-1 as: When the presence of cross-girders -1
is needed to prevent buckling of the d = w0’ smB4
EI = KcEcdIc + KsEsIs
slab in compression, they must be p4
Ks = 1 designed for stiffness and strength
f ck /20 = 40/20 = 1.41 so that they do in fact restrict the
K1 = where
buckling length of the slab to the
K2 = distance between cross-girders. This Ist is the second moment of
48.5
h l =0.2 3500/72.2 =0.2 =0.0571 is achieved by designing them as area of the composite
170 170 170 transverse stiffeners to EN 1993-1-5 section
clause 9.2.
k1k2 w’0 =w0 + wEd
Kc= = 1.41 x 0.0571 =0.0805 The stiffness of the composite
(1+jef) (1+0)
transverse girder may conservatively
be based on its fully cracked section w0 is the initial imperfection
EI = 0.0805 x 29200 x 1.302 x 109 + which, according to EN
properties but it will usually be
1 x 200000 x 17.2 x 106 = 6.50 x 1012 Nmm2
adequate to use uncracked properties 1090-2, Annex D1.6(5), for
for the slab, as the permanent one cross girder level relative
The design value of axial load per cross girder moment will usually be to the adjacent girders, is
metre width is: sagging. This sagging moment will 2L/400 = L/200
be increased by the destabilising sm is the destabilizing effect
NEd = hAc f cd = 0.2 x 250000 x effect of the slab if the cross girder
22.7 x 10-3 = 1133 kN of the load in the slab, which
being checked has a net downward
Structures

can conservatively be taken,


The critical force per metre width is: deflection compared to the adjacent for the case of cross girders,
girders. If an adjacent girder is as:
NB= p2 EI/L2 = p2 x 6.50 x 1012/35002 x loaded, the destabilising effect
10-3 = 5237 kN would tend to push the cross girder 2NEd 2scbtslab 2sctslab
sm = = =
up and relieve the sagging moment BL BL L
Conservatively assume that the
(and does not therefore need to be
distribution of the first order
97
In which sc is the mean longitudinal
stress in the slab. This value can Acknowledgement
either be determined according to
the actual design effects or to the The authors thank Mabey Bridge for the supply of the photograph in
value if resistance is fully mobilised. Figure 1.

Strength requirement
References
The destabilising load on the cross
girder depends on longitudinal 1. J.Schlaich and H Scheef (1982), Concrete box girder bridges,
imperfection and its peak value (at Structural engineering Documents 1e, IABSE, Switzerland.
the centre of the cross girder) is
2. PD 6687-2 (2008), Recommendations for the design of structures to
(w0’ =d)sm . Assuming that this is BS EN 1992-2:2005, BSI, England
a sinusoidal imperfection, this slab
3. C.R.Hendy and C.J.Murphy (2007), Designers’ Guide to EN 1993-2
applies an additional moment on the
Eurocode 3: Part 2: Design of Steel Structures Part 2, Steel Bridges,
cross girder of:
Thomas Telford, UK.
smB 2
(w0’ =d)
p2

This additional moment must be


included in the ULS verification of the
cross girder.

98

You might also like