1.General Characteristics
Moducab 19” floor standing cabinets are intended for digital infrastructures.
Moducab floor standing cabinets are made up of aluminium extruded frame structure and provide IP20-IK08 protection.
The Moducab floor standing cabinets comes in 2 range of colors, range 1- combination of RAL 7037 & 7035. range 2- fully
RAL 9005(customized).
Moducab floor standing cabinets can be joined together and can be equipped with the base plinth.
Equipment and accessories for thermal and cable management such as
Front door, Rear door, side panels, Plinths, Cable manager, Castor, Earthing strip,
Support Angle and the 19” equipment such as Monitor tray, Keyboard
tray, Fan housing tray, Blank panel, Power distribution unit. Complete
the range.
1.1 Presentation
The main parts of Moducab 19” floor standing cabinets are:
§ 2 aluminium alloy frameworks consisting of 4 vertical and 4 horizontal
sections bolted together with 4 depth sections to form a structure.
§ 1 Top Cover and 1Bottom Cover with gland plate and rubber grommets for
cable entry provisions.
§ 4 Recess mounting angles.
§ 2 pairs of support channel for up to 32U and 3 pairs of support channel
for above 32U height.
§ 2 pairs of Reducing cable channel.(only for 800W).
§ 8 Corner Brackets.
§ 2 Side panels fitted with slam latch and cam lock.
1/31
1. General Characteristics(continued)
1.1 Presentation(continued)
‘B’
Fig 1.1
The basic structure of rack is made up of 4 vertical aluminum alloy extruded members bolted with 4 horizontal aluminum
alloy extruded members which forms 2 frame structures which are joined together by 4 depth sections with nut plates as
shown in Detail A.
The structure of the frame are strengthened by using a corner Bracket as shown in the Detail B which gives stability at
adverse loading Conditions.
The top and bottom cover comprises of gland plate with cable entry points in 56mm round cut out edge protected
with rubber grommets. The top cover also has cutout for 4 fan fitment.
Depth support channels are fitted along the depth to equate the load evenly and also used to fit the 19” equipment
mounting angle.
19” Equipment mounting angle facilitate in mounting the 19” equipment. The hole pattern on the equipment mounting angle is
according to the standard DIN 41494. It contains U printing pattern which can be read from down to up and vice versa.
Reducing cable channel is mounted all along the vertical usable height only for 800W Moducab racks which helps in routing all
cables vertically.
Reducing channels are fitted only for 800mm wide Moducab racks to maintain the 19” Equipment mounting fitment.
STANDARDS
IEC 60529
NF C 20-010) Degrees of protection provided by enclosures (IP code)
EN 60529
2. Range
Range of Moducab racks are classified by their Capacity, Width and Depth
3/31
2. Range(continued)
2.i. Assembled All Dimensions are in mm
Sr No Item Code Description Capacity Width Depth 35 465034 MCAB PT 36U610 A
36 U 600 1000
1 465000 MCAB PT 17U665 A 36 465035 MCAB BT 36U610 A
17 U 600 650
2 465001 MCAB BT 17U665 A 37 465036 MCAB PT 36U88 A
36 U 800 800
3 465002 MCAB PT 17U68 A 38 465037 MCAB BT 36U88 A
17 U 600 800
4 465003 MCAB BT 17U68 A 39 465038 MCAB PT 36U810 A
36 U 800 1000
5 465004 MCAB PT 22U665 A 40 465039 MCAB BT 36U810 A
22 U 600 650
6 465005 MCAB BT 22U665 A 41 465040 MCAB PT 36U812 A
36 U 800 1200
7 465006 MCAB PT 22U68 A 42 465041 MCAB BT 36U812 A
22 U 600 800
8 465007 MCAB BT 22U68 A 43 465042 MCAB PT 42U665 A
42 U 600 650
9 465008 MCAB PT 24U665 A
44 465043 MCAB BT 42U665 A
24 U 600 650
10 465009 MCAB BT 24U665 A
45 465044 MCAB PT 42U68 A
11 465010 MCAB PT 24U68 A 42 U 600 800
24 U 600 800 46 465045 MCAB BT 42U68 A
12 465011 MCAB BT 24U68 A
47 465046 MCAB PT 42U610 A
13 465012 MCAB PT 24U610 A 42 U 600 1000
24 U 600 1000 48 465047 MCAB BT 42U610 A
14 465013 MCAB BT 24U610 A
49 465048 MCAB PT 42U612 A
15 465014 MCAB PT 27U665 A 42 U 600 1200
27 U 600 650 50 465049 MCAB BT 42U612 A
16 465015 MCAB BT 27U665 A
51 465050 MCAB PT 42U88 A
17 465016 MCAB PT 27U68 A 42 U 800 800
27 U 600 800 52 465051 MCAB BT 42U88 A
18 465017 MCAB BT 27U68 A
53 465052 MCAB PT 42U810 A
19 465018 MCAB PT 27U610 A 42 U 800 1000
27 U 600 1000 54 465053 MCAB BT 42U810 A
20 465019 MCAB BT 27U610 A
55 465054 MCAB PT 42U812 A
21 465020 MCAB PT 32U665 A 42 U 800 1200
32 U 600 650 56 465055 MCAB BT 42U812 A
22 465021 MCAB BT 32U665 A
57 465056 MCAB PT 45U610 A
23 465022 MCAB PT 32U68 A 45 U 600 1000
32 U 600 800 58 465057 MCAB BT 45U610 A
24 465023 MCAB BT 32U68 A
59 465058 MCAB PT 45U810 A
25 465024 MCAB PT 32U88 A
45 U 800 1000
32 U 800 800
26 465025 MCAB BT 32U88 A 60 465059 MCAB BT 45U810 A
3.3 Design
• Robust frame structure made of aluminum alloy + powder coated.
• Top cover made of CRCA sheet + powder coated.
• Top gland cover plate made of CRCA sheet + powder coated.
• Bottom cover made of CRCA sheet + powder coated.
• Bottom gland cover plate made of CRCA sheet + powder coated.
• Recess mounting angle made CRCA sheet + powder coated.
• Depth Support channel made of CRCA sheet + powder coated.
• Corner Bracket made of CRCA sheet + powder coated..
3.7 UL Certification
• This is a UL approved product as per UL 2416.
7/31
3. Technical Characteristics(continued)
3.8 Weight
Net weight excluding packaging
8/31
3. Technical Characteristics(continued)
3.8 Weight(continued)
Net weight excluding packaging
9/31
4.Dimensions
4.1. Overall Dimensions
Overall Height
Overall
Capacity Height(H)mm
17U 902
22U 1124
24U 1213
27U 1347
32U 1569
36U 1747
42U 2013
45U 2147
Front/Rear View Side View
48U 2280
Overall dimensions(mm)
Rack Size A B W D
600Wx650D 903 1715 601 652
600Wx800D 903 1865 601 802
600Wx1000D 903 2065 601 1002
600Wx1200D 903 2665 601 1202
800Wx800D 1240 2265 801 802
800Wx1000D 1240 2465 801 1002
800Wx1200D 1240 2665 801 1202
Top View
10/31
4. Dimension(Continued)
4.2 Support channel positioning and recess mounting
Support Channel
The Fig to the left shows the side view of the 19” floor standing cabinets,
The recess angle positioning location on the depth support channel are
particular for varying depths as per the table below.
Support Channel
(F)Front Side (R)Rear Side
11/31
4. Dimension(Continued)
4.3 Usable Dimensions(Continued)
4.3.1 600mm wide floor standing cabinet
Height Chart
Usable
Capacity Height(h)mm
17U 756
22U 978
24U 1067
27U 1200
Section A-A 32U 1422
36U 1600
42U 1867
45U 2000
48U 2134
Depth Chart(mm)
Front View Side View Depth Usable Depth(d)
650 526
800 676
1000 876
1200 1076
Bottom View
12/31
4. Dimension(Continued)
4.3 Usable Dimensions(continued)
4.3.2 800mm wide floor standing cabinet
Height Chart
Usable
Capacity Height(h)mm
17U 756
22U 978
24U 1067
27U 1200
32U 1422
Section A-A 36U 1600
42U 1867
45U 2000
48U 2134
Depth Chart(mm)
Depth Overall Depth Usable Depth(d)
650 652 526
800 802 676
1000 1002 876
1200 1202 1076
Bottom View
13/31
4. Dimension(Continued)
4.3 Usable Dimensions(continued)
4.3.3 Recess
Height Chart
Capacity Height(h)mm
17U 756
22U 978
24U 1067
27U 1200
32U 1422
36U 1600
42U 1867
45U 2000
48U 2134
14/31
5. Baying
‘A’
Det A
‘B’
Det B
• The Moducab Floor Standing cabinets can be joined together using baying kit of two colors -Item code: 1)CBM-DT-A , 2)CBM-BT-A.
•CBM-DT-A – for combination of RAL 7035&7037, CBM-BT-A- for fully RAL 9005(customized).
•The Baying kit consists of the coupling plate made up of CRCA sheet + powder coated.
•M6 hexagonal bolt is used to screw the coupling plate onto the nut plate which is inserted from the vertical section and the
horizontal section which will hold both the racks coupled together.
•There will be 4 coupling plates fixed vertically for up to 32 U and 6 coupling plates for above 32U height racks. 3 in front and 3 in rear
side. 4 coupling plates fixed horizontally, 2 on top and 2 on bottom.
The door opening angle remain same for the coupled cabinets
15/31
6. Door
• The 19” inch Moducab floor standing cabinets can be equipped with door which comes in three types viz. clear toughened glass,
honeycomb perforated or square mesh.
• In case of glass doors as shown in Fig , it comprises of one piece frame unlike trims at edges where in 4mm thick toughened tinted
glass is fixed.
• Perforated door has perforations for ventilation. The perforations are in the shape of honeycomb structure as shown in Fig.
• Meshed doors have square slot patterns as shown in Fig.
• The doors are made up of CRCA sheet + powder coating
i. Glass door
16/31
6. Door(continued)
6.i. Glass door with cam lock All dimensions in mm
Glass door with cam lock
Sr No Item Code Description Height Width
1 465080 MCAB GDR DT 17U6 CAM 852 532
2 465081 MCAB GDR BT 17U6 CAM 852 532
3 465082 MCAB GDR DT 22U6 CAM 1074 532
4 465083 MCAB GDR BT 22U6 CAM 1074 532
5 465084 MCAB GDR DT 24U6 CAM 1163 532
6 465085 MCAB GDR BT 24U6 CAM 1163 532
7 465086 MCAB GDR DT 27U6 CAM 1296 532
8 465087 MCAB GDR BT 27U6 CAM 1296 532
9 465088 MCAB GDR DT 32U6 CAM 1519 532
10 465089 MCAB GDR BT 32U6 CAM 1519 532
11 465090 MCAB GDR DT 32U8 CAM 1518 732
12 465091 MCAB GDR BT 32U8 CAM 1518 732
13 465092 MCAB GDR DT 36U6 CAM 1696 532
14 465093 MCAB GDR BT 36U6 CAM 1696 532
15 465094 MCAB GDR DT 36U8 CAM 1696 732
16 465095 MCAB GDR BT 36U8 CAM 1696 732
17 465096 MCAB GDR DT 42U6 CAM 1963 532
18 465097 MCAB GDR BT 42U6 CAM 1963 532
19 465098 MCAB GDR DT 42U8 CAM 1963 732
20 465099 MCAB GDR BT 42U8 CAM 1963 732
21 465100 MCAB GDR DT 45U6 CAM 2097 532
22 465101 MCAB GDR BT 45U6 CAM 2097 532
23 465102 MCAB GDR DT 45U8 CAM 2097 732
24 465103 MCAB GDR BT 45U8 CAM 2097 732
17/31
6. Door(continued)
Sr No Item Code Description Height Width
17 465120 MCAB GDR DT 42U6 HDL 1963 532
18 465121 MCAB GDR BT 42U6 HDL 1963 532
19 465122 MCAB GDR DT 42U8 HDL 1963 732
20 465123 MCAB GDR BT 42U8 HDL 1963 732
21 465124 MCAB GDR DT 45U6 HDL 2097 532
22 465125 MCAB GDR BT 45U6 HDL 2097 532
23 465126 MCAB GDR DT 45U8 HDL 2097 732
24 465127 MCAB GDR BT 45U8 HDL 2097 732
6.iii. Mesh door with cam lock
Mesh door with cam lock
Sr No Item Code Description Height Width
1 465128 MCAB MDR DT 17U6 CAM 852 532
2 465129 MCAB MDR BT 17U6 CAM 852 532
3 465130 MCAB MDR DT 22U6 CAM 1074 532
4 465131 MCAB MDR BT 22U6 CAM 1074 532
5 465132 MCAB MDR DT 24U6 CAM 1163 532
6 465133 MCAB MDR BT 24U6 CAM 1163 532
7 465134 MCAB MDR DT 27U6 CAM 1296 532
8 465135 MCAB MDR BT 27U6 CAM 1296 532
9 465136 MCAB MDR DT 32U6 CAM 1519 532
10 465137 MCAB MDR BT 32U6 CAM 1519 532
11 465138 MCAB MDR DT 32U8 CAM 1518 732
12 465139 MCAB MDR BT 32U8 CAM 1518 732
13 465140 MCAB MDR DT 36U6 CAM 1696 532
14 465141 MCAB MDR BT 36U6 CAM 1696 532
15 465142 MCAB MDR DT 36U8 CAM 1696 732
16 465143 MCAB MDR BT 36U8 CAM 1696 732
17 465144 MCAB MDR DT 42U6 CAM 1963 532
18 465145 MCAB MDR BT 42U6 CAM 1963 532
19 465146 MCAB MDR DT 42U8 CAM 1963 732
20 465147 MCAB MDR BT 42U8 CAM 1963 732
21 465148 MCAB MDR DT 45U6 CAM 2097 532
22 465149 MCAB MDR BT 45U6 CAM 2097 532
23 465150 MCAB MDR DT 45U8 CAM 2097 732
24 465151 MCAB MDR BT 45U8 CAM 2097 732
6.iv. Mesh door with 3 point lock
Mesh door with 3 point lock
Sr No Item Code Description Height Width
1 465152 MCAB MDR DT 17U6 HDL 852 532
2 465153 MCAB MDR BT 17U6 HDL 852 532
3 465154 MCAB MDR DT 22U6 HDL 1074 532
4 465155 MCAB MDR BT 22U6 HDL 1074 532
5 465156 MCAB MDR DT 24U6 HDL 1163 532
18/31
6. Door(continued)
Sr No Item Code Description Height Width
6 465157 MCAB MDR BT 24U6 HDL 1163 532
7 465158 MCAB MDR DT 27U6 HDL 1296 532
8 465159 MCAB MDR BT 27U6 HDL 1296 532
9 465160 MCAB MDR DT 32U6 HDL 1519 532
10 465161 MCAB MDR BT 32U6 HDL 1519 532
11 465162 MCAB MDR DT 32U8 HDL 1518 732
12 465163 MCAB MDR BT 32U8 HDL 1518 732
13 465164 MCAB MDR DT 36U6 HDL 1696 532
14 465165 MCAB MDR BT 36U6 HDL 1696 532
15 465166 MCAB MDR DT 36U8 HDL 1696 732
16 465167 MCAB MDR BT 36U8 HDL 1696 732
17 465168 MCAB MDR DT 42U6 HDL 1963 532
18 465169 MCAB MDR BT 42U6 HDL 1963 532
19 465170 MCAB MDR DT 42U8 HDL 1963 732
20 465171 MCAB MDR BT 42U8 HDL 1963 732
21 465172 MCAB MDR DT 45U6 HDL 2097 532
22 465173 MCAB MDR BT 45U6 HDL 2097 532
23 465174 MCAB MDR DT 45U8 HDL 2097 732
24 465175 MCAB MDR BT 45U8 HDL 2097 732
19/31
6. Door(continued)
6.vi. Perforated door with 3 point lock
Honeycomb door with 3 point lock
Sr No Item Code Description Height Width
1 465272 MCAB PDR DT 32U6 HDL 1518 532
2 465273 MCAB PDR BT 32U6 HDL 1518 532
3 465274 MCAB PDR DT 32U8 HDL 1518 732
4 465275 MCAB PDR BT 32U8 HDL 1518 732
5 465276 MCAB PDR DT 36U6 HDL 1696 532
6 465277 MCAB PDR BT 36U6 HDL 1696 532
7 465278 MCAB PDR DT 36U8 HDL 1696 732
8 465279 MCAB PDR BT 36U8 HDL 1696 732
9 465280 MCAB PDR DT 42U6 HDL 1963 532
10 465281 MCAB PDR BT 42U6 HDL 1963 532
