ODISHA POWER TRANSMISSION CORPORATION LIMITED

GUARANTEED TECHNICAL PARTICULARS


Tender Notice No.
Tender Specification No.
NAME OF THE WORK
NAME OF THE BIDDER CG POWER AND INDUSTRIAL SOLUTIONS LTD
2 Installation [indoor/outdoor] Outdoor
3 Reference standards IS-2026
4 Continuous Ratings IS-6600
a Type of cooling ONAN/ONAF
b Rating [MVA]
i With ONAN cooling 16000
ii With ONAF cooling 20000
c Rated voltage
i HV [KV rms.] 132
ii LV [KV rms.] 33
d Highest system voltage
i HV [KV rms.] 145
ii LIV [KV rms.] 36
e Rated frequency with ±% variation 5%
f Number of phases Three

g Current at rated full load and on Principal tap


i HV [Amps] 69.98 / 87.48 A
ii LV [Amps] 279.93 / 349.91 A
5 Connection
i HV Star
ii LV Star
6 Connection symbol and vector group YNyno
7 Temparature Rise

a Temperature rise of oil above ambient


temperature

i At full ONAN rating [°C] 40


ii At full ONAF rating [°C] 40
Temperature rise of windings above ambient
b temperature [By resistance method]
i At full ONAN rating [°C] 45
ii At full ONAF rating [°C] 45
c Hot Spot Temperature rise of windings abvoe
ambient temperature
i At full ONAN rating [°C] 91.8°C over an yearly weighted average ambient temp. of 32°C with resistance method
ii At full ONAF rating [°C] 91.8°C over an yearly weighted average ambient temp. of 32°C with resistance method
d Temperature gradients between windings & oil. 18 Deg C

Limit of Hot spot temperature for which the


e 98°C over an yearly weighted average ambient temp. of 32°C
Transformer is designed [°C]
Period of operation of transformer at full load
f without calculated winding hot spot
Temperature exceeding 140°C and with
i 50% Coolers 10 minute
ii 100% Coolers 20 minute
8 Type of ON load tap changing switch On load tap changer / Intank
9 Tapping on windings for
i Constant flux/variable flux/combined CFVV
Regulation.
ii Tapping provided at HV winding
iii Number of steps 16
Range of tapping for variation [+ percent to-
iv +5% to -15% in step of 1.25%
Percent]
No load loss at rated voltage and frequency at
10 i 11.0 KW max
Principal tap [KW]
No load loss at the voltage corresponding to
ii 11.0 KW max
Highest tap [KW]
Load loss at rated output, rated frequency,
11 corrected for 75 °C winding temperature at: - ONAN ONAF
(Copper loss + cooler loss)

i Principal tap [In KW] DDE 60+1 KW max


ii Highest tap [In KW] DDE 59+1 KW max
iii Lowest tap [In KW] DDE 64+1 KW max
Auxiliary losses at rated output, normal ratio,
12 rated voltage, rated frequency and ambient 1 KW max
Temperature [KW]

