TECHNICAL SPECIFICATION OF NYFGbY

5x16 rm 0.6/1.0 (1.2) kV Cable


TYPE & SIZE OF CABLE

NYFGbY 5x16 rm (mm²)


VOLTAGE GRADE, U0/U (Um)
Permissible Service Voltage, U₀/U

0.6/1.0 (1.2) kV
0.72/1.2 kV
RELEVANT STANDARDS

IEC 60502-1, IEC 60228


TECHNICAL SPECIFICATION
Cross-sectional area of conductor, nominal 16 mm2
Number of core 5 core
Material Annealed Copper
Maximum conductor temperature in normal operation 70⁰ C
Conductor
Class of conductor Class 2
Shape of conductor Stranded Circular
Minimum number of wire & Diameter (manufacturing) 7/1.70 No./mm
Material PVC
Thickness, nominal 1.0 mm
Insulation
Thickness, minimum 0.8 mm
Color of insulation Red , Yellow, Blue, Black & Green
Material Extruded PVC
Inner Covering Color Black
Thickness 1.0 mm
Armour Material Flat Galvanized Steel Strip
Dimension (WxT) 0.8 mm
Binder(Optional) Material Galvanized Steel Tape
Material Extruded PVC
Color Black
Sheath Thickness, nominal 1.8 mm
Thickness, minimum 1.24 mm
Overall diameter, approximate 26.4 ± 2 mm
Electrical Characteristics Other Characteristics
D.C resistance of conductor at 200C, maximum 1.15 Ohm/Km Minimum bending radius 15 x Overall diameter
0
Insulation resistance constant ki at 20 C, minimum 36.7 M. ohm-km Operating temperature -15°C to 70°C
A.C. Voltage test for 05 minutes (2.5U₀+2 kV) 3.5 Kv
Current carrying capacity- Signature A K M Iftakher Ahmed
a. in ground at 30°C (Direct Laid) 83 A In Charge (QC & PD)

b. in free air at 35°C (Open) 75 A Date 20 September, 2020