11 465282 MCAB PDR DT 42U8 HDL 1963 732
12 465283 MCAB PDR BT 42U8 HDL 1963 732
13 465284 MCAB PDR DT 48U6 HDL 2230 532
14 465285 MCAB PDR BT 48U6 HDL 2230 532
15 465286 MCAB PDR DT 48U8 HDL 2230 732
16 465287 MCAB PDR BT 48U8 HDL 2230 732
20/31
6. Door(continued)
6.viii. Mesh double door with 3 point lock
Mesh Double door with 3 point lock
Sr No Item Code Description Height Width
1 465200 MCAB MDDR DT 17U6 HDL 852 532
2 465201 MCAB MDDR BT 17U6 HDL 852 532
3 465202 MCAB MDDR DT 22U6 HDL 1074 532
4 465203 MCAB MDDR BT 22U6 HDL 1074 532
5 465204 MCAB MDDR DT 24U6 HDL 1163 532
6 465205 MCAB MDDR BT 24U6 HDL 1163 532
7 465206 MCAB MDDR DT 27U6 HDL 1296 532
8 465207 MCAB MDDR BT 27U6 HDL 1296 532
9 465208 MCAB MDDR DT 32U6 HDL 1519 532
10 465209 MCAB MDDR BT 32U6 HDL 1519 532
11 465210 MCAB MDDR DT 32U8 HDL 1518 732
12 465211 MCAB MDDR BT 32U8 HDL 1518 732
13 465212 MCAB MDDR DT 36U6 HDL 1696 532
14 465213 MCAB MDDR BT 36U6 HDL 1696 532
15 465214 MCAB MDDR DT 36U8 HDL 1696 732
16 465215 MCAB MDDR BT 36U8 HDL 1696 732
17 465216 MCAB MDDR DT 42U6 HDL 1963 532
18 465217 MCAB MDDR BT 42U6 HDL 1963 532
19 465218 MCAB MDDR DT 42U8 HDL 1963 732
20 465219 MCAB MDDR BT 42U8 HDL 1963 732
21 465220 MCAB MDDR DT 45U6 HDL 2097 532
22 465221 MCAB MDDR BT 45U6 HDL 2097 532
23 465222 MCAB MDDR DT 45U8 HDL 2097 732
24 465223 MCAB MDDR BT 45U8 HDL 2097 732
21/31
6. Door(continued)
6.x. Perforated double door with 3 point lock
Perforated Double door with 3 point lock
Sr No Item Code Description Height Width
1 465240 MCAB PDDR DT 32U6 HDL 1519 532
2 465241 MCAB PDDR BT 32U6 HDL 1519 532
3 465242 MCAB PDDR DT 32U8 HDL 1519 732
4 465243 MCAB PDDR BT 32U8 HDL 1519 732
5 465244 MCAB PDDR DT 36U6 HDL 1696 532
6 465245 MCAB PDDR BT 36U6 HDL 1696 532
7 465246 MCAB PDDR DT 36U8 HDL 1696 732
8 465247 MCAB PDDR BT 36U8 HDL 1696 732
9 465248 MCAB PDDR DT 42U6 HDL 1963 532
10 465249 MCAB PDDR BT 42U6 HDL 1963 532
11 465250 MCAB PDDR DT 42U8 HDL 1963 732
12 465251 MCAB PDDR BT 42U8 HDL 1963 732
13 465252 MCAB PDDR DT 48U6 HDL 2230 532
14 465253 MCAB PDDR BT 48U6 HDL 2230 532
15 465254 MCAB PDDR DT 48U8 HDL 2230 732
16 465255 MCAB PDDR BT 48U8 HDL 2230 732
22/31
7.Plinths
The Moducab 19” floor standing cabinets can be equipped with a 100mm high metal plinth which can be easily fitted
Onto the enclosure.
• Made up of CRCA sheet and powder coated.
• It also contains gland plates which are removable if required for cable entry provision.
The concrete floor on which the rack is going to be grouted is drilled first according to the provisions provided in
the base plinth. They are grouted using anchor fasteners.
The base plinth consist of four C-channels which are welded together as shown in the fig .
Plinth Dimensions(mm)
Item Code Description H W D
465506 BS PLINTH BT 1HX6X65 A 100 601 652
465507 BS PLINTH PT 1HX6X65 A 100 601 652
465508 BS PLINTH BT 1HX6X8 A 100 601 802
465509 BS PLINTH PT 1HX6X8 A 100 601 802
465510 BS PLINTH BT 1HX6X10 A 100 601 1002
465511 BS PLINTH PT 1HX6X10 A 100 601 1002
465512 BS PLINTH BT 1HX6X12 A 100 601 1202
465513 BS PLINTH PT 1HX6X12 A 100 601 1202
465514 BS PLINTH BT 1HX8X65 A 100 801 652
465515 BS PLINTH PT 1HX8X65 A 100 801 652
465516 BS PLINTH BT 1HX8X8 A 100 801 802
465517 BS PLINTH PT 1HX8X8 A 100 801 802
465518 BS PLINTH BT 1HX8X10 A 100 801 1002
465519 BS PLINTH PT 1HX8X10 A 100 801 1002
465520 BS PLINTH BT 1HX8X12 A 100 801 1002
465521 BS PLINTH PT 1HX8X12 A 100 801 1202
23/31
8.Cable Management
8.i. Cable manager plastic loop mountable
The moducab 19” floor standing cabinets can be equipped with cable managers as shown . The plastic cable loops are fixed on the
Cable managers.
The cable managers are fitted onto the racks either horizontally or vertically as shown below.
The cable managers are made up of CRCA sheet + powder coated.
Plastic Loop
Horizontally mounted
24/31
8.Cable Management(continued)
8.iii. PVC Cable manager
The moducab 19” floor standing cabinets can be equipped with cable managers as shown . The PVC cable loops are fixed on the
Cable managers.
The cable managers are fitted onto the racks either horizontally or vertically as shown below.
The cable managers are made up of CRCA sheet + powder coated.
9.Castor
The Moducab 19” floor standing cabinets can be equipped with a set of 4 castors.
25/31
10.Earthing Strip
• Earthing bars made up of copper and provided for achieving electrical ground.
• All enclosures components such as doors, side walls, roofs should be bonded directly to the frame grounding points from the
frame to the external building ground should be concluded.
Characteristics:
• Earthing strips used in ProTek Floor Standing cabinets is of length 150mm as shown in the below drawing.
11.Support Angle
• The Moducab 19” floor standing cabinets can be equipped with support angle as shown in Fig.
• Support angles comes in varying sizes as shown in the corresponding table.
• They are used for supporting any 19” equipment if the equipment is heavy or needs extra support
• The Support angles are available in 4 depths as shown in Table .
• The Support angle is made up of CRCA sheet + powder coating
Support Angle
Item Depth
Description
Code (D)mm
465532 SUP ANGL PT 5050375 A 375
465533 SUP ANGL BT 5050375 A 375
465534 SUP ANGL PT 5050475 A 475
465535 SUP ANGL BT 5050475 A 475
465536 SUP ANGL PT 5050600 A 600
465537 SUP ANGL BT 5050600 A 600
465538 SUP ANGL PT 5050700 A 700
465539 SUP ANGL BT 5050700 A 700
26/31
12.19” Equipment
i. Cantilever Tray
• The Moducab 19” floor standing cabinets can be equipped with Cantilever trays of width 483mm.
• The Moducab floor standing cabinet consist of two sizes of cantilever trays as shown in the Figures.
• It consists of slots as shown in the below figures for ventilation.
• They are only capable of carrying lightweight components.
• They are made up of CRCA sheet + powder coating
Cantilever tray
Item Code Description
465485 CANT TRAY PT 1U255 A
465486 CANT TRAY BT 1U255 A
465487 CANT TRAY PT 2U400 A
465488 CANT TRAY BT 2U400 A
ii.1 ii.2
27/31
12.19” Equipment(continued)
ii.3 ii.4
Monitor tray
Item Code Description
465472 MONITOR TRAY PT 6X375 A
465473 MONITOR TRAY BT 6X375 A
465474 MONITOR TRAY PT 6X475 A
465475 MONITOR TRAY BT 6X475 A
465476 MONITOR TRAY PT 6X600 A
465477 MONITOR TRAY BT 6X600 A
465478 MONITOR TRAY PT 6X700 A
465479 MONITOR TRAY BT 6X700 A
• The Moducab 19” floor standing cabinets can be equipped with blank panel as
shown in the Fig.
• The table shows the range of blank panels which are in use.
• They are used to fill the unnecessary blank spaces which are left after the
installation of all components. They prevent the dust from entering inside the
cabinet.
• Blank panel is made up of CRCA sheet + powder coated.
28/31
13. Power Distribution Unit
• The Moducab 19” Floor standing cabinets can be equipped with Power Distribution Units which can be mounted either
horizontally which is of 19” or vertically according to the requirement.
