PMC-680i & 670 Catalogue (20200819S)
PMC-680i & 670 Catalogue (20200819S)
Fe a t u r e s S u m m a r y
electricity consumers at all levels due to the recent proliferation of
sensitive power electronic equipment and non-linear loads in industrial,
commercial and domestic applications, which cause them to be much
more sensitive to voltage dips and transients. At the same time, these
loads are highly harmonic and would potentially pollute the supply
networks, cause safety concerns, reduce supply reliability and above all
result in damages to capital-intensive appliances and significant
economic losses. Utilities have recently raised their alert levels and
started to invest heavily on power quality monitoring and reporting to
obtain the much needed information to validate compliance, improve
system stability as well as supply reliability. Further, the large-scale
deployment of renewable energy generation as well as high penetration
of solar inverters would cause additional PQ concerns and destabilize
public electricity supply networks.
PMC-680i & PMC-670 are advanced power International Front Panel & Built-in
quality monitoring products that have been certified for IEC Standards PMC-680i PMC-670 Web Interface
61000-4-30 Class A compliance and therefore can provide a
· IEC61000-4-30 Class A Certified DIN 192 (186x186 Cutout) DIN 144 (138x138 Cutout) · 5.7” Color LCD Display @ 640x480
complete picture of PQ Compliance Level at any critical points in a
· IEC61000-4-15 Flicker · EN50160 Report
power transmission or distribution network. This allows both the 4G/8G 2GB
· IEC61000-4-7 Harmonics · PQ Event with ITIC/SEMI F47 Plot
suppliers and the consumers to understand power quality related
· IEC62053-22 Class 0.2S Compliant Optional Split-Core CT
issues as well as make decisions quickly and effectively to address any · High-Resolution, WFR and DWR
· IEC61850 for Smart Grid (optional)
potential problems. CET’s PMC-680i & PMC-670 provide complete IEC · Real-time Waveform Capture
61000-4-30 compliance measurements, generate EN50160 reports · Harmonic & Interharmonic Histogram
and capture power quality events such as Dips, Swells, Transients and · Harmonic Power and Energy
Interruptions with High-Resolution Voltage and Current waveforms Industrial Grade · Phasor Diagrams
and extended duration.
Components · SOE & PQ Log
· I/O status
Typical Applications Extended Temperature Range
· Device configuration
Standard Tropicalization
· Diagnostics
Utility Extended Warranty
· PQ monitoring at HV, MV and LV Utility Substations
· Benchmarking for Supply Reliability and PQ performance
·
·
Identify the improvement areas on Power System
Fault location and PQ Event investigation Comm. & I/Os Time Synchronization
· Substation Automation · 2xRS-485 · Battery-backed Real-time clock @ 6ppm
· 2xEthernet Ports (PMC-680i) · Time Sync. via Modbus RTU protocol,
Industrial and Commercial 1xEthernet Port (PMC-670) SNTP and GPS @ 1PPS
· PQ monitoring at Mains and Critical feeders
· 8xDIs, 4xROs · Optional IRIG-B input
· Harmonic and Disturbance Monitoring
· 4xDOs (PMC-680i)
· EN50160 & IEC61000-4-30 Class A Compliance Verification
· Energy Efficiency improvement 2xDOs (PMC-670)
· Modbus RTU/TCP, HTTP, SNTP, SMTP
Advanced Power
Quality Features
Dips/Swells, Transients, Flickers &
Comprehensive Data Enhanced Monitoring, Harmonics Monitoring
Disturbance Waveform Recording (DWR)
Recording Alarming & Control and Waveform Recording (WFR) @ 512
· Statistical Data Recorders Samples/Cycle for Power Quality events
PQ Setpoints
· Real-time / HS Data Recorders Disturbance Direction Indicator (PMC-680i)
Control Setpoints COMTRADE Compatible
· Interval Energy Log
DI Setpoints EN50160 Compliance Reporting
· Max./Min. Log
· SOE Log Trigger DO/RO, SOE Log, Data Recording, PQDIF Support for PMC-680i
· PQ Log Waveform Recording or Alarm Email Optional 1024 Samples/Cycle for PMC-680i
Copyright © CET Inc. All rights reserved. Comprehensive and Reliable PQ Guard for Your Infrastructure
Cost Effective High Performance
Power Quality (PQ) is an important issue for many
Fe a t u r e s S u m m a r y
electricity consumers at all levels due to the recent proliferation of
sensitive power electronic equipment and non-linear loads in industrial,
commercial and domestic applications, which cause them to be much
more sensitive to voltage dips and transients. At the same time, these
loads are highly harmonic and would potentially pollute the supply
networks, cause safety concerns, reduce supply reliability and above all
result in damages to capital-intensive appliances and significant
economic losses. Utilities have recently raised their alert levels and
started to invest heavily on power quality monitoring and reporting to
obtain the much needed information to validate compliance, improve
system stability as well as supply reliability. Further, the large-scale
deployment of renewable energy generation as well as high penetration
of solar inverters would cause additional PQ concerns and destabilize
public electricity supply networks.
