South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
SECTION-III
E&M WORKS
In general all applicable IS codes and CPWD Specifications and specifications provided in
this section wherever applicable shall be followed for E&M works.
ELECTRICAL WORK:
INTERNAL ELECTRICAL INSTALLATION (IEI)
1. General Specifications.
1.0 The electrical wiring installations shall be carried out in conformity with the requirements of the
Indian Electricity Rules, 1956 as amended up to date and to the relevant regulations of the electric
supply authority concerned, and IS: 732 Indian Standards Code of Practice for Electrical wiring
installations.
1.1 (a) All the equipment, fittings and accessories, materials selected for the wiring installations shall
conform to the relevant Indian Standards wherever these exist. These will be of makes as
specified in the tender or as approved by the NBCC/Client.
(b) The work under this contract shall be carried out in accordance with schedule ‘A’, General
Specifications, the particular specifications, drawings and other provisions in CPWD Schedule
and specifications.
(c) The term ‘General Specifications’ referred to in above, as well as referred to in CPWD2013
General Conditions of Contracts shall mean the specifications contained in the CPWD
schedule/specification.
(d) General Rules, specifications, Special Conditions and all preambles in the schedule and CPWD-
DSR & Specifications shall be deemed to apply to the work under this contract. In case of any
discrepancy, the provisions in this tender document shall take precedence over the aforesaid
provision in the CPWD schedule/DSR.
(e) The contractor shall produce samples of all materials and shall obtain approval in writing from
NBCC/Client before he places bulk order for the materials for incorporation in the work. In
respect of materials for which samples are not kept or detailed specifications are not given here-
in-after, the materials shall comply with latest relevant Indian Standard Specifications whether
listed in Schedule/DSR and under these specifications or not. Materials having ISI Mark shall be
given preference over those not having ISI Mark.
(f) DSR items shall be executed as per CPWD specification (latest version).
1.2 The Contractor shall be responsible for obtaining the NOC from Electrical Safety Inspector of the
State.
1.3 The internal wiring shall be done by "A" class Electrical, Contractor approved by the State /
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-1
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
2.0 WIRING
2.1 GENERAL
Technical specifications in this section cover item of wiring installations comprising of :
Point wiring including circuit wiring for light, fan and call bell points as also lighting and power
convenience socket outlet points in concealed/surface conduit. Sub main wiring in
concealed/surface conduit.
3.0 CONDUITING:
Conduits shall be rigid PVC of minimum thickness of 2mm thick. Conduits shall be ISI
marked confirming to IS : 9537 (Part-3)-1983. All conduit and conduit accessories shall be
of PVC. Conduits shall be joined together by vinyle type cement / solvents. Minimum size
of conduit shall be 20mm dia. Conduit shall be fixed on ceiling or wall. All conduits shall
be concealed in wall ceiling etc. or fixed on surface of wall with clamps at regular interval
as called for elsewhere. For termination of PVC conduits into switch outlet boxes, PVC
female adopters shall be used. Wherever conduit run exceeds 10 metre, circular junction
boxes shall be provided to facilitate pulling & inspection of wires. Inspection boxes shall
be suitable located in co-ordination with the Engineer-in-charge. Conduits shall be bend
using suitable size springs. Long radius bends shall be provided. Heating shall not be used
to bend the conduits. Size of conduit shall depend upon number and size of wires to be
drawn.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-2
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
3.2 MS Conduit:
Wiring shall be carried out in recessed /surface MS conduits. The MS conduits conform to IS
9537 Part-II-1981 and shall be ISI embossed. All joints in conduits shall be sealed/cemented with
approved solvent cement. Damage conduits/fittings shall not be used. Cut ends of conduits shall
not have sharp edges. (Only 10% MS conduits are used in Buildings as per approved by
NBCC/Client)
3.3 Bends:
As far as possible, the conduit system shall be so laid out that it shall obviate use of tees,
elbows and sharp bends. No length of conduit shall have more than the equivalent of two
quarter bends from inlet to outlet.
The conduit wiring system shall be complete in all respects, including their accessories.
Bends, couplers etc. shall be solid type in recessed type of works and may be solid or inspection
type as required, in surface type of works. The accessories shall conform in all respects to the
relevant ISS. Samples shall be got approved by NBCC/Client before use.
3.5 Sheet Metal Outlet/Draw/Inspection/Junction Boxes.
3.6 General
Wherever required, outlet boxes of required sizes shall be fabricated from 1.6 mm thick MS
sheets excepting ceiling fan outlet boxes which shall be fabricated from minimum 2 mm thick
sheets. Outlet boxes shall be provided with minimum 16 mm projected threaded collars. The
outlet boxes shall be of approved quality, finish and manufacture. All outlet boxes shall be
provided with an earth stud. The boxes shall be protected from rust by zinc phosphate primer
process. For concealed conduiting work, boxes with primer only could be embedded. For surface
conduiting work, the boxes shall be finished with minimum one coat of enamel paint of approved
colour. The outlet boxes shall be so protected at the time of fixing that no mortar find its way
inside during concrete filling or plastering. For concealed conduiting work, outlets boxes shall be
completely embedded in walls/ceilings leaving edges flush with finished wall/ceiling surface.
Boxes suitable to house modular type switches/sockets of required ratings, and fan regulators as
required shall be provided. In case the number of switches in one box is not tallying with that
available in standard manufacture, the box accommodating the next higher number of switches
shall be provided without any extra cost. In case fan regulator/regulators is /are to be provided at
a later stage, suitable provision for accommodating such regulators shall be made in the switch
boxes and blank off covers shall be provided without any extra cost. The outlet boxes shall be of
MS having external and internal surface true to finish. All boxes shall have adequate number of
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-3
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
knock out holes of required diameter and earth stud. Unless otherwise stated boxes shall be
located with bottom at 1200 mm above finished floor level.
These shall be minimum 75 mm x 75 mm x 50 mm deep and provided with threaded collars for
conduit entry as required. For ceiling mounted florescent fittings, the boxes shall be provided.
300 mm off centre for a 1200 mm fitting and 150 mm off centre for a 600 mm fitting so that the
wiring is taken directly to the down rod. 3 mm thick Perspex/hylam sheet cover of matching
colour shall be provided.
Draw boxes of minimum 75mm x 75mm x 50mm deep or larger as required shall be provided at
convenient locations to facilitate drawing of long runs of conductors. These shall have screwed
covers of 3mm thick Perspex/hylam sheet.
Inspection Boxes / Junction Boxes: Inspection boxes of minimum 75mm x 75mm x 50mm deep
shall be provided at suitable location in conduit runs to permit inspection and maintenance. These
shall have screwed covers of 3mm thick Perspex / hylam sheet.
Cross Section
The conduits shall be of ample sectional area to facilitate simultaneous drawing of wires and
permit future provision also. Total cross section of wires measured overall shall not normally be
more than half the area of the conduit. Maximum number of PVC insulated 650/1100 Volt grade
copper conductor wires conforming to IS : 694 – 1990 shall be as per table given below.
Nominal Cross
20 mm 25 mm 32 mm 38 mm 51 mm 64mm
Sectional area of
conductor in sq.
S B S B S B S B S B S B
mm
1.5 5 4 1 8 18 12 - - - - - -
2.5 5 3 8 6 12 10 - - - - - -
4 3 2 6 5 10 8 - - - - - -
6 2 - 5 3 4 8 7 - - - - -
10 2 - 4 3 6 5 8 6 - - - -
16 - - 2 2 3 3 6 5 1 7 1 8
25 3 2 5 3 8 6 9 7
35 3 2 6 5 8 6
50 5 3 6 5
70 4 3 5 4
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-4
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
Notes:
The above table shows the maximum capacity of conduits for a simultaneous drawing in of cables.
The columns headed ‘S’ apply to runs of conduits which have distance not exceeding 4.25 m
between draw boxes and which do not deflect form the straight by an angle of more than 15
degrees. The columns headed ‘B’ apply to runs of conduit which deflect form the straight by an
angle of more than 15 degrees. Conduits sizes are the nominal external diameters.
Conduits shall be laid either concealed in walls and ceilings or on surface on walls and ceilings or
partly concealed and partly on surface, as required. Same rate shall apply for concealed and
surface conduiting in this contract.
Concealed conduits in brick work shall be laid in chases to be cut by electrical Contractor in brick
work before plastering. The chases shall be cut by a chase cutting electric machine. The chases
shall be of sufficient width to accommodate the required number of conduits and of sufficient
depth to permit full thickness of plaster over conduits. The conduits shall be secured in the chase
by means of suitable clamps at intervals of maximum 1 meter. The chases shall then be filled with
cement and coarse sand mortar (1:3) and properly cured by watering. Chicken wire mesh shall be
used for closing the chases with cement plaster.
Entire concealed conduit work in concrete members and in brick work shall be carried out in
close coordination with progress of civil works. Conduits in concrete members shall be laid
before casting and conduits in brick work shall be laid before plastering. Should it become
necessary to embeded conduits in already cast concrete members, suitable chase shall be cut in
concrete for the purpose. For minimizing this cutting, conduits of lesser diameter than 25 mm and
outlet boxes of lesser depth than 50 mm could be used by the Contractor for such extensions only
after obtaining specific approval from NBCC/Client. For embedding conduits in finished and
plastered brick work, the chase would have to be made in the finished brick work. After fixing
conduit in chases, chases shall be made good in most workmanlike manner to match with the
original finish.
Cutting chases in finished concrete or finished plastered brick work for embedding conduits and
outlet boxes etc shall be done by the Contractors without any extra cost.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-5
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
Surface Conduiting Wherever so desired, conduits shall be laid on surface over finished concrete
and/or plastered brickwork. Suitable spacer saddles of approved make and finish shall be fixed to
the finished structural surface along the conduit route at intervals not exceeding 600 mm. Holes in
concrete or brick work for fixing the saddles shall be made neatly by electric drills using masonry
drill bits. Conduits shall be fixed on the saddles by means of good quality heavy duty MS clamps
screwed to the saddles by counter sunk screws. Neat appearance and good workmanship of
surface conduiting work is of particular importance. The entire conduit work shall be in absolute
line and plumb.
Painting of Conduits and Boxes
The entire conduit system including outlets and boxes shall be thoroughly cleaned after
completion of erection and before drawing in of cables.
3.12 Earthing
Continuous earth wire shall be provided for all points, outlets and sub-mains. Earthing terminals
shall be provided inside all switch boxes, outlet boxes and draw boxes etc.
4.0 WIRES
4.1 Material
Wires shall be PVC insulated with stranded copper conductors, unless otherwise stated, of
650/1100 volt grade, conforming to IS : 694 -1990. All wires shall bear manufacturer’s label and
shall be brought to site in new and original packages. Manufacturer’s certificate, certifying that
wires brought to site are of their manufacture shall be furnished as required.
Wires carrying current shall be so bunched in conduits that the outgoing and return wires are
drawn into the same conduit. Wires originating from two different phases shall not be run in the
same conduit.
Drawing of Wires:
The drawing of wires shall be executed with due regard to the following:-
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-6
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
No wire shall be drawn into any conduit, until all work of any nature that may cause injury to
wires is completed. Care shall be taken in pulling the wires so that no damage occurs to the
insulation of the wire. Bushes shall be provided at conduit edges.