13 Total losses at normal ratio inclusive of auxiliary 72.0 KW max


equipment losses [KW]
Positive sequence impedance on rated MVA
14 base at rated current and frequency at 75°C
Winding temperature at
i Principal tap [%] 10 % with no negative tolerance
ii Highest tap [%] 10.3 % approx
iii Lowest tap [%] 9.6 % approx
Zero sequence impedance at reference
15 80 to 90 % of positive sequence Impedance
Temperature of 75°C at principal tap [%]
% reactance at rated MVA base at rated Current
16
and rated frequency at
i Principal tap [%] 9.995%
ii Highest tap [%] 10.295%
iii Lowest tap [%] 9.594%
17 % resistance at rated MVA base at rated current
and rated frequency at
i Principal tap [%] 0.32%
ii Highest tap [%] 0.32%
iii Lowest tap [%] 0.34%
18 % Impedance at rated MVA base at rated
Current and rated frequency at
i Principal tap [%] 10 % with no negative tolerance
ii Highest tap [%] 10.3 % approx
iii Lowest tap [%] 9.6 % approx
Polarisation index i.e. ratio of Megger values at
19 a. 600 secs to 60 secs, (H.V. to E, L.V. to E, H.V. to >= 1.5 & <= 5
L.V.
Regulation at full load and 75°C winding
b. Temperature expressed as a percentage of
normal voltage
i At unity power factor [%] 0.7990%
ii At 0.8 power factor [lagging][%] 6.5420%
20 Efficiency at 75°C winding temperature derived Unity power factor 0.8 Power factor
from guaranteed loss figures at
a At full load [%] 99.64 99.56
b At ¾ load [%] 99.70 99.62
c At ½ load [%] 99.74 99.67
21i. Maximum efficiency [%] 99.74%
ii Load at which maximum efficiency occurs[% of 42.81%
full load]

Time in minutes for which the transformer can


22 be run at full load without exceeding the
maximum permissible temperature at reference
ambient temperature when supply to: -

i Fans are cut off 10 minute


ii Fans & Pumps is cut off NA
23 Short time thermal rating of
i HV winding in KA and duration in seconds 31.5KA for 5 sec
ii LV winding in KA and duration in seconds 25KA for 5 sec
24 Permissible over loading: -
a HV winding As per IS 6600
b LV winding As per IS 6600
25 Terminal arrangement
a High voltage [HV] Bare Bushing
b Low voltage (LV) Bare Bushing
c Neutral Bare Bushing
26 Insulating and cooling medium Minerial oil as per IEC 296
27 [A] Test voltage HV LV
i. Lightning impulse withstand test voltage [KVP] 650 170

Power frequency withstand test voltage [dry and


ii 275 70
wet][for 1 minute] [KV-rms.]
28 Partial discharge level as per IEC / ISS As per relevant up-to-date IEC

Noise level when energized at normal voltage,


29 frequency without load and with all cooling fans, As per latest NEMA Std. Tr-1.
oil pumps in running condition.

External short circuit withstand capacity [MVA]


30 as per IS-2026
and duration [seconds]
Over-fluxing withstand capability of the
31 110% continuous, 125% for 1,min, 140% for 5 sec & 170% for 2 sec.
Transformer
32 DETAILS OF CORE
a. Type of core construction Core type (boltless)
b Type of corner joints of the core steplap joint
c. Maximum flux density at
Rated voltage [132/33 KV] & rated frequency 50
i 1.41 wb/m^2
Hz][in Tesla]

Highest system voltage [145/36 KV] and lowest


ii 1.6 wb/m^2
system frequency [48.5Hz.][In Tesla]

No load current, no load loss and no load power No load No load


d factor at normal ratio and frequency No load power factor
[Amp/KW/p.f.] current(Amp) loss(KW)

i 10 percent of rated voltage


ii 25 percent of rated voltage
iii 50 percent of rated voltage
iv 85 percent of rated voltage
v 100 percent of rated voltage
vi 105percent of rated voltage
vii 110 percent of rated voltage
viii 112.5 percent of rated voltage
ix 115 percent of rated voltage
x 120 percent of rated voltage
xi 121 percent of rated voltage
xii 125 percent of rated voltage
e Core laminations:-
i Material of core lamination [HIB/Laser grade] CRGO HIB
ii Grade of core laminations HIB Grade
iii Thickness of core lamination [mm] 0.27 mm or Less
iv Specific loss [watt/Kg.] at rated voltage and DDE
rated frequency

v Specific loss [watt/Kg.] at highest system voltage DDE


and lowest system frequency

vi Whether specific core loss graph [flux density vs. DDE


watt/Kg.submitted

vii VA/Kg at rated voltage and rated frequency DDE

viii VA/Kg. at highest system voltage and lowest DDE


system frequency

ix Whether VA/Kg. Vs. flux density graph DDE


submitted.
x Insulation of core laminations Carlite
f CORE ASSEMBLY:-
i Core diameter [mm] DDE
ii Core window height [mm] DDE
iii Core leg centre [mm] DDE
iv Gross core cross-sectional area [m²] 0.1967