PMC-680i & PMC-670 are advanced power International Front Panel & Built-in
quality monitoring products that have been certified for IEC Standards PMC-680i PMC-670 Web Interface
61000-4-30 Class A compliance and therefore can provide a
· IEC61000-4-30 Class A Certified DIN 192 (186x186 Cutout) DIN 144 (138x138 Cutout) · 5.7” Color LCD Display @ 640x480
complete picture of PQ Compliance Level at any critical points in a
· IEC61000-4-15 Flicker · EN50160 Report
power transmission or distribution network. This allows both the 4G/8G 2GB
· IEC61000-4-7 Harmonics · PQ Event with ITIC/SEMI F47 Plot
suppliers and the consumers to understand power quality related
· IEC62053-22 Class 0.2S Compliant Optional Split-Core CT
issues as well as make decisions quickly and effectively to address any · High-Resolution, WFR and DWR
· IEC61850 for Smart Grid (optional)
potential problems. CET’s PMC-680i & PMC-670 provide complete IEC · Real-time Waveform Capture
61000-4-30 compliance measurements, generate EN50160 reports · Harmonic & Interharmonic Histogram
and capture power quality events such as Dips, Swells, Transients and · Harmonic Power and Energy
Interruptions with High-Resolution Voltage and Current waveforms Industrial Grade · Phasor Diagrams
and extended duration.
Components · SOE & PQ Log
· I/O status
Typical Applications Extended Temperature Range
· Device configuration
Standard Tropicalization
· Diagnostics
Utility Extended Warranty
· PQ monitoring at HV, MV and LV Utility Substations
· Benchmarking for Supply Reliability and PQ performance
·
·
Identify the improvement areas on Power System
Fault location and PQ Event investigation Comm. & I/Os Time Synchronization
· Substation Automation · 2xRS-485 · Battery-backed Real-time clock @ 6ppm
· 2xEthernet Ports (PMC-680i) · Time Sync. via Modbus RTU protocol,
Industrial and Commercial 1xEthernet Port (PMC-670) SNTP and GPS @ 1PPS
· PQ monitoring at Mains and Critical feeders
· 8xDIs, 4xROs · Optional IRIG-B input
· Harmonic and Disturbance Monitoring
· 4xDOs (PMC-680i)
· EN50160 & IEC61000-4-30 Class A Compliance Verification
· Energy Efficiency improvement 2xDOs (PMC-670)
· Modbus RTU/TCP, HTTP, SNTP, SMTP
Advanced Power
Quality Features
Dips/Swells, Transients, Flickers &
Comprehensive Data Enhanced Monitoring, Harmonics Monitoring
Disturbance Waveform Recording (DWR)
Recording Alarming & Control and Waveform Recording (WFR) @ 512
· Statistical Data Recorders Samples/Cycle for Power Quality events
PQ Setpoints
· Real-time / HS Data Recorders Disturbance Direction Indicator (PMC-680i)
Control Setpoints COMTRADE Compatible
· Interval Energy Log
DI Setpoints EN50160 Compliance Reporting
· Max./Min. Log
· SOE Log Trigger DO/RO, SOE Log, Data Recording, PQDIF Support for PMC-680i
· PQ Log Waveform Recording or Alarm Email Optional 1024 Samples/Cycle for PMC-680i
Copyright © CET Inc. All rights reserved. Comprehensive and Reliable PQ Guard for Your Infrastructure
PQ Monitoring Multifunction
Metering Data and Event Recorders
PMC-680i and PMC-670 perform basic measurements at 1-second Demands PMC-680i and PMC-670 offer 4GB and 2GB, respectively, of extended Max./Min. Recorder (MMR)
update rate and High-Speed measurements for event detection at ½ non-volatile memory for data and event recording. Data Recorders
cycle update rate. · Demand is defined as the average power consumption over a fixed interval Logging of Max./Min. values for Real-time measurements of U, I, kW,
support programmable Sources, Recording Intervals, Depths and
· Sliding Window Demands with programmable interval (1 to 60 minutes) kvar, kVA, PF, Freq., Unbalance, K-Factor, THD.
