Air Mantenance Devise

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Model AMD-2 Automatic Air Maintenance Device


Compressor Control Type
With Field Adjustable Pressure Switch
General Technical
Description Data
The Model AMD-2 Automatic Air Main- Approvals
tenance Device is an automatic, field- UL and ULC Listed. FM Approved.
adjustable device that controls the on- NYC under MEA 206-02-E.
off cycling of an air compressor. It is
used to control the pressure in a dry Pressure Switch Differential
pipe sprinkler system, preaction sys- 6 psi (0,4 bar)
tem, or dry pilot line system of a dry Field Adjustable Minimum Cut-In
pilot actuated deluge or preaction (On) Pressure
valve. The AMD-2 is utilized in appli- 14 psi (1,0 bar)
cations where it is desirable or neces- than that which will be exhausted by
sary to use a small, non-tank mounted Field Adjustable Maximum Cut-Out
(Off) Pressure the operation of a 5.6 K-Factor sprin-
compressor that is to be dedicated for kler.
the system to be pressurized. The 60 psi (4,1 bar)
AMD-2 monitors system pressure and Factory Set Outlet Pressure Given a small leak in the system, the
automatically cycles the air compres- 35 to 41 psi (2,4 to 2,8 bar) Pressure Switch will automatically
sor on and off to maintain system pres- transfer its contacts at the cut-in pres-
sure within preset limits. Assembly sure to start the air compressor and
Major components illustrated in Figure then shut off the air compressor once
The AMD-2 Automatic Air Mainte- 1 are factory assembled with galva- the cut-out pressure is reached.
nance Device features a Pressure nized steel nipples and malleable iron
Switch with integral unloading valve pipe fittings.
which automatically bleeds the pres-
sure between the air compressor and
AMD-2 after the air compressor has
been automatically shut off. This fea-
ture prevents starting of the air com-
pressor under load.
The Model AMD-2 Automatic Air Main-
tenance Device is a redesignation for
the Central Model DU-2, Gem Model Operation
F326, and Star Model S465. The By-Pass Valve in the AMD-2 is
opened to fast fill the system during the
WARNING initial pressurization. Once the cut-out
The Model AMD-2 Automatic Air Main- pressure of the Pressure Switch is
tenance Device described herein must reached, its actuating lever will trans-
be installed and maintained in compli- fer the DPDT switch contacts to shut
ance with this document, as well as off the air compressor and also open
with the applicable standards of the the unloader valve to bleed pressure
National Fire Protection Association, between the air compressor and the
in addition to the standards of any Restrictor Check Valve. The By-Pass
other authorities having jurisdiction. Valve is then closed to place the AMD-
Failure to do so may impair the per- 2 in automatic operation.
formance of this device.
The Restrictor Check Valve prevents
The owner is responsible for maintain- the unloader valve from bleeding down
ing their fire protection system and de- the system. Also, with the By-Pass
vices in proper operating condition. Valve closed, its 3/32 inch (2,4 mm)
The installing contractor or sprinkler orifice limits flow of air into the system
manufacturer should be contacted to a value which is significantly less
with any questions.

Page 1 of 4 MARCH, 2005 TFP1231


Page 2 of 4 TFP1231

PRESSURE SWITCH BY-PASS VALVE


1/2" CONDUIT (WITH UNLOADER VALVE) (NORMALLY CLOSED)
OPENINGS P/N 92-326-1-001 P/N 46-047-1-004

1/2" NPT INLET


CONNECTION
1/2" NPT OUTLET
(FROM AIR
CONNECTION 7"
COMPRESSOR)
(TO SYSTEM) (177,5 mm)

12-1/2"
(317,5 mm)

2-1/2"
(63,5 mm)

RESTRICTOR
CHECK VALVE STRAINER
P/N 92-326-1-003 P/N 92-322-1-001
4" 16-1/2"
(101,6 mm) (419,1 mm)