Before the wires are drawn conduits, conduits shall be thoroughly cleaned of moisture, dust, dirt
or any other obstruction by forcing compressed air through the conduits if necessary.
While drawing insulated wires into the conduits, care shall be taken to avoid scratches and kinks
which could cause breakage of conductors.
Sub-circuit wiring shall be carried out in looping system. Joints shall be made only at distribution
board terminals, switches/buzzers and at ceiling roses/connectors/lamp holders terminals of
lights/fans/socket outlets. No joints shall be made inside conduits or junction/draw/inspection
boxes.
Insulation shall be shaved off for a length of 15 mm at the end of wire like sharpening of a pencil
and it shall not be removed by cutting it square or wringing.
Strands of wires shall not be cut for connecting terminals. All strands of wires shall be soldered at
the end before connection.
Conductors having nominal cross sectional area exceeding 4 sq. mm shall always be provided
with crimping sockets.
At all bolted terminals, brass flat washer of large area and approved steel spring washers shall be
used.
The pressure applied to tighten terminal screws shall be just adequate, neither too much nor too
less.
Switches controlling lights, fans, socket outlets etc. shall be connected to the phase wire of
circuits only.
Load Balancing
Balancing of circuits in three phase installation shall be planned before the commencement of
wiring and shall be strictly adhered to.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-7
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
5.1 Switches
All 6 and 16 amps switches shall be of modular flush mounting type, unless otherwise stated,
suitable for 250 volt AC supply, best quality and of approved make. The switch moving and
fixed contacts shall be of silver nickel and silver graphite alloy and contact tips coated with
silver. Housing of switches shall be made from high impact resisting flame retarding and ultra
violet stabilized engineering plastic materials. Switches shall be fixed inside the box on
adjustable MS strips/plates with tapped holes brass machine screws, leaving ample space at the
back and side for accommodating wires.
6A 3 pin / 2 pin combination outlets mounted on switch boards along with other lighting control
switches. Each such outlet will have a corresponding controlling switch mounted next to the
outlet. Such outlets may be looped into the corresponding lighting circuit.
6/16 amps socket outlets shall be of modular flush mounting type, unless otherwise stated, and
shall be switched, three pin type and fitted with automatic linear safety shutters to ensure safety
from prying fingers. Socket outlets shall be made from high impact resistant, flame retarding and
ultra violet stabilized engineering plastic material.
Switches and sockets shall be located in the same plate. Plates for 6 amp switched/
unswitched power and telephone outlets shall be of the same size and shape.
An earth wire shall be provided along the wires feeding socket outlets for electrical appliances.
The earth wire shall be connected to the earthing terminal screw inside the box. The earth
terminal of the socket shall be connected to the earth terminal provided inside the box.
Light fixtures and fittings shall be assembled and installed complete as required and ready for
service, in accordance with details, drawings, manufacturer's instructions and to the satisfaction
of the EMPLOYER.
Wires brought out from junction boxes shall be encased in G.I. flexible pipes for connecting to
fixtures concealed in suspended ceilings. Flexible pipes shall be provided with check nuts at both
ends.
Pendant fixtures specified with overall lengths are subject to change and shall be checked with
site conditions and installed as required.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-8
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
All suspended fixtures shall be mounted rigid and fixed in position in accordance with drawings,
instructions and as approved by Architect/Employer.
Fixtures shall be suspended true to alignment, plumb, level and capable of resisting all lateral and
vertical forces.
All suspended light fixtures, fans etc. shall be provided with concealed suspension arrangement in
the concrete slab/roof members. Making provisions for such arrangements at the appropriate
stage of construction is deemed to be included in contractors’ scope.
Exhaust fans shall be fixed at locations shown on the drawings. They shall be wired to a plug
socket at a convenient location near the fan in flexible conduits.
All switch and outlet boxes and fan regulators shall be bonded to earth with PVC insulated
stranded copper wire as specified.
Flexible conduits, wherever used, shall be of make and quality approved by NBCC/Client.
Power circuits shall normally have maximum one 16 amps socket outlet unless otherwise stated.
Separate circuit shall be run for each geyser, kitchen equipment, window air conditioners and
similar appliances.
Point wiring rates shall include painting of conduits and other accessories as required.
Point wiring rates shall include cleaning of dust, splashes of colour wash or paint from all
fixtures, fans, fittings etc. at the time of taking over of the installation.
Rates quoted for wiring for groups of more than one light controlled by one switch shall be on
the same basis as above excepting that the cost of interconnection looping wiring between the
first light and subsequent lights controlled by one switch shall also be included in the point
wiring rate.
Wiring for DB controlled groups of lights shall be done through MCB directly from DB.
Control switches are not required and cost of MCB is also not included in the point wiring
rate since this cost is included in the item of DB. Rates quoted for the DB controlled
groups of lights shall be on the same basis as for switch controlled groups excepting that
the cost of switches shall not be included. One DB control circuit should not have
maximum 8 points.
7.0 EARTHING
All switch-gears shall have continuous run of earth bus-bar. The size and materials of the earth
bus bar shall be as specified. All connections to earth and earthing of neutral shall be carried out
in accordance with IS 3043/1987.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-9
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
CONSTRUCTION
i) Sheet Steel – 14 SWG thick CRCA sheet with folded or braced construction to provide rigid
support for compartments.
ii) Welded construction, with shipping section bolted together. All such joints to be gasket,
lifting lugs to be provided.
iii) The panels shall be totally dust and vermin proof conforming to IP 54 and shall be
floor/wall/Rising Main mounting type.
iv) All doors to be hinged type except bus-bar chamber covers, which shall be bolted type. The
panels shall be of flush front design, suitable for access from front and rear.
vi) The design shall be such as to have individual feeders in separate compartments, with proper
barriers between adjacent/ feeders, bus-bars chamber and cable box chambers.
PAINTING
All sheet steel work shall be properly cleaned and degreased. Rust and scale shall be removed by
pickling and phosphatising. Powder coating of approved shade.
FUSES
All fuses shall be of HRC cartridges fuse-link type having a certified rupturing capacity of not
less than 80 KA at 415 volts AC. The HRC fuses shall conform to IS 13703 (part-II), section 1
EC 269 (Part I & II), IS certified. All fuses shall have visible indication to indicate ‘Blown’
condition.
The HRC fuse carriers/bases shall be of high grade PHENOLIE mouldings. The contacts shall be
silver-plated and the contact blocks shall be suitable to receive the rated conductors of aluminum.
The fuses carriers shall have an aperture to view the conditions of HRC fuses mounted inside.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-10
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
CONTACTORS
The CONTACTORS shall be of the electromagnetic, double-break, non-gravity type rated for
uninterrupted duty suitable for class AC-3A utilization category as per IS: 13947 Part I & II. The
contacts shall be silver-plated.
The operating coils shall have class ‘B’ insulation or higher and shall be suitable for operation of
any specified control supply system.
The moulded case circuit breakers, MCCB’s shall conform to the latest applicable standard IS
13947 Part I & II.
For AC Circuits the MCCB’s shall be triple/four pole construction and shall have independent
manual opening and closing mechanism. The mechanism shall be quick-make and quick-break
type and the breakers of trip tree in operation. The ‘ON’, ‘OFF’ and ‘TRIP’ mechanism shall be
clearly indicated.
It shall be possible to mount accessories on the MCCB’s like shunt-trip and under voltage release,
alarm contacts, etc.
The MCCB’s shall have microprocessor based/ thermal & static trip devices.
The MCCB’s shall have rupturing capacities as specified in BOQ/Single Line Diagram and
specifications.
The MCB’s shall be of single pole, double pole, triple pole or four pole as required conformed to
IS 8828 – 1978. The MCB’s shall be of magnetic / thermal release type with a maximum
rupturing capacity of 10 KA at 415 V and with mid trip knob.
CURRENT TRANSFORMERS
The CTs shall be of dry type epoxy resin cast and shall have short time withstand rating of the
associated switchgear for 1 second.
The measuring instrument CTs shall be of 15 VA, minimum accuracy class 1.0 and an instrument
safety factor of5.
The protection relay CTs shall be of 15 VA, minimum accuracy class 1 & 5P10 and an accuracy
limit factor of 10.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-11
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
Electrical indicating instruments shall be 96 mm square size, suitable for flush mounting.
INDICATING LAMPS
Indicating lamps shall be provided with neon and HRC fuse link for protection.
The bus-bars shall be of high conductivity electrolytic aluminum alloy or copper tinned as
specified in BOQ. The bus bars shall be of uniform cross-section throughout the length of the
Panels. Neutral bus-bar size shall be half the size of phase and neutral colours.
All main and auxiliary bus-bars shall be insulated with heat shrink sleeves. The sleeves shall be
of high dielectric strength, non-corrosive and of high dielectric strength, non-corrosive and of
phase and neutral colours.
The bus-bars shall be supported on cast epoxy/ resin /DMC/ Fibre glass insulators and the spacing
of the supports shall be such as to withstand the stresses of the short circuit currents. The bus-bar
spacing shall be adequate for a phase voltage up to 600 V.
The bus-bar shall be as chosen for specific current ratings with a maximum density of 1 Amp per
sq.mm area for aluminum and 1.5 A per sq.mm area for copper bus-bars.
INTERNAL WIRING
All internal wiring shall be carried out with 1100 V grades FRLS PVC insulated, stranded
conductor copper wires. The minimum size of wires shall be 1.5 sq.mm copper and for CTs 2.5
sq.mm copper.
All individual control and CTs wiring shall be labelled with engraved identifications ferrules,
yellow in colour with black letters.
All wiring shall be terminated on stud with spread type terminal blocks through crimping type
sockets. No more than 2 connections shall be made on any one terminal block.
All spare auxiliary contacts of contactors and relays shall be wired to control terminal blocks.
TERMINAL BLOCKS
Terminal blocks for power and control shall be of reputed make sturdy type, with washers, nuts
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-12
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
and lock nuts. All adjacent terminals shall have insulating barriers.
All power terminal blocks shall be appropriately rated for current with a minimum of 30 Amps.
The control terminal blocks shall be rated for a minimum of 10 A and suitable for at least 2
conductors each of 2.5 sq.mm termination of power cables direct in switches shall be preferred.
All sets of power and control power terminal blocks shall be identified with engraved plastic
labels, black background and white letters.
IDENTIFICATION LABELS
All labels shall be black plastic with white engravings of letters of minimum 6 mm sizes.
TESTS
Operational Test.
* Suitable rating Floor panel shall be mounting in Floor feed form Rising main & It shall be
separate for all services.
9.1 MATERIALS
9.1.1 Enclosure
The enclosure shall be made from CRCA sheet steel of 2m thickness for side channel and 1.6 mm
thickness for the front and covers.
Bus trunking system should conform to IEC-139 Part 1 & 2 and shall be suitable for 45 KA
symmetrical fault level 415 volt 3 phase 4 wire 50 Hz supply, insulation voltage 660 volts .
*Rising Main/Bus Bar shall be made of Aluminium Conductor and it shall be appropriate in
size & Rating.