Whether details of core widths, stacks and


v Yes
Calculation furnished as per enclosed annexure

vi Distance between centres [mm] DDE


vii Total height of core [mm] DDE
viii
1) Details of core belting. FG taping / MS Belt
2) Material, grade & type. FG / MS
3) Width. 40 mm / 20 mm
4) Thickness. 2 mm
5) Fixing method. with screw bolt
ix Details of top end frame. plate frame
x Details of Bottom end frame. plate frame
xi Details of clamp plate [Material, thickness, MS Plate, 20 mm thk with 3mm PB
Insulation]

xii Details of clamp plate [Material, thickness, MS Plate, 20 mm thk with 3mm PB
Insulation]
xiii Total core weight [kg] 15956
Core loss basing on core loss graph at operating
xiv Flux density [rated voltage and rated Frequency] DDE
[kw]
xv Core stacking factor 0.97
xvi Net core area Sq. m. DDE
xvii Margin towards corner joints, cross fluxing etc DDE
[kw]

xviii Total core loss at rated voltage and rated 11


Frequency [xv+xviii] [kw]

xix Dielectric loss at rated voltage and rated -


Frequency [KW]

xx No load loss at rated voltage and rated 11


Frequency [xix+xx] [KW]
g Describe location/method of core grounding
h Details of oil ducts in core NA
Peak value of magnetising Inrush current (% of
i 1% of full load rated current
HV rated current).
33 DETAILS OF WINDINGS HV LV Regulating
a Type of winding Disc Disc Disc
Electrolytic
b Material of the winding conductor. Electrolytic copper Electrolytic copper
copper

c Maximum current density of windings [At rated HV LV Regulating


current] [normal tap] and Conductor area

i Current density(A/cm2) 2.8 A/ mm² 2.8 A/ mm² 2.8 A/ mm²


ii DDE DDE DDE
Cond.Area(Cm2)
d Whether HV windings are interleaved. Partial interleaved
e Whether windings are pre-shrunk? yes
Whether adjustable coil clamps are provided for
f Yes
H.V.and L.V. windings?
Whether steel rings are used for the windings? If
g Permawood ring will be used in place of MS ring
so, whether these are split?
Whether electrostatic shields are provided to
h obtain uniform voltage distribution in the yes
Windings?
Winding Insulation (Type & class Grade or Un
i Graded) HV LV Regulating

PCB,paper/cla
(i) Type & class PCB,paper/classA PCB,paper/classA
ss A
(ii) Grade or Un Graded Graded un graded Graded
j Insulating material used for
i H.V. & Regulating winding. PCB/PB/Paper
ii L.V Winding PCB/PB/Paper
iii For core bolts washers and end plates. FG tube/PW
iv Tapping connection.
k Insulating material used between
i H.V. and L.V. winding PCB/PB/Paper
ii H.V. and Regulating winding. PCB/PB/Paper
iii Core and L.V.winding PCB/PB/Paper
iv HV to HV winding (between phases) PCB
l Type of axial coil supports.
i H.V. winding PCB
ii Regulating winding PCB
iii LV winding. PCB
m Type of radial coil supports
i HV winding PCB
ii Regulating winding PCB
iii LV winding PCB
HV LV Regulating
Maximum allowable torque on coil clamping
n
bolts
o Bare conductor size (mm). DDE DDE DDE DDE
p Insulated conductor size (mm). DDE DDE DDE DDE
q No. of conductors in parallel (Nos.). DDE DDE DDE DDE
r No. of turns/phase DDE DDE DDE DDE
s No. of discs/phase DDE DDE DDE DDE
t No. of turns/disc DDE DDE DDE DDE
u Gap between discs. (mm). DDE DDE DDE DDE
v Inside diameter (mm). DDE DDE DDE DDE
w Outside diameter (mm). DDE DDE DDE DDE
x Axial height after shrinkage (mm). DDE DDE DDE DDE
y D.C.RESISTANCE
i L.V winding at 75 ° C (Ohms). DDE
ii HV winding at 75° C (Ohms). DDE
HV winding and Regulating winding at normal
iii DDE
tap at 75° C (Ohms).
HV winding and regulating winding at highest
iv DDE
tap.750C (Ohms).

