Professional Documents
Culture Documents
20 Mva GTP
20 Mva GTP
xii Details of clamp plate [Material, thickness, MS Plate, 20 mm thk with 3mm PB
Insulation]
xiii Total core weight [kg] 15956
Core loss basing on core loss graph at operating
xiv Flux density [rated voltage and rated Frequency] DDE
[kw]
xv Core stacking factor 0.97
xvi Net core area Sq. m. DDE
xvii Margin towards corner joints, cross fluxing etc DDE
[kw]
PCB,paper/cla
(i) Type & class PCB,paper/classA PCB,paper/classA
ss A
(ii) Grade or Un Graded Graded un graded Graded
j Insulating material used for
i H.V. & Regulating winding. PCB/PB/Paper
ii L.V Winding PCB/PB/Paper
iii For core bolts washers and end plates. FG tube/PW
iv Tapping connection.
k Insulating material used between
i H.V. and L.V. winding PCB/PB/Paper
ii H.V. and Regulating winding. PCB/PB/Paper
iii Core and L.V.winding PCB/PB/Paper
iv HV to HV winding (between phases) PCB
l Type of axial coil supports.
i H.V. winding PCB
ii Regulating winding PCB
iii LV winding. PCB
m Type of radial coil supports
i HV winding PCB
ii Regulating winding PCB
iii LV winding PCB
HV LV Regulating
Maximum allowable torque on coil clamping
n
bolts
o Bare conductor size (mm). DDE DDE DDE DDE
p Insulated conductor size (mm). DDE DDE DDE DDE
q No. of conductors in parallel (Nos.). DDE DDE DDE DDE
r No. of turns/phase DDE DDE DDE DDE
s No. of discs/phase DDE DDE DDE DDE
t No. of turns/disc DDE DDE DDE DDE
u Gap between discs. (mm). DDE DDE DDE DDE
v Inside diameter (mm). DDE DDE DDE DDE
w Outside diameter (mm). DDE DDE DDE DDE
x Axial height after shrinkage (mm). DDE DDE DDE DDE
y D.C.RESISTANCE
i L.V winding at 75 ° C (Ohms). DDE
ii HV winding at 75° C (Ohms). DDE
HV winding and Regulating winding at normal
iii DDE
tap at 75° C (Ohms).
HV winding and regulating winding at highest
iv DDE
tap.750C (Ohms).
38 CONSERVATOR
a Total volume [Liters] 1375
b Volume between the highest and lowest visible 1220
Oil levels [Litres]
c Power required by heaters [If provided][KW] NA
d Conservator sheet thickness (mm.) 3
39 OIL QUALITY
a Governing standard IEC 296
b Density in gms/cu-cm 0.89 g/cu.cm.
c Kinematics viscosity in CST 27Cst.
d Inter facial tension at 27°C in N/m 0.04 N/m
e Flash point in °C 140 deg.C
f Pour point in °C -6 deg.C
g Acidity [neutralization value] in mg of KOH/gm 0.03 mg KOH/g
h Corrosive sulfur in % Non-corrosive
i Electric strength [Breakdown voltage]
i As received [KV-rms.] 30 KV (rms) if the above value is not attained, the oil shall be filtered)
ii After treatment [KV-rms.] 60 KV (rms)
j Dielectric dissipation factor [Tan-delta] at 90°C 0.002
k Saponification value in mg of KOH/gm 0.05 mg KOH/gm (max.)
l Water content in ppm 50(Max.)
m Specific resistance
i At 90°C [ohm-cm] 35 x 10¹² Ohm-cm.
ii At 27 °C [ohm-cm] 1500 x 10¹² Ohm-cm.
n N- dm analysis CA%
CM% -
CP% -
o Oxidation stability 0.10% by- weight.
i Neutralization value after oxidation
ii Total sludge after oxidation 0.05% (max.)
p Characteristic of oil after ageing test as per
ASTMD-1934
i Specific resistance at 27°C [ohm-cms] 2.5 x (10)¹² Ohm-cm.
90°C [ohm-cms] 0.2 x (10)¹² Ohm-cm.
ii Tan delta 0.2 (max.).
iii Sludge content 0.05% (max.)
iv Neutralization number 0.4 mg KOH/g.
v Percentage of Napthenic content More than 40%
vi Percentage of paraffinic content Less than 56%
vii Details of oil preserving equipment offered COPS
40 RADIATORS
a Overall dimensions lxbxh [mm] DDE
b Total weight with oil [Kg.] DDE
c Total weight without oil [Kg.] DDE
d Thickness of radiator tube [mm] 1
e Types of mounting tank mounted
f Vacuum withstand capability 1 torr
g Total radiating surface in sq.m 205
h Type and make of material used for the radiators GLI/Tarang ,CRCA
a Make Easun-MR
b Type intank
c Power flow [Uni.-directional/bi - Bi-directional
directional/restricted bi-directional]
d Rated voltage to earth [KV] 72.5
e Rated current [Amps.] 350A
f Step voltage [volts] 1650/952.62
g Number of steps 16
h Control - manual/local-electrical/remote- Shall be provided
electrical
i Voltage control [Automatic/Non -automatic] Shall be provided
j Line drop compensation provided/not provided Shall be provided
k Parallel operation Shall be provided
l protective devices Shall be provided
m Auxiliary supply details 110 V
n Time for complete tap change [one step][Sec.] 3-4 sec
b. Grade, Trade Name and Thickness of the core CRGO HI B Grade; As per Vendor List ; 0.27 mm thickness
material, to be imported
Name of the core-cutting vendor and whether
the said vendor has got In-House CNC Machine
c. Yes; Names as per Vendor List attached
facility for cutting of core materials and whether
the said vendor has been accredited by ISO