Professional Documents
Culture Documents
Example Settings For Applying The SEL-487B To A Six-Breaker Bus
Example Settings For Applying The SEL-487B To A Six-Breaker Bus
INTRODUCTION
Each SEL-487B Bus Differential and Breaker Failure Relay provides differential protection for as
many as six single-phase zones and includes circuit breaker failure protection for as many as six
three-phase circuit breakers. Advanced zone selection logic in the SEL-487B uses disconnect
auxiliary contacts to automatically reconfigure bus protection during disconnect switch operation.
However, many stations have only one busbar and do not require zone selection or, in many
cases, circuit breaker failure protection. This application guide discusses how to configure the
SEL-487B for a simplified bus differential application in a basic station.
This guide uses ACSELERATOR QuickSet® SEL-5030 Software to create a settings file.
® ®
ACSELERATOR QuickSet is a Microsoft Windows -based program that allows for creating,
exchanging, downloading, and uploading relay settings. ACSELERATOR QuickSet is available for
download on the SEL website at http://www.selinc.com/softwaresolutions/. The relay settings
discussed in this application guide are provided in an ACSELERATOR QuickSet file that is
available for download. This settings file can serve as a starting point for single busbar
applications.
Table 1 is from the SEL-487B worksheet and lists the protection functions that are used in this
application. We are using only the basic bus differential protection.
Table 2, also from the SEL-487B worksheet, lists the user-defined functions that are programmed
in the SELOGIC® control equations. For this application, we use a front-panel pushbutton to put
the SEL-487B in a test mode.
The SEL-487B worksheet also helps to determine the number of current inputs, bus zones, digital
inputs, and digital outputs required for more complex applications.
Source
S1
2000:5
52-1
Table 3 is a copy of Table 6 from the SEL-487B worksheet. This table is used to identify the
current inputs to the SEL-487B and any alias names that might be used for the currents. The alias
is arbitrary and intended to provide easy identification for metering and event reports. The order
and grouping of the current inputs are flexible. In this example, the three-phase currents from
each source are grouped. The inputs also could have been grouped by phase.
This application is a simple bus without zone selection. However, this application does require
three separate bus zones: one for each phase. Table 4 is a partial copy of Table 7 from the
SEL-487B worksheet.
SETTINGS
Although other settings categories exist in the relay (such as port and automation settings), we
consider only the settings categories necessary for this application:
• Alias settings
• Global settings
• Zone configuration group settings
• Protection group settings
• Control output settings
Alias Settings
Alias settings are useful in event reports or customized logic programming. The default settings
in the SEL-487B include a number of alias settings. The exact number depends on the options
ordered in the relay. When changing the alias settings, make sure that you do not delete an alias
you wish to use. Figure 2 and Figure 3 show a partial list of the default alias settings. Figure 4
shows the modified alias settings used in this example.
Global Settings
In the global settings category, we change three settings: RID (relay ID), SID (station ID), and
NUMBK (number of breakers). Enter the relay name (RID := Sample Bus) and the station name
(SID := Demo).
The number that you enter for the NUMBK setting influences two other settings: the number of
breaker status input equations (global settings) and the number of trip equations (group settings).
For example, with the default NUMBK setting of five, there are five breaker input equations and
five trip equations available. Because this application only requires a single output from the
SEL-487B to operate a lockout relay, set NUMBK to 1, as shown in Figure 5. Do not change the
default settings for disconnect auxiliary inputs (NUMDS) or breaker auxiliary inputs (52A01),
because we do not require either of these for this application.
For the terminal-to-bus zone connections settings, assign each phase input to a bus zone. Each of
the current inputs (I01–I18) can be assigned to any of six bus zones (BZ1–BZ6). Table 3 shows
the bus zone assignment for this application. The assignment is under the terminal bus zone
connections. The associated settings for Terminal 1 are shown in Figure 7. The SELOGIC control
equations for the terminal-to-bus connection are not used in this application. The settings also
allow the polarity of the CT to be reversed in the relay. For this application, all CT polarities are
set to P.