Offsets in FIFO or Stop-When-Full mode.
and No. of Demand Intervals
Basic Measurements (1-second update) · Optional Demand Synchronization through DI
Interval Energy Recorder (IER) PQ Log
· 3-phase U & I, Power, PF, U4, I4, (I5 for PMC-680i only) · PQ Demands for THD/TOHD/TEHD, etc.
· Frequency and Phase Angle · Max. Demands for This Month and Last Month Recording the time and characteristic data of the captured PQ events
· kWh, kvarh Import/Export and kVAh Total, Total Harmonic kWh, kvarh
· kWh, kvarh Import/Export/Net/Total and kVAh Total such as Transients, Dips/Swells, Interruptions, Rapid Voltage Changes
Import/Export
and all PQ related parameters with maximum 1024 FIFO entries
Multi-Tariff TOU Capability · Recording interval from 1 to 65,535 minutes
time-stamped to ±1ms resolution.
High-Speed Measurements (½ cycle update) · FIFO and Stop-When-Full mode
Two independent sets of TOU Schedules, each supporting
· 3-phase U & I, Power, PF, U4, I4, (I5 for PMC-680i only) · Up to 12 Seasons SOE Log
· High-Speed Frequency detection · 90 Holidays or Alternate Days and 3 Weekdays Real-Time and High-Speed (HS) Data Recorder
- 1 cycle for PMC-680i · 20 Daily Profiles, each with 12 Periods in 1-minute interval · Setup changes, System events, Setpoint events and I/O operations
· Recording interval
- 5 cycles for PMC-670 · 8 Tariffs, each providing the following information: · 1024 FIFO events time-stamped to ±1ms resolution
- 1s to 40 days for Real-time Data Recorder
- kWh/kvarh Import/Export and kVAh - ½ cycle to 60 cycles for HS Data Recorder
- kW/kvar Import/Export Maximum Demands · Max. Depth @ 65,535 Statistical Data Recorder (PMC-680i only)
- Register rollover at 100,000,000,000 kXh
Power Quality (PQ) Metering No. of Data Recorders PMC-680i PMC-670
· Recording of the Max., Min., Avg. and 95th percentile for Real-time
measurements including U, I, Freq., Flicker, Harmonics and Unbalances
8 16 in 16 different recorders of 64 parameters each
Both PMC-680i and PMC-670 comply with IEC61000-4-30 Class A, IEC61000-4-15, IEC61000-4-7 and EN50160, offering accurate harmonic Real-Time (32 Parameters/Recorder) (16 Parameters/Recorder) · Recording interval from 1 minute to 60 minutes
measurements up to the 63rd order and capable of capturing disturbance events such as Transients, Dips, Swells and Interruptions. In addition, the 4 4 · 30 days @ 1-minute, 300 days @ 10-minute, 450 days @ 15-minute
High-Speed (HS)
PMC-680i provides High-end fault recorder feature with its Disturbance Waveform Recorder (DWR), capable of capturing events that last over 300 (16 Parameters/Recorder) (16 Parameters/Recorder)
· On-board trending via Front Panel display
seconds in duration in varying resolutions. This feature likely gives the PMC-680i the highest Performance/Cost ratio of any panel-mount PQ · PQDIF file format, downloadable from the on-board FTP Server
Analyzers for the utility market today.