v HV winding and regulating winding at lowest DDE


tap. (Ohms).

vi Total I²R losses at 75 ° C. for normal tap. (KW). DDE

vii Total I²R losses at 75 ° C. for highest tap. (KW) DDE


viii Total I²R losses at 75 ° C for lowest tap.(KW). DDE
ix Stray losses including eddy current losses in
winding at 75°C (KW).
a Normal tap position DDE
b Highest tap position DDE
c Lowest tap position. DDE
Any special measures taken to reduce eddy
d current losses and stray losses, mention in No
details.
z Load losses at 75°C [I²R + stray].
a Normal tap position [KW]. 60
b Highest tap position [KW]. DDE
c Lowest tap position [KW]. DDE
Details of special arrangement provided to
aa improve surge voltage distribution in the Static End Ring
Windings

bb Maximum Tan delta(power factor) of Windings Can be measured during testing


at 20oC.
34 BUSHINGS. HV LV HV Neutral LV Neutral
a Make and type CGL CJI/Jaipur CJI/Jaipur CJI/Jaipur glass
glass glass
i Rated voltage class [KV-rms.] 145 36 52 36
ii Rated current [Amps.] 1250 1000 1000 1000
b. Lightning Impulse withstand test voltage [1.2/50 650 170 250 170
microsecond][KVP]
c Switching surge withstand test voltage [KVP] NA NA NA NA
d Power frequency withstand test voltage - - - -

i Wet for 1 minute [KV-rms] 275 70 95 70

ii Dry for 1 minute [KV-rms] 275 70 95 70

e. Power frequency visible corona discharge 275 - - -


Voltage [KV-rms.]
f Partial discharge level [PC]
g Minimum creepage distance in mm 3625 900 1300 900
h Minimum creepage distance in mm [protected] 1812.5 450 650 450
i Whether test-tap is provided? Yes no no no
j Quantity and grade of oil in bushing and IEC Oil and 11.3 Kg NA NA NA
Specification of oil used [Kg.] oil
k Weight of assembled bushing [Kg.] 135 Kg 30 Kg 40 Kg 30 Kg
l Minimum clearance height for removal of 2700 1100 1200 1100
Bushing [mm]
Under oil flashover or puncture impulse voltage - - - -
m [KVP]

