Heta Pump - Selection PDF
Heta Pump - Selection PDF
Specifications
Structure
Platform
Compressors
Twin screw semi-hermetic compressors. The compressors have a crankcase heater, lubrication ensured by a
pressure difference between delivery and suction, and independent refrigerant circuits. The motor has an integral
electronic protection with temperature sensors fitted directly in the windings and on the delivery pipes. Star-
triangle starting. The compressor is mounted on rubber vibration dampers to reduce the transmission of vibration
to the unit.
continuous from 25% to100% of the load, which enable to maximise the energy yield of the unit inevery
functioning condition. Start-up and switch off of the machine happenwith a partialisation of 25%.
Source-side heat exchanger
of the dry expansion type. Optimized for use with R134a, this allows the COP of the unit to be improved, with
smaller size and refrigerant charge.
User-side heat exchanger
of the dry expansion type. Optimized for use with R134a, this allows the COP of the unit to be improved, with
smaller size and refrigerant charge. This is insulated with a shell of closed-cell foam material.
Each heat exchanger is provided with a temperature probe for freeze protection and a probe for measuring the
outgoing water.
- Compressor timings
- Automatic rotation of compressor starting sequence
- Alarm signalling
- Alarm reset
- Capacity reduction
- Cumulative alarm contact for remote signalling
- Forcing of capacity reduction due to pressure limit
- Digital input for remote ON/OFF
- Double set point from digital input
- Alarm log recording with "black box" function
- Management of the log of the main variables
By default, the serial connections present as standard are enabled only for reading from BMS. Enabling of writing
from BMS is to be requested when ordering.
- Display of the following on the display:
--> Outgoing water temperature
--> Incoming water temperature
--> Temperature and differential set points
--> Description of alarms
--> Hour meter of operation and number of start-ups of unit, compressors and pumps (if present)
--> High pressure and relevant temperature
--> Low pressure and relevant temperature
Standard power supply [V/ph/Hz]
400/3~/50
CONTROLS AND SAFETY DEVICES
All the units are fitted with the following control and safety
components:
- high pressure switch with manual reset
- high pressure safety device with automatic reset, for a limited number of occurrences, managed by the controller
- low pressure safety device with automatic reset and limited tripping managed by the controller
- high pressure safety valves
- antifreeze probe at the outlet of the user-side heat exchangers
- differential pressure switch already fitted on the user-side heat exchangers
- overtemperature protection for compressors and fans
overtemperature protection for compressors and fans
- High pressure switch with automatic reset and limited interventions managed by the control;
- Low pressure switch with automatic reset and limited interventions managed by the control;
- High pressure safety valve;
- Protection against overtemperature for compressors;
- Protection against overtemperature for fans;
Testing
All the units are factory-tested and supplied complete with oil and refrigerant.
CONFIGURED UNIT ACCESSORIES DESCRIPTION
/HWT: unit for high temperatures of produced water
Units with /HWT option use compressors with oversize electric motor for production of water at high temperature.
This option is available for /HP units or for cold only units with /DC option.
(S2) Sound pressure values measured at 1 meter from the unit in free field conditions and directional factor Q=2
Technical calculations may change according to calculation methods. Techical data may be revised.
SOUND LEVEL
Sound
63 [Hz] 125 [Hz] 250 [Hz] 500 [Hz] 1000 [Hz] 2000 [Hz] 4000 [Hz] 8000 [Hz]
Level
Lw [dB] 100 87 84 77 84 80 75 65 Lw_tot dB(A) 87
Lp [dB] 82 69 66 59 66 62 57 47 Lp_tot dB(A) 69