9.1.2 Bus bars Bus bars shall be made of electrical grade E-9/E Aluminium bus bars. The rating of
busbar shall be as specified in drawing /Bill of quantities
Maximum temperature rising of the Rising Mains Bus/ Trunking System shall be as per IEC
o o
standards and temperature rise shall not exceed 50 C above 40 C ambient.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-13
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
9.1.3 Bus bars shall be of sufficient cross section so that a current density of 0.8 A/1 A Sq mm is not
exceeded at nominal current.
9.1.4 The cross section of the neutral bus bar shall be the same as that of the phase busbar for bus bars
of capacities.
Each bus bar shall be individually insulated by means of heat shrinkable PVC sleeves
Bus bar supports/insulators shall be made of thermal resistant epoxy resin as insulation material
and shall be of suitable size and spacing to withstand dynamic stresses due to short circuit
currents in the system.
9.3. MOUNTINGS
9.3.1 Tap off boxes shall be located at specified intervals and shall be installed at a height of 1.5 m to 5
m above the floor level. These shall be permanently connected to the bus bars of the rising mains/
bus trunking system.
9.3.2 An end feed unit for connecting to the incoming cables shall be provided at the bottom end of the
rising mains /bus trunking system.
9.3.3 Tap off boxes shall be suitable for mounting over rising mains bus trunking system. The rating
shall be as specified in the BOQ and on drawings.
9.3.4 The tap off unit shall be complete in all respect having moulded case circuit breaker as protective
switching devices with rotary handles. The rating shall be as specified in drawing and tender
document.
9.4 CONSTRUCTION
9.4.1 Enclosure
9.4.2 The rising mains bus trunking system shall be manufactured in convenient sections to facilitate
transportation and installation. The sections shall be connected to form a horizontal /vertical run
at site. Each section shall be provided with suitable wall strips/fixing arrangement at convenient
intervals for fixing to the wall.
9.4.3 The enclosure shall be study so as to withstand the internal and external forces resulting from the
various operating conditions.
9.4.4 The entire bus trunking system shall be designed for dust and vermin proof construction. The
enclosure shall have degree of protection not less than IP-42 in accordance with IS-2147.
9.4.5 Built in fire proof barriers shall be provided to restrict the spread of fire through the bus trunking
system from one section to the adjacent section. The fire barriers comply with resistance class F-
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-14
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
120.
Neoprene rubber gaskets shall be provided between the covers and channels to satisfy the
operating conditions imposed by temperature, weathering durability etc.
Necessary earthing arrangement shall be made alongside the rising mains enclosure by means of a
GI strip of adequate size bolted to each section and shall be earthed at both ends. The rising mains
enclosure shall be bolted type.
9.4.6 The enclosure shall be treated with anti corrosion paint and shall be coated with powder spray
paint. The power spray paint shall be applied electro-statically and baked on to the enclosure.
9.5.1 Bus bars joint shall be thoroughly cleaned and suitable oxidizing grease shall be applied before
making joints.
9.5.2 The rising mains bus trunking shall have four bus bar. Bus bar shall be supported every 250 mm
long the length on class B fire retardant insulating supports.
9.5.3 High tensile, bolts, plain and spring washers shall be provided to ensure good contacts at the
joints.
9.5.4 Expansion joint made of aluminium strips shall be provided wherever necessary to take care of
expansion and contraction of the bus bars under normal operating conditions. This shall be
invariably provided wherever the length of the rising mains bus trunking exceed fifteen meter.
9.5.5 The bus bar shall be provided with thrust pads so that the expansion of the conductor is upwards
only.
9.5.6 The bus bar clamps and insulator shall be designed to withstand the forces due to short circuit
current. They shall also permit free vertical movement of the busbars during expansion and
construction.
10 INSTALLATION
10.1.1 Rising Mains Bus trunking shall be installed on walls to which suitable supports shall be provided
by the contractor without extra payment.
10.1.2 All opening in floors provided by the client shall be closed by the contractor after installing rising
mains bus trunking system by any suitable means as approved by NBCC/Client without any extra
payment.
10.1.3 Mountings The accessories used with the rising mains bus trunking system for tapping and
distribution shall be as per clause 1.4
10.1.4 Earthing Two no. earth strip shall be provided for body earthing of the rising mains bus trunking
system. Earth strip shall be terminated on the earth strip (coming from mains LT panels) at the
bottom end/end feed units of the rising mains bus trunking system. Metallic body of all mounting
shall be bonded to the earth strip. Earth continuity conductor for further distribution shall also be
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-15
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
10.1.5 The entire installation including mounting shall be provided in such a manner that there are no
chances of entry of insects into the rising mains bus trunking system.
10.1.6 Danger notice board Danger notice board shall be provided on the rising mains bus trunking
system at every floor level.
10.1.7 Commissioning Before connecting mains supply after installation, pre-commissioning checks
comprising megger test, checking the tightness of the connections body earth connection etc.
shall be carried out and record.
-o-o-o-
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-18
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
1.0 GENERAL
This specification is intended to cover supply, installation, testing and commissioning of
1000KVA Package Sub-Station.
2.1 All equipment shall be of the class most suitable for working under the conditions specified and
shall withstand the atmospheric conditions without deterioration.
2.2 Minor civil work is included in the contractor’s scope of work. However, the responsibility of
coordination with the civil and other contracting agencies ensuring completion of turnkey
contract rests with the contractor.
2.3 Contractor shall co-ordinate with all other agencies working at site for interconnection and safety
aspects.
2.4 Also the supplier shall furnish back up combined guarantee for 2 years from the date of
successful commissioning. In case there is any defect, the free replacement of any part or in
whole shall be made immediately at no loss to Owner.
2.6 Packing and transportation from the manufacturer’s works to the site.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-19
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
2.7 Receipt, storage, preservation and conservation of equipment at the site including handling.
2.8 Fabrication, pre-assembly if any, erection, testing and putting into satisfactory operation of all the
equipment including successful completion of trial operation.
2.9 Performance guarantee tests including performance demonstration after successful completion of
trial operation.
3.1 All equipment and material shall be designed manufactured and tested in accordance with the
latest applicable Indian Standard / IEC standard.
a) Equipment and material confirming to any other standard which ensures equal or better quality
may be accepted. In such case copies of English version of the standard adopted shall be
submitted.
b) The Unitized Sub-station offered shall in general comply with the latest issues including
amendments of the following standards but not restricted to it.
C. DESIGN CRITERIA
i. Compact Sub-station shall consist of 11KV SF6 insulated compact switchgear with SF6 insulated
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-20
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
ii. The Switchgear and component thereof shall be capable of withstanding the mechanical and
thermal stresses of short circuit listed in ratings and requirements clause without any damage or
deterioration of the materials.
iii. For continues operation at specified ratings temperature rise of the various switchgear
components shall be limited to permissible values stipulated in the relevant standard and / or this
specification.
D. SERVICE CONDITIONS:
I. The equipment offered shall be suitable for continuous satisfactory operation in Tropical area of
Installation with altitude not exceeding 1000m and relative humidity of 95%.
II. The Enclosure consisting of High Voltage switchgear-control gear, Low Voltage switchgear-
control gear & Transformer of the Unitized Sub-station shall be designed to be used under normal
outdoor service conditions. The enclosure should take minimum space for the installation
including the space required for approaching various doors & equipment inside. The enclosure
construction shall be such that it fully protects ingress of rain water, dust & rusting. For personnel
safety, the enclosure shall be of non-walk-in design.
E. SPECIFIC REQUIREMENT
a. The main components of a prefabricated-unitized substation are Transformer, High-voltage
switchgear-control gear, Low-voltage switchgear-control gear, corresponding interconnections
(cable, bus bar) & auxiliary equipment. The components shall be enclosed, by either common
enclosure or by an assembly of enclosure. All the components shall comply with their relevant IS
/ IEC standards.
4.1.1 Ratings:
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-21
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
4.1.3 The enclosure shall be made of 1.5+/-0.5mm thickness Galvanized Sheet Steel Tropicalised to
meet Indian weather conditions including all the partition sheets & doors.
i. The base of the enclosure shall be of 4.0 mm thickness Hot Dip Galvanized Sheet Steel to ensure
rigidity for easy transport & installation. The entire Package Substation shall be Factory
Assemble & Factory Fitted. It should be with continuous sheet made not Bolted construction
type.
b. The transformer tank or metal frame of transformer,
c. The frame &/or enclosure of low voltage switchgear,
d. Internal Illumination: There shall be arrangement for internal lighting activated by associated
switch on doors for HV, Transformer & LV compartments separately.
e. Labels: Labels for warning, manufacturer’s operating instructions etc. & those according to local
standards & regulations shall be pasted / provided inside and shall be durable & clearly legible.
ii. The structure of the substation shall be capable of supporting the gross weight of the roof of the
substation compartment shall be designed to support adequate loads. In case of relocation of the
Package Substation, the entire substation should be capable of getting lifted and placed as a
Single Unit without dismantling of any of the major equipments inside.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-22
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
iii. There shall be proper / adequate ventilation inside the enclosure so that hot air inside enclosure is
directed out by help of duct. Louvers apertures shall be provided so that there is circulation of
natural air inside the enclosure. The Package Substation should be designed & engineering to
have natural cooling & ventilation instead of forced cooling / ventilation as the same would
derate the Transformer further and shall be an additional load on the Transformer.
vi. Internal Fault: Failure within the unitized substation due either to a defect, an exceptional
service condition or mal-operation may initiate an internal arc. Such an event may lead to the risk
of injury, if persons are present. It is mandatory that the offered design shall be tested for Internal
Arc fault test to the tune of at least 20KA for 1 second adhering to as per latest IEC 62271-
200/202 with offered design of RMU situated inside the CSS compartment
vii. Covers & Doors: Covers & doors are part of the enclosure. When they are closed, they shall
provide the degree of protection specified for the enclosure. All covers, doors or roof shall be
provided with locking facility or it shall not be possible to open or remove them before doors
used for normal operation have been opened. The doors shall open outward at an angle of at least
90O & be equipped with a device able to maintain them in an open position. The top cover shall
be slightly otherwise. Proper padlocking facility compartment. There should not be any provision
for opening of transformer compartment from outside of PSS to avoid direct access. It should be
from inside of MV & LV Compartment.
viii. Earthing: All metallic components shall be earthed to a common earthing point. It shall be
terminated by an adequate terminal intended for connection to the earth system of the
installation, by way of flexible jumpers / strips & Lug arrangement. The continuity of the earth
system shall be ensured taking into account the thermal & mechanical stresses caused by the
current it may have to carry. The components to be connected to the earth system shall include :
a. The enclosure of Unitized / prefabricated substation,
b. The enclosure of High voltage switchgear & control gear from the terminal provided for the
purpose,
c. The metal screen & the high voltage cable earth conductor,
(i) The paints shall be carefully selected to withstand tropical heat rain. The paint shall not scale off
or crinkle or be removed by abrasion due to normal handling. For this purpose powder coating
shall be used.
(ii) Special care shall be taken by the manufacturer to ensure against rusting of nuts, bolts and fittings
during operation. All bushings and current carrying parts shall be cleaned properly after final
painting.