n. Under oil flashover or puncture power - - - -


frequency Voltage (KV-rms).
Phase to earth clearance in air of live parts at 1230 mm 320 mm 320 mm 320 mm
o. the top of bushings.
p. Maximum tan delta value at 20 deg. C
35 Minimum clearance [mm] Between Winding Phase to ground
(A) Out of Oil
(i) HV DDE DDE
(ii) LV DDE DDE
(B) In Oil
(i) LV to Core DDE DDE
(ii) LV to top yoke DDE DDE
(iii) LV to bottom yoke DDE DDE
(iv) LV to HV (radially) DDE DDE
(v) HV to Regulating (radially) DDE DDE
(vi) HV to top yoke DDE DDE
(vii) HV to bottom yoke DDE DDE
(viii) Regulating to top yoke DDE DDE
(ix) Regulating to bottom yoke DDE DDE
(x) Reg winding to Reg winding DDE DDE
(xi) Regulating winding to Tank. DDE DDE
a] Length wise DDE DDE
b] Breadth wise DDE DDE
c] Width wise DDE DDE
N.B:Winding Arrangement -CORE-LV-HV-REGULATING
36 Weight [Tolerance + 5%] [Approximate value is
not allowed]
a Core [Kg.] 15956
b Core with clamping [Kg.] 17250
c H.V. winding insulated conductor [Kg.] 4715
d L.V. winding insulated conductor [kg.] 3790
e Regulating winding insulated conductor [Kg.] 1325
f. Coils with insulation [Kgs,] 11305
g Core and winding [Kg.] 28175
h. Oil required for first filling [Liter/Kg] 16950 lits / 14747 Kg
i Tank and fittings with accessories [Kg.] 12180
j Untanking weight [Kg.] 28650
k Total weight with oil and fittings 55102
37 DETAILS OF TANK
a Material for Transformer tank Mild Steel
b Type of tank Convertional
c Thickness of sheet [No approximate value to be
mentioned]
i Sides [mm] 8
ii Bottom [mm] 10
iii Cover [mm] 12
iv Radiators [mm] 1
v Conservator 3
d Inside dimensions of main tank [No
approximation in dimensions to be used]
i Length [mm] Top = 4530 & btm = 3580
ii Breadth [mm] 1500
iii Height [mm] 3020 / 2230
e Outside dimensions of main tank [No
approximation in dimensions to be used]
i Length [mm] Top = 4546 & btm = 3596
ii Breadth [mm] 1516
iii Height [mm] 3030 / 2240
f. Thickness of spray galvanisation of tank bottom. 100 micron min.

Vacuum recommended for hot oil circulation As per CBIP


g. [torr]

h. Vacuum to be maintained during oil filling in As per CBIP


Transformer tank [torr]

i. Vacuum to which the tank can be subjected As per CBIP


without distortion (tor)
j. No. of bi-directional wheels provided four
k. Track gauge required for the wheels
i Transverse axis 1676 mm Rail Gauge
ii Longitudinal axis 1676 mm Rail Gauge

l Type and make of pressure relief device and Sukrut/Yogya,7 PSI


minimum pressure at which it operates [Kpa]

38 CONSERVATOR
a Total volume [Liters] 1375
b Volume between the highest and lowest visible 1220
Oil levels [Litres]
c Power required by heaters [If provided][KW] NA
d Conservator sheet thickness (mm.) 3
39 OIL QUALITY
a Governing standard IEC 296
b Density in gms/cu-cm 0.89 g/cu.cm.
c Kinematics viscosity in CST 27Cst.
d Inter facial tension at 27°C in N/m 0.04 N/m
e Flash point in °C 140 deg.C
f Pour point in °C -6 deg.C
g Acidity [neutralization value] in mg of KOH/gm 0.03 mg KOH/g
h Corrosive sulfur in % Non-corrosive
i Electric strength [Breakdown voltage]
i As received [KV-rms.] 30 KV (rms) if the above value is not attained, the oil shall be filtered)
ii After treatment [KV-rms.] 60 KV (rms)
j Dielectric dissipation factor [Tan-delta] at 90°C 0.002
k Saponification value in mg of KOH/gm 0.05 mg KOH/gm (max.)
l Water content in ppm 50(Max.)
m Specific resistance
i At 90°C [ohm-cm] 35 x 10¹² Ohm-cm.
ii At 27 °C [ohm-cm] 1500 x 10¹² Ohm-cm.
n N- dm analysis CA%
CM% -
CP% -
o Oxidation stability 0.10% by- weight.
i Neutralization value after oxidation
ii Total sludge after oxidation 0.05% (max.)
p Characteristic of oil after ageing test as per
ASTMD-1934
i Specific resistance at 27°C [ohm-cms] 2.5 x (10)¹² Ohm-cm.
90°C [ohm-cms] 0.2 x (10)¹² Ohm-cm.
ii Tan delta 0.2 (max.).
iii Sludge content 0.05% (max.)
iv Neutralization number 0.4 mg KOH/g.
v Percentage of Napthenic content More than 40%
vi Percentage of paraffinic content Less than 56%
vii Details of oil preserving equipment offered COPS
40 RADIATORS
a Overall dimensions lxbxh [mm] DDE
b Total weight with oil [Kg.] DDE
c Total weight without oil [Kg.] DDE
d Thickness of radiator tube [mm] 1
e Types of mounting tank mounted
f Vacuum withstand capability 1 torr
g Total radiating surface in sq.m 205
h Type and make of material used for the radiators GLI/Tarang ,CRCA

