Professional Documents
Culture Documents
Concentric Eccentric Reducers PDF
Concentric Eccentric Reducers PDF
Journal of the South African Institution of Civil Engineering • Volume 56 Number 3 October 2014 65
Table 1 Summary of reducer design requirements
Reducer
Reference Reference type Conditions for selection Reason for reducer selection
selection
Vertical inlet pipes
Concentric Ensures no air accumulation
Installations where there is no potential for vapour accumulation
reducer
Minimum straight lengths of pipe are required Ensures disturbance-free flow
ANSI (2009) National standard
Horizontal installations where air accumulation is possible
Eccentric Allows for transportation of air
Flat section on top
reducer
Minimum straight lengths of pipe are required Ensures disturbance-free flow
Flat section on top for suction pipe entering in a horizontal plane
Eccentric Allows for transportation of air
Bloch (2010) Journal article Flat section on top for suction pipe entering from below
reducer
Flat section at the bottom for suction pipe entering from above Ensures no air accumulation
Eliminates the potential problem in
Mackay Eccentric eddy currents in a high point in the
Pump station handbook Flat section on top
(2004) reducer suction line that might travel into the
impeller eye
Bloch & Eccentric Flat section on top Allows for transportation of air
Pump station handbook
Burdis (2010) reducer Minimum straight pipe and reducer length required Ensures disturbance-free flow
Pump manufacturer
KSB (2012)
operating instructions
Jones et al Eccentric
Pump station handbook Flat section on top Allows for transportation of air
(2008) reducer
SAPMA
Pump station handbook
(2002)
66 Journal of the South African Institution of Civil Engineering • Volume 56 Number 3 October 2014
Table 2 A summary of recommended maximum velocities for pump inlet piping
Recommended maximum
Reference Reference type Conditions for recommendation
velocity (m/s)
Suction pipe at least as large as the pump suction connection
Valves and other flow-disturbing fittings are to be at least one pipe size larger than the
pump suction nozzle
Excludes slurries
ANSI/HI 9.6.6
National standard 2.4 Values greater than 2.4 m/s are to be evaluated with respect to flow distribution,
(2009)
erosion, NPSH, noise, water hammer and the manufacturer’s recommendations
Maximum velocity applies to any point in the suction piping
For fluids close to the vapour, pressure velocities are to be kept low enough to avoid
flashing of the liquid in the piping
Velocities may be increased at the pump suction flange by the use of a gradual reducer
Higher velocities are acceptable, provided the piping design delivers a smooth inlet flow
to pump suction (velocity distributions are specified)
The velocity in the pump suction piping should be constant or increasing as the flow
approaches the pump
ANSI (1998) National standard 2.4 The velocity is to be large enough to prevent sedimentation in horizontal piping
There shall be no flow-disturbing fittings closer than five suction pipe diameters from
the pump (fully open, non-flow disturbing valves, vaned elbows, long-radius elbows and
reducers are not considered as flow-disturbing fittings)
The suction diameter is to be at least one size larger than the suction fitting on the
pump, in such cases an eccentric or concentric reducer fitting is fitted
Pump station
Mackay (2004) The suction diameter is to be at least one size larger than the suction fitting on the pump
handbook
The suction pipe should never be smaller than the suction connection of the pump and
in most cases should be at least one size larger
Pump station Pipe velocities should be in the range of 0.5 m/s to 0.75 m/s unless suction conditions
SAPMA (2002) 0.75
handbook are exceptionally good
Elbows or tees located adjacent to the pump suction flange will result in uneven flow
patterns which prevent the liquid from filling the impeller evenly
Bloch & Burdis Pump station Maximum velocity applies to any point in the suction piping
2.5
(2010) handbook Suction pipe at least as large as the pump suction nozzle
A reason for this preference is, however, not and fittings depending on the pipeline at the pump inlet. A summary of recom-
provided by ANSI/HI. slope, flow rate and fitting geometry. A mended maximum velocities for pump inlet
The philosophy of prescribing the use concentric reducer with the correct flow piping as identified in a literature review is
of an eccentric reducer with the flat side on rate and geometry will allow air to be provided in Table 2. It can be observed that
top will aid in the transport of air through hydraulically transported through it. acceptable velocities for pump suction pipe-
the reducer. However, the following three ■■ The non-uniform velocity distribution work are typically in the range of 0.75 m/s to
aspects are not addressed: on the impeller created by the flow 2.5 m/s, and the suction pipework is to be at
■■ The origin of air at this position in the through the eccentric reducer. The least one size larger than the pump inlet noz-
pumping system. If a pump station sump, geometry of an eccentric reducer is asym- zle, thereby defining the use of a reducer.
