Tech Spec-IEM EE

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 72

IMPERIAL ERA MANSION PROJECT

Pasay City, Metro Manila

TECHNICAL SPECIFICATIONS FOR ELECTRICAL


WORKS

July 16,2018
Date

RENATO A. EUGENIO
Professional Electrical Engineer

Reg. No. : 3371


TIN : 168-954-684
PTR No. : 66-159-962
Date Issued : January 05,2018
Place Issued : Makati City
IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16 – ELECTRICAL

TABLE OF CONTENTS

SECTIONS CONTENTS

16000 ELECTRICAL GENERAL REQUIREMENTS

16030 INTERIOR WIRING SYSTEM

16164 PANELBOARDS

16400 LOW VOLTAGE SWITCHBOARDS

16112 BUSWAY

16401 AUTOMATIC TRANSFER SWITCH (ATS)

16208 DIESEL ENGINE GENERATOR

16400 PADMOUNTED TRANSFORMER

16402 UNDERGROUND ELECTRICAL WORKS

16100 GROUNDING SYSTEM

16601 LIGHTING PROTECTION SYSTEM

16160 TESTING

16720 FIRE DETECTION AND ALARM SYSTEM

16727 SECURITY SYSTEM

16760 TELEPHONE SYSTEM

R.A.EUGENIO + PARTNERS Page 1 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16: ELECTRICAL


SECTION 16000
ELECTRICAL GENERAL REQUIREMENTS

PART 1.00 – GENERAL

1.1 GENERAL DESCRIPTION

A. The work to be done under this Division of the Specifications consists of the fabrication, furnishing,
delivery and installation, complete in all details of the Electrical System, at the project premises
and all work materials incidental to the proper completion of the installation, except those portions
of the work which are expressly stated to be done by others. All works shall be in accordance with
the governing Codes and regulations and with the specifications, except those where same conflict
with such Codes, etc., where the latter shall then govern. The requirements with regards to
materials and workmanship specify the required standards for the finishing of all labor, materials,
and appliances necessary for complete installation of the work specified herein and indicated in
the drawings. The Specifications are intended to provide a broad outline of the required
equipment, and are not intended to include all details of design and construction.

B. SITE OF WORK

Pasay City, Metro Manila

C. SCOPE OF WORK

Under this section of the specification, provide all labor, materials and equipment and perform all
the work necessary for the complete execution of all Electrical System as shown on Electrical
Drawings. Scope of Work shall include but not be limited to the following principal items of work:

1. Furnish and install all conduits for power, telephone and CATV service entrances.

2. Furnish and install all feeder and distribution wires and conduit for power, telephone, and
auxiliary system as required on the plans.

3. Furnish and install busway, support and fittings as required on the plans.

4. Furnish and install main circuit breaker, generator emergency switchboard, automatic transfer
switch, distribution and lighting panelboard, circuit breaker and disconnect switches, meter
center and other protective devices as required on the plans.

5. Furnish and install complete distribution for lighting, power and fire detection and alarm
system to include conduits, wiring devices as required on the plans.

6. Furnish and install a complete wiring system for all pumps and motors to include conduits,
wires and fittings up to circuit breaker protection. Circuit breaker protection shall be included
as indicated in the plan.

7. Furnish and install complete telephone system to include conduit, cable, terminal block,
wooden backboard, house wiring and other related accessories as indicated in the plan.

R.A.EUGENIO + PARTNERS Page 2 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

8. Furnish and install all feeder wires and conduit complete with support and other related
accessories as indicated in the plan.

9. Application of electric power, telephone and CATV connection including preparation of all
necessary plans, forms and related documents, payments of all required fees and charges
and coordination with other authorities or person involved in the procedure.

10. Perform all terminations to include testing.

11. Preparation of as-built plans and drawing.

12. All work materials, equipment, fittings, support, etc. that are indicated in the plans but are
necessary for the completion of the works must be included in this division of work.

Works Not Included:

1. Furnish and installation of power service, telephone and CATV service entrance cable
facilities and hardware including termination except for entrance conduit.

2. Furnish and installation of pad mounted transformer and generator set as indicated in the
plan.

QUALIFICATIONS

A. Seismic Restraints – Seismic restraints shall be provided for all electrical equipment and
installation for Zone 4 seismic forces. The Contractor shall be responsible for certifying the
adequacy of seismic restraints details. Restraints shall consist of isolator with independent
bumpers, rigid connections, slack cables, expansion joints, flexible joints and others as required
restraints shall be submitted for review to the Architect.