Total number of radiators/Banks for


i DDE
Transformer and dimensions of tubes.

j Thickness of hot dip galvanization of radiators. 80 micron


41 COOLING EQUIPMENT
a Make and type Marathon (make),exhaust typ
b No. of connected units 4
c No. of stand -by units 2
d Rated power input 0.5 kW
e Capacity [cu-m/min. or] [liters/min] 175
f Rated voltage [volts] 415V AC
g Locked rotor current [Amps.] 1
h Efficiency of motor at full load [%] 74%
i Temperature rise of motor at full load [°C] -
j BHP of driven equipment -
k Temperature range over which control is -40 deg C to 50 deg C
adjustable [°C]

Whether the fans are suitable for continuous yes


l operation at 85 % of their rated Voltage.

m Estimated time constant in hours for


i Natural cooling 4 to 6 hours
ii Forced air cooling 4 to 6 hours
42 GAS AND OIL OPERATED RELAY
a Make Atvus/yogya
b Type Flote type
c Size 3"
d Whether supervisory alarm and trip contacts one ararm & one trip contact
provided and their sizes and Nos.
43 [I] TEMPERATURE INDICATORS Oil Temp. Indicator Winding Temp. Indicator
a Make and type Precimeasur Precimeasure
b Permissible setting ranges for alarm and trip 85 to 90 95 to 100
c Number of contacts 4 4
d Current rating of each contact 2 2
e Whether supervisory alarm contacts provided? no no
f Size [lxbxd]
g Nos. 2 2
h Ratio and type of CT used for winding 350/2A,CL-5,7.5VA & 103/2A,CL-
Temperature indicators. 5,7.5VA

OPTIC FIBER TEMPERATURE SYSTEM


[II]

MAKE & TYPE NOT IN CG SCOPE


a.
Whether the offered Optic Fiber Temperature
System fulfills the stipulations for the same as NOT IN CG SCOPE
b. per this Specification
Whether the end-user’s certificate for offered
Optic Fiber Temperature System, from Indian NOT IN CG SCOPE
c. Utilities furnished
Whether, the Bidder has got past experience of
supply of Transformers with Optic Fiber NOT IN CG SCOPE
d. Temperature System [YES/NO]

If ‘YES’, please state the No. of such


Transformers, supplied along with the name(s)
of Organisation(s), to whom supplied with Make NOT IN CG SCOPE
e.
of the Optic Fiber Temperature System, supplied
and performance of the same.

APPROXIMATE OVERALL DIMENSIONS OF


44 TRANSFORMER INCLUDING COOLING SYSTEM,
TAP CHANGING GEAR ETC.
a Length [mm] 6600
b Breadth [mm] 4300
c Height [mm] 5700
Minimum clearance height for lifting core and
45 a 200
Winding from tank [mm]
Minimum clearance height for lifting tank cover
b 200
[mm]
46 SHIPPING DETAILS
a Approximate weight of heaviest package [Kg.] 32500

b Approximate dimensions of largest Package [Kg.] 5200 * 2400 * 4200 mm

47 Transformers will be transported with oil/gas. N2 Filled


48 Size of rail recommended for the track. 1676 mm
49 Details of Current Transformers NCT Bushing CT
a Quantity 1 Not applicable
b Type and voltage class Outdoor type; 36 kV Not applicable
c No. of cores one Not applicable
d Ratio Details required from OPTCL Not applicable
e VA burden NA Not applicable
f Accuracy class PS Not applicable
g Minimum knee point voltage [volts] 600 V Not applicable
h Maximum magnetization current at minimum 25 mA Not applicable
Knee point voltage [mA]

i Maximum secondary winding resistance at 75°C 5 Not applicable


[ohms]
50 MARSHALLING KIOSK
a Make and type Chandra Electrical
b Details of apparatus proposed to be housed in shall be provided
the Kiosk