fore bay, intake bay, suction pipework and metrical, and flow through a fitting of this The requirements for maximum velocity
reservoir outlets are correctly designed it nature will produce asymmetrical flow distributions are to limit the radial thrust
is impossible for air to accumulate. Pumps conditions, such as non-uniform velocity on the pump’s shaft and couplings. The
typically operate under positive suction and pressure distributions. These flow phenomenon of radial thrust is illustrated in
pressure heads (when started) and there- conditions are contradictory to the recom- Figure 3, where the pressure/velocity differ-
fore air should not be able to enter the sys- mended pump inlet designs, which recom- ential between positions P1 and P2 causes an
tem on the suction side. Under first-time mend symmetrical flow conditions with a additional imbalance of forces on the pump’s
start-up conditions after construction or uniform velocity and pressure distribution. impeller. The bearings, shafts and casings of
after maintenance where air may be pre- a pump are designed to resist the anticipated
sent in the system, the air may be released radial load, but pumps have been destroyed
with a manual bleed-off valve. PUMP INLET PIPING REQUIREMENTS within days, or even a few hours, through
■■ The hydraulic capacity of the system Pump inlet piping requirements are typically excessive wear in bearings, seals, shaft sleeves
to transport air. Trapped air in pipelines prescribed according to a maximum allow- and wearing rings caused by excessive shaft
can be hydraulically transported along able velocity in the suction pipework and deflections resulting from radial thrust
the length of a pipeline through valves valves, and an allowable velocity distribution (Jones et al 2008). The ideal is therefore that
Journal of the South African Institution of Civil Engineering • Volume 56 Number 3 October 2014 67
the approach flow to a pump should be an
undisturbed flow – free from unequal velocity Discharge
distributions, unequal pressure distributions, Impeller
Thrust bearing
entrained air or gas bubbles, vortices and Impeller
P1 P1
excessive pre-swirl at the pump inlet – to
Inlet velocity
minimise the unbalanced forces directed onto distribution
the impeller in the axial direction (ANSI 1998; P2
P2 Radial bearing
Sulzer 2010; Jones et al 2008).
Radial thrust
Volute
D2
manners (Van Vuuren et al 2004):
D1
D1
D2
68 Journal of the South African Institution of Civil Engineering • Volume 56 Number 3 October 2014
Table 3 Geometries of the reducers modelled Prism layer
ER 20 20.0 148
Journal of the South African Institution of Civil Engineering • Volume 56 Number 3 October 2014 69
piping. The constant density model was Fluid wall
selected to model the equation of state. Velocity inlet Pressure outlet
■■ Reynolds-Averaged turbulence. A model (inflow (outflow
boundary) boundary)
needs to be selected to provide closure to Fluid wall
the RANS equations. The K-Epsilon model
was selected for this study, as it provided Figure 6 CFD boundary conditions
a lower computational cost and was well
suited to the flow properties of the study.
■■ K-Epsilon model. STAR-CCM+ provides a Probe position 4 D2
choice of seven different K-Epsilon models. Y
X
The selection of the K-Epsilon turbulence Probe position 3
Y
model is determined by the wall treatment Probe position 2 X
(near-wall modelling assumptions), the Y
Probe position 1 X
Reynolds number and the coarseness or D2
1x
the fineness of the mesh. The standard Y
X
D2
two-layer K-Epsilon model and the realis- 1x
able two-layer K-Epsilon model offer the D2
1× X-Y plane velocity
most mesh flexibility. They can be utilised scalar (m/s)
on a wide range of y+ values (all – y+). The
two-layer all y+ wall treatment and reali
zable K-Epsilon two-layer were automati-
ion
cally selected on selection of the K-Epsilon D1 ir ec t
wd
turbulence model. This selection cor- F lo
responds to the guidelines described above Y-Z plane velocity
and was not changed in the study. scalar (m/s)
Boundary conditions
Appropriate boundary conditions that repre- Figure 7 Location of the four probe positions and orientation of the x-axis and y-axis
sent the real physical fluid flow conditions are
required to be selected in the CFD software.