B. Sleeves, Chases and Openings

1. Furnish templates, sleeves or details for chases and openings to be left in the floors and
walls to accommodate the work. Layout the work in accordance with accepted shop drawing.
Furnish and set in place in advance of pouring of slabs or construction of walls, all inserts and
sleeves necessary to complete the work.

2. Pipe sleeves for all electrical conduits passing through walls, partitions, ceiling, floors, etc.
shall be of sufficient length to extend through the full thickness of the construction, with ends
flush with the finish on each side, unless noted otherwise.

3. Chases, sleeves and openings in fire rated walls and floors (electrical room, etc.) shall be
“fire stooped” with acceptable fire safe insulation. Fire safe details shall be based on UL listed
assemblies “Hilti”, “Specsael” or approves equal.

C. Access Panels (By Main Contractor – For Reference Only)

1. Coordinate size and location of access panels as required for access to pull boxes and
electrical equipment. Where, in the opinion on the Contractor, access panels are required,
but are not shown on the drawings, the omission shall be brought to the attention of the
Architect before installation of equipment, all access panels and their sizes shall be noted on
shop drawings.

R.A.EUGENIO + PARTNERS Page 3 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

D. Equipment Foundations and Support

1. All floor mounted equipment and apparatus will be provided with necessary concrete
pedestal, base, pads, curbs and anchor blocks as shown or required. Provide anchor bolt,
slab insert, supports, hangers and sleeves as may be required or necessary for proper
support or attachment to the building structures for all conduit, equipment and apparatus.

2. Concrete pads shall be 150mm high unless otherwise indicated, with steel reinforcing and
necessary bolts, anchors, etc. Where concrete pad is set directly on concrete floor, provide
dowels in floors to tie base to floor. Pads shall be extended at least anchor bolts, etc. to the
Main Contractor. Provide acceptable seismic restraints anchor plates flush with top of
housekeeping pads are required.

1.3 SUBMITALS

Specified items requiring submittals shall be as specified, shop drawings shall be submitted and approved
by procurement, fabrication or delivery of such item to the job site. Partial submittal will not be acceptable;
such submittals will be returned without review.

A. MANUFACTURER’S DATA

Submittals for each manufactured items shall include manufacturer’s descriptive literature,
equipment drawing, diagrams, performance and characteristic curves and catalog cuts. Each
submittal shall have the manufacturer’s name, trade catalog model or number, nameplate date,
size, layout, dimensions, capacity, specification reference, Industry Specification references, and
all other information necessary to establish contact compliance.

B. SHOP DRAWING

Shop drawings shall show all types, sizes, accessories, elevations, floor plans, sectional views,
installation details, elementary diagrams and wiring diagrams. Wiring diagrams shall identify circuit
terminals and shall indicate the internal wiring for each item of equipment and the interconnection
between the items. Drawings shall also indicate adequate clearance for operation, maintenance
and replacement of operating equipment devices. If any equipment is disapproved, the drawings
shall be revised to show acceptable equipment and may be re-submitted.

C. STANDARD COMPLIANCE

When materials or equipment must conform to the standards of organizations such as American
National Standard Institute (ANSI), American Society for Testing and Materials Association
(NEMA) and Underwriter’s laboratories (UL), proof of such conformance shall be submitted to the
Engineer for approval.

If an organization uses a label or listing to indicate compliance with a particular standard, the label
or listing will be acceptable evidence, unless otherwise specified in the individual sections. In lieu
of the level or listing, the Contractor shall submit a certificate from and independent testing
organization, which is competent to perform acceptable test and is approved by the Engineer. The
certificate shall state that the item has been tested in accordance with the specified organizations
test methods and that the items conforms to the specified organization’s standards. For material
and equipment, whose compliance with the organizational standards or specifications is not
regulated by an organization using its own listing or label as proof of compliance, a certificate of
compliance from the manufacturer shall be submitted for the approval. The certificate shall identify
the manufacturer, the product and the reference standard and shall simply state that the

R.A.EUGENIO + PARTNERS Page 4 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

manufacturer certificate that the product conforms to all requirements of the project specification
and of the reference standard listed.

