Cooling Water parameters Analysis as on 14-07-2020-MICROCHEM DOSING SYSTEM

Make up Water Cooling water Parameters

SL. Analysis
UOM
No Parameter
Design Parameter Parameter as of
Recommended Range
Range as of 14th 14th

1 pH - 6.8 - 7.4 9.7 7.2 - 7.8 8

2 Turbidity. NTU 1 4 50 max. 8


Micro
3 Conductivity 250 190 3000 max. 610
mhos/cm
4 M. Alkalinity ppm as CaCO3 20 - 40 60 300 max. 105
Total
5 ppm as CaCO3 60 - 80 70 500 max. 110
Hardness
Calcium
6 ppm as CaCO3 40 - 60 30 350 max. 70
Hardness
7 Chloride ppm 20 - 50 43 700 max. 131

8 Sulphate ppm 20 - 50 15 1000 max. 43

9 Silica as SiO2 ppm 08 - 15 3 70 max. 11

10 Total Iron ppm < 0.1 0.24 2 max. 4.1

11 Zn ppm -   1.5 - 2.5 -


Ortho
12 ppm -   8 to 10 9
phosphate
13 Dispersant ppm -   30 -40 -

14 FRC ppm -   0.3 - 0.5 0


Actual Cycle
15   -   04 to 06 2.3
By Hard
Actual Cycle
16   -   04 to 06 3.6
By Silica
17 RSI   -   6.0 to 6.5 3

18 LSI   -   (-0.3to 0.5)  


Wetbulb
19 oC -   oC 35
Temperature
Return Head
20 oC -   oC 38
Temp