(iii) The fabrication process shall ensure that there are no sharp edges on the GI sheets used.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-23
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
3) Compartmentalized Yes
4) Rated temperature enclosure class 10
5) Degree of protection for external IP23 Transformer Compartment.
enclosure IP54 MV & LV Compartment
4.2.1 Non-extensible SF6 Insulated Compact Switchgear as required shall consist of following items:
a. Load Break Cable Switch with integral earth switch having full making capacity shall be used for
Incoming cables.
b. SF6 insulated Vacuum Circuit Breaker shall be used for distribution network of HT switchgear.
Circuit Breaker complete with operating mechanism, self powered,
4.3 Cable Termination: Each Cable compartment shall be provided with three bushings of adequate
sizes to terminate the incoming outgoing 11kV, 3 Core as the case may be. There shall be enough
height from the base of the mounted switchgear so that the cables can be bent and taken vertically up
to the bushings. The Cable termination shall be done by Heat shrinkable Termination method so that
adequate clearances shall be maintained between phases for Termination. Access to all the cables
should be possible form the front/side of RMU. Cable Termination boots shall be supplied by the
switchgear manufacturer.
4.4 Locking Arrangement: Suitable padlocking arrangements shall be provided as stated below:
i. Circuit Breaker manual operating handle in the “OFF” position.
ii. Each feeder Panel operating handle in ‘Closed’ ‘Open” or ‘Earth’ position.
iii. Each isolator operating handle in ‘Closed’, ‘ Open’, or ‘Earth’ position.
static type O/C,E/F protection relay with associated Current Transformers shall be
used for control and protection of Transformer. An integral cable earthing switch
with full making capacity shall be provided.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-24
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
The above Load Break Cable Switch, SF6 insulated Vacuum Circuit Breaker, Copper
c.
Bus bars should be mounted inside a sealed for life, stainless steel tank. The
operating mechanism of the switches and breakers shall be outside the SF6 tank and
accessible from front/side. The tank should be filled with SF6 gas at an adequate
pressure. The degree of protection for gas tank should be IP67. Moreover the
Stainless Steel Gas Tank shall confirm to the sealed pressure system as per IEC and
ensure the gas leakage to 0.1 % per year as per IEC.
d. The SF6 insulated Vacuum Circuit Breaker is required to control 11 kV/433 volts
distribution Transformer of rating upto 2000 KVA and relay settings and Current
Transformers shall be selected accordingly.
e. General Finish: Totally enclosed, metal enclosed, vermin and dust proof suitable
for tropical climate use as detailed in the specification.
f. Ratings: The bus bars shall be made of Copper and have continuous rating of 630
Amps. The isolator and Circuit Breaker shall have a continuous rating of 630 Amps
in accordance with relevant IS / IEC standard
g. Breaking & Making Capacity: The Load Break Cable Switches shall be capable for
breaking rated full load current. The same along with its earthing switch shall also
making
be suitable for full of the system as specified. The com
capacity
switchgear shall be suitable for breaking capacity of 21kA symmetrical at 11000
volts three phase for 11kV system for 3 sec.
h. Busbar: Switchgear shall be complete with all connection, bus-bars etc. Copper
busbars continuous rating shall be 630 Amps. The busbars should
encapsulated by SF6 gas inside the tank.
j. Protection: The SF6 insulated Vacuum circuit breaker shall be fitted with numerical
type self powered relay inside password protected the front cover to avoid any
tampering. The same shall be used in conjunction with suitable CT’s and Tripping
Coil for fault tripping of the Circuit Breakers. CT’s shall be mounted on bushing of
breaker. CT’s mounted inside breaker compartment on cable inside
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-25
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
5.4 Ratings :
Non-Extensible radial / ring compact switchgear with SF6 insulated Vacuum circuit breaker
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-26
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
5.5 Isolator: The Isolators offered shall conform to same standards as RMU as amended to date. The
isolator shall be triple pole, spring assisted, hand operated, non-automatic type with quick break contacts.
The operating handle shall have three positions ‘ON’, ‘OFF’ and ‘EARTH’ which shall be clearly marked
with suitable arrangement to padlock in any position. A safety arrangement for locking shall be provided
by which the isolator operation shall be prevented from ‘ON’ position to ‘EARTH’ position or vice versa.
5.6 Switchgear: Sealed for life, the enclosure shall meet the “sealed pressure system” criteria in
accordance with IEC: 298 (a system for which no handling of gas is required throughout service life of
approximate 30 years covered by manufacturer’s warranty, or otherwise have possibility of gas-refilling
at site.) There shall be no requirement to ‘top up’ the SF6 gas warranted by manufacturer, or otherwise
shall have provision to top-up the same. In addition, manufacturer shall confirm that maximum leakage
rate is lower than 0.1% per year. It shall provide full insulation, making the switchgear insensitive to the
environment. Thus assembled, the active parts of the switchgear unit shall be maintenance free.
The switchgear & switchboard shall be designed so that the position of different devices is visible
to the operator on the front of the switchboard via true-position indicators. The switchboard shall
be designed so as to prevent access to all live parts during operation without the use of tools.
RMU should be tested for internal arc fault test inside the CSS.
5.7 Circuit Breaker: The Unit shall consist of Tee-off spring assisted, three pole SF6 insulated
Vacuum Circuit breaker, with in-series fault making / dead breaking earth switch. The function
shall be naturally interlocked to prevent the main bus bar from getting
earthed . The selection of the main/earth switch lever on the panel front facial, The lever shall be
able to pad locked in either the main or earth position.
5.7.1 Protection: The Circuit breaker shall be fitted with numerical type self powered relay password
protected to avoid any tampering. The relay shall be capable of tripping on Low and High set for
Over current and Earth Fault. Relay should have facility to display the maximum loaded phase
current and record minimum 5 fault records with time
stamping. Relay shall be operated via Resin cast Ring Core Protection CTs of suitable ratio and
burden, pre-installed in the respective cable-box.
5.8.1.3 Rating: The transformer shall have a continuous rating as specified at any of the
specified tapping position and with the maximum temperature rise specified.
5.8.1.4 Temperature Rise: The maximum temperature rise at the specified maximum
continuous output shall not exceed 40°C by thermometer in the hottest portion of the oil
or 50° C measured by resistance of winding above ambient temperature, not exceeding
40°C daily average or 50°C maximum.
5.8.1.5 Type of Load: The transformer shall be suitable for carrying load within temperature rise
indicated in the Indian Standard specification IS:6600 ‘Guide for loading of oil immersed
Transformer’.
5.8.1.6 Overloads: The transformers shall be suitable for carrying overload within temperature
rise indicated in IS:6600 ‘Guide for Loading of oil immersed Transformer’.
5.8.1.7 Connections: H.V. Delta and L.V Star connected with neutral brought out on the
secondary side for connection to earth; Vector group DYn11 of IS:2026.
5.8.1.8 Tapping :
a) Each transformer shall be provided with Rotary type tap switch so as to provided for a
voltage adjustment on H.V. from +5% to –5% of rated voltage of 11000 volts in 4 equal
steps (5 position) to obtain rated voltage of 433 volts on LV side. The tapping shall be
provided for following voltage ratios at no load.
b) Each transformer shall be provided with adjustable tapping Links such as to provided
for a voltage adjustment on H.V. from +5% to –5% of rated voltage of 11000 volts in 4
equal steps (5 position) to obtain rated voltage of 433 volts on LV side. The tapping shall
be suitable to change on H.V. side by links provided for this purpose.
5.8.2 Cleaning & Painting :
5.8.2.1 a) All steel surfaces shall be thoroughly cleaned by sand blasting or chemical agents,
as required to produce a smooth surface free of scales, grease and rust.
b) The internal surfaces in contact with insulating oil shall be painted with heat resistant
insulation paint which shall not react & be soluble in the insulating liquid used.
c) The external Surfaces, after cleaning, shall be given two coats of high quality epoxy
based rust resisting primer as per IS:2074 followed by filler coats.
d) The transformer shall be furnished with coats of weather resisting battleship gray epoxy
based enamel paint as per IS:2932 specially recommended for transformer use.
e) The paints shall be carefully selected to withstand tropical heat rain, effect of proximity
to the sea etc. The paint shall not scale off or crinkle or be removed by abrasion due to
normal handling.
f) Special care shall be taken by the manufacturer to ensure against rusting of nuts, bolts
and fittings during operation. All bushings and current carrying parts shall be cleaned
properly after final painting.
5.8.2.2 Both H.V. and L.V. bushings shall have creepage corresponding to very heavily polluted
atmosphere.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-28
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-29
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
they shall not obstruct the movements of rollers. The earthing continuity for all the
connected equipments shall be properly done.
b) Two lifting lugs for complete transformer as well as enclosure.
c) Off circuit tapping switch shall be rotary type, 3 pole gang operated, top mounting draw
out type only. Tap switch shall be suitable for rated current considering 20% overloading
& operating voltage. Switch shall be provided with externally operating hand wheel
handle with indicator and locking device, with direction changing facility and locking
arrangement.
e) Rating plate and diagram plate of durable non-corroding metal giving information as
required under IS:2026. Rating plate shall also include Transformer Actual %Z, No-
Load Loss & Full-Load Loss at 75°C along with details like Purchase Order Number,
date. The name plate marking shall be done with fluorescent colour. Each equipment
shall carry individual name-plate with proper instructions & affixed with screws.
5.10 LT Switchgear:
5.10.1 System:-
a) Declared voltage :– 3 Phase,400V (±6%) 50 Hz,
b) Neutral :– Solidly earthed at substation.
5.10.2 General finish:- Tropical, totally enclosed, metal-clad, weather-proof, vermin and dust
proof.
5.10.3 Enclosure:- Type of enclosure shall be able to provide the degree of protection IP:54 .
5.10.4 Circuit Ways:
As per the requirement given in the specifications / schedule of requirement.
5.10.5 Construction :
5.10.5.1 The terminals shall be of sufficient mechanical strength and shall provide
adequate electrical contact for the appropriate size of cable used. They shall be capable
of receiving appropriate size of Aluminum conductors. They shall be provided with
stainless steel nut bolts, plane washers and spring washers for cable connection.
5.10.5.2 The enclosure shall be of sheet steel of 2mm CRC sheet steel, dust vermin proof,
duly powder coated and wired as per standard engineering practice and CPRI tested.
5.10.5.3 No contact pressure shall be transmitted through insulating material & the
gripping of the conductor shall take place between metal faces.
5.10.6 Earthing :
5.10.6.1 Earthing arrangement shall be provided for earthing each cable, PVC cable gland,
neutral busbar, chassis and frame work of the cubicle with separate earthing terminals at
two ends. The main earthing terminals shall be suitably marked .The earthing terminals
shall be of adequate size, protected against corrosion, and readily accessible. These shall
be identified by means of sign marked in a legible manner on or adjacent to terminals.
5.10.6.2 Neutral bus bar strip shall be connected to Earthing terminal with help of copper
strip of suitable capacity & nut-bolt arrangement.
5.10.7 Accessories: The following accessories shall be supplied duly mounted..
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-31
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
One incandescent lamp (with necessary fuse) to illuminate the fuse board internally.