D. CERTIFIED TEST REPORTS

Before delivery of materials and equipment, certified copies of all test reports specified in the
individual section shall be submitted for approval.

E. OPERATION AND MAINTENANCE MANUAL

The Contractor shall furnish an operation and maintenance manual for each System and for each
piece of equipment. Five (5) copies of the complete manual bound in hardback binders or an
approved equivalent shall be provided to the Owner, one manual shall be furnished before the
contract is completed.The following identification shall be inscribed on the cover: the words “
OPERATING AND MAINTENANCE MANUAL”, the name and location of the project and the name
of the Contractor, the manual shall include the names, addresses,and telephone number of each
sub-contractor installing the equipment and system, and of the local representatives for each item
of equipment and each system. The manual shall have a table of contents and be assembles to
conform to the table of contents with the tab sheets placed before instruction covering the subject.
The instructor sheets shall be legible with large sheets of drawings folded in. the manual include,
but not limited to the following: a system layout showing circuit, devices and control; wiring and
control diagram with data to explain detailed description of the function of each principal
component of the system, the procedure for operating: shutdown instruction; installation
instruction; maintenance instruction; test procedures; performance data; and parts list.

The parts list for equipment for shall indicate the sources of supply, recommended spare parts,
and the service organization, which is reasonably convenient to the building site. The manual shall
be complete in all respects for all equipment, controls and accessories provided.

1.4 DELIVERY AND STORAGE

Equipment and material shall be properly stored and adequately protected and carefully handled to
prevent damage before and during installation. Equipment and materials shall be handled, stored and
protected in accordance with the manufacturer’s recommendations and as approved by the Engineer.
Cables shall be sealed, stored and handled carefully to avoid damage to the covering or insulation and
damage from moisture and weather. Damaged or defective items hall be replaced with new items at no
cost to the Owner.

1.5 CATALOGED PRODUCTS

Materials and equipment shall be cataloged products of manufacturer’s regularly engaged in production
of such materials or equipment and shall be of manufacturer’s latest standard design that complies with
the specification requirements. When two or more units of the same type, class and size of equipment are
required, these units shall be the products of a single manufacturer; and serial number on a nameplate
securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.

1.6 MANUFACTURER’S RECOMMENDATIONS

Where installation procedures are specified to be in accordance with the recommendations of the
manufacturer of the material or equipment being installed, printed copies of these recommendations shall
be furnished to the Engineer prior to installation. Installation of the item will not be allowed to proceed until

R.A.EUGENIO + PARTNERS Page 5 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

the recommendations are receive. Failure to furnish these recommendations can be a cause for rejection
of the material.

1.7 COORDINATION

Electrical work shall be coordinated with other trades involved in the construction of the project. All work
shall be carefully laid out in advance, coordinating electrical features with architectural and structural
features of construction.

1.8 CODES, INSPECTIONS, PERMITS AND FEES

A. The work under this Contract is to be installed according to the requirements of the latest edition of
the Philippine Electrical Code, the rules and regulations of the local authorities.

B. All permits and fees required for this work shall be obtained by and at the expense of the Contract.
The Contract shall furnish the Engineers and the Owner final certificates of electrical inspection
and approval from the proper government authorities after completion of the work. The Contractor
shall prepare all as built and all forms and documents required by the approving authorities.

1.9 RECORD DRAWINGS

The Contractor shall, during the progress of the work, keep a careful record of all changes where the
actual installation differs from that shown on the Contract Drawing. Upon completion, the Contractor
shall, in a neat and accurate manner, finalized “As-Built” drawings of tracing paper. These drawings shall
be submitted to the Engineers for approval. Final payment will be withheld until receipt of the approved
record drawings showing circuit runs and pull boxes with sufficient information for future re-wiring,
maintenance and identification. The final submittal of record drawings shall be in one (1) set original
tracing paper, three (3) sets of blue prints and one (1) set electronic copy of “As-Built Drawings” of
Electrical System Works. The print copies shall be duly signed and sealed by a Registered Professional
Electrical Engineer of the Contractor. These approved final submittals shall become property of the
Owners.

