02 - Automatic Sprinkler System Design Calculations
02 - Automatic Sprinkler System Design Calculations
Height: Assuming floor to floor height to be 3m, Total height will be3metres
Water storage:
Based on the floor height requiring automatic sprinkler system, OH2-
15 meters has been selected according to the table.The sprinkler tank
design capacity is 105 cubic meters
Hydraulic calculation The size or sizes of the pipe work (including main distribution pipes and
of distribution pipe all risers) between the 16/18 sprinkler points at the extremities of
work systems at the highest level and the installation valves is to be
calculated hydraulically on the basis that with a rate flow of
1000lts/min the aggregate pressure loss due to friction must not
exceed 0.5bar.Reffered 0n table 4122.2 on page 68
Hydraulic for different design points in relation to the poiont from where installation valve is
Point B to instalation Pipe size (Nominal Length Loss of pressure mb/m length Loss
controll valve diameter)( mm) (m) of pipe with a flow of
1000ltrs/min
Selected pump
specifications
Water flow rate: 1000ltrs/min
16.67 ltrs/sec
0.01667m3/sec
Selected duty pump SPP EUROSTREAM (Electrical)
DISCHARGE & PERFORMANCE
32 mm to 100 mm
Outputs up to 360 m3 /h(0.1 cubic meters per sec)
Head up to 105m
Jockey pump GRUNDFOS CM3-4A, Head 20M, flow rate 2.5M3 /hr