Y-axis
The boundary types selected to represent the
fluid flow problem are velocity input, pressure
outlet and fluid wall. The locations of these OD = 165.1 mm
boundary conditions are illustrated in Figure D
6. Descriptions and input parameters for the C
ID = 156.1 mm
selected boundary types are provided below:
■■ Velocity inlet. This boundary type was
selected for the inflow boundary (upstream
end) of the model and represents normal X-axis E G H F
flow conditions entering the pipe perpen-
dicularly, with a constant velocity that is
supplied as an input parameter.
HRW 1: 0.8 × ID = 124.88 mm
■■ Pressure outlet. This boundary type was B
selected for the outflow boundary (down-
A
stream end) and represents a uniform
HRW 2: 0.6 × ID = 93.66 mm
constant pressure at the outlet that is
supplied as an input parameter. The pres-
sure was set to 150 000 Pa (150 kPa) to
provide a positive pressure for the model.
■■ Wall. A wall boundary represents an Figure 8 Assessment criteria positions
impermeable surface and is applicable as
an impermeable boundary for inviscid used for fittings in water pump stations in the propagation of the velocity differential
flows and as an impermeable, non-slip South Africa). through the reducer. In addition to the
boundary for viscous flow simulations scalar scenes, X-Y plots of the velocity were
(CD-adapco 2012). A roughness value CFD visualisation and reporting generated along both the x-axis and y-axis
(0.06 mm) was added to the fluid wall to In order to visualise the magnitude of the of the pipe at four different positions (probe
enable near-wall turbulence and thereby velocity distribution through the pump inlet positions). The four probe positions are
apply friction to the model in order to pipework, two scalar scenes were created. defined with Probe Position 1 starting at the
accurately model the pipework. The The first scene was created on the X-Y plane downstream end of the reducer and repeated
roughness value utilised was obtained at the downstream end of the reducer – this at intervals of 1 x D2 (downstream diameter),
from Wallingford and Barr (2006) for scene allows for the visualisation of the ending at Probe Position 4. XY velocity plots
an epoxy-lined steel pipe in a normal simulation velocity results. The second scene along two circles with diameters of 0.8 x ID2
condition (typically the type of lining was created on the Y-Z plane to visualise and 0.6 x ID2 at Probe Position 1 were also
70 Journal of the South African Institution of Civil Engineering • Volume 56 Number 3 October 2014
created. The orientation of the scalar scenes,
CR 2 Probe positions
the locations of the four probe positions
1 2 3 4
and the orientation of the x-axis, y-axis and
z-axis are illustrated in Figure 7.
Limitations
In the analyses, uniform flow conditions
were provided at the inlet of the geometry;
Velocity: Magnitude (m/s) in engineering applications this may seldom
Y 0 0.57088 1.1418 1.7126 2.2835 2.8544 be the case. These non-uniform flow condi-
Z X tions may influence the velocity distribution
in such a way that a concentric or eccentric
CR 20 reducer within the recommended range may
Probe positions
produce a velocity distribution that is outside
1 2 3 4
of the acceptance criteria, which needs to be
quantified when designing the inlet pipework
to a pump.
ASSESSEMNT CRITERIA
Velocity: Magnitude (m/s) Further to the velocity and approach flow
Y 0 0.61991 1.2398 1.8597 2.4797 3.0996 requirements provided in Table 2, assess-
Z X ment criteria were defined in order to
compare the performance of the various
reducer geometries. ANSI (1998) and Jones et
ER 2.5 Probe positions
al (2008) specified the requirement for time-
1 2 3 4
averaged velocities at the pump suction to be
within 10% of the cross-sectional area aver-
age velocity. Wallingford (2001) in Sinotech
CC (2005), and Van Vuuren (2011) provided
the following guidelines for velocity distribu-
tion variations in suction pipework:
Velocity: Magnitude (m/s) ■■ Velocity variation along line ABCD is
Y 0 0.57222 1.1444 1.7167 2.2889 2.8611 less than 10% of the average velocity (see
Z X Figure 8).
■■ Maximum velocity variation along a
circle AEDF is ± 5% of the average veloc-
ER 30 Probe positions
ity (see Figure 8).