·
·
IEC61000-4-7 Compliance
U & I THD. TOHD, TEHD, Harmonics & Inter-Harmonics up to 63rd Setpoints
· Harmonic kW, kvar, kVA and PF from Fundamental to 63rd
· Total harmonic kWh, kvarh Import/Export/Net/Total PMC-680i and PMC-670 provide extensive control by allowing users to initiate an action in response to a specific condition from PQ events, Control
· Individual harmonic Total kWh, kvarh Import/Export/Net/Total parameters or Digital Input status. Typical applications include SOE or PQ Log reporting, Waveform and Data Recording as well as DO/RO Trigger-
ing for Alarm or Control Actions.
Rapid
Voltage Voltage Inputs and Outputs
Changes & Interruptions
Flickers Digital Inputs Digital Outputs
Dips and · Voltage Interruption Events
· Detection of quick RMS Voltage PMC-680i and PMC-670 are equipped with 8 self-excited Digital Inputs for
Swells if the residual voltage is less PMC-680i and PMC-670 come standard with Mechanical Relay Outputs
transitions between two steady
state conditions according to than the Interruption external status monitoring, Demand Synchronization or pulse counting (RO) for setpoint alarming and control as well as Solid State Digital
IEC61000-4-30 Threshold with programmable weight for collecting WAGES (Water, Air, Gas, Outputs (DO) for energy pulsing.
· Flicker measurements Electricity, Steam) information.
according to IEC61000-4-15 PMC-680i PMC-670
· Dips and Swells Detection @ · Internally wetted at 24 VDC with programmable debounce 2 Form A Mechanical Relays
RO 4 Form A Mechanical Relays
10ms (½ cycle at 50Hz) with 2 Form C Mechanical Relays
SOE and WFR/DWR @ 512
· 1,000Hz sampling
4 Solid State Digital Outputs 2 Solid State Digital Outputs
samples/cycle · Time Sync. via GPS's 1PPS output DO (Optically Isolated) (Optically Isolated)
Copyright © CET Inc. All rights reserved. Comprehensive and Reliable PQ Guard for Your Infrastructure
PQ Monitoring Multifunction
Metering Data and Event Recorders
PMC-680i and PMC-670 perform basic measurements at 1-second Demands PMC-680i and PMC-670 offer 4GB and 2GB, respectively, of extended Max./Min. Recorder (MMR)
update rate and High-Speed measurements for event detection at ½ non-volatile memory for data and event recording. Data Recorders
cycle update rate. · Demand is defined as the average power consumption over a fixed interval Logging of Max./Min. values for Real-time measurements of U, I, kW,
support programmable Sources, Recording Intervals, Depths and
· Sliding Window Demands with programmable interval (1 to 60 minutes) kvar, kVA, PF, Freq., Unbalance, K-Factor, THD.
Offsets in FIFO or Stop-When-Full mode.
and No. of Demand Intervals
Basic Measurements (1-second update) · Optional Demand Synchronization through DI
Interval Energy Recorder (IER) PQ Log
· 3-phase U & I, Power, PF, U4, I4, (I5 for PMC-680i only) · PQ Demands for THD/TOHD/TEHD, etc.
· Frequency and Phase Angle · Max. Demands for This Month and Last Month Recording the time and characteristic data of the captured PQ events
· kWh, kvarh Import/Export and kVAh Total, Total Harmonic kWh, kvarh
· kWh, kvarh Import/Export/Net/Total and kVAh Total such as Transients, Dips/Swells, Interruptions, Rapid Voltage Changes
Import/Export
and all PQ related parameters with maximum 1024 FIFO entries
Multi-Tariff TOU Capability · Recording interval from 1 to 65,535 minutes
time-stamped to ±1ms resolution.
