MOTOR PROTECTION RELAY

37,46,47,48,49,50/51,51LR,64,66,68,74
MM30-743 m Thermal Image with prealarm level.
m Current Unbalance.
m Earth Fault.
m Locked Rotor.
O>

ROTOR
STALL
St No

I>>
I< Is>

START
INHIBIT

m Reduced Voltage Starting Control. m Overcurrent. IA 500A


m Control of n° of startings.
N81 -R1
m No-Load Running.
m Blocking Output.
M-LINE MODE SELECT +

m Autosetting. MULTIFUNCTION
MOTOR PROTECTION _
m Remote Trip Control. RELAY TYPE
MM30-743 PROG.

m Speed Control input.


m Trip circuit supervision (Optional).
M
ENTER/RESET

LINE m RTD input.


m Modbus Communication Protocol.
m UL / CSA listed.

Complete motor protection relay designed for the protection and active security of medium and large size
induction motors.

The relay also computes the positive (Id) and negative (Is) sequence components of phase-current
system.

The earth current input circuit includes a 3rd harmonic active filter.

¤ Real Time Measurements = T/Tn- IA - IB - IC - Io - I1 - I2


¤ Maximum Demand and Inrush Recording = T/Tn - IA - IB - IC - Io - I1 - I2 - tstart
Programmable Input Quantities
¤ Fn = System frequency : (50 - 60)Hz

¤ In = Rated primary current of phase Cts : (1 - 9999)A, step 1A

¤ On = Rated primary current of earth fault detection Cts : (1 - 9999)A, step 1A


Connection Diagram

C US LISTED
19CN MS-SCE1811-R1 MS-SCE1798-R1
RINA IND.CONT.EQ. Standard Output Standard Output with F74

1/4
MM30-743 M N81-R1

F49 - Thermal Image


The current I producing motor warming-up is computed as a conventional composition of positive and negative sequence
components of the motor current.

¤ Measured current :I = I12 + 3I2 2


¤ Im = Motor full load current : (0.1 - 1.5)In, step 0.01In
¤ Ist = Motor start-up (Locked Rotor) current : (0.5 - 10)Im, step 0.1Im
¤ tst = Motor starting time : (1 - 120)s, step 1s (I/Im ) 2 − (Ip /Im ) 2
¤ tm = Motor warming-up time constant : (1 - 60)m, step 1m t = [tm ] l n
(I/Im ) 2 − (Ib /Im ) 2
¤ to = Steady motor cooling-down time constant : (1 - 10)tm, step 1tm
¤ Ta/n = Thermal prealarm : (50 - 110)%Tn, step 1%
¤ Ts/n = Restart thermal level : (40 - 100)%Tn, step 1%
¤ Ib = Rated maximum continuous current of the motor : (1 - 1.3)Im, step 0.05Im

F51LR - Locked Rotor


¤ Trip Current level : ILR = (1 - 5)Im, step 0.1Im
¤ Inhibition time at motor starting : 2tst
¤ Trip time delay : tLr = (1 - 25)s, step 1s
F46 - Current Unbalance
¤ Negative sequence current : Is> = (0.1 - 0.8)Im, step 0.1Im
¤ Inverse time current curve : tIs> = (1 - 8)s, step 1s (tIs> = trip time @ Is = In)
F37 - No-Load Running
¤ Under current level : I< = (0.15-1)Im, step 0.01Im
¤ Trip time delay : tI< = (0.1-90)s step 0.1s
When current is below 0.1 Im the function is disabled

F64 - Earth Fault


¤ Current setting range : O> = (0.02 - 2)On, step 0,01On
¤ Istantaneous output : ≤ 0.03s (Reset time of instantaneous output : tO> + tBO)
¤ Independent time delay : tO> = (0.05 - 5)s, step 0.01s
F50/51 - Overcurrent
¤ Current setting range : I> = (1 - 5)Ist, step 0.1Ist (limited to 20 In)
¤ Istantaneous output : ≤ 0.03s (Reset time of instantaneous output : tI> + tBO)
¤ Independent time delay : tI> = (0.05 - 1)s, step 0.01s
¤ Reset time delay of the blocking output relay : tBO = (0.05 - 0,5)s, step 0,01s

F66 (StNo) - Limitation of N° of Startings


¤ Numbers of startings : StNo = (1 - 60), step 1
¤ Time interval for counting of StNo : tStNo = (1 - 60)min, step 1min
If during the set interval the StNo is attained, a new start is inhibited for the time tBst.
¤ Reset time after trip : tBst = (1 - 60)min, step 1min.

Starting Sequence Control


During start-up of the motor, the unit can control an output contact used to operate the switch-over of Reduced Voltage
motor starter (star-delta, resistance or impedance, autotransformers, etc.) to automatically manage the starting transition:

¤ Switch-over (transition) current : Itr = (0.1-1)Ist, step 0.1Ist.


¤ Maximum switch-over time delay : tTr = (0.5-50)s, step 0.1s.