1 2 3 4
The requirement described by Wallingford
(2001) in Sinotech CC (2005), and Van
Vuuren (2011) did not indicate the location
of the circle AEDF. Two circles were
therefore defined (0.6 × D2 and 0.8 × D2) to
assess the sensitivity of the location of the
Velocity: Magnitude (m/s) circle. The assessment criteria were labelled
Y 0 0.73908 1.4782 2.2172 2.9563 3.6954 and the final assessment criteria used are
Z X summarised in Table 5.
Criterion 3 Cross-sectional area average Velocity variation along line EGHF (x-axis) is less than Scalar scene results
x-axis velocity 10% of the defined average velocity
The scalar scenes generated through the study
Criterion 3 Cross-sectional area average Velocity variation along line ABCD (y-axis) is less than allow for the development of the velocity dis-
y-axis velocity 10% of the defined average velocity
tribution through the reducer to be visualised.
Journal of the South African Institution of Civil Engineering • Volume 56 Number 3 October 2014 71
Four scalar scenes for an input velocity of
CR 2
1.5 m/s are provided as examples in Figure
9 and Figure 10 to illustrate the difference
in velocity distributions resulting from the
different reducer types and geometries. The
main observations resulting from the scalar
scenes are:
■■ The downstream flow distribution evens
out rapidly and presents a typical uniform
distribution by the time it reaches a dis-
tance of 1 x D2 from the reducer (Probe
Position 2).
Velocity: Magnitude (m/s)
■■ The velocity distribution for the
Y 0 0.55887 1.1177 1.6766 2.2355 2.7943
concentric reducers produce velocity
Z X
distributions that are symmetrical around
the centre of the pipe, i.e. the velocity
contours are circular in shape. CR 20
■■ The eccentric reducers produce areas
of high velocities towards the bottom
(sloped) side of the reducer, which result
in non-uniform velocity distribution
at the downstream end of the reducer
(Probe Position 1).
■■ The magnitude of variance in the velocity
distributions increases with an increase
in reducer angle.
■■ In the case of the reducers with larger
angles, the resulting velocities may be of Velocity: Magnitude (m/s)
such a nature that they will fall outside of Y 0 0.62269 1.2454 1.8681 2.4908 3.1135
Results –
ER 2.5
Criterion 1 and Criterion 3 y-axes
Criterion 1 requires the velocity variation
along line ABCD to be less than 10% of the
average velocity along line ABCD. Criterion
3 y-axis requires the velocity variation along
line ABCD (y-axis) to be less than 10% of
the cross-sectional average velocity. The
average velocities at the downstream end of
the reducer (at ID2) were calculated and the
average velocities along line ABCD (y-axis)
at Probe Position 1 were calculated for all Velocity: Magnitude (m/s)
the simulations. The average velocities along Y 0 0.56724 1.1345 1.7017 2.2690 2.8362
line ABCD are within 0.9% (0.4 m/s) of the
Z X
average velocity. Therefore the Criterion 1
and Criterion 3 y-axes were assumed to be
equal for the assessment, and the assess- ER 30
ment was conducted on the cross-sectional
area average velocity. The results for Probe
Positions 2, 3 and 4 are not provided due to
the uniformity in the velocity distribution at
these positions, as illustrated in Figure 9.
The results for all four velocities pre-
sented similar outcomes. The upper end of
the eccentric reducers (ER 15, ER 20 and ER
30) and the CR 20 model concentric extend
past the upper limit of the acceptance enve-
lope and therefore do not pass acceptance Velocity: Magnitude (m/s)
Criterion 1 and Criterion 3 y-axes. The Y 0 0.74494 1.4899 2.2348 2.9797 3.7247
72 Journal of the South African Institution of Civil Engineering • Volume 56 Number 3 October 2014
Velocity distributions for 1.5 m/s models – Y axis at probe position 1 270°
3.6
3.4
180° 0°/360°
3.2
Velocity (m/s)
2.6
to be less than 5% of the average velocity
Lower limit – VAverage = 0.1 × VAverage along circle BGCH. The results for Probe
Positions 2, 3 and 4 were not plotted due to
2.4
–0.08 –0.06 –0.04 –0.02 0 0.02 0.04 0.06 0.08 the uniformity in the velocity distribution
Position (m) – X axis at these positions, as was demonstrated
CR 2 – 1.5 m/s CR 2.5 – 1.5 m/s CR 5 – 1.5 m/s CR 10 – 1.5 m/s in Figure 9. The concentric reducers were
CR 15 – 1.5 m/s CR 20 – 1.5 m/s ER 2.5 – 1.5 m/s ER 5 – 1.5 m/s not assessed according to Criterion 2, as
ER 10 – 1.5 m/s ER 15 – 1.5 m/s ER 20 – 1.5 m/s ER 30 – 1.5 m/s their velocity distributions are symmetrical
around the centre of the pipe, i.e. the veloc-
Figure 11 Criterion 1 and Criterion 3 y-axis 1.5 m/s velocity distributions ity contours are circular in shape and will
produce results that will fall within the
acceptance envelope.