In this application, I01, I04, I07, I10, I13, and I16 (A-phase currents) are connected to Bus
Zone 1; I02, I05, I08, I11, I14, and I17 (B-phase currents) are connected to Bus Zone 2; and I03,
I06, I09, I12, I15, and I18 (C-phase currents) are connected to Bus Zone 3. In this application, the
terminals will always be connected to the zone, so the terminal-to-bus connection SELOGIC
control equations are all set to 1.
The SEL-487B also has bus-to-bus zone connections. For this application, there are no
connections between the bus zones. They are all set to N, as shown in Figure 8. In this simple
application, we are not using zone supervision, zone switching supervision, or check zone
supervision. The zone open CT detector is used, and the settings are left at the default values, as
shown in Figure 9.
Under the group settings, ACSELERATOR QuickSet shows the current normalization factors, as
shown in Figure 10. These are not settings to be entered. The relay calculates these values based
on the entered CT ratios. The normalization factors are similar to the tap settings used in
transformer differential relays. Normalization factors are shown only for those current inputs used
in the differential protection.
The coupler security logic, terminal out-of-service, breaker failure logic, definite-time
overcurrent elements, inverse-time overcurrent elements, and voltage elements are not used in
this application.
Figure 12 shows the tripping logic for TRIP01 in the SEL-487B. Asserting TR01 asserts TRIP01
directly via input OR Gate 1 and starts the minimum trip duration timer (TDURD). TRIP01
asserts for a minimum of TDURD cycles, even if TR01 is asserted for as little as one processing
interval or if the unlatch portion of the logic is asserted before TDURD expires. The default
TDURD setting is 12 cycles. The SEL-487B includes 18 separate trip SELOGIC control equations
for those applications that require a separate trip output for each of the associated breakers. The
number of individual trip equations available is determined by NUMBK in the breaker inputs
settings in the global settings. For this application, all tripping is via an 86 lockout relay, so only
one trip equation is required.
TRIP01 also seals itself in via AND Gate 1. This AND gate receives the negated inputs from the
unlatching functions. As long as ULTR01, RSTTRGT, or TRGTR are not asserted, TRIP01
remains sealed in. TRIP01 is used to drive an output contact to initiate tripping of the breaker.
You can use one of four methods to unlatch the trip logic:
• Assert either SELOGIC control equation setting ULTR01 or setting RSTTRGT.
• Push the {TARGET RESET} pushbutton on the front panel.
• Send the TAR R serial port command to assert Relay Word bit TRGTR. Relay Word bit
TRGTR also resets the LED (light-emitting diode) targets on the front panel.
• Assert ULTR01, RSTTRGT, or TRGTR, which places a zero input on AND Gate 1, and
thereby breaks the TRIP01 seal-in loop.
Note that TRIP01 is always asserted when TR01 is asserted, regardless of the action of ULTR01
or the target reset commands. TRIP01 will assert for a minimum of TDURD cycles no matter
how short the length of time TR01 has been asserted.
Figure 13 shows the trip logic for the Zone 1 (A-phase) differential element. Trip logic for Zone 2
(B-phase) and Zone 3 (C-phase) differential elements is similar.
Relay Word bit 87R1 (the output of the Zone 1 differential element) is the top input to the AND
gate shown in Figure 13, and Relay Word bit Z1S (supervision conditions) is the bottom input to
the AND gate. This application does not use zone supervision (Z1S = 1). Relay Word bit 87Z1 is
the input to the dynamic zone selection logic, which determines the terminals that should trip
based on the particular zone configuration. Our application is a single busbar that does not change
dynamically.
Because our application does not use zone supervision logic and dynamic zone selection, enter
Relay Word bits 87R1, 87R2, and 87R3 directly in the trip equation (TR01), instead of Relay
Word bits 87Z1, 87Z2, and 87Z3.
The protection logic settings are shown in Figure 16. Note that PLT03 was added to the alias
settings as RTM.
Output Settings
With the lockout relay tripping the circuit breakers, we only need to operate the lockout relay for
all busbar faults. To trip the lockout relay, assign the output from the trip logic (TRIP01) to
output OUT101, OUT102, and OUT103. OUT101 and OUT102 are the logical AND of TRIP01
and NOT RTM. RTM is the relay test mode entered via PB4 on the front panel of the relay.
