STRUCTURAL ANALYSIS (1 Storey)
STRUCTURAL ANALYSIS (1 Storey)
FOR
Schedule of Loads
Slab = 9.6kPa
Floor finish = 2.20kPa
Ceiling loads = 0.24kPa
Others = 1.0kPa
Computations:
Design Loads
wu = 1.4DL + 1.7LL
= 1.4(13.04) + 1.7(2.40)
wu = 22.336kPa
4 @ 3m = 12m
8.376 20.1
20.10 18.27 18.27 18.27 20.1 8.376
0 0
14.36 12.56 12.56 14.36
f’c = 28
fy = 420
As = ρbd
= 0.00333(1000)(100)
As = 333 mm²
ρb = 0.85f’cβ1(600)
fy (fy + 600)
= 0.85(28)(0.85)(600)
420(420 + 600)
ρb = 0.02833
Use ρ = 0.50 ρb
ρ = 0.50 ρb
= 0.50(0.02833)
ρ = 0.014
Solving for the effective depth of slab:
Ru = f’cw [ 1 – 0.59w ]
= [28(0.21)] – [1 – 0.59(0.21)]
Ru = 5.15
d² = Mu
ØRub
= 20,100,000
0.90 (5.15) (1000)
d = 65.85mm
t = 65.85 + 40 + 5
t = 110.85mm say 110mm
Actual d:
d = 110 – 40 – 5
d = 65 mm
ρ = As
bd
= [ ¶ (10)²] [5]
____4____
(1000) (65)
ρ = 0.00604
THEREFORE: ρmin < ρ < ρmax = 0.00333 < 0.00604 < 0.02125 (SAFE!)
2. ISOLATED FOOTING
PDL = 133 kN
PLL = 36 kN
Moments:
MDL = 5 kN-m
MLL = 2 kN-m
Depth = 300 mm
qult = Pu ( 1 + 6e )
B² B
Factored Load:
Factored Moment:
qult = Pu ( 1 + 6e )
B² B
= 247.40 [ 1 + 6(0.04204)]
0.9m² 0.9
Max. qult = 391.03 kPa
Min. qult = 219.83 kPa
D = 300 mm
Vc = 1/6 √f’c
= 1/6 √21
Vc = 0.7638 MPa (ALLOWABLE)
y = 172
0.09 0.9
y = 17.20 kPa
Vu = 391(0.09)(0.9) – ½ (17.20)(0.09)(0.9)
Vu = 30.97 kPa
Vn = Vu = 30.97(1000)
Øbd 0.85(900)(300)
For Bending:
y = 172
0.39 0.9
y = 74.53 kPa
Mu = 391(0.09)(0.39/2) – ½ (74.53)(0.09)(0.39/2)
Mu = 25.062 kN-m
Mu = ØRub d²
25,062,000 = 0.90 Ru (900) (300)²
Ru = 0.3438
ρ = 0.85f’c [ 1 - 1 – 2Ru ]
fy √ 0.85 f’c
ρ = 0.85(21) [ 1 - 1 – 2(0.3438) ]
275 √ 0.85(21)
ρ = 0.00126
As = ρbd
= 0.00509(900)(300)
As = 1,374.54 mm²
Use 7 - 16 mm Ø RSB
THEREFORE: ρmin < ρ < ρmax = 0.00509 < 0.00521 < 0.02837 (SAFE!)
3. REINFORCED CONCRETE BEAM
Design Criteria
F’c = 21 MPa
Fy = 275 MPa
Loads:
Wslab = 2.40kPa
Wwall = 3.60kPa
Wceiling = 0.24kPa
Wbeam = 2.88kPa
Roof = 4.646kPa
At support:
MDL = 13.976 (0.3) = 4.14 kN-m
MLL = 0.38 (0.3) = 0.114 kN-m
MU = 1.4 (1.14) = 5.796 kN-m
FACTORED LOAD
ρ = 0.50 ρmax
= 0.50 (0.02837)
ρ = 0.01418
ρ = As
bd
0.01418 = As
120(300)
As = 510.66mm²
THEREFORE: ρmin < ρ < ρmax = 0.00509 < 0.0157 < 0.02837 (SAFE!)
4. COLUMN
Trial Design:
B = 120 mm
D = 300 mm
F’c = 21 MPa
Fy = 275 MPa
PD = 200 kN
PL = 45 kN
ρ = As
bd
= [ ¶ (12)²] [6]
____4____
(120) (300)
ρ = 0.01885
DL + LL = 200 kN + 45 kN = 245 kN
5. ROOF
Width = 6.20 m
Weight of wood = 2.30 kPa
Allowable Bending = 16.26 MPa
Allowable Shear = 1.10 Mpa
Load Analysis
a. DEADLOAD
Pn = 2Psinθ
1 + sin²θ
Where:
P = 0.003 (125)²
= 46.9 psf
P = 2.24 kPa
Combination of Loads:
DL + LL = 15.93 kN