5.10.8 LT Switchgear
Specification/Selection of Air Circuit Breaker and Moulded Case Circuit Breakers:-
1) Upto 160A MCCBs shall be used of 25kA Short Ckt. Current and should be Thermal
Magnetic.
2) From 200A-300A MCCBs shall be used of 35kA short Ckt. Current and should be
Thermal Magnetic.
5.11 LT SYSTEM LT compartment shall be suitable to house following equipment, a) Bus bar
connection from transformer to LT ACB
b) Bus bars and outgoing MCCB’s if called for in the schedule of quantities.
i. IEC-439-1, 1992 Low voltage Switch gear and Control gear assemblies
Part-I, type tested and partially type tested assemblies.
ii. IEC-947-1, 1998 Low voltage Switch gear and Control gear Part-I general
rules.
iii. IEC-1180-1, 1992 High voltage test techniques for low voltage
equipment Part–I definition test and Procedure requirement
.a. Overload releases should be settable from 50% to 100% of the rated current In.
.b. Ambient temperature compensated type and there should not be de-rating of ACB current
carrying capacity at 50°C. The testing of ACB for the temperature rise shall be carried out by the
manufacturer as per the prevailing, IS / IEC or any other international standards.
.c. ACB shall be provided with sensitive overload and short circuit release. Short circuit release
should have settable value as required with an adjustable times, to have a proper co-ordination with short
circuit release of outgoing MCCBs.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-32
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
.(xii) It shall conform to IS 13947 / pt.2 / 1993 with latest amendment, if any.
.a. Performance category -Utilization category – B or as defined by CSS manufacturer.
.b. The status of open and close shall be clearly visible.
.(xiii) The trip indication separated for overload and individual phase wise trip indication for short
circuit to be provided.
.a. The ACB shall have the provision to lock the operating mechanism in off position.
.b. The operating mechanism should be form front and the Enclosure should have the degree of
protection IP – 54.
.c. The CT’s mounted for thermal overload release.
.d. Two nos. earthing bolts for propose of earthing of ACB may also be provided & suitable for G.I
stay wire of size 7 / 10 SWG.
.e. The bus bar size shall be confirming to relevant IS and the neutral bus bar shall be of At least
50% of size as phase bus bar and should be suitable for connecting neutral.
.f. The ACB shall be tested in accordance with the provision of IS: 13947 – Part I or relevant IEC
MCCB up to 250 A with thermal-magnetic releases & beyond 250 A shall be with micro
processor based releases.
Connection between Transformer LT terminals to ACB shall be through 4 pole aluminum bus
bars.
5.12.3 Interconnecting Bus bar Bus bar shall be of high conductivity aluminum (E91E) supported on
insulators made of non-hygroscopic, non-inflammable material with tracking index equal to or
more than that defined in BIS. The main bus bars shall have uniform current ratings throughout
their length as specified in data sheet / job specification. The current rating of the neutral shall be
half that of the phase bus bars. Removable neutral links shall be provided on feeders to permit
isolation of the neutral bus bar.
The hot spot temperature of bus bars including joints at design ambient temperature shall not
exceed permissible limits as per IEC.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-33
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
The current rating of the bus bars shall be as required for design ambient temperature at site
conditions and for being inside the cubicle at fully loaded condition. The vendor shall suitably de-
rate the nominal rating to suit the above condition.
Minimum clearance between live parts, between live parts / neutral to earth shall be sufficient to
meet insulation requirement. However clearances between terminals at components shall be as
per applicable individual standard for components.
Interconnections between the main bus bars and individual units shall be made using vertical /
horizontal aluminum bus bars of adequate rating.
6.0 DESIGN
8.0 DEVIATIONS
Should the contractor desire to deviate from this specification in any way, he shall draw specific
attention to such deviation giving complete reasoning/comparison with other products.
Unless such deviations are recorded in the separately attached Deviation Sheets, as submitted
with offer, it will be taken for granted that the offer is made in conformity with this specification.
Manufacturer shall submit its QAP along with drawings for approval. Inspection of the product
shall be done as per approved QAP.
2. MV/MAIN LT PANELS
2.1 Enclosures of factory Built Assemblies:
2.1.1 Unless otherwise indicated, enclosures shall provide a minimum degree of protection of IP 42
when located within buildings and IP54 when located outside building.
a. Door shall have adequate fastenings with provision for locking in the
closed position.
b. Fixing holes for equipment may be inside or outside the enclosure.
c. Earthing terminals shall be fitted to each enclosure, suitable for internal
and external connection to enable the exposed conductive parts of the
protective conductor.
d. Where the enclosure has a painted finish, provision shall be made for
earthing terminal to be electrically connected to the enclosure without
need to remove any paint from ferrous metal.
e. Cable terminals shall be suitable for the number, size and type of cables as
indicated. Adequate spacing shall be allowed for spreading of cable tails to
avoid stress on the insulation or terminals; if necessary, extension boxes
shall be fitted to standard enclosures. Terminals for neutral conductors for
three phase and neutral circuits shall be the same
conductor, except where reduced section neutral cable cores are indicated.
f. 2 Nos. of Gland Plates for cable entry made of 3 mm thick CRCA sheet,
complete with required Knock Outs shall be provided at top or bottom
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-35
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
with number and size of knock outs to be sufficient for the incoming and
outgoing as specified in the panel details as per site conditions.
g. Metallic enclosures for location within buildings shall have a stove dried
painted finish of the manufacturer’s standard colour, unless otherwise
indicated. Ferrous parts shall be degreased and adequately rust protected
immediately prior to painting.
h. The compartment door shall be interlocked mechanically with the switch
so that the door cannot be opened unless the switch is in OFF position.
Means shall be provided for releasing this interlock at any time.
i. All MCCBs shall be provided with Rotary handle on the front door unless
specifically mentioned otherwise and the panel will be Mechanical &
Electrical interlocked as per NBCC/Client Approval.
j. All Bus bar in LT Panel & Floor Panel shall be made Aluminium Conductor.
2. Construction:
a. Basic Structure:
.a. All electrical panels will be fabricated from 14 SWG thick CRCA sheet steel for robust
construction properly supported with angles and channels.
.b. Panels shall be totally enclosed, dust and vermin proof, fully compartmentalized, cubical design
modular construction. The covers and doors shall be very well gasketted with neoprene rubber gaskets so
as to obtain dust proof enclosure.
.c. The cubicle will be floor-mounted type unless specified otherwise.
.d. The cabinet will be bolt construction.
e. Doors:
.a. Door shall be made of 14 SWG thick CRCA sheet steel, with foamed seal polyurethane gasket,
square section under tabular frame with punching in DIN pitch pattern.
.b. The door will be provided with concealed hinges and panel locks of superior quality. The hinges
will be union joint type to facilitate easy removal of the doors when necessary. Neoprene gaskets shall be
provided beneath all doors and corners and also between adjacent sections, and on gland plates.
.c. The doors will be provided in a similar fashion as generally provided for the outdoor cabinet,
where water cannot enter in the cabinet from the door.
.d. The door will be provided with strengthening arrangement to avoid wobbling and distortion.
.e. Wherever the doors are opened on horizontal hinges, an arrangement will be provided to latch the
doors in an open condition for inspection of the wiring.
.f. Generally meter, relays push buttons, signal lamps and control components will be provided on
separate compartments for in-comer feeders only.
.g. The circuit components will be mounted on sectionalized 3 mm thick CRCA sheet with suitable
threading in the sheets to facilitate easy maintenance, future addition etc..
.h. The panels shall be manufactured with separate bus bar chamber isolated from unit feeder
chambers and cable alleys, to provide extra safety for working personnel.
2. Dimensions:
1. The height of the panel will be as per the drawing but not be more than 2400 mm. Depth
of the panel will not be less than 1000 mm and width of the panel will be given in the
particulars of panel specifications or as per actual site conditions. Shop drawings shall
have to be approved by the NBCC/Client before fabrication is taken up by hand.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-36
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
5. Bus bars:
.a. The bus bars will be of Aluminium with a current density of 1.0 Amp per Sq. mm. The bus bars
will be insulated with heat shrinkable sleeves and properly supported. All live parts shall be shrouded by
means of acrylic / steel /FRP sheets to ensure no accidental contact with live parts during maintenance
and provide simultaneous inspection. The bus bar supports will be designed to withstand short circuit
current equivalent to 35 MVA at 415 volts. The bus bars will be adequately insulated and protected to
prevent accidental contact during operation and maintenance.
.b. Non-hygroscopic SMC supports shall be used for bus bar to give better mechanical and electrical
strength and to ensure capability to withstand specified fault current.
6. Insulation:
a. The insulation between phases and between phases and ground of the power
conductors will be made of synthetic resin board/moulding, resistant to dust and
dampness. All insulating material will be non-hygroscopic, fungus-proof and treated
with suitable synthetic varnishes.
7. Terminals:
a. Up to 35 sq. mm cables, the terminal will be provided of clip-on type generally
manufacture by approved make and above 35 sq. mm, cable end terminals will
provide of brass stud type designed of rugged construction.
8. Wire ways:
a. PVC extruded wire ways of required size will be provided for wiring in the control
panel.
12. Earthing:
a. The earth busbars should be GI/AI unless otherwise specified. Bolts to be of cadmium
plated with washers. Earth bus bars will be provided all around the cubicle at the
bottom with duplex external earth connection arrangement.
d. The MCCB on main LT Panel shall have ratings: 63A, 100A, 125 A, 160
A, 200 A, 250A, 320A, 400A / 630A with 35 KA (minimum) rupturing
capacity.
e. Bus bar should have sufficient mechanical strength to with stand the
effects of short circuit until it can be cleared by appropriate protecting
device. All bus bars should be clearly marked with appropriate colour
code to enable immediate identification of the phase and neutral.
(Mechanical strength up to 50KA/1 Sec).
f. The vertical bus bar should have a number of laminations to give
appropriate current rating and can be graded to suit the current rating
required at each point by omitting laminations at the points of current
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-38
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
decrease.
g. Arrangements should be provided to receive PVC cables either from the
topside or from the bottom (as specified). End plates should be mounted
inside the bus bar at unit level for cables from above or below.
h. All sheet-steel parts used in the construction of a cubicle board should
have undergone rigorous rust proofing process which must comprise of
alkaline degreasing descaling in dilute sulphuric acid and a recognized
phosphate process. The steel work shall be finished with powder coating
paint.
i. The equipment when assembled shall form a neat and compact unit and
shall be complete with supporting framework, mounting channels, and
foundation bolts etc. and shall be designed so as to ensure complete
interchange ability of components.
3. Constructional Feature:
a) Capacitor bank shall be suitable for operation on 415 volts 3 phase, 4 wire, 50 c/s and solidly
earthed AC supply system. The capacitor shall be connected to the 415 V Switchgear bus and
shall be manually as well as automatically
switched in and out in steps so as to correct the power factor as per the required
value depending on the actual KVAR requirement of bus.
b) The capacitor bank shall be complete with the required capacitor units with the
supporting post insulators, sheet steel cubicles, bus bars, connecting strips,
foundation channels, fuses, corrosion proof rating plate etc.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-39
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
are to be given adequate outside insulation and should be put in all welded
surface treated MS containers. These capacitors shall be impregnated with
special grade of capacitor oil under high vacuum. The metal case shall be
equipped with porcelain bushings to permit connection between power lines
and active capacitors.
d) Externally each capacitor unit shall have two separate earthing points, name
plate conforming to the requirements of IS:2834 (amended up to date),
discharge resistance etc.
e) The capacitor bank may comprise suitable number of single phase self cooled
hermetically sealed units in series parallel combination to achieve required
KVAR rating. However, failure of one unit shall not create an over voltage on
other units connected in parallel to avoid failure of parallel units.
h) Capacitor units shall also be protected against internal faults and the effected
units/banks shall be automatically and immediately isolated in the event of such
fault.
i) Each capacitor unit shall continuously operate at the following overload
conditions separately.
