Air System Design Load Summary for DINERS ATRIUM

Project Name: DINERS ATRIUM 10-07-2020


Prepared by: UNIVERSAL ENGINEERING 02:39PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 104.4 °F / 82.9 °F HEATING OA DB / WB 49.0 °F / 41.1 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 903 ft² 0 - 903 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 4600 W 8526 - 0 0 -
Task Lighting 5520 W 14616 - 0 0 -
Electric Equipment 4000 W 12280 - 0 0 -
People 40 8058 10800 0 0 0
Infiltration - 8541 10551 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 20% / 20% 10404 4270 0% 0 0
>> Total Zone Loads - 62425 25621 - 0 0
Zone Conditioning - 77967 25621 - 0 0
Plenum Wall Load 30% 0 - 0 0 -
Plenum Roof Load 70% 0 - 0 0 -
Plenum Lighting Load 30% 4709 - 0 0 -
Return Fan Load 4764 CFM 0 - 4764 CFM 0 -
Ventilation Load 410 CFM 13858 18871 410 CFM 8417 0
Supply Fan Load 4764 CFM 9535 - 4764 CFM -9535 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 4% 2497 - 4% 0 -
>> Total System Loads - 108565 44492 - -1117 0
Central Cooling Coil - 108565 44494 - -1117 0
>> Total Conditioning - 108565 44494 - -1117 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.50 Page 1 of 1