High-Speed Measurements (½ cycle update) · FIFO and Stop-When-Full mode
Two independent sets of TOU Schedules, each supporting
· 3-phase U & I, Power, PF, U4, I4, (I5 for PMC-680i only) · Up to 12 Seasons SOE Log
· High-Speed Frequency detection · 90 Holidays or Alternate Days and 3 Weekdays Real-Time and High-Speed (HS) Data Recorder
- 1 cycle for PMC-680i · 20 Daily Profiles, each with 12 Periods in 1-minute interval · Setup changes, System events, Setpoint events and I/O operations
· Recording interval
- 5 cycles for PMC-670 · 8 Tariffs, each providing the following information: · 1024 FIFO events time-stamped to ±1ms resolution
- 1s to 40 days for Real-time Data Recorder
- kWh/kvarh Import/Export and kVAh - ½ cycle to 60 cycles for HS Data Recorder
- kW/kvar Import/Export Maximum Demands · Max. Depth @ 65,535 Statistical Data Recorder (PMC-680i only)
- Register rollover at 100,000,000,000 kXh
Power Quality (PQ) Metering No. of Data Recorders PMC-680i PMC-670
· Recording of the Max., Min., Avg. and 95th percentile for Real-time
measurements including U, I, Freq., Flicker, Harmonics and Unbalances
8 16 in 16 different recorders of 64 parameters each
Both PMC-680i and PMC-670 comply with IEC61000-4-30 Class A, IEC61000-4-15, IEC61000-4-7 and EN50160, offering accurate harmonic Real-Time (32 Parameters/Recorder) (16 Parameters/Recorder) · Recording interval from 1 minute to 60 minutes
measurements up to the 63rd order and capable of capturing disturbance events such as Transients, Dips, Swells and Interruptions. In addition, the 4 4 · 30 days @ 1-minute, 300 days @ 10-minute, 450 days @ 15-minute
High-Speed (HS)
PMC-680i provides High-end fault recorder feature with its Disturbance Waveform Recorder (DWR), capable of capturing events that last over 300 (16 Parameters/Recorder) (16 Parameters/Recorder)
· On-board trending via Front Panel display
seconds in duration in varying resolutions. This feature likely gives the PMC-680i the highest Performance/Cost ratio of any panel-mount PQ · PQDIF file format, downloadable from the on-board FTP Server
Analyzers for the utility market today.
·
·
IEC61000-4-7 Compliance
U & I THD. TOHD, TEHD, Harmonics & Inter-Harmonics up to 63rd Setpoints
· Harmonic kW, kvar, kVA and PF from Fundamental to 63rd
· Total harmonic kWh, kvarh Import/Export/Net/Total PMC-680i and PMC-670 provide extensive control by allowing users to initiate an action in response to a specific condition from PQ events, Control
· Individual harmonic Total kWh, kvarh Import/Export/Net/Total parameters or Digital Input status. Typical applications include SOE or PQ Log reporting, Waveform and Data Recording as well as DO/RO Trigger-
ing for Alarm or Control Actions.
Rapid
Voltage Voltage Inputs and Outputs
Changes & Interruptions
Flickers Digital Inputs Digital Outputs
Dips and · Voltage Interruption Events
· Detection of quick RMS Voltage PMC-680i and PMC-670 are equipped with 8 self-excited Digital Inputs for
Swells if the residual voltage is less PMC-680i and PMC-670 come standard with Mechanical Relay Outputs
transitions between two steady
state conditions according to than the Interruption external status monitoring, Demand Synchronization or pulse counting (RO) for setpoint alarming and control as well as Solid State Digital
IEC61000-4-30 Threshold with programmable weight for collecting WAGES (Water, Air, Gas, Outputs (DO) for energy pulsing.
