Electrical data
IPN Primary nominal current rms 125 A
Features
IPM Primary current, measuring range 0 .. ± 200 A
RM Measuring resistance TA = 70 °C TA = 85 °C ●● Closed loop (compensated)
RM min RM max RM min RM max current transducer using the Hall
with ± 12 V @ ± 125 A max 5 52 14 50 Ω effect
@ ± 200 A max 5 20 14 18 Ω ●● Insulating plastic case recognized
with ± 15 V @ ± 125 A max 25 74 40 72 Ω according to UL 94-V0.
@ ± 200 A max 25 34 40 1) 40 1) Ω
ISN Secondary nominal current rms 125 mA Special features
K N Conversion ratio 1 : 1000
●● Connection to secondary circuit
U C Supply voltage (± 5 %) ± 12 .. 15 V
on 3 pins 0.63 x 0.56 mm
IC Current consumption 16 (@ ± 15 V) + IS mA
●● Secondary connection complies
Accuracy - Dynamic performance data with LT 100-P.
Advantages
X Accuracy @ IPN, TA = 25 °C @ ± 15 V (± 5 %) ± 0.60 %
@ ± 12 .. 15 V (± 5 %) ± 0.80 % ●● Excellent accuracy
εL Linearity error < 0.15 % ●● Very good linearity
Typ Max ●● Low temperature drift
IO Offset current @ IP = 0, TA = 25 °C ± 0.40 mA ●● Optimized response time
IOM Magnetic offset current 2) @ IP = 0 and specified RM, ●● Wide frequency bandwidth
after an overload of 3 x IPN ± 0.50 mA ●● No insertion losses
IOT Temperature variation of IO 0 °C .. + 70 °C ± 0.15 ± 0.50 mA ●● High immunity to external
- 25 °C .. + 85 °C ± 0.15 ± 0.60 mA interference
tra Reaction time < 500 ns ●● Current overload capability.
tr Step response time 3) 4) to 90 % of IPN < 1 µs
di/dt di/dt accurately followed 4) > 200 A/µs Applications
BW Frequency bandwidth 4) (- 1 dB) DC .. 100 kHz
●● AC variable speed drives and
General data servo motor drives
●● Static converters for DC motor
TA Ambient operating temperature - 25 .. + 85 °C drives
TS Ambient storage temperature - 40 .. + 90 °C ●● Battery supplied applications
RS Secondary coil resistance @ TA = 70 °C 32 Ω ●● Uninterruptible Power Supplies
@ TA = 85 °C 33.5 Ω (UPS)
m Mass 40 g ●● Switched Mode Power Supplies
Standard EN 50178: 1997 (SMPS)
●● Power supplies for welding
Notes: 1) Measuring rang limited to ± 180 A max applications.
2)
Result of the coercive field of the magnetic circuit
3)
With a di/dt of 100 A/µs Application domain
4)
The primary conductor is best filling the through-hole and/or the return of
●● Industrial.
the primary conductor is above the top of the transducer.
25April2013/version 11 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
Current Transducer LA 125-P/SP3
Isolation characteristics
U d Rms voltage for AC insulation test, 50 Hz, 1 min 3 kV
ÛW Impulse withstand voltage 1.2/50 µs 7 kV
Min
dCp Creepage distance 6.7 mm
dCI Clearance 6.7 mm
CTI Comparative Tracking Index (group IIIa) 175
Applications examples
Safety
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
25April2013/version 11 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
Dimensions LA 125-P/SP3 (in mm)
Connection
IS
IP
Page 3/3
25April2013/version 11 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com