Specifications for
FK1230™ (FK-5-1-12) Fire
Suppression System
(25 bar/42 bar UL Listed
System Used with Seamless
Cylinder)
Cryptzo Fire Suppression Systems shall be designed for the following classes of fire:
• Class A: Surface Type Fires—wood or other cellulose-type material
• Class B: Flammable liquids
• Class C: Energized electrical equipment
For hazards beyond the scope described above, the designer shall consult with OEM and
NFPA 2001.
a) The name of the manufacturer shall appear on all major components
b) All equipment shall be UL Listed Any other system with VdS/LPCB system shall
not be qualified for this Tender.
c) All device, components and equipment shall be the products of the same manufacturer,
or supplied by the same manufacturer.
d) All devices, components and equipment shall be new, standard products of the
manufacturer’s latest design and suitable to perform the functions intended.
1.1.4. CODES AND COMPLIANCE
1. The design, installation, testing and maintenance of the Cryptzo Fire Suppression Systems,
employing FK 1230™ (FK-5-1-12), shall be in accordance with the following codes,
standards and regulatory bodies:
a) NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems.
b) UL 2166: Standard for Halocarbon Clean Agent Extinguishing System Units
2. The manufacturer shall meet ISO 9001 requirements for the design, production and
distribution of the engineered fire suppression system.
3. All components of the total flooding suppression system shall be the products of the same
manufacturer or listed by that manufacturer as compatible with those devices, components
and equipment.
1.1.5. SYSTEM DESIGN CRITERIA
The designer shall consider and address possible Fire hazards within the protected volume at
the bid stage. The delivery of the FK 1230™ (FK-5-1-12) system shall provide for the highest
degree of protection and minimum extinguishing time. The design shall be as per NFPA 2001.
Sub floor and the ceiling void to be included in the protected volume.
The FK 1230™ System to be supplied by the bidder must satisfy the requirement of the
Authority having Jurisdiction over the location of the protected area and must be in accordance
with OEM’s product design criteria.
The discharge time required to achieve 95% of the minimum design concentration for flame
extinguishment shall not exceed ten (10) seconds. In accordance with NFPA Standard 2001.
Welded cylinders for agent storage will not be acceptable- nor shall such Seamless cylinders
that do not have the approval of Chief Controller of Explosives, Nagpur.
Offer Cylinder shall be seamless type, manufactured and tested in accordance with IS 7285
Standard and approved by PESO for their use.
A total flooding, clean agent fire suppression system, filled with FK 1230™, shall be installed
to meet a minimum design concentration of 4.5 % for Class C Fire.
1.1.6. Application. This specification outlines the requirements for an automatic fixed
fire suppression system using FK 1230™ as the suppression agent. The hazard(s)
to be protected are:
1.1.7. SUBMITTALS OF
1.1.8. Engineered Design Drawings
The OEM-authorized Distributor or OEM shall provide all required installation drawings per
NFPA 2001.
1.1.9. Flow Calculation Reports
The system flow calculations shall be carried out on certified software, suitable for the
particular seamless cylinder container being offered for this project. Such System flow
calculations carried out for this project shall be further vetted by the OEM for its accuracy, and
the only such vetted calculations shall be admissible for approval by the Consultant.
1.1.10. Installation Drawings
Four (4) sets of installation drawings for each installed engineered suppression system and one
(1) set of the calculation report, owner’s manual and product data sheets shall be submitted to
the end-user/owner.
Upon completion of installation and commissioning acceptance, three (3) sets of “As-
Built” installation drawings and One (1) set of the calculation report for each installed
engineered suppression system shall be given to the owner/end-user for use and reference.