· Flicker measurements Electricity, Steam) information.
according to IEC61000-4-15 PMC-680i PMC-670
· Dips and Swells Detection @ · Internally wetted at 24 VDC with programmable debounce 2 Form A Mechanical Relays
RO 4 Form A Mechanical Relays
10ms (½ cycle at 50Hz) with 2 Form C Mechanical Relays
SOE and WFR/DWR @ 512
· 1,000Hz sampling
4 Solid State Digital Outputs 2 Solid State Digital Outputs
samples/cycle · Time Sync. via GPS's 1PPS output DO (Optically Isolated) (Optically Isolated)
Copyright © CET Inc. All rights reserved. Comprehensive and Reliable PQ Guard for Your Infrastructure
High Accuracy Substation Automation
Communications System Integration Accuracy Relay Outputs (RO1, RO2, RO3, RO4)
PMC-680i PMC-670
Parameters Accuracy Resolution Type Form A Mechanical Relay
RS-485 PecStar® iEMS PMC-680i PMC-670 Loading 5A @ 250VAC / 30VDC 5A @ 250VAC / DC
Both PMC-680i and PMC-670 are equipped with two RS-485 ports for The PMC-680i is supported by CET’s PecStar® iEMS software. In Voltage (U) ±0.1% 0.01V
Type Form C Mechanical Relay
serial communications addition, the PMC-680i can be easily integrated into other 3rd party Current (I) ±0.1% 0.001A Loading 8A @ 250VAC / 24VDC -
· Optically isolated with baud rate from 1.2 to 115.2 kbps systems because of its support of multiple communications ports as kW, kVA ±0.2% 0.001kX
· Modbus RTU protocol well as different industry standard protocols such as Modbus and kvar ±0.2% 0.001kvar Digital Outputs (COM, DO1, DO2, DO3, DO4)
optional IEC61850. kWh, kVAh IEC62053-22 Class 0.2S 0.1kXh
Type Form A Solid State Relay
Ethernet Port kvarh IEC62053-23 Class 2 0.1kvarh
Isolation Optical
100BaseT for High-Speed data connection supporting the following Protocols 3 Party System Integration
rd
Power Factor ±0.2% ±0.5% 0.001 Max. Load Voltage 80V
· Modbus TCP · Ethernet Gateway Easy integration into Substation Automation or Utility SCADA systems Frequency ±0.005Hz 0.001Hz
Max. Forward Current 50mA
· HTTP, SNTP, SMTP, FTP · Optional IEC61850 via Modbus RTU, Modbus TCP or IEC61850. Harmonics IEC61000-4-7 Class A 0.01%
Simultaneous
supports the configuration for most Setup parameters via a web browser Current Unbalance ±0.5% 0.01%
10 Modbus TCP 10 Modbus TCP
Client Connections 12 IEC61850 (optional) 8 IEC61850 (optional) without using any proprietary software. The on-board, password LCD Display
protected FTP Server allows logged data in PQDIF or COMTRADE
format to be downloaded and then subsequently viewed using any
Technical Specifications Type Color TFT LCD, Industrial Grade
Time Synchronization 3rd-party software that supports the industry standard PQDIF and
Voltage Inputs (V1, V2, V3, V4, VN)
Resolution
View Area
640x480
115x86mm (5.7”)
COMTRADE file formats.
PMC-680i PMC-670
· Battery-backed Real-time clock @ 6ppm (≤ 0.5s/day)
· Time Synchronization via Modbus RTU protocol, SNTP, GPS @ 1PPS
or optional IRIG-B input Optional SCCPs
Standard (Un)
Optional (Un)
240ULN/415ULL
400ULN/690ULL
400ULN/690ULL
-
Safety Standards
Standard 1V-150% of Un 10V-120% of Un Safety Requirements
Range
Optional 1V-200% of Un - PMC-680i PMC-670
2xUn continuous, 1.2xUn continuous, LVD Directive 2006/95/EC EN61010-1-1: 2001
Overload 4xUn for 1s 4xUn for 1s
PMC-SCCP-5kA-500mV-B-C-C- Insulation IEC60255-5: 2000
Model No. PMC-SCCP-50A-500mV-B-A-B PMC-SCCP-200A-200mV-B-B-B PMC-SCCP-500A-500mV-B-B-B 371/254/150/100 Burden <0.1VA/phase
Between Power,
Primary 1-1,000,000V 2kV @ 1 minute
5A 20A/200A 500A 500A/5000A Rogowski Coil Dielectric Test AC Circuits, and GND
Measurement Range
(50A Imax) (200A Imax) (500A Imax) (5,000A Imax) Secondary 100-690V Between I/O, GPS and GND 500V @ 1 minute
PT Ratio
Max. Allowable Current 50A 260A 500A 10, 000A V4 Primary 1-1,000,000V Between Power,
>100MΩ
AC Circuits, and GND
AC 10mV/A @ 20A AC 1mV/A @ 500A V4 Secondary 100-690V 1-400V Insulation
AC 10mV/A AC 1mV/A Between GPS and GND >100MΩ >10MΩ
Output Voltage AC 1mV/A @ 200A AC 0.1mV/A @ 5000A 42Hz-58Hz @ 50Hz Resistance
(Max. 500mV) (Max. 500mV) Frequency
(Max. 200mV) (Max. 500mV) 50Hz-70Hz @ 60Hz Between Voltage and GND >5MΩ
Copyright © CET Inc. All rights reserved. Comprehensive and Reliable PQ Guard for Your Infrastructure
High Accuracy Substation Automation
Communications System Integration Accuracy Relay Outputs (RO1, RO2, RO3, RO4)
PMC-680i PMC-670
Parameters Accuracy Resolution Type Form A Mechanical Relay
RS-485 PecStar® iEMS PMC-680i PMC-670 Loading 5A @ 250VAC / 30VDC 5A @ 250VAC / DC
Both PMC-680i and PMC-670 are equipped with two RS-485 ports for The PMC-680i is supported by CET’s PecStar® iEMS software. In Voltage (U) ±0.1% 0.01V
Type Form C Mechanical Relay
serial communications addition, the PMC-680i can be easily integrated into other 3rd party Current (I) ±0.1% 0.001A Loading 8A @ 250VAC / 24VDC -
· Optically isolated with baud rate from 1.2 to 115.2 kbps systems because of its support of multiple communications ports as kW, kVA ±0.2% 0.001kX
· Modbus RTU protocol well as different industry standard protocols such as Modbus and kvar ±0.2% 0.001kvar Digital Outputs (COM, DO1, DO2, DO3, DO4)
optional IEC61850. kWh, kVAh IEC62053-22 Class 0.2S 0.1kXh
Type Form A Solid State Relay
Ethernet Port kvarh IEC62053-23 Class 2 0.1kvarh
Isolation Optical
100BaseT for High-Speed data connection supporting the following Protocols 3 Party System Integration
rd
Power Factor ±0.2% ±0.5% 0.001 Max. Load Voltage 80V
· Modbus TCP · Ethernet Gateway Easy integration into Substation Automation or Utility SCADA systems Frequency ±0.005Hz 0.001Hz
Max. Forward Current 50mA
· HTTP, SNTP, SMTP, FTP · Optional IEC61850 via Modbus RTU, Modbus TCP or IEC61850. Harmonics IEC61000-4-7 Class A 0.01%
Simultaneous
supports the configuration for most Setup parameters via a web browser Current Unbalance ±0.5% 0.01%
10 Modbus TCP 10 Modbus TCP
Client Connections 12 IEC61850 (optional) 8 IEC61850 (optional) without using any proprietary software. The on-board, password LCD Display
protected FTP Server allows logged data in PQDIF or COMTRADE
format to be downloaded and then subsequently viewed using any
Technical Specifications Type Color TFT LCD, Industrial Grade
Time Synchronization 3rd-party software that supports the industry standard PQDIF and
Voltage Inputs (V1, V2, V3, V4, VN)
Resolution
View Area
640x480
115x86mm (5.7”)
COMTRADE file formats.