Criteria 2 assessment: ER 15 – 1.5 m/s
3.00 The velocities along the circumference
of the two circles are plotted on the y-axis
2.95 and an angle relating to the position of
the cylinder is plotted on the x-axis. This
2.90 angle is a component of the coordinate
system illustrated in Figure 12. The result
2.85 +5% range for the ER 15 Model at 1.5 m/s is provided
in Figure 13 as example of the results
Velocity (m/s)
2.80
Average velocity circle AEDF obtained for Criterion 2. Models ER 20 and
ER 30 fall outside both the HRW 1 and
+5% range
2.75 HRW 2 criteria, and the ER 15 model falls
outside the HRW 1 criteria. Therefore ER
–5% range Average velocity circle BGCH
2.70 15, ER 20 and ER 30 do not pass acceptance
Criterion 2. The remainder of the eccentric
2.65 reducers (ER 2.5, ER 5 and ER 10) are within
–5% range
the acceptance envelope for Criterion 2.
2.60
This highlights that the positions of the
Criterion 2 circles have an effect on the
2.55
outcomes of the results.
2.50
0 50 100 150 200 250 300 350 Results – Criterion 3 x-axis
Position (degrees) Criterion 3 x-axis requires the velocity varia-
ER 15 – 1.5m/s – HRW 1 Mean ER 15 – 1.5m/s – HRW 2 Mean tion along line EGHF (x-axis) to be less than
ER 15 – 1.5m/s – HRW 1 –5% ER 15 – 1.5m/s – HRW 1 +5% 10% of the cross-sectional average velocity.
ER 15 – 1.5m/s – HRW 2 –5% ER 15 – 1.5m/s – HRW 2 +5% The results for Probe Positions 2, 3 and 4 are
Poly. (ER 15 – 1.5 m/s – HRW 1) Poly. (ER 15 – 1.5m/s – HRW 2) not provided, due to the uniformity in the
velocity distribution at these positions, as
Figure 13 Criterion 2 ER 15 – 1.5 m/s velocity distribution illustrated in Figure 9.
The results for all four velocities
within Criterion 1 and Criterion 3 y-axes. Results – Criterion 2 presented similar results. The CR 20 model
The results for the velocity distributions Criterion 2 HRW1 requires the velocity falls outside of acceptance Criterion 3 x-axis
along the y-axis (line ABCD) for the 1.5 m/s variation along circle AEDF to be less than for all four flow velocities, and the ER 30
velocity are provided as an example of the 5% of the average velocity along circle model falls outside of acceptance Criterion
results obtained for Criterion 1 and Criterion AEDF, and Criterion 2 HRW2 requires 3 axis for the 1.5 m/s, 2 m/s and 2.4 m/s
3 y-axes in Figure 11. the velocity variation along circle BGCH velocities, and falls within the criteria for the
Journal of the South African Institution of Civil Engineering • Volume 56 Number 3 October 2014 73
1 m/s velocity. The remainder of the models Table 6 Calculated critical velocities (m/s)
(CR 2, CR 2.5, CR 5, CR 10, CR 15, ER 2.5,
Slope Diameter Critical velocity Critical velocity Critical velocity
ER 5, ER 10, ER 15 and ER 20) all fall within Model
(°) (m) (Eq 1) (Eq 2) (Eq 3)
the Criterion 3 x-axis acceptance envelopes.
CR 2 2.0 0.2191 0.293 1.278 0.422
The results of the velocity distributions along
the x-axis (line EGHF) used in Criterion 3 CR 2.5 2.5 0.2100 0.328 1.259 0.451
x-axis for the 1.5 m/s velocity are provided CR 5 5.0 0.2100 0.463 1.290 0.596
as an example of the results obtained for
CR 10 10.0 0.2100 0.654 1.334 0.787
Criterion 3 x-axis in Figure 14.
