APPENDIX E (FIRE ALARM AND DETECTION SYSTEM

INSTALLATION INSPECTION CHECK LIST)


To be completed by the Inspector at the time of Inspection
Attach additional sheets, data or calculation as necessary to provide a complete record

Inspection Date: 02.03.2020

FACTORY INFORMATION

Factory Name : NRN Knitting & Garments Ltd.


Address :181, jamgora, Ashulia, Savar, Dhaka

Representative Name : Prottoy Chakrabarty

Designation : Fire Safety Officer

Phone : 01628610332
E-mail : prottoyeng440@gmail.com

INSTALLATION, SERVICE AND TESTING CONTRACTOR INFORMATION

Contractor Name: SCENIC (Engineers, Planners, Installation)

Address: 70 green Road, Fattah Plaza (8th floor) Dhaka.

Inspector or Tester Name: Eng Joshim Uddin

Qualification of Inspector or Tester: BSC in EEE

Phone: 01956844356 Fax: _______________

E-mail: scenicbd@yahoo.com

A Contract for Inspection & testing in accordance with NFPA is in effect as of:
__________

The Contract Expires: ________________Frequency of Test: Monthly

WITNESS BY

Company Name : NRN Knitting & Garments Ltd.


Address : 181, jamgora, Ashulia, Savar, Dhaka

Representative Name : Noor Hossain

Designation : HR Officer (Compliance)

Phone : 01683387239

E-mail : compliance @nrnbd.com


MANUFACTURER INFORMATION

System Manufacturer: Context Plus

Country of Origin: UK
Address: Export House, 175 mauldeth Road, Fallowfield Manchesterr M146SG, UK

Local Agent (If any): SCENIC (Engineers, Planners. Ins)

Local Agent’s Address: 70 green Road, Fattah Plaza ( 8th floor) Dhaka
Local Agent’s Representative Name: _________________________________________

Designation: COO
Phone:01956844356 Fax: _______________

E-mail: scenicbd@yahoo.com

SYSTEM INFORMATION

Type of System: Conventional Addressabl

Number of Detectors: Smoke Detector: 251


Heat Detector: 16
Beam Detector: N/A
Multi Sensor Detector: 225
Others (Specify):

Pull Station: 29

Alarm Sounder (with/without) Flasher: 26


Horn/Chime/Strobe/Speaker: ______________________

Others (Specify): I/P Module - 33


Battery: 12v+12v Manufacturer: ___ Type: Lead-Acid

Nominal Voltage: 12Amp/Hour Rating: __________________ Attach additional sheets as

necessary to provide a complete record

0
INSPECTION CHECKLIST
34 | 47

Sl. No Description Yes No

01 A copy of the Fire Alarm installation


certificate and Record of completion is
properly filled out and available from the
installer..

02 More than one contractor was responsible Yes No N/A


for installation of the Fire Alarm System
and each contractor has filled out the Fire
Alarm installation certificate and Record
of completion..

03 A copy of the as-built Fire Alarm System


drawing signed by a competent body is
available on site..

04 An Owner’s Manual, a copy of the


Manufacturer’s instruction, written
sequence of operation are available on
site..

05 For Addressable System a list of each


device with the corresponding location is
provided.. The device addressing shall
reflect actual room names or numbers
that are current to the building use..

06 For Addressable System a copy of the


specific software with software revision
number, software update date available
on site

Fire Alarm Control Panel (FACP)

07 The dedicated 220V ac branch circuit for


the fire alarm panel is labeled “Fire Alarm
Circuit” on the panel schedule of the
electrical panel and the actual circuit
breaker is colored RED as per NFPA72..

08 The dedicated 220V ac branch circuit


shall be mechanically protected (i..e..
breaker lock) as per NFPA72..

09 Fire Alarm Control Panel is grounded


properly by Earth Continuity Conductor..
(connection can be taken from electrical
panel board’s earth bus-bar)

10 The location of the dedicated 220V ac


branch circuit shall be permanently
marked inside the fire alarm control panel
as per NFPA72..

11 A device location and zone map / Schematic co


Diagram shall be provided at or beside the fire alarm pa
35 |

and remote annunciator as per NFPA72.. This


47

Schematic Diagram shall be approved by the


competent body..

