CONTRACT NO.

: 725-C03 CONTRACT TITLE: PRIMARY INFRASTRUCTUE IN CONTRACTOR'S DATE: 06/10/2018


MARDUMAH SUBMITTAL NO.

DOCUMENTS NO.: PREPARED BY: MOHAMMED NAGATY CHECKED BY: SAVAD TS

SUBMITTAL TITLE: DUCT LINER Page: __1___ OF _2_

SPEC. REF. I.E. REMARK (IDENTIFY


MAT'L SOURCE
SECTION, PAGE, SPECIFICATION REQUIREMENT PROPOSED MATERIAL ANY DEVIATIONS FM
(MFR SUPPLIER)
NO,, ETC SPECS AND JUSTIFY

Manufacturer: DUCT INSULATION 2.04 Proposed Model : SRW DUCT LINER


SAUDI ROCKWOOL, F. Duct Liner
SPECS. Section: Brand: SAUDI ROCKWOOL
Al Khobar, 31952 COMPLY with RC
15080 Duct Liner E-M, complying with ASTM C1071 .1 Thickness : 25 mm, Density : 48 kg/m3
P.O Box 49455, specification
MECHANICAL Kingdom Of Saudi Type I and NFPA 90A and 90B; or Rigid Plenum
INSULATION Arabia Liner, complying with ASTM C1071 Type II and Proposed Material : SRW DUCT LINER insulation
PART-2.04. F Tel: +966138875119 .NFPA 90A and 90B for duct acoustic insulation meeting ASTM C612
Page 43 & 44 of 51 Fax: +966138820100 & Non-combustible NFPA 90A and NFPA 90B
Supplier: a) Insulation
:Drawing No SAUDI AIRCON
1) Incombustible glass fiber, flexible blanket, rigid Proposed Duct Liner are Light weight rigid / semi
725-320-20UC-ME- Al-Jubail Industrial
board, and preformed round liner board; rigid insulation faced with woven black fiber
004 City Kingdom of COMPLY with RC
Saudi Arabia impregnated surface and edges coated with poly glass (WBFG).Fungus and bacteria resistance by specification
Tel:+966-13-3408700 vinyl acetate polymer, or acrylic polymer shown to .testing ASTM C665
fax: +966-13- be fungus and bacteria resistant by testing to ASTM
3408539 .G21

WE CERTIFY THAT ALL THE REQUIREMENT


OF THIS SPECIFICATION FOR THE
PROPOSED PRODUCT HAVE BEEN Q.C .Manager: INTIKHAB ALI DATE:
COMPARED, AND THE DEVIATIONS FROM Name Signature
THE SPECIFICATION HAVE BEEN SPECIALLY
IDENTIFIED.
Project Manager: IYAD GHANNAM DATE:
CONTRACT NO.: 725-C03 CONTRACT TITLE: PRIMARY INFRASTRUCTUE IN CONTRACTOR'S DATE: 06/10/2018
MARDUMAH SUBMITTAL NO.

DOCUMENTS NO.: PREPARED BY: MOHAMMED NAGATY CHECKED BY: SAVAD TS

SUBMITTAL TITLE: DUCT LINER Page: __2___ OF _2_

SPEC. REF. I.E. REMARK (IDENTIFY


MAT'L SOURCE
SECTION, PAGE, SPECIFICATION REQUIREMENT PROPOSED MATERIAL ANY DEVIATIONS FM
(MFR SUPPLIER)
NO,, ETC SPECS AND JUSTIFY

SPECS. Section: Manufacturer:


15080 SAUDI ROCKWOOL, b) Thermal Conductivity (K-Value) Thermal Conductivity (K-Value)
Al Khobar, 1) 0.035 W/m °K (0.24 Btu in/hr ft² °F), when tested 1) 0.036 W/m °K (0.25 Btu in/hr ft² °F), when
MECHANICAL
Kingdom Of Saudi .in accordance with ASTM C177 at 24°C (75°F) tested in accordance with EN 12667:2001 at
INSULATION
Arabia .24°C (75°F)
PART-2.04. F Tel: +966138875119 c) Service Temperature
Page 43 & 44 of 51 Fax: +966138820100 .1) Up to 121°C (250°F) Maximum use Temperature 750°C as per ASTM COMPLY with RC
Supplier: C411 specification
:Drawing No SAUDI AIRCON d) Noise Reduction Coefficient (NRC)
725-320-20UC-ME- Al-Jubail Industrial 1) 0.45 or higher for 13 mm (½ in.) product, 0.70 or Noise Reduction Coefficient (NRC)
004 City Kingdom of higher for 25 mm (1 in.) product, when tested in Noise reduction Co-efficient is 0.7 when tested
Saudi Arabia .accordance with ASTM C423 in Type A mounting in accordance with ASTM C423
Tel:+966-13-3408700
fax: +966-13-
3408539

WE CERTIFY THAT ALL THE REQUIREMENT


OF THIS SPECIFICATION FOR THE
PROPOSED PRODUCT HAVE BEEN Q.C .Manager: INTIKHAB ALI DATE:
COMPARED, AND THE DEVIATIONS FROM Name Signature
THE SPECIFICATION HAVE BEEN SPECIALLY
IDENTIFIED.
Project Manager: IYAD GHANNAM DATE: