Material List: 2.1. Table of Abbreviations

You might also like

Download as rtf, pdf, or txt
Download as rtf, pdf, or txt
You are on page 1of 7

Produced on 07/09/2020 with Xpress Selection V8.9.1 - database DIL 15.2.

Project name 1
Project address 1
Viet Nam
Reference 1
Client name 1
Client address 1
Revision 1

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Qty Description
RXQ16TAYM 1 Cooling only VRV IV STANDARD
FXDQ40NBVE 1 VRV D - Slim Ceiling Mounted Duct
FXDQ50NBVE 1 VRV D - Slim Ceiling Mounted Duct
FXDQ63NBVE 1 VRV D - Slim Ceiling Mounted Duct
FXMQ100PAVE 1 VRV M-PA - Ceiling Mounted Duct
FXMQ63PAVE 1 VRV M-PA - Ceiling Mounted Duct
FXMQ80PAVE 1 VRV M-PA - Ceiling Mounted Duct
KHRP26A22T 1 Refnet branch piping kit
KHRP26A33T 1 Refnet branch piping kit
KHRP26A72T 3 Refnet branch piping kit
BRC1E63 6 Wired Remote Controller (Navigation Remote
Controller)

2. Indoor Unit Details


2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / RH)
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tdis C Indoor unit discharge air temperature in cooling
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Max HC Available heating capacity
Tdis H Indoor unit discharge air temperature in heating
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 1
WxHxD WidthxHeightxDepth
Wght Weight of the device

2.2. Out 1 - RXQ16TAYM


Capacity data at conditions and connection ratio (99%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C kW kW kW kW °C °C °C kW kW °C l/s
Ind 1 FXDQ50NBVE 24.0 / 55% n/a 5.5 n/a 3.7 Auto 9.4 n/a n/a n/a n/a 208
Ind 2 FXDQ40NBVE 24.0 / 55% n/a 4.4 n/a 3.0 Auto 9.9 n/a n/a n/a n/a 175
Ind 3 FXDQ63NBVE 24.0 / 55% n/a 7.0 n/a 4.7 Auto 10.0 n/a n/a n/a n/a 275
Ind 4 FXMQ63PAVE 24.0 / 55% n/a 7.0 n/a 5.1 Auto 11.2 n/a n/a n/a n/a 325
Ind 5 FXMQ80PAVE 24.0 / 55% n/a 8.8 n/a 6.5 Auto 11.3 n/a n/a n/a n/a 417
Ind 6 FXMQ100PAVE 24.0 / 55% n/a 10.9 n/a 8.0 Auto 11.8 n/a n/a n/a n/a 533

Required cooling capacity towards the outdoor unit: 43.5kW.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
Ind 1 31-35 220V 1ph 1 900×200×620 28
Ind 2 30-34 220V 1ph 1 900×200×620 27
Ind 3 32-36 220V 1ph 1.1 1100×200×620 31
Ind 4 38-42 220V 1ph 1.8 1000×300×700 35
Ind 5 39-43 220V 1ph 2.3 1000×300×700 35
Ind 6 39-43 220V 1ph 2.9 1400×300×700 45

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 2
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / RH)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 3
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC
% °C kW kW °C kW kW
Out 1 RXQ16TAYM 99 35.0 44.0 43.5

Name Model Piping Refrigerant


m Type Bse Refr Ex Refr
kg kg
Out 1 RXQ16TAYM 7.5 R410A 10.4 n/a

Name Model PS MCA WxHxD Wght


A mm kg
Out 1 RXQ16TAYM 380V 3ph 31 1240×1657×765 285

3.2.1. Out 1 - RXQ16TAYM

Piping Limitations
Maximum total length 1000.0m
Maximum longest actual length 165.0m
Maximum longest equivalent length 190.0m
Maximum equivalent length (size up of main pipe required if longer) 89.9m
Maximum length first branch to indoor unit (size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor units 90.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference between indoor units 30.0m
Connection ratio range 50-130%

Pipe Capacities
Maximum Connection Index Diameters
149.9 9.5×15.9
199.9 9.5×19.1
289.9 9.5×22.2
419.9 12.7×28.6
> 419.9 15.9×28.6
Main pipe size up 15.9×31.8

4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 4
4.1. Piping Out 1
Out 1
RXQ16TAYM

12.7×28.6 12.7×28.6 12.7×28.6 9.5×22.2 9.5×19.1


KHRP26A72T KHRP26A72T KHRP26A72T KHRP26A33T KHRP26A22T

6.4×12.7 6.4×12.7 9.5×15.9 9.5×15.9 9.5×15.9 9.5×15.9

Ind 1 Ind 2 Ind 3 Ind 4 Ind 5 Ind 6


FXDQ50NBVE FXDQ40NBVE FXDQ63NBVE FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 5
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

5.1. Wiring Out 1


P1,P2
Out 1 Ind 1 BRC1E63
RXQ16TAYM FXDQ50NBVE
IN F1,F2 F1,F2
L1,L2,L3,N 31A 3ph L,N 1A 1ph
P1,P2
Ind 2 BRC1E63
FXDQ40NBVE
F1,F2
L,N 1A 1ph
P1,P2
Ind 3 BRC1E63
FXDQ63NBVE
F1,F2
L,N 1.1A 1ph
P1,P2
Ind 4 BRC1E63
FXMQ63PAVE
F1,F2
L,N 1.8A 1ph
P1,P2
Ind 5 BRC1E63
FXMQ80PAVE
F1,F2
L,N 2.3A 1ph
P1,P2
Ind 6 BRC1E63
FXMQ100PAVE
F1,F2
L,N 2.9A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 6
6. Device Options

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 7