SEISMIC LOAD ANALYSIS

(X-Direction)

Seismic Zone: Zone 2

Importance Factor: I = 1.0 for occupancy category

Soil Profile Type: Soft Soil (SF)

Seismic Zone Factor: z = 0.2

Seismic Source Type: C

Seismic Coefficient: CA = 0.34 ; Cv = 0.64

Structural System Factors: R = 5.5

Frame Material Factor: Ct = 0.0488

Base Shear Computation:

1. Fundamental Period of Vibration


3 3
T = Ct(h ) 4 = 0.0488(9.5 m) 4 = 0.26 Sec.
n

2. Total Design Base Shear

IWC v 0.64(1.0)(1931.04)
Vact = = = 864.24 KN
RT 5.5(0.26)
3. Total Design Base Shear needed not Exceeded

2.5 IWC a 2.5(0.34)(1.0)(1931.04)


Vmax = = = 298.43 KN
R 5.5
4. Total Desig Base Shear Needed not Exceed

Vmin = 0.11CAIW = 0.11(0.34)(1.0)(1931.04) = 72.22 KN

Vmin<Vact>Vmax Use Vmax = 298.43 KN

Vertical Distribution Of Forces:

Force at top due to whiplash

Ft = 0

T ≤ 0.7 sec

0.26 sec < 0.7 Sec


T ≤ 0.7sec

0.7 < T < 3.6

T ≥ 3.6

The remaining portion of the base shear shall be distributed by:

Wh
Ft = (V-Ft)
∑ wh
W = Dead Load @ Level I.

H = height in m above the base level I.

LEVEL W h Wh F
Roof Deck 476 9.5 4522 116.4
3rd Floor 659.36 6.5 4285.84 110.33
2nd Floor 795.68 3.5 2784.88 71.69
1st Floor 1931.04 0 0 0
SEISMIC LOAD ANALYSIS

(Y-Direction)

Seismic Zone: Zone 2

Importance Factor: I = 1.0 for occupancy category

Soil Profile Type: Soft Soil (SF)

Seismic Zone Factor: z = 0.2

Seismic Source Type: C

Seismic Coefficient: CA = 0.34 ; Cv = 0.64

Structural System Factors: R = 5.5

Frame Material Factor: Ct = 0.0488

Base Shear Computation:

1. Fundamental Period of Vibration


3 3
T = Ct(h ) 4 = 0.0488(9.5 m) 4 = 0.26 Sec.
n

2. Total Design Base Shear

IWC v 0.64(1.0)(1931.04)
Vact = = = 864.24 KN
RT 5.5(0.26)
3. Total Design Base Shear needed not Exceeded

2.5 IWC a 2.5(0.34)(1.0)(1931.04)


Vmax = = = 298.43 KN
R 5.5
4. Total Desig Base Shear Needed not Exceed

Vmin = 0.11CAIW = 0.11(0.34)(1.0)(1931.04) = 72.22 KN

Vmin<Vact>Vmax Use Vmax = 298.43 KN

Vertical Distribution Of Forces:

Force at top due to whiplash

Ft = 0

T ≤ 0.7 sec
0.26 sec < 0.7 Sec

T ≤ 0.7sec

0.7 < T < 3.6

T ≥ 3.6

The remaining portion of the base shear shall be distributed by:

Wh
Ft = (V-Ft)
∑ wh
W = Dead Load @ Level I.

H = height in m above the base level I.

LEVEL W h Wh F
Roof Deck 476 9.5 4522 116.4
3rd Floor 659.36 6.5 4285.84 110.33
2nd Floor 795.68 3.5 2784.88 71.69
1st Floor 1931.04 0 0 0