12 Batteries are permanently marked with Month &


Year of manufacture as per NFPA72..

13 Fire Alarm Control Panel and/or Remote


Annunciator receive the correct information when
device has been activated.. (i..e.. device location,
device type, alarm type)

Emergency Voice/Alarm Communication Comments

If available check the following Yes No N/A

14 Fire Alarm System is monitored by a


monitoring station..

15 Primary communication line is tested and


monitoring station receives the proper information
from the fire alarm system.

16 Secondary communication line is tested and


monitoring station receives the proper information
from the fire alarm system..

Notification Devices Comments

Sl. No Description Yes No

17 Fire Alarm signaling devices sound


throughout the occupancy..

18 The minimum sound pressure level of 15dBA above


the ambient noise level or 5dBA above a maximum
sound level lasting for at least 60 seconds, whichever
is greater as per NFPA72..

19 The sound level of sleeping rooms (i..e..


dormitory) is at least 15dBA above average
ambient sound level or 75dBA measured at the
pillow, whichever is greater as per NFPA72..

20 If sounder with flasher used, flasher is working


properly or not..

Initiating Devices

21 All initiating devices have been tested as per


manufacturer instructions..

22 All the initiating devices labeled properly..


23 Smoke Detectors initiate alarm throughout the
fire alarm panel.

24 Heat Detectors initiates alarm throughout the


fire alarm panel.

25 Pull Stations initiate alarm throughout the fire


alarm panel.

26 Duct Detectors shut down HVAC unit and Yes No N/A


send a supervisory signal to the fire alarm
panel..

27 Are Smoke Detectors are installed instead Yes No N/A


of Duct Detectors and shut down all HVAC
units when detectors activate..

28 Clean Agent Suppression system initiates Yes No N/A


alarm throughout the fire alarm panel.

Sprinkler System Comments

Sl. No Description Yes No

29 Sprinkler flow switch initiates alarm through the


fire alarm panel.

30 All control valves for the sprinkler system are


monitored and the movement of the valve
initiates a trouble signal at the fire alarm
panel..

31 Low air pressure for the sprinkler system


sends a trouble signal to the fire alarm
panel..

32 For sprinkler system with a pressure tank, the


high and low pressure of the tank sends a
supervisory signal to the fire alarm panel..

Fire Pump

33 When the fire pump is running a supervisory


signal is sent to the fire alarm panel..

34 When there is a loss of any phase at the line


terminals of the motor contactor of the electric
driven fire pump a supervisory signal is sent to
the fire alarm panel.

35 Phase reversal of the electric supply to the


electric driven fire pump shall send a
supervisory signal is sent to the fire alarm
panel..

36 Pump room temperature is controlled by


exhaust fan..
Other Services Comments

Sl. No Description Yes No N/A

37 All the notification and initiating devices


wiring by FP200/ Fire resistant cable as per
standards and size as mentioned on the
approved drawings..

38 Smoke Detector present at Fire Alarm


Control Panel room..

39 Emergency Light with battery/IPS backup


present at Fire Alarm Control Panel room..

40 IPS/UPS used as emergency backup of fire Yes No N/A


alarm panel..

41 Activation of fire alarm or spot smoke


detector release door hold open devices..

42 Exit doors equipped with door unlocking Yes No N/A


devices unlock with activation of fire
alarm system..

43 Activation of fire alarm or spot smoke


detector drops fire doors.

44 Activation of fire alarm or spot smoke Yes No N/A


detector activates smoke dampers..

45 Activation of fire alarm or spot smoke Yes No N/A


detector activates smoke control/
evacuation system..

46 Activation of the elevator lobby smoke Yes No N/A


detector activates the elevator recall and
initiates an alarm signal at the fire alarm
panel..

47 Activation of smoke/heat detectors to


shutdown elevator shutdown is tested..

48 Activation of fire alarm or spot smoke Yes No N/A


detector shut down HVAC system..

49 Wiring between fire alarm panel and Yes No N/A


relays for the safety equipment (i..e.. door
hold-open/release, door unlocking, HVAC
Disclaimer: The list is not all encompassing due to the extensive list of adopted codes. The Inspector shall documents all fire and life safety violations and corrections when any are discovered during inspecti
controls etc..) shall be monitored for

Factory Owners Signature


Inspector Sign Date:
Date: