Spec No.

: ZTT 18-86342

TECHNICAL SPECIFICATION
13.2kV MV Underground Cables

A December 12, 2019 Joey Reddy Felix

Version Date Prepared Reviewed Approved

Address: No.5, Zhongtian road, Nantong economic and technological development zone, Jiangsu Province, China
Tel: +86-513-89191138 Fax: +86-513-8359 9670 Zip code: 226010 Website: www.zttcable.com
1. Drawing and CONSTRUCTION CHARACTERISTICS
Item Description Material
1 Conductor Circular compacted aluminum(Class 2)
2 Conductor screen Semi-conductive compound
3 Insulation XLPE
Semi-conductive compound(easily
4 Insulation screen
strippable)
5 Wrapper Semi-conductive tape
6 Metallic screen Stranding helix copper wires
7 Metallic tape counter helix copper tape
8 Wrapper Non-woven fabric
9 Outer sheath Anti-UV PE(ST7)
Core identification Natural
Outer sheath color Red

Note: The above drawing is only for reference


www.zttcable.com ALL Rights Reserved Copyright © 2018 page 2
2. DATE SHEET

No, Description 3x1x50 1x500 1x400


0 Material Company Code 0101-0276 0101-0424 0101-0458
1 Conductor
1.1 No. of conductor(pcs) 3x1 1 1
1.2 Min. number of stands of conductor(pcs) 19 53 53
1.3 Approx. diameter(mm) 8.0 26.2 23.0
1.4 DC resistance at 20°C(Ω/km) 0.641 0.0605 0.0778
2 Conductor screen
2.1 Nominal thickness(mm) 0.7 0.7 0.7
2.2 Minimum thickness(mm) 0.5 0.5 0.5
2.3 Maximum volumetric resistivity at 90°C (Ω.cm) 50000 50000 5000
3 Insulation
3.1 Nominal thickness(mm) 4.5 4.5 4.5
3.2 Minimum thickness(mm) 3.95 3.95 3.95
3.3 Diameter over insulation(mm) 18.3±1 37.4±1 34.2±1
4 Insulation screen
4.1 Nominal thickness(mm) 0.8 1.4 1.4
4.2 Minimum thickness(mm) 0.6 1.0 1.0
4.3 Maximum volumetric resistivity at 90°C (Ω.cm) 50000 50000 5000
4.4 Strippability(daN) 1.5-7 1.5-7 1.5-7
5 Semi-conductive tape
5.1 No of layer x Nominal thickness(mm) 2x0.12 2x0.12 2x0.12
5.2 Overlap rate (%) 20 20 20
5.3 Maximum volumetric resistivity at 90°C (Ω.cm) 50000 50000 5000
6 Metallic screen
6.1 Material Copper Copper Copper

www.zttcable.com ALL Rights Reserved Copyright © 2018 page 3


6.2 Section 25(per phase) 50 50
6.3 Number of copper wires(pcs) 40(per phase) 60 60
6.4 Diameter of copper wires(mm) 0.9 1.04 1.04
7 Metallic tape
7.1 Nominal thickness(mm) 0.1 0.1 0.1
8 Wrapper
8.1 Nominal thickness(mm) 0.2 0.2 0.2
9 Outer sheath
9.1 Nominal thickness(mm) 1.8 2.4 2.3
9.2 Minimum thickness(mm) 1.43 1.94 1.86
9.3 Approx. diameter over outer sheath(mm) 27.0 47.9 44.0
9.4 Approx. outer diameter of pre-assembled 58.2 / /
10 Approx. weight of completed cable(kg/km) 2550 3000 2560

www.zttcable.com ALL Rights Reserved Copyright © 2018 page 4


3. Packing and Drum
ZTT cables are packed in iron-wooden drums. During transportation, right tools should be used to avoid damaging the package and to handle with ease.
Cables should be protected from moisture; kept away from high temperature and fire sparks; protected from over bending and crushing; protected from
mechanical stress and damage.
The inner end of cable is then sealed with heat shrinkable end cap to prevent ingress of water and is made available for testing. The outer end of cable is
equipped with heat shrinkable end cap. Outer sheath marking legend can be changed according to user’s requests.

Drum length Drum Dimensions (mm) Approx. Gross weight per drum
NO. Cable Type
(m) D d b B (kg)

1 AL/XLPE/CWS/PE-13.2kV-3x1x50 500 2240 1120 900 1120 1880


2 AL/XLPE/CWS/PE-13.2kV-1x500 500 1850 1000 900 1120 2000
3 AL/XLPE/CWS/PE-13.2kV-1x400 500 1800 900 900 1120 1760