At motor's start, counting of tTr begins. If during tTr the motor current drops below ITr, switching-over is operated; if motor
current stays over ITr longer than tTr, the Locked Rotor element is activated.
Autosetting
The complexity of properly set a motor protection, frequently produces undesired tripping or non-operation of some of the
data functions. The relay MM30 automatically selects the best setting of the according to motor and system basic data.
These parameters are: System frequency, Rated primary current of phase CTs., Rated primary current of earth fault CT,
Motor rated current, Motor starting current, Starting time,Transition current level, Transition time.
Once these settings have been programmed the AUTOSET function can be activated and all the variables are computed
and automatically set at values suitable for a normal duty of the motor. Variables can be anyhow manually modified if
different setting is needed.
2/4
MM30-743 M N81-R1

OVERALL DIMENSIONS (mm)


PROTECTION DEGREE IP44
(IP54 on request)
164

135

134
195
213
PANEL CUT-OUT
115x137 (LxH) 232

Overall Dimensions - Multi-Modules (mm)

51
135
164

32 + (n x 51) 2 195
213

9 4 + (n x 51) 225

PROTECTION
DEGREE IP44
(IP54 on request)

PANEL CUT-OUT
(11+(n x 51)) x 137 (LxH)

3/4
MM30-743 M N81-R1

APPROVAL : CE
REFERENCE STANDARDS IEC 60255 - CE Directive - EN/IEC61000 - IEEE C37 - BSI
¤ Dielectric test voltage IEC 60255-5 2kV, 50/60Hz, 1 min.
¤ Impulse test voltage IEC 60255-5 5kV (c.m.), 2 kV (d.m.) - 1,2/50µs
¤ Insulation resistance >100 M

Environmental Std. Ref. (IEC 680068)


¤ Operation ambient temperature -10°C / +55°C
¤ Storage temperature -25°C / +70°C
¤ Environmental testing (Cold) IEC60068-2-1
(Dry heat) IEC60068-2-2
(Change of temperature) IEC60068-2-14
(Damp heat, steady state) IEC60068-2-78 IEC68-2-3 RH 93% Without Condensing 40°C

CE EMC Compatibility (EN61000-6-2 - EN61000-6-4 - EN50263)


¤ Electromagnetic radiated and conducted emission EN55011 Industrial Environment
¤ Radiated electromagnetic field immunity test IEC61000-4-3 level 3 80-2000MHz10V/m
ENV50204 900MHz/200Hz 10V/m
¤ Conducted disturbances immunity test IEC61000-4-6 level 3 0.15-80MHz10V
¤ Electrostatic discharge test IEC61000-4-2 level 3 6kV contact / 8kV air
¤ Power frequency magnetic test IEC61000-4-8 1000A/m, 50/60Hz
¤ Pulse magnetic field IEC61000-4-9 1000A/m, 8/20ms
¤ Damped oscillatory magnetic field IEC61000-4-10 100A/m, 0.1-1MHz
¤ Immunity to conducted common mode disturbance 0/150KHz IEC61000-4-16 level 4
¤ Electrical fast transient/burst IEC61000-4-4 level 4 2kV, 5kHz
¤ HF disturbance test with damped oscillatory wave IEC60255-22-1 class 3 400pps, 2.5kV (m.c.), 1kV (d.m.)
(1MHz burst test)
¤ Oscillatory waves (Ring waves) IEC61000-4-12 level 4 4kV(c.m.), 2kV(d.m.)
¤ Surge immunity test IEC61000-4-5 level 4 2kV(c.m.), 1kV(d.m.)
¤ Voltage interruptions IEC60255-4-11 50ms
¤ Resistance to vibration and shocks IEC60255-21-1 - IEC60255-21-2

Typical Characteristics
¤ Accuracy at reference value of influencing factors 2% In for measurements
0.2% On
2% + (to=20-30ms) for times
¤ Rated current In = 1 or 5A - On = 1 or 5A
¤ Current overload 200A for 1 sec; 10A continuous
¤ Burden on current input Phase: 0.01VA at In = 1A; 0.2VA at In = 5A
Neutral: 0.03 at On = 1A; 0.2VA at On = 5A
¤ Average power supply consumption <8.5 VA
¤ Output relays rating 5 A; Vn = 380 V
A.C. resistive switching = 1100W (380V max)
make = 30 A (peak) 0.5 sec.
break = 0.3 A, 110 Vcc,
L/R = 40 ms (100.000 op.)

Power Supply
Type 1 : 24 ÷ 110V A.C.(±20%) - 24 ÷ 125V D.C. (±20%)
Type 2 : 80 ÷ 220V A.C.(±20%) - 90 ÷ 250V D.C. (±20%)

Order code - Example : MM30-743-1-5-1-1

MM30-743
Power Supply Current input Output Options Mounting
1 = Type 1 1 = 1A 1 = Standard (without F74) 1 = Surface
2 = Type 2 5 = 5A 2 = with F74 2 = Flush

via Alberelle 56/58, 20089 Rozzano, Milano (Italy)


Tel. +3902575731 - Fax +390257510940 / http://www.microelettrica.com - sales.relays@microelettrica.com
The performances and the characteristics reported in this catalogue are not binding and can modified at any moment without notice