OUT103 is not supervised via RTM and can be used to test the relay operation without tripping
the 86 lockout relay. OUT107 is set to RTM to provide an external indication that the SEL-487B
is in the test mode. The RTM is part of the default logic in the SEL-487B but does not need to be
used in the application. Set output OUT107 to close when a CT open-circuit or short-circuit
condition is detected via the sensitive differential elements. Leave output OUT108 with default
settings, as shown in Figure 17.
The SEL-487B is now configured to protect a station with a single bus with six breakers.
Report Settings
The report settings do not affect the differential protection, but they do provide valuable
information for evaluating operations of the relay. The SEL-487B includes both SER (Sequential
Events Recorder) and event (oscillography) files. Figure 18 shows a view of the SER points and
alias settings screen. By clicking on the small box to the right of the setting, additional dialog
boxes may be opened to make the selection of the SER points easier. A complete list of the SER
points chosen for this application is in the appendix. Note that the default SER settings do not
include any points.
In the SEL-487B, the user can select which Relay Word bits are included in the event file. This is
different from earlier SEL relays in which the event report data are fixed. Figure 19 shows the
event reporting digitals settings screen. A complete list of the event reporting digitals chosen for
this application is in the appendix.
CONCLUSION
This application guide has provided an introduction to setting the SEL-487B for a simple bus
differential application. The settings developed in this guide may be used as a starting point to
create settings for a specific bus differential application.
APPENDIX
Table 5 Alias Settings
Terminal Analog Channel Alias
1 I01 S1_A
2 I02 S1_B
3 I03 S1_C
4 I04 FDR1_A
5 I05 FDR1_B
6 I06 FDR1_C
7 I07 FDR2_A
8 I08 FDR2_B
9 I09 FDR2_C
10 I10 FDR3_A
11 I11 FDR3_B
12 I12 FDR3_C
13 I13 FDR4_A
14 I14 FDR4_B
15 I15 FDR4_C
16 I16 FDR5_A
17 I17 FDR5_B
18 I18 FDR5_C
19 BZ1 PHASE_A
20 BZ2 PHASE_B
21 BZ3 PHASE_C
22 PLT01 DIFF_EN
23 PLT03 RTM
24 87R1 PH_A_TR
25 87R2 PH_B_TR
26 87R3 PH_C_TR
27 OUT101 BUSDIF1
SER Settings
SER points (Relay Word bit, reporting name, set state name, clear state name, HMI [human-
machine interface] alarm)
1: 87S1,“87S1”,“Asserted”,“Deasserted”,N
2: 87S2,“87S2”,“Asserted”,“Deasserted”,N
3: 87S3,“87S3”,“Asserted”,“Deasserted”,N
4: 87ST1,“87ST1”,“Asserted”,“Deasserted”,Y
5: 87ST2,“87ST2”,“Asserted”,“Deasserted”,Y
6: 87ST3,“87ST3”,“Asserted”,“Deasserted”,Y
7: PH_A_TR,“87R1”,“Asserted”,“Deasserted”,N
8: PH_B_TR,“87R2”,“Asserted”,“Deasserted”,N
9: PH_C_TR,“87R3”,“Asserted”,“Deasserted”,N
10: RTM,“PLT03”,“Asserted”,“Deasserted”,Y
11: SALARM,“SALARM”,“Asserted”,“Deasserted”,N
12: HALARM,“HALARM”,“Asserted”,“Deasserted”,N
13: BADPASS,“BADPASS”,“Asserted”,“Deasserted”,N
14: BUSDIF1,“OUT101”,“Asserted”,“Deasserted”,N
15: BUSDIF2,“OUT102”,“Asserted”,“Deasserted”,N
16: TST_TRP,“OUT103”,“Asserted”,“Deasserted”,N
17: OUT106,“OUT106”,“Asserted”,“Deasserted”,N
18: OUT107,“OUT107”,“Asserted”,“Deasserted”,N
19: ALARM,“OUT108”,“Asserted”,“Deasserted”,N
FACTORY ASSISTANCE
We appreciate your interest in SEL products and services. If you have questions or comments,
please contact us at:
Schweitzer Engineering Laboratories, Inc.
2350 NE Hopkins Court
Pullman, WA 99163-5603 USA
Telephone: +1.509.332.1890
Fax: +1.509.332.7990
www.selinc.com • info@selinc.com