51 Details of anti-earthquake device provided, if Yes


any
52 Separate conservator and Buchholz relay No
provided
53 TAP CHANGING EQUIPMENT

[These details refer to the basic rating of O.L.


T.C. as guaranteed by OLTC manufacturers]

a Make Easun-MR
b Type intank
c Power flow [Uni.-directional/bi - Bi-directional
directional/restricted bi-directional]
d Rated voltage to earth [KV] 72.5
e Rated current [Amps.] 350A
f Step voltage [volts] 1650/952.62
g Number of steps 16
h Control - manual/local-electrical/remote- Shall be provided
electrical
i Voltage control [Automatic/Non -automatic] Shall be provided
j Line drop compensation provided/not provided Shall be provided
k Parallel operation Shall be provided
l protective devices Shall be provided
m Auxiliary supply details 110 V
n Time for complete tap change [one step][Sec.] 3-4 sec

o Diverter selector switch transient time [cycles] -

p Value of maximum short circuit current [Amps] 5 KA for 3 sec

Maximum impulse withstand test voltage with


q 1.2/50 microseconds full wave between switch 350 KV
Assembly and ground [KVP]

Maximum power frequency test voltage


r 140 KV
between Switch assembly and earth [KV-rms]

Maximum impulse withstand test voltage with


s 1.2/50 microseconds across the tapping range 95 KV
[KVP]
Approximate overall dimensions of tap changer
t 1300 Ht & 395 dia
[WxBxD] in mm.
u Approximate overall weight [Kg.] 110
v Approximate mass of oil [Kg.] 70
Particulars of the OLTC control panel for
w -
installation in control room
54 DRIVING MECHANISM BOX
a Make and type KIRLOSKAR &3phase,415 V, 0.37kA
Details of apparatus proposed to be housed in
b the box Shall be provided

55 Types of terminal connectors and drawing No


a HV Stud type
b LV Stud type
56 Details of painting, galvanization conforms to yes
this Specification [Yes/No]
Type of oil level indicator and whether
57 Supervisory alarm contact for low oil level Magnetic oil level gauge with A/T contact
provided [Yes/No]
58 Type and size of thermostat to be used stem type: 175mm
59 No. of breathers provided [Nos.]
60 Type of dehydrating agent used for breathers 2
61 Valve sizes and numbers
a Drain valves- mm-Nos. 1 No - 50mm for Main tank, 1 No-25mm for conservator
b Filter valves- mm-Nos. 50mm, 2 Nos (1-Top & 1-Btm)
c Sampling valves- mm-Nos. 25mm, 2 Nos (1-Top & 1-Btm)
d Radiator valves- mm-Nos. 8 Nos-80mm plate valve (Cast iron )
e Other valves- mm-Nos. 1 No-50mm for Hydrain monitor, 1 No - 100mm for vacuum control,
2 No -25mm drain & filter valve for OLTC
62 a) Type and make of PRV. T6 & make:sukrut
b) No. of each type of devices per transformer 1
c) Min. pressure at which device operates. 7 PSI

Please enclose the list of accessories and fittings,


63 being provided on transformer. Please confirm, Enclosed
these are as stipulated in the tender.

Whether the transformer, covered is fully type


64 tested and if so, whether copies of type test No,Similar rating type test Enclosed
certificates, enclosed with the tender.

Whether tenderer can supply transformer,


wound on vertical coil winding machine.
65 Preference shall be given to the tenderer who yes
will ensure supply of transformer wound on
vertical winding machines.