CR 15 15.0 0.2100 0.798 1.367 0.925
Comparison –
CR 20 20.0 0.2100 0.918 1.394 1.038
Hydraulic transportability of air
The critical velocity for each of the
concentric reducers was calculated with the
Velocity distributions for 1.5 m/s models – X axis at probe position 1
upstream (larger) diameter (D1) as the input 3.1
diameter in the calculation, as the velocity
increases through the reducer, thereby Upper limit = VAverage + 0.1 × VAverage
3.0
increasing the capacity to hydraulically
transport the air. The calculated critical
velocities are provided in Table 6. The 2.9
values calculated with Equation 1 and
Equation 3 are representative of one
Velocity (m/s)
2.8
another. However, the values calculated
with Equation 2 are not representative
(this could be due to the addition of a 2.7
constant of 0.825 x (gD)0.5 that affects the
equation at low velocities). Only the values
2.6
obtained with Equation 1 and Equation 3
were utilised to assess the hydraulic
transportation of air through the models. 2.5
The only model where air could not be Lower limit = VAverage – 0.1 × VAverage
hydraulically transported through it is the
2.4
CR 20 model at 1 m/s. This model, however, –0.08 –0.06 –0.04 –0.02 0 0.02 0.04 0.06 0.08
also fails Criterion 1 and Criterion 3. It is Position (m) – X axis
noted that the critical velocity is a function CR 2 – 1.5 m/s CR 2.5 – 1.5 m/s CR 5 – 1.5 m/s CR 10 – 1.5 m/s
of the pipe diameter (Equations 1, 2 and CR 15 – 1.5 m/s CR 20 – 1.5 m/s ER 2.5 – 1.5 m/s ER 5 – 1.5 m/s
3), and other results will differ from the ER 10 – 1.5 m/s ER 15 – 1.5 m/s ER 20 – 1.5 m/s ER 30 – 1.5 m/s
results presented for the DN 200 upstream
diameter utilised in this study. The Figure 14 Criterion 3 x-axis 1.5 m/s velocity distribution
hydraulic transportability of air will need to
be assessed during the design of the pump
Standard concentric reducer sizes
station pipework. 25
Results matrix
The final assessment of the 48 models 20
simulated with CFD according to the four Reducer slopes exceeding the allowable limit
criteria, is provided in Table 7. Concentric
Reducer angle (°)
74 Journal of the South African Institution of Civil Engineering • Volume 56 Number 3 October 2014
Table 7 Final results matrix
Acceptance CR 2 CR 2.5 CR 5 CR 10 CR 15 CR 20 ER 2.5 ER 5 ER 10 ER 15 ER 20 ER 30
Criterion 1 ✓ ✓ ✓ ✓ ✓ ✗ ✓ ✓ ✓ ✗ ✗ ✗
Criterion 2 HRW 1 N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ ✗ ✗ ✗
1 m/s velocity
CONCLUSIONS
25
Figures 15 and 16 present charts illustrating
Reducer angle (°)
Journal of the South African Institution of Civil Engineering • Volume 56 Number 3 October 2014 75
RECOMMENDATIONS where the hydraulic transport of air Mackay, R 2004. Practical pump handbook. Oxford:
through the concentric reducer is Elsevier Advanced Technology.
Review of pump inlet criteria explored, to assess which one of the Pothof, I W M & Clemens, F H L R 2011. Experimental
Based on the results obtained from this hydraulic transport of air equations best study of air-water flow in downward sloping
research it is recommended that concentric suits this problem. pipes. International Journal of Multiphase Flow,
reducers be considered to improve the inlet 37: 278–292.
conditions at pumps and that the following SAPMA (South African Pump Manufacturers
criteria should be considered during the REFERENCES Association) 2002. Pumps: Principles & practice,
assessment of pump suction pipe work: AWWA (American Water Works Association) 2008. 4th ed. Johannesburg: K Myles and Associates.