4. Each capacitor unit shall be individually protected by HRC fuses/MCCB/MCB with visual indication
for operation as specified.
5. Capacitor Control Panel:
a) The control panel shall be indoor/Outdoor type, floor mounted, dust and
vermin proof conforming to degree of protection IP42/IP54.
b) Cubicle shall comprise rigid structural frame enclosed by 14 SWG thick cold
rolled sheet steel; doors and covers shall be 14 SWG thick cold rolled sheets
steel. Structural framework with foundation bolts etc. shall be provided at the
bottom to mount control panel directly on concrete/floor/steel channel base.
c) All doors, removable covers shall be gasketed all around preferably with
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-40
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
neoprene gaskets.
d) The capacitors control panel shall, in general, comprise of the following and shall
be housed in well-ventilated panels. Capacitors and their control elements may
be installed in different compartments of the same panel to minimize space
requirement.
vi. Change-over switch for either automatic operation or manual operation with push button control.
e) Switches shall be triple pole, air break AC-23 duty. The switch shall have a quick make, quick
break mechanism operated by a suitable external handle complete with position indicator.
f) The compartment door shall be interlocked mechanically with the switch so that the door cannot
be opened unless the switch is in OFF position. Means shall be provided for releasing this
interlock at any time.
g) Fuses (if used) shall be HRC, preferably link type, with a minimum interrupting capacity equal to
the listed short circuit current. Fuses shall be complete with fuse base and fitting of such design
as to permit easy and safe replacement of fuse element. Visible indication shall be provided on
blowing of the fuse.
h) The Contactors shall be Three Pole, Air Break Type designed for duty class III category AC3
with non-bouncing silver alloy contacts. Each Contactor shall be
provided with 2 NC and 2 NO. Indicating lamps shall be LED type shall be
replaceable from front.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-41
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
j) For all bus connections adequate contact pressure shall be ensured by means of
two bolt connection with plain and spring washers and locknuts.
k) Bus bars and connections shall be fully insulated for working voltage with
adequate phase/ground clearance. Insulating sleeves for bus bars and shrouds
for joints shall be provided. Shrouds for bus bar joints and tapping points shall
be of two part epoxy resin cast/fibre glass moulded. Minimum clearance of
33mm is required between phases and between phase and earth irrespective of
sleeve/shrouds provided for bus bar. Insulating shrouds shall be of moulded
type.
l) Bus supports shall be non-hygroscopic type epoxy/SMC/DMC with high creep
age surface.
m) All buses and connections shall be supported and braced to withstand the
stresses due to maximum short-circuit current and also to take care of any
thermal expansion.
n) Bus bars shall be colour coded for easy identification and so located that the
sequence R-Y-B shall be from left to right, top to bottom or front to rear, when
viewed from the front to panel assembly.
o) The horizontal bus bar chamber shall be separate and totally enclosed.
r) All internal wiring inside the cubicle shall be carried out with 1100 V grade,
FRLS insulated copper wires duly ferruled at either end. The power wiring above
100A shall be carried out with PVC insulated aluminium links.
s) Separate labels shall be provided for relay, instruments, switch, indicating lamp
etc. Approval for the type of label shall be taken from the NBCC/Client.
t) Painting shall include emulsion cleaning, pickling with dilute acid, washing and
rinsing by water, phosphating and oven drying. One (1) coat of stoving type zinc
chromate primer and two (2) coats of synthetics enamel.
3.1.1 Construction:
.a. All HT Cables shall be of 11 KV grade XLPE insulated & PVC sheathed flat steel wires (strips)
armoured electrical purity aluminium conductor cables, manufactured and tested in accordance with
IS:7098 (Part II) 1985.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-42
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
.b. The conductor shall be made of electrical purity aluminium wires and shall be of stranded
construction and shall comply to IS: 8130. High quality XLPE unfilled insulating compound shall be used
for insulation.
.c. Insulation shall be carried out by extrusion process and shall be chemically cross-linked in
continuous vulcanization process. Core screen shall consist of a layer of extruded semi-conducting
compound. Additional insulation shield shall
be provided with semi conducting and metallic tape shield over the extruded
insulation shield.
d. Inner and outer sheathing with insulation shall have perfect bonding. Cores shall
be stranded together with suitable non-hygroscopic fillers in the interstices and
provided with common covering of plastic tape wrapping. Armouring shall be
applied over the inner sheath and shall comprise of flat steel wires (strips).
e. Outer sheath shall be of tough, heat resistance PVC compound as per IS: 5831
and shall be extruded over the armouring. Cables shall be tested for type tests
and routine tests in accordance with IS: 7098 (Part II).
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-43
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
3.2.6 For joints in armoured cables, a bonding conductor shall be connected across the
armouring. A spilt ferrule shall be placed under the armouring to prevent
deformation of the cable by the clamp.
3.2.7 At terminations, armouring and metal sheaths shall be connected directly to the
external earthing terminal of the equipment by a bonding conductor. For LV
cables the bonding conductor shall have a cross sectional area in accordance
with IEE wiring Regulations. Metal sheaths of single core cables shall be bonded
and earthed at one point only, as indicated; insulated glands shall be used at the
open-circuit end or ends.
3.2.8 At terminations, cable tails shall be formed by separating and bringing out the
long
cores. Each tail shall be to connect to the terminals of the
enough
equipment.
3.2.9 At the terminations of single core cables, gland plates shall comply with relevant
clause. For three phase circuits, the phase conductors shall be arranged, if
possible, in trefoil formation where they pass through the enclosure of
equipment.
3.2.12 Solder shall be used only for connecting or terminating paper-insulated cables.
All other connections and terminations shall be by means of compression fittings
or mechanical clamps.
3.2.13 Compression connectors and associated dies for compression tools shall be of
correct type and size. Tools shall be so designed that the correct compression
must be applied before it can be released.
3.3.2 Insulating tapes used in joints and terminations shall be compatible with and
have a temperature rating and insulating property not less than the cable
insulation. They shall be complying with BS 3925.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-44
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
3.3.5 Resin filling should be, as far as is reasonably practicable, safe and without risk
to health. Each pack shall include warnings as to any hazards in its use, e.g.
dramatic or toxic properties with details of precautions, which the user must
take to minimize these.
3.3.6 Hot pouring sealing compound shall be hard setting and comply with BS
1858:1973(1986). Selection of the compound shall take account of the ambient
temperature of installation as well as characteristics of the joint.
3.3.7 Care shall be taken to prevent voids occurring in consequence of too rapid
cooling.
10.3.8 Resin filling shall be used with PVC/XLPE type cables and hot poured compound
shall be used with paper insulated lead covered cables.
orange over sheaths, they shall be identified by adhesive bands coloured orange, complying with
BS 178. The bands shall not be less than 100 mm long, located at least once within each separate
compartment through which the cables pass at intervals not exceeding 12 m.
3.6.2 Except where cables are buried or enclosed in conduit, trunking or ducting, they shall be
permanently identified by discs. Discs shall be of laminated plastic materials with black
characters on white: characters shall be not less than 3 mm high. The inscription shall indicate
nominal voltage, designation of load, number and cross sectional area of cores and rated voltage
of cable.
3.6.3 Cable identification discs shall be attached to the cables with ties. Discs shall be located within
500 mm of terminations and joints, at least once within each separate compartment through which
cables pass and at intervals not exceeding 24 m, they shall coincide with the colour bands.
3.8.3 The pipes on road crossings shall preferably be on the skew to reduce the angle of
bend as the cable enters and leaves the crossing. This is particularly important for
high voltage cables.
3.8.5 Pipes shall be continuous and clear of debris or concrete before cable is drawn.
Sharp edges at ends shall be smoothened to prevent injury to cable insulation or
sheathing.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-46
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
3.8.6 Pipe for cable entries to the building shall slope downwards from the building and
suitably sealed to prevent entry of water inside the building. Further the mouth of
the pipes at the building end shall be suitably sealed to avoid entry of water.
3.8.7 All chases and passages necessary for the laying of service cable connections to
buildings shall be cut as required and made good to the original finish and to the
satisfaction of the NBCC/Client.
3.8.8 Cable grips / draw wires and winches etc. may be employed for drawing cables
through pipes/closed ducts etc.
3.9.3 Ducts may be filled with dry sand after the cable is laid and covered as above or
finished with cement plaster especially in high voltage applications.
3.9.4 Splices or joints of any type shall not be permitted inside the ducts.
3.9.5 As far as possible laying of cables with different voltage ratings in the same duct
shall be avoided.
3.9.6 Where considered necessary, hooks or racks shall be provided for supporting the
cables in masonry / concrete cable ducts, cable troughs. Otherwise cables shall be
laid direct in the trench or trough etc. While deciding the layout of cables in such
ducts, care should be exercised to ensure that unnecessary crossing of cables is
avoided.
1. Protection of Cables:
a. The cables shall be protected by bricks laid on the top layer of the sand for the full
length of underground cable. Where more than one cable is laid in the same
trench, the bricks shall cover all the cables and shall project a minimum of
approximately 80 mm on either side of the cables. Cable under road crossings and
any other GI places subject to heavy traffic shall be protected by running them
through Hume / GI Pipes of suitable size as specified.
b. All HT Cables used in building/Block of 11KV shall be XLPE armoured Type
Aluminium XLPE cable with FRLS, manufactured and tested in accordance
with IS: 7098(PART-1) & ISI MARKED.
4.1.1 Cables shall be PVC/XLPE insulated and shall be of 1100 volts grade or as specified and shall
have been manufactured confirming to BS 6346 and Indian Standard Specifications IS: 694 and
IS: 7098 (Part-1) as applicable. These shall be of approved types accepted by the Fire Insurance
Association of India for use in Industrial risks and to the following specifications. The contractor
shall submit the Manufacturer’s catalogues giving electrical characteristics of the cables.
4.1.2 The fire retardant low smoke (FRLS) cables shall be 1100V grade multi core having annealed
tinned copper wires, insulated with special polymeric material suitable to withstand 150 degree
for 30 minutes, cores laid up melinex taped, special low halogen and low smoke elastomeric
material inner sheathed black, armoured with
G.I. Wires/cast steel strips, melinex taped outer sheathed with special low halogen and low smoke
elastomeric material unless otherwise specified.
1. Flexible cables:
a. Twin flexible cables used for pendants and connections to other lighting fixtures shall have
cross-section area or should be of 0.001 sq. inch (equivalent to 23/0.0076) or larger and be
insulated in accordance with relevant IS specifications. The metric equivalent size for
23/0.0076 wherever mentioned may be noted as 23/0.20 mm. All wires and cable shall be of
FRLS type.