In case Sl.No.65 is not confirmed, what are the


additional pre-cautions, which shall be taken by
the tenderer to justify that the coil, wound on
66 -
horizontal machine shall be equivalent in all
respects to that which are wound on vertical
winding machine.

What are the arrangements, available for


jointing the Winding. Preference shall be given
to the tenderer using high-frequency brazing
67 machines. In case other jointing techniques are yes,high frequency machine we are using
used; adequacy of the same is to be recorded.
Please note that bolted joints in the winding are
not acceptable. This should be confirmed here.

Please confirm that you will guarantee


68 maximum impedance variation between phases yes
within the limit of 2% only.
Please confirm that the transformer shall be
69(a) dried by vapour-phase drying method. Please Yes
specify level of dryness.

In case, other methods of drying are used, the


b)            level of dryness, so achieved should be identical NA
       to that by VPD. Adequacy of such system should
be justified.

Please confirm whether the In-House facilities


for all routine tests as per this Tender
70 Specification are available with the tenderer Yes
and the tenderer shall agree
to conduct these tests on the transformer in the
event of order.
Whether the Tenderer has got In-House core-
71 cutting facility for cutting core materials for the No
transformer ratings as offered. (YES/NO)

72 If ‘YES’, following informations/confirmations


are required: -

Name of the manufacturer of HIB Grade core


material from whom core materials will be
directly imported or through their accredited
marketing organization of repute. If to be
imported through the accredited Marketing
a. Organisation, please state the name of such NA
Marketing Organisation and please enclose the
relevant documents with the Tender Offer
regarding accreditation of the said Marketing
Organisation by the manufacturer of the HIB
core material.

Grade, Trade Name and Thickness of the core


b. NA
material, to be imported
Whether agreed for witnessing of core materials
c. Yes
by OPTCL’s representative(s)

Whether, the Bidder has past experience


towards direct import of core materials. If ‘YES’,
d. the copies of recent past Import documents to NA
be furnished with the Tender Offer (Please state,
whether the said import documents are
enclosed with the Tender Offer)

e. Whether, the Bidder has got In-House CNC NA


Machine facility for cutting of core materials

Whether the Bidder is agreed to follow the


procedures, as stipulated at Cl.No.5.4.8 (o), (p)
f. &(q) of this Technical Specification, as applicable NA
for those, who have got In-House core-cutting
facility

If the Bidder has no In-House core-cutting


73 facility, the following No In house Core cuting facility
informations/confirmations are required: -

Name of the manufacturer of HIB core materials


from whom core materials will be directly
imported or through their accredited marketing
organization of repute. If to be imported
through the accredited Marketing Organisation,
a. please state the name of such Marketing As per Vender List attached.
Organisation and please enclose the relevant
documents with the Tender Offer regarding
accreditation of the said Marketing Organisation
by the manufacturer of the HIB core
material.

b. Grade, Trade Name and Thickness of the core CRGO HI B Grade; As per Vendor List ; 0.27 mm thickness
material, to be imported
Name of the core-cutting vendor and whether
the said vendor has got In-House CNC Machine
c. Yes; Names as per Vendor List attached
facility for cutting of core materials and whether
the said vendor has been accredited by ISO

Whether, the Bidder has past experience


towards direct import of core materials. If ‘YES’,
d. the copies of recent past import documents to Yes
be furnished with the Tender Offer (Please state,
whether the said import documents are
enclosed with the Tender Offer)

Whether the Bidder is agreed to follow the


procedures, as stipulated at Cl.No.5.4.8 (o), (p) &
e. (q) (I) (2), (3), (4), (5), (6) & (7) of this Technical Yes
Specification, as applicable for those, who have
got no In-House core-cutting facility.

Please confirm that the facility for partial


discharge test is available with the tenderer and
74 the tenderer shall agree to conduct. This test on Yes
transformer in the event of order.