• The parameters for selecting the PDU are overall dimension, electrical rating, number of sockets required and the other
accessories which are required .viz. Plug and Cable.
• The range of Electrical Ratings for the Power Distribution Unit are as follows:
o Rated Voltage – 220 to 240 VAC, 50 Hz
o Full Load Current - 6 to 32Amp
o Full Load Power – 1.2 Kva to 6 Kva
o Powder coated Black RAL 9005(customized)
Horizontally Mounted
Vertically mounted
The table shows the overall dimensions for all the types of PDU varieties (All dimensions in mm)
Overall Dimensions
PDU Type Item Code Description
W H D
1 465568 PDU 6A 4SKT SWT PLG A
2 465569 PDU 6A 6SKT SWT PLG A
482 80 58
3 465570 PDU 13A 6SKT MCB PLG A
4 465571 PDU 16A 6SKT MCB PLG A
5 465572 PDU 13A 8SKT MCB PLG A
5B 465573 PDU 13A 8SKT MCB W/O WIRE A
5C 465574 PDU 13A 8SKT MCB W/O PLG A
5D 465575 PDU 13A 8SKT MCB INDPLG A
702 80 58
6 465576 PDU 16A 8SKT MCB PLG A
6B 465577 PDU 16A 8SKT MCB W/O WIRE A
6C 465578 PDU 16A 8SKT MCB W/O PLG A
6D 465579 PDU 16A 8SKT MCB INDPLG A
29/31
13. Power Distribution Unit(continued)
7 465580 PDU 13A 10SKT MCB PLG A
7B 465581 PDU 13A 10SKT MCB W/O WIRE A
7C 465582 PDU 13A 10SKT MCB W/O PLG A
7D 465583 PDU 13A 10SKT MCB INDPLG A
8 465584 PDU 16A 10SKT MCB PLG A
8B 465585 PDU 16A 10SKT MCB W/O WIRE A
8C 465586 PDU 16A 10SKT MCB W/O PLG A
8D 465587 PDU 16A 10SKT MCB INDPLG A
9 465588 PDU 13A 5SKT 16A 5SKT INDPLG A 822 80 58
9B 465589 PDU 13A5SKT 16A5SKT W/O WIRE A
9C 465590 PDU 13A5SKT 16A5SKT W/O PLG A
10 465591 PDU 13A 12SKT MCB INDPLG A
10B 465592 PDU 13A 12SKT MCB W/O WIRE A
10C 465593 PDU 13A 12SKT MCB W/O PLG A
11 465594 PDU 16A 12SKT MCB INDPLG A
11B 465595 PDU 16A 12SKT MCB W/O WIRE A
11C 465596 PDU 16A 12SKT MCB W/O PLG A
12 465597 PDU 13A6SKT 16A6SKT INDPLG A
12B 465598 PDU 13A6SKT 16A6SKT W/O WIRE A 1062 80 58
12C 465599 PDU 13A6SKT 16A6SKT W/O PLG A
13 465600 PDU 13A 15SKT MCB INDPLG A
13B 465601 PDU 13A 15SKT MCB W/O WIRE A
13C 465602 PDU 13A 15SKT MCB W/O PLG A
1122 80 58
14 465603 PDU 16A 15SKT MCB INDPLG A
14B 465604 PDU 16A 15SKT MCB W/O WIRE A
14C 465605 PDU 16A 15SKT MCB W/O PLG A
Degree Bracket
Degree Bracket
Adjustable leg
Item Code Description
465480 ADJT LEG ZP 90H A
• Moducab 19” Floor standing cabinets can be equipped with 4 sets of levelling legs as shown in Fig above
• It consists of a degree bracket which are screwed to the bottom cover.
• The degree bracket as shown in the Fig above has a nut weld which makes it easy for the adjustable leg to directly screw to it.
• The adjustable leg can be adjusted according to the surface on which the rack will be placed.
30/31
15. Cooling Fan
Fan
Item Code Description
465483 DOUBLE FAN FOR MCAB/PROFI
465484 FOUR FAN FOR MCAB/PROFI
• The 19” ProTek Wall Mount racks can be equipped with cooling arrangement within the space cavity used
by the top cover.
• It can be equipped with thermostat control for controlling the temperature of the enclosure interior for
forced ventilation (each fan has a 90cfm capacity) without using any of the equipment installation space.
31/31