.h. At terminations, cable tails shall be formed by separating and bringing out the cores. Each tail
shall be long enough to connect to the terminals of the equipment.
.i. At the terminations of single core cables, gland plates shall comply with relevant clause. For three
phase circuits the phase conductors shall be arranged, if possible, in trefoil formation where they pass
through the enclosure of equipment.
.j. Core identification at terminations shall be by coloured or numbered plastic stretch or shrink ferrules.
.k. Continuity of spare cores shall be maintained at joints and at terminations; the cores shall be
connected to spare terminals.
.l. Solder shall be used only for connecting or terminating paper-insulated cables. All other
connections and terminations shall be by means of compression fittings or mechanical clamps.
.m. Compression connectors and associated dies for compression tools shall be of correct type and
size. Tools shall be so designed that the correct compression must be applied before it can be released.
3. Cable Identification:
.a. For multi core cables, PVC ferrule type indicators or tags shall be provided at both ends for core
identification. For phase identification of 2/3/3.5/4 core cables, coloured PVC tapes shall be used at both
ends.
.b. All cables shall be provided with aluminium tags of approved design, spaced not less than 7.5
meters. Apart and these shall contain the following: Feeder No.
Size
No. of Cores
5. Cable Supports:
.a. Unless otherwise indicated the type of cable supports used shall be selected by the Contractor to
suit the circumstances of the installation, but they shall comply with these specification and the following
preferences shall be taken into account: For Horizontal runs, Cable Tray For vertical runs Clabber Cleats,
Where marshalling of cables occurs e.g. at switchboards Cable Racks.
.b. Unless otherwise indicated all ferrous metal for cable tray, cable racks, and cable ladder, cable
hangers and their fixings and suspensions shall have a galvanized finish.
.c. For general use inside buildings the galvanised finish shall be a coating equivalent to and not less
than type G275 to BS 2989, but manufacturer’s standard finishes will be accepted for slotted angles. All
metal exposed during fabrication shall be given a coat of zinc-rich paint, brushed on or finished to match
the manufacturer’s finish.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-49
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
.d. Metal cable tray shall be used unless otherwise indicated and it shall comply with these
specifications where cables are laid in the cable tray they shall be secured by ties, each tie securing the
cables of only one circuit. The ties shall be of a proprietary type not requiring screws or bolts for fixing
the use of wire or similar material will not be permitted. Ties shall be spaced at not greater than 600 mm
along each cable and within 100 mm of each bend or set.
.e. Where cable tray is installed in the veritable plane, cables shall be supported by cable cleats.
.f. Cable tray shall be fixed at regular intervals not exceeding 1200 mm and at 225 mm from bends
and intersections. A minimum clear space of 20 mm shall be left behind all cable trays
6. Cable cleats:
.a. Cable cleats shall be made from materials, which are resistant to corrosion without the need for
treatment of special finish.
.b. Cable cleats shall be of a size such that they can be tightened down to grip the cables without
exerting undue pressure or strain on them. For vertical cable two bolt cable cleats shall be used which
shall grip the cables firmly enough to prevent them slipping.
.c. The spacing of cable cleats shall comply with the IEEE Wiring Regulations. At bends in the
cable, cleats shall be located immediately on each side.
7. Cable Hangers:
a. Cable hangers shall be used only where indicated. They shall be made from mild steel flat bar
complying with these specifications.
Note: Where cable cleats are fixed direct to concrete, brick or building block, fiber plugs and screws may
be used as appropriate.
.c. No shot firing shall be used and no drilling or welding of structural steel shall be done without
approval of the NBCC/Client.
.d. Suspensions and fixings shall be complying with relevant clause.
.e. Bolts, nuts, washers and screws shall be cadmium or zinc Electroplated or passivity.
9. Bonding:
a. Supplementary bonding shall be installed between component parts of cable trays, racks or
ladders where the method of mechanical connection does not provide permanent and reliable
metal to metal joints of negligible impedance.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-50
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
a. The cables shall be protected by bricks laid on the top layer of the sand for the full
length of underground cable. Where more than one cable is laid in the same
trench, the bricks shall cover all the cables and shall project a minimum of
approximately 80mm on either side of the cables. Cable under road crossings and
any other places subject to heavy traffic shall be protected by running them
through Hume Pipes of suitable size.
b. All LT used in building/Block of .433KV shall be Armoured aluminium XLPE
Cables with solid/stranded copper conductor with FRLS, XLPE insulated,
manufactured and tested in accordance with IS: 7098(PART-1) & ISI
MARKED.
This specification covers the design, manufacture, assembly, shop testing, packing, dispatch,
transportation supply, erection, testing, commissioning, performance and guarantee testing of
Diesel Gen-Sets, complete in all respects with all equipment, fitting and accessories for efficient
and trouble free operation as specified here under.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-53
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
Cooling System : -
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-54
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
-
-
a. By pass thermostat. Fuel
System : -
-
-
-
a. Complete piping
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-55
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
b. Residential silencer (2) to limit the noise level and extending silencer outside the canopy.
Starting System : Consisting of:
-Starter 24V with suitable ampere capacity.
a. Charging Alternator with inbuilt regulator 24 V minimum 30 AMP DC or as per battery capacity.
Connecting links between battery & alternator.
Coupling Arrangement : Consisting of -Flexible coupling -
Flywheel -Flywheel Housing -
Coupling Guard
Instrument Panel : Consisting of:
-Lube oil pressure gauge
-Water temperature gauge
-RMP Indicator & Hour Meter.
-Battery charger ammeter.
iii) BATTERIES
For electrical control ckt of 24V D.C. of suitable ampere hour complete with battery
charger, leads and wooden base plate and shall be placed inside canopy.
5.8 COOLING:
The diesel engine should be Air cooled with air cooled coil coolers system. The
cooling system should include temperature gauge with high temp., alarm/trip
corrosion resistor etc.
regulation and shall be Al type as per BS: 5514 in order to take care of heavy motor
starting. It shall have necessary characteristics to maintain the speed substantially
constant even with sudden variation in load. However, a tripping shall be provided if
speed exceeds maximum permissible limit. The governor shall be suitable for
operation without external power supply.
Safeguards shall be provided and arranged when necessary to stop the engine automatically by
the following:
.a. Energising a solenoid coupled to the stop lever on the fuel injection pump rack.
.b. De-energising the “fuel on” solenoid
.c. Energising the “fuel -cut off” solenoid.
.d. If any of the door opens.
The operation of the safeguard shall at the same time give individual warning of the failure by
illuminating an appropriate local visual indicator and remote alarm at generator panel.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-58
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
The contactors, relays and other devices necessary for signal and control, for above purposes shall
be provided at Generator panel.
At the set at a easily accessible place an “EMERGENCY STOP” mushroom head stay put type
P.B shall provided to stop the set in emergency mode.
The safe guard to “STOP THE SET” shall stop the set irrespective of mode selection of the set
viz Auto, Manual or test for following cases, with simultaneous isolation of alternator ckt.
.a. Emergency stop P.B’s operation
.b. Over speed.
.c. Low lube oil pressure.
.d. Earth fault or restricted earth fault or differential faults of Alternator.
Supplying and fixing 6mm thick laminated mounted sheet inside the window mounted on and i/c
providing and welding 3 nos. G.I. strips 4mm thick of suitable length and having suitable size
tapped holes -10 nos. as required.
Supplying and fixing of 63 Amp terminal blocks suitable for 25 Sq.mm conductor -4 nos. and
fixing DIN channel of suitable length -2 Nos. on the existing laminated sheet with 6A MCB and
cable.
* Each Street Light pole shall have maximum 15-20 meter distance as per electrical layout plan
and approved by NBCC/Client.
* Minimum 20 no’s 4 Meter Pole with 23W CFL Post Top lantern light fixture with Suitable
Rating and all accessories with as approved by NBCC/Client.
* 26W CFL Bollard will be proposed in some areas as per architectural Plan.
SCOPE OF WORK
a. Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC
insulated copper conductor single core cable in surface / recessed medium class PVC conduit,
with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-59
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
b. Wiring for twin control light point with 1.5 sq.mm FR PVC insulated copper conductor single
core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate,
suitable GI box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single
core cable etc as required.
*Stair case as per Electrical layout.
c. wiring for SP MCB controlled light points/ fan point with 2 x 1.5 sq.mm FR PVC insulated
stranded copper conductor wire in surface / recessed pvc conduit, along with 1 No. 1.5 sq.mm FR
PVC insulated copper conductor single core cable for loop earthing as required. (mcb cost are not
included in that item)
*Corridor & common area as per Electrical Layout.
d. Wiring for secondary/loop light point controlled by switch with 2 x 1.5 sq.mm FR PVC insulated
stranded copper conductor wire in surface / recessed pvc conduit, along with 1.5 sq.mm FR PVC
insulated copper conductor single core cable for loop earthing as required.
*Hall & wide areas as per Electrical layout.
a. Modular switch/ socket on the existing modular plate & switch box including connections but
excluding modular plate etc. as required.
* Telephone socket outlet etc as per Electrical Layout.
b. Suitable size GI box with modular plate and cover in front on surface or in recess, including
providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch,
connection etc. as required.
*In all Area’s as per technical Sheet/Electrical Layout.
c. Suitable size GI box with modular plate and cover in front on surface or in recess, including
providing and fixing 6 pin 16 A & 6 A modular socket outlet and 16 A modular switch,
connection etc. as required.
* In all Area’s as per technical Sheet/Electrical Layout.
d. 20amp, 220 volts, SPN/30 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and
earth, metal enclosed plug top along with 20/30 amps “C” curve, TPMCB, in sheet steel
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-60
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
enclosure, on surface or in recess, with chained metal cover for the socket out let and complete
with connections, testing and commissioning etc.
*Specified areas like in kitchen etc as per Electrical Layout.
a. 1x28W T5 light fixture, Recessed Ceiling Mounted with extra slim extruded Aluminium frame,
mat finish open diffuser for glare free and uniform lighting , Electronic driver, pre-wired upto
main connections.
b. 1x28W recessed Linear light fixture, suitable for Techzone false ceiling with white epoxy Powder
coated extruded housing, mat finish open diffuser for glare free and uniform lighting, Electronic
driver, and pre-wired upto main connections.
c. 2x28W Recessed light fixture Ceiling Mounted with single piece pressure die cast powder coated
housing, mat finish open diffuser for glare free and uniform lighting, electronic driver, and pre-
wired upto main connections.
d. 1x28 W light fixture wall/Surface Mounted with electronic driver, minimum 2 no’s bracket
proving for mounting, pre-wired upto main connections.
e. Surface mounted type light fixture suitable for 1 x 28 W T5 fluorescent tube with electronic
driver and mounting arrangement (in contractor scope), pre-wired upto main connections.
f. Wall/Surface type 1x28 W T5 light fixture with electronic drive with mounting brackets, pre-
wired upto main connection.
g. 1x14 W light fixture long wall Mounted with electronic driver, bracket proving for mounting,
pre-wired upto main connections.
h. Bulkhead luminaries suitable for use with PL-S 9W compact fluorescent lamps with frosted glass
having single piece die cast aluminium housing & glass retaining frame, acrylic cover for PL-S
version.
a. Earthing with GI earth plate 600 mm x 600 mm x 6.0 mm thick including accessories, and
providing masonry enclosure with cover plate having locking arrangement and watering pipe etc.
with coke and salt.
