The document provides general notes and specifications for an electrical installation project. It specifies that all electrical work must comply with relevant codes and regulations. The power service will be 220V, 1ø, 2 W + ground and 60 Hz. All conductors shall be copper THHN wire with a minimum size of 3.5mm, with specific colors for lines, ground and neutral wires. Mounting heights for electrical equipment such as outlets and switches are listed, though the architect will determine final heights and locations. All materials must be new and approved types. Non-current carrying metal parts must be grounded, and the contractor must submit shop drawings for routing approval. A licensed electrical engineer must supervise all electrical works.
The document provides general notes and specifications for an electrical installation project. It specifies that all electrical work must comply with relevant codes and regulations. The power service will be 220V, 1ø, 2 W + ground and 60 Hz. All conductors shall be copper THHN wire with a minimum size of 3.5mm, with specific colors for lines, ground and neutral wires. Mounting heights for electrical equipment such as outlets and switches are listed, though the architect will determine final heights and locations. All materials must be new and approved types. Non-current carrying metal parts must be grounded, and the contractor must submit shop drawings for routing approval. A licensed electrical engineer must supervise all electrical works.
The document provides general notes and specifications for an electrical installation project. It specifies that all electrical work must comply with relevant codes and regulations. The power service will be 220V, 1ø, 2 W + ground and 60 Hz. All conductors shall be copper THHN wire with a minimum size of 3.5mm, with specific colors for lines, ground and neutral wires. Mounting heights for electrical equipment such as outlets and switches are listed, though the architect will determine final heights and locations. All materials must be new and approved types. Non-current carrying metal parts must be grounded, and the contractor must submit shop drawings for routing approval. A licensed electrical engineer must supervise all electrical works.
The document provides general notes and specifications for an electrical installation project. It specifies that all electrical work must comply with relevant codes and regulations. The power service will be 220V, 1ø, 2 W + ground and 60 Hz. All conductors shall be copper THHN wire with a minimum size of 3.5mm, with specific colors for lines, ground and neutral wires. Mounting heights for electrical equipment such as outlets and switches are listed, though the architect will determine final heights and locations. All materials must be new and approved types. Non-current carrying metal parts must be grounded, and the contractor must submit shop drawings for routing approval. A licensed electrical engineer must supervise all electrical works.
BE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE RULES, REGULATIONS AND REQUIREMENTS OF THE LOCAL POWER COMPANY AND THE LAWS AND ORDINANCES OF LOCAL ENFORCING AUTHORITY.
2. THE TYPE OF POWER SERVICE SHALL BE
220V, 1ø, 2 W + GROUND, 60 CYCLES.
3. ALL CONDUCTORS SHALL BE COPPER, TYPE
THHN 90˚C, 600 VOLT INSULATION, MINIMUM SIZE SHALL BE 3.5mm (NO. 12 AAWG.) UNLESS OTHERWISE SPECIFIED. COLOR OF THE CABLES SHALL BE AS FOLLOWS: LINE WIRES – FOR SINGLE-PHASE CIRCUIT YELLOW AND WHITE AND THREE PHASE CIRCUIT, RED, YELLOW AND BLUE; GROUND WIRE – GREEN; NEUTRAL WIRE – WHITE.
4. UNLESS SHOWN, OTHERWISE, THE
MOUNTING HEIGHT FROM FINISHED FLOOR LEVEL FOR THE VARIOUS ITEMS OF ELECTRICAL EQUIPMENTS SHALL BE AS FOLLOWS : RECEPTACLE OUTLETS – 300mm TO CENTER LINE: LIGHTING SWITCHES – 1200mm TO CENTER LINE; DISTRIBUTION BOARD – GENERALLY 1400mm TO CENTER LINE OF MAIN CIRCUIT BREAKER OR AS PER ARCHITECTURAL RECOMMENDATION. FINAL MOUNTING HEIGHTS AND LOCATIONS OF ELECTRICAL DEVICES SHALL BE DETERMINED BY THE ARCHITECT UPON COORDINATION WITH THE ELECTRICAL ENGINEER AND FURNITURE SUPPLIER.
4. ALL MATERIALS SHALL BE NEW AND OF
THE APPROVED TYPE IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS FOR THE LOCATION INTENDED.
6. ALL NON-CURRENT CARRYING METAL
PARTS OF ELECTRICAL EQUIPMENT AND LIGHTING FIXTURE SHALL BE EFFECTIVELY GROUNDED.
7. RACEWAY AND OTHER WIRE ROUTING
SHOWN ARE ONLY REPRESENTATION. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS ON ALL PROPOSED ROUTING (SHOWN OR EVEN NOT SHOWN IN THE PLAN) AND INSTALLATION FOR APPROVAL.
8. ALL ELECTRICAL WORKS SHALL BE DONE
UNDER THE DIRECT SUPERVISION OF A DULY LICENSED/REGISTERED ELECTRICAL ENGINEER.