1. Click “GET F2” icon to enable other setting icon.

2. Connect RS232 cable between UPS and computer.


3. Connect battery to UPS.
4. Plug in utility to UPS and let the UPS light up.
5. Click “ByUp +25%” icon to set bypass range high limit to 137VAC of rated output voltage.
6. Dis-plug utility from UPS and let the UPS to shutdown itself and save the setting.
7. If necessary , set bypass enable by previous software tool.
8. After that , do the bypass testing see if there is bypass output when UPS is turned off from
utility mode.