* As per Chart.
b. Earthing with Copper earth plate 600 mm x 600 mm x 3 mm thick including accessories, and
providing masonry enclosure with cover plate having locking arrangement and watering pipe etc.
with coke and salt.
* As per Chart.
c. Earthing with GI earth pipe 4.5 meter long, 40 mm dia including accessories, and providing
masonry enclosure with cover plate having locking arrangement and watering pipe etc. with coke
and salt
*As per Chart.
d. Lighting conductor for G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning
conductor complete as required.(For horizontal run) & G.I. tape 20 mm X 3 mm thick on parapet
or surface of wall for lightning conductor complete as required. (For vertical run)
*Cover whole Building top area as per CPWD norms.
e. Any other component/item required for the system.
Earthing Scheme
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-62
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
.a. PVC conduit for wiring shall be used in majority services like-
.a. Lighting
.b. Power
.c. UPS
.d. AC
.e. Data, Voice & all services.
.f. Steel conduit for wiring shall be used in few services like-
.a. Warm & Hazards full area as per NBCC/Client.
.b. Any other component/item required for the system.
.a. All HT Cables used in building/Block of 11KV shall be XLPE armoured Type Aluminium cable,
manufactured and tested in accordance with IS: 7098(PART-1) & ISI MARKED.
.b. Any other component/item required for the system.
.a. All LT Cables used in building/Block of .433KV shall be Armoured Aluminium XLPE Cable
with solid/stranded copper conductor, XLPE insulated, manufactured and tested in accordance with IS:
7098(PART-1) & ISI MARKED.
.b. Copper power cable for UPS.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-63
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
.a. Following size of perforated pre-painted M.S. cable trays with all accessories perforation not
more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S.
suspenders including bolts & nuts, painting suspenders etc as required.
.a. 150 mm width X 50 mm depth X 1.6 mm thickness
.b. 300 mm width X 62.5 mm depth X 2.0 mm thickness
.c. 600 mm width X 75 mm depth X 2.0 mm thickness
.d. 900 mm width X 75 mm depth X 2.0 mm thickness
*Basement, Electrical Shaft, Electrical Room, Pump Room etc size as required.
a. M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and
vitreous enameled white on both sides, and with inscription in signal red colour on front side.
*Minimum 10 number as per CPWD Norms.
b. H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and
vitreous enamelled white on both sides, and with inscription in signal red colour on front side
as required.
* Minimum 5 number as per CPWD Norms.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-64
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
.e. safety instruction chart in word duly framed with 5mm thick glass as required ( Approx front area
1.20 sq.mtr)
.f. Set of 4 No’s .9.5 Litre capacity GI bucket painted in post office red colour with prior coat of red
oxide paint and written with white paint (fire) and mounted on MS angel iron frame with bracket of
appropriate size and capacity including filling sand etc.
h. Insulating mat 1 metre wide 3mm thick to withstand 15 KV dielectric strength as per IS
15652 -200.
* Minimum 20 Meter as per CPWD Norms.
i. Any other component required for the system.
a. UPS On line double conversion (VFI) Appropriate KVA Modular UPS ( Three Phase Input
– Three Phase Output ) ,Nominal Power: Appropriate KVA Power Factor : Unity. Topology:
On Line Double Conversion VFI, Technology: Hi frequency PWM, Passing through Neutral,
Modular Architecture based on 6.7kVA Power Modules, Possibility to configure the system in
N+1 internal redundancy in the inverter cabinet, Possibility to remove and replace power and
battery modules without switch the load on bypass, Equipped with batteries type: lead acid,
sealed, free maintenance, VRLA, installed into the system or in a dedicated external battery
cabinets. Batteries must guarantee a minimum back up time of 15 Minutes with Common
battery bank.
The UPS must be configurable as N+X power redundant system, with modules of 6.7kVA
contained in same cabinet for three phase run. This kind of redundancy must guarantee
continuous supply and protection whenever one module fails. Redundancy must be obtained
through the load sharing technology.
b. UPS Input/output Panel Input/output panel for Appropriate KVA Online UPS,BUS BAR-
Appropriate Amp 3Phase 4Wire 415Volt 50KA, 50Hz Aluminium BUS BAR, Appropriate Amp
4P 36KA Thermal Magnetic MCCB with S/C, O/L, Protection Release for UPS INPUT and
3x320A 4P 36KA Thermal Magnetic MCCB with S/C, O/L Protection Release for UPS
OUTPUT.
*UPS shall feed all Workstation, 50% Corridor Lights, Access Control System,
CCTV System, AV System in Conference room/OPS room/Media room.
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-65
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
FIRE ALARM SYSTEM: The Following Specifications/Items to be provide for Fire Alarm
System
a. Fire Alarm Panel
Networkable Appropriate Loop Micro processor based fire alarm panel, 2 wire fault tolerant loop
with optional network module, each loop shall have the capability of connecting minimum 126
devices. The fire alarm control panel shall have built in degrade mode function. The panel should
have inbuilt TCP/IP communication for Panel Program and Remote Monitoring option through
LAN or WAN communication. The panel shall be able to give location of all fire and More Fire
/fault and Isolation conditions of addressable units via the address codes. The panel shall have the
capacity of storing upto 2000 events. Further, the panel must be able to automatically switch ON
/OFF respective control module when ever any alarm is triggered. The panel should have inbuilt
common Alarm, Fault and monitored sounder output. The panel shall have a 8x40 characters
LCD display with resolution of Appropriate pixels, and analog output with optional inbuilt /
external printer to log all fire or fault events complete in all respects. The Panel should have
protection category of IP30. Also the panel should have the option to operate in manned and
unmanned mode. The Panel shall have the option of 24/48/96 Zones with Individual LED
Indicators or within the Loop mimic driver for 96 LED indicators. The panel shall have built in
power supply and battery charger along with maintenance free Appropriate AH, Appropriate volt
SMF Lead acid batteries capable of running for a minimum of 24 hours with battery charger
complete as required and as per specifications and duly Approved by EN54/LPCB/VDS/FM.
*1 no’s Main Fire Control Panel located at Fire Control Room on ground floor.
b. Repeater Panel
Analog Addressable type Active Loop Repeater (Loop power/external power) Fire terminal with
inbuilt turbo isolator, Backlit LCD Display 6x40 characters display, having Controls For Reset,
Mute, Accept , Silence alarms and Self Test, with programmable free keys and Duly Approved by
EN54/LPCB/VDS/FM
c. Response Indicator Response Indicator with matching screws complete, Cable lugs at cable end
and ferruling.
*To be provided with above ceiling detector.
d. Multi-Sensor type Smoke Detector Intelligent Analog Addressable Multi-Sensor type Smoke
Detector with inbuilt turbo Isolator and integral response indicator with 360 degree viewing
angle. Detector shall communicate 3 danger levels for differentiated alarm activation and high
tolerance to dust,dirt, temperature fluctuations and air currents. Detector should have unque
address for communication and assigned through panel with Mounting Base as required with the
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-66
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
* Manual Call point shall used in each floor near stair cases.
h. Addressable Input & Input/output module Addressable input/output module with inbuilt isolator
and shall have the LED indication for Normal, Fault, test, and activation. The module shall have
the option for configuration as fail safe operation and duly approved by EN54/LPCB/VDS/FM.
* To be provided in adequate numbers at appropriate place as per the whole system.
i. Fire Survival Low Smoke Armoured cable 2 twisted pair x 1.5 mm, Multistranded AT Copper,
Fire Survival Low Smoke Armoured cable, RED in Colour, laid on surface with GI saddle-
spacers every 0.3 meters. Complete with Junction Box, lugs, cable tags and Ferruling.
rear door, ventilation grills on all sides, 2 set of castor wheel, 230 V AC 90 CFM fan 4 ,Mounting
Hardware, Cable manager Horizontal 1U, PDU
*To be provided in adequate number on each floor as per final Data/voice Scheme.
b. Wall Mounting Cabinet 12 U Wall mountable cabinet with reversable door made of tinted glass.
Mounting Hardware Cable manager Horizontal 1U, PDU.
*To be provided in adequate number on each floor as per final Data/voice Scheme.
c. Universal module Category 6 & Category 5e RJ45, 8-position, 8-wire universal module.TG Style,
Right angle wire cap allows cable to be terminated to right side of module. Blue.
*To be provided in adequate number on each floor as per final Data/voice Scheme. .
d. 4-pair, UTP copper cable Enhanced Category 6 & Category 5e, CM, 4-pair, UTP copper cable.
Copper conductors are 24 & 23 AWG construction with HDPE insulation. Conductors are twisted
in pairs, separated by an integrated pair divider, and protected by a flame-retardant PVC jacket.
e. Face Plate Single gang, 86mm x 86mm shuttered faceplate with label and icon slots. Accepts
Two & Four Mini-Com™ Modules. Includes two M3.5-0.5 x 30mm pan head mounting screws.
*To be provided in adequate number on each floor as per final Data/voice Scheme.
f. Patch Panels Category 6(For Data) & 5e (For Voice) /Class D, punch down patch panels shall
terminate 4-pair, 22 – 26 AWG, 100 ohm unshielded twisted pair cable with an industry standard
single wire 110 punch down tool. Patch panels shall include a universal label coded for T568A
and T568B wiring schemes and mount to 19" and 23" racks. Patch panels shall be easy to identify
with pre-printed numbers, write-on areas and optional label kits
*To be provided in adequate number on each floor as per final Data/voice Scheme.
g. Patch Cords for data & Voice Category 6 (For Data) & 5e (For Voice), UTP patch cords shall be
constructed of 24 AWG unshielded twisted pair stranded copper cable with an enhanced
performance modular plug at each end. Patch cord cable shall be offered in multiple colored UTP
cable for design flexibility with a clear strain relief boot on each modular plug. All patch cords
shall be compatible with both T568A and T568B wiring schemes. Blue UTP Cable, 2 Meter & 1
Meter.
*Patch cord 1 meter category 5e for Voice & Patch cord 1&2
meter Category 6 for Data. *To be provided in adequate
_____________________________________________________________________________________________
Signature of Contractor NBCC Ltd. TS Elect-68
NBCC (India) Ltd. South Zone Construction of NIA, Branch Office and Residential Buildings & Allied
works at Hi-tech City Hyderabad
ii. LC to pigtail simplex pigtail, 900µm buffered fiber (one LC connector on one end and open
on the other end) – 9/125µm. 900µm buffered fiber, SC to LC patch cord
iii. SC to LC patch cord, OM3 MM, riser, duplex (1.6 mm jacket) (two SC connectors on one
end and one duplex LC connector on the other end) – 9/125µm.
.iv. Rack Mount LIU which Pre-loaded fiber drawer with 12 LC duplex adapters for 50/125μm
(OM3/OM4) multimode fiber
.v. 6-fiber 10Gig™ 300 50/125μm Cable.
_____________________________________________________________________________________________