PMC-680i PMC-670
· Battery-backed Real-time clock @ 6ppm (≤ 0.5s/day)
· Time Synchronization via Modbus RTU protocol, SNTP, GPS @ 1PPS
or optional IRIG-B input Optional SCCPs
Standard (Un)
Optional (Un)
240ULN/415ULL
400ULN/690ULL
400ULN/690ULL
-
Safety Standards
Standard 1V-150% of Un 10V-120% of Un Safety Requirements
Range
Optional 1V-200% of Un - PMC-680i PMC-670
2xUn continuous, 1.2xUn continuous, LVD Directive 2006/95/EC EN61010-1-1: 2001
Overload 4xUn for 1s 4xUn for 1s
PMC-SCCP-5kA-500mV-B-C-C- Insulation IEC60255-5: 2000
Model No. PMC-SCCP-50A-500mV-B-A-B PMC-SCCP-200A-200mV-B-B-B PMC-SCCP-500A-500mV-B-B-B 371/254/150/100 Burden <0.1VA/phase
Between Power,
Primary 1-1,000,000V 2kV @ 1 minute
5A 20A/200A 500A 500A/5000A Rogowski Coil Dielectric Test AC Circuits, and GND
Measurement Range
(50A Imax) (200A Imax) (500A Imax) (5,000A Imax) Secondary 100-690V Between I/O, GPS and GND 500V @ 1 minute
PT Ratio
Max. Allowable Current 50A 260A 500A 10, 000A V4 Primary 1-1,000,000V Between Power,
>100MΩ
AC Circuits, and GND
AC 10mV/A @ 20A AC 1mV/A @ 500A V4 Secondary 100-690V 1-400V Insulation
AC 10mV/A AC 1mV/A Between GPS and GND >100MΩ >10MΩ
Output Voltage AC 1mV/A @ 200A AC 0.1mV/A @ 5000A 42Hz-58Hz @ 50Hz Resistance
(Max. 500mV) (Max. 500mV) Frequency
(Max. 200mV) (Max. 500mV) 50Hz-70Hz @ 60Hz Between Voltage and GND >5MΩ
Copyright © CET Inc. All rights reserved. Comprehensive and Reliable PQ Guard for Your Infrastructure
Environmental and Environmental Conditions
PMC-680i PMC-670
Power Quality
Mechanical Tests
Voltage Characteristics of Electricity Supplied by EN50160
Vibration Response IEC60255-21-1: 1988 Level II Public Distribution Systems
Test Endurance IEC60255-21-1: 1988 Level I General Guide on Harmonics and Interharmonics
Measurements and Instrumentation, For Power Supply IEC61000-4-7
Response IEC60255-21-2: 1988 Level I Systems and Equipment Connected Thereto
Shock Test
Endurance IEC60255-21-2: 1988 Level I Flicker Meter - Functional and Design Specifications IEC61000-4-15
Bump Test IEC60255-21-2: 1988 Level I Testing and Measurement Techniques IEC61000-4-30
Power Quality Measurement Methods (Certified by PSL)
Ordering Information
Product Code Description
PMC-680i Advanced Power Quality Analyzer
A 512 Samples/Cycle
Sample/Cycle
B* 1024 Samples/Cycle
4 4GB
On-board Memory
8* 8GB
5 5A
1 1A
Input Current
SCCPA^ SCCP Option for use with CT Clamps with Max. 500mV Output
SCCPB~ SCCP Option for use with CT Clamps with Max. 5V Output @ 1mV/1mA
System 5 8 DI + 60Hz
50Hz
4 RO + 4DO
Frequency 6 60Hz
I/O A 8xDI + 4xRO
2x100BaseT + 4xDO
+ 2xRS-485
A 2x100BaseT
Communications B* None
Phone: +86.755.8341.5187
Product Code Description Email: sales@cet-global.com
Website: www.cet-global.com
PMC-670 C & I Advanced Power Quality Monitor
Input 5 5A
Copyright © CET Inc. All rights reserved.
Current 1 1A
Input Voltage 3 400ULN/690ULL
2 95-250VAC/VDC, 47-440Hz
Power Supply
3 20-60VDC
Your Local Representative
System 5 50Hz
Frequency 6* 60Hz
I/O A 8DI + 4RO + 2DO
Communications A
V.00 19.08.2020
1x100BaseT + 2xRS-485
X None
IEC61850
A* IEC61850 Protocol Support
Language E English