FIGURE 1
MODEL AMD-2 AUTOMATIC AIR MAINTENANCE DEVICE

Code. Refer to Figure 3 for identifica- air supply trim to the system to be
Installation tion of the wiring terminals. pressurized.
The Model AMD-2 Automatic Air Main- Wiring to the Pressure Switch is made Step 3. Apply electrical power to the
tenance Device must be installed in through two 1/2 inch conduit openings Pressure Switch, to pressurize the
accordance with the following instruc- in the base of its enclosure. The No. 8 system.
tions: screw terminals will accept up to No.
Step 4. Close the By-pass Valve after
12 AWG wire. The switch ratings are as
the Pressure Switch cuts-out. Note the
NOTE follows:
cut-out pressure.
Suitable consideration must be given
to the removal of excessive moisture 115 VAC, 1 Phase . . 2 HP Step 5. Open a connection to the sys-
from the compressed air supply. 230 VAC, 1 Phase . . 3 HP tem just enough to slowly reduce the
230 VAC, 3 Phase . . 5 HP air pressure and close it immediately
575 VAC, 3 Phase . . 5 HP after the Pressure Switch cuts-in.
Step 1. Connections between the air 115 VDC . . . . . . . 2 HP
compressor and the AMD-2, as well as Verify that the cut-in pressure meets
230 VDC . . . . . . . 2 HP the minimum requirements of the sys-
between the AMD-2 and the system to
be pressurized, are to be a minimum tem to be pressurized, and note the
NOTE cut-out pressure.
of 1/2 inch (DN15) pipe size. The housing of the Pressure Switch
Step 2. A drip leg is to be installed in meets the requirements of NEMA 1. If necessary, remove the cover from
the air line between the air compressor Consequently, the Model AMD-2 Air the Pressure Switch and adjust the
and AMD-2 as shown in Figure 2, if a Maintenance Device must not be used cut-in pressure adjustment screw
moisture filter with integral drain is not in an application where potentially ex- shown in Figure 3. The cut-in pressure
installed at the outlet of the air com- plosive atmospheres are present or in changes approximately 1.5 psi (0,1
pressor. an application where a NEMA 1 enclo- bar) per half-turn of the screw.
sure is not acceptable.
Step 3. A 1/2 inch (DN15), non-spring NOTE
loaded, rubber faced, swing type The cut-in pressure should be set at
check valve must be located between the minimum required value, in order
the AMD-2 and the system to be pres-
surized. A check valve of this type is Setting to minimize the time to system trip in
the event of a sprinkler operation.
provided in the air supply trim of Tyco
Fire Products dry pipe valves, preac- Procedure Step 6. Repeat Step 5 if the cut-in
tion valves, and dry pilot trim. pressure required adjustment. Note
The Model AMD-2 Automatic Air Main- both the cut-in and cut-out pressures.
Step 4. Conduit and electrical connec- tenance Device must be set in accord-
tions to the Pressure Switch are to be ance with the following instructions:
made in accordance with the require- Step 1. Open the By-Pass Valve in the
ments of the Authority Having Jurisdic- AMD-2.
tion and/or the National Electrical
Step 2. Open the control valve in the
TFP1231 Page 3 of 4

Care and
Maintenance
The following inspection procedure
must be performed as indicated, in ad-
dition to any specific requirements of
the NFPA, and any impairment must
be immediately corrected.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in FIGURE 2
addition to the standards of any INSTALLATION OF DRIP LEG BETWEEN AIR COMPRESSOR
authority having jurisdiction. The in- AND MODEL AMD-2 AIR MAINTENANCE DEVICE
stalling contractor or product manufac-
turer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
code.

NOTE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
first be obtained from the proper
authorities and all personnel who may
be affected by this decision must be
notified.
After placing a fire protection system FIGURE 3
in service, notify the proper authorities
and advise those responsible for moni- ADJUSTING SCREW AND WIRING TERMINALS
toring proprietary and/or central sta- (COVER REMOVED)
tion alarms.
It is also recommended that accumu- valve and open the main drain valve.
lated moisture be removed from air Close the Accelerator Control Valve,
supply moisture filtration equipment, if the system is so equipped.
at least quarterly. More frequent in-
spections may be necessary in par- 4. Open a connection to the system
ticularly humid environments. just enough to slowly reduce the air
Do not allow condensed moisture to pressure and close it immediately
back-up into the air compressor cylin- after the Pressure Switch cuts-in.
der. Verify that the cut-in and cut-out
pressures are essentially the same
The Model AMD-2 Automatic Air Main- as the previously established re-
tenance Device must be inspected quirements.
quarterly in accordance with the fol-
lowing instructions: 5. Open the Accelerator Control Valve,
as applicable.
1. Verify that the By-Pass Valve is
closed. 6. Slowly open the main control valve
and after water begins to flow, slowly
2. Clean out the 1/4 inch Strainer lo- close the main drain valve and then
cated at the inlet to the Restrictor completely open the main control
Check Valve. Be sure to reinstall the valve. The AMD-2 Air Maintenance
strainer screen and tighten the cap Device is now ready for service.
securely.

3. Close the system’s main control


Page 4 of 4 TFP1231

Limited Ordering
Warranty Information
Products manufactured by Tyco Fire Orders for the AMD-2 and replace-
Products are warranted solely to the ment parts must include the descrip-
original Buyer for ten (10) years tion and Part Number (P/N).
against defects in material and work-
manship when paid for and properly AMD-2:
installed and maintained under normal Specify: Model AMD-2 Automatic Air
use and service. This warranty will ex- Maintenance Device,
pire ten (10) years from date of ship- P/N 52-326-2-001.
ment by Tyco Fire Products. No war-
ranty is given for products or Replacement Parts for
components manufactured by compa- AMD-2 Air Maintenance Device:
nies not affiliated by ownership with (Specify description) for use with
Tyco Fire Products or for products and Model AMD-2 Automatic Air Mainte-
components which have been subject nance Device, P/N (see Figure 1).
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS
OR IMPLIED, INCLUDING WARRAN-
TIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PUR-
POSE.

TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446

You might also like