■■ Criterion 1: Velocity variation along line C208-07: Dimensions for fabricated steel water pipe Sinotech CC 2005. CFD modelling of the pipe work on
ABCD is less than ±10% of the average fittings. Denver: AWWA. the inlet side of the abstraction works. Unpublished
velocity along line ABCD. ANSI (American National Standards Institute) 1998. Technical Report. Available from Sinotech CC:
■■ Criterion 2: Velocity variation along line ANSI/HI 9.8-1998: American National Standard http://www.sinotechcc.co.za
EGHF is less than ±10% of the average for pump intake design. Parsippany, NJ: Hydraulic Sturm, T W 2010. Water, water everywhere. Journal of
velocity along line EGHF. Institute. Hydraulic Engineering, 136(1): 1–2.
■■ Criterion 3: Maximum velocity variation ANSI (American National Standards Institute) 2009. Sulzer Pumps Ltd 2010. Centrifugal pump handbook,
along a circle AEDF is ±5% of the average ANSI/HI 9.6.6-2009: American National Standard 3rd ed. Oxford: Butterworth-Heinemann.
velocity along circle AEDF; the diameter for rotodynamic pumps for pump piping. Parsippany, Van Vuuren, S J 2011. Standards for sumps, pumps and
of circle AEDF is 0.8 x ID. NJ: Hydraulic Institute. pipe work. Report SHW 795 – Pump station design.
■■ Criterion 4: Maximum velocity variation Bloch, H P 2010. Eccentric reducers and straight Pretoria: University of Pretoria, Department of
along a circle BGCH is ±5% of the average runs of pipe at pump suction. Hydrocarbon Civil Engineering.
velocity along circle BHCG; the diameter Processing, September, 9. Available at: http://www. Tu, J, Yeoh, G H & Liu, C 2008. Computational
of circle BGCH is 0.6 x ID. hydrocarbonprocessing.com/article/2663961 fluid dynamics – A practical approach. Oxford:
■■ Criterion 5: Time-averaged velocity at any Bloch, H P & Burdis, A R 2010. Pump user’s handbook Butterworth-Heinemann.
point is to be within ±10% of the cross- life extension, 3rd ed. Lilburn, GA: The Fairmont Van der Westhuizen, W 2011. Case study: Inlet
sectional area average velocity. Press. conditions leading to problems – Knysna. Report
■■ Criterion 6: Air must be able to be CD-adapco. 2012. USER GUIDE STAR-CCM+ Version SHW 795 – Pump station design. Pretoria:
hydraulically transported through the 7.04.006. University of Pretoria, Department of Civil
reducer. Hirsch, C 2007. Numerical computation of Engineering.
internal and external flows. Fundamentals of Van Vuuren, S J, Van Dijk, M & Steenkamp, J N 2004.
Intended further research Computational Fluid Dynamics, 2nd ed. Oxford: Guidelines for effective de-aeration. WRC Report No
It is recommended that: Butterworth-Heinemann. 1177/2/04. Pretoria: Water Research Commission.
■■ Additional examples with various bends, Jones, G M, Sanks, R L, Tchobanoglous, G & Bosserman Wallingford, H R 2001. In: Sinotech CC 2005. CFD
elbows and sweep tees typically found II, B E (Eds) 2008. Pumping station design. Pumps: modelling of the pipe work on the inlet side of the
in pump inlet pipework that could pos- Intake design, selection, and installation, 3rd ed. abstraction works. Unpublished Technical Report.
sibly create swirl or non-uniform flow Burlington, MA: Butterworth-Heinemann. Available from Sinotech CC: http://www.sinotechcc.
conditions entering into the suction Kalinske, A A & Bliss, P H 1943. Removal of air from co.za
reducers, are to be modelled. With this pipelines by flowing water. ASCE Journal, 13: 480. Wallingford, H R & Barr, D I H 2006. Tables for the
information, guidelines on typical suction KSB 2012. Operating instructions ETA centrifugal hydraulic design of pipes, sewers and channels,
manifold and suction pipework can be pump (A,B,C,D pedestals). Available at: http:// 8th ed. Vol II. London: Thomas Telford.
developed. www.ksbpumps.co.za//products/eta c & d/eta c Wisner, P E, Mohsen, F N & Kouwen, N 1975. Removal
■■ Additional CFD modelling and/or physi- d_operating_instructions.pdf. [Accessed on 12 April of air from water line by hydraulic means. Journal of
cal model studies should be performed, 2012]. the Hydraulic Division, ASCE, 101(HY2): 243–257.
76 Journal of the South African Institution of Civil Engineering • Volume 56 Number 3 October 2014