1.10 MINOR MODIFICATIONS

The plans as drawn are based upon architectural plans and details and show conditions as accurately as
it is possible to indicate them in a scale. The plans are diagrammatic and do not necessarily show all
fittings, etc., necessary to fit the conditions. The location of the equipment, apparatus and appliances
shown on them are approximate. Contractor shall be responsible for the proper location in order to make
them fit with architectural details and instructions from Owner’s representative at the site.

1.11 GUARANTEES

A. The contractor shall guarantee that the system are free from all grounds and from all detective
workmanship and materials and will remain so for a period of one year from date of acceptance of
work. Any defects, appearing within aforesaid period,shall be remedied by the Contractor at his
own expense.

B. The Contractor shall indentify and save harmless the Owner and the Engineers from and against
all liabilities for damages arising from injuries or liabilities to persons or damage to property
occasioned by any act or omission of the Contractor or any of his Sub-Contractor, including, any
and all expenses, legal or otherwise, which may be incurred by the Owner or the Engineers in the
defense of any claim, action or suit.

R.A.EUGENIO + PARTNERS Page 6 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

1.12 SUB-CONTRACTOR, ETC.

The Contractor shall be held fully responsible for the work of any sub-contractor or manufacturer
performing work or supplying material and ascertain that the work, when finally delivered to the Owner,
shall be ready in every respect for satisfactory and efficient operation.

1.13 WORKMANSHIP

A. The work throughout shall be executed in the best and the most thorough manner under the
direction of the Contractor and to the satisfaction of the Owner and the Engineers who will

jointly interpret the meaning of the drawings and specification and shall have authority to reject any
work materials which, in their judgment, are not in full accordance therewith.

B. The Contractor shall have on file, for ready access and reference, a set of drawings indicating all
work as actually installed incorporating in the same all changes and additions. Upon the
termination of the Contract, he shall prepare a set of tracing indicating thereon the work as actually
and finally installed. The drawings shall be returned over to the Engineers.

C. The Contractor shall be responsible for keeping stocks of material and equipment stored on the
premises in a neat and orderly manner.

1.14 CONTRACT DRAWINGS

A. The location of outlets, apparatus and equipment indicated on the drawing are shown as
accurately as possible, that the small scale drawings are necessary diagrammatic and that such
location, as shown, are subject to slight revisions, as the work is installed which may be necessary
to fit construction conditions. No major changes shall be made, however without the approval in
writing of the Engineers.

B. The Contractor shall examine and study the architectural scale drawing large scale and full size
detail. The approved shop drawing of other parties and he shall frequently consult with them to
ascertain any changes that may have been made and he shall be guided accordingly before
establishing the precise location of conduits runs, pull and junction boxes and devices. All outlets
covered or partially covered by ducts, piping, etc., shall be extended laterally or to underside of
same so that the equipment may be properly installed.

C. The Contractor shall effectively protect his own work from damage during, and as may be
necessary after installation, and he shall likewise protect adjoining work of other parties from
damaged resulting from his installation.

1.15 LOCATION OF WIRING AND EQUIPMENT

A. The Contractor shall coordinate his work with all parties involved so that exact locations may be
obtained for all apparatus, appliances and wiring.

B. The location of equipment shown on diagrammatical wiring plans shall be considered as


approximate and it shall be incumbent upon the Contractor before installation. To study all
pertinent drawings and obtain precise information from the architectural schedules, scale
drawings, large scale and full size details of finished rooms, approved shop drawings of other
parties involved or from the Engineer.

R.A.EUGENIO + PARTNERS Page 7 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

1.16 BUILDING PROVISION

Certain provisions have been made in the Building for the accommodationof electrical installation these
provision include space allocation, holes through beams and structural slabs, etc. The provisions so
made are shown on the drawings. Before proceeding with the works, the Contractor is to check and
confirm that the provisions are adequate and satisfactory for the works, and where necessary, additional
information is to be provided.

It is the Contractor’s responsibility to ensure that the Builder is informed of all holes required in the
structure. Any subsequent structural openings required due to negligence in providing sleeves
beforehand shall be at the expense of the Contractor unless they are covered on duly authorized variation
order issued by the Architect.

It is the Contractor’s responsibility to ensure that all holes, openings, etc. are provided correctly during
construction of the building.

1.17 MATERIALS PROPOSED

The Contractor is required to state in his bid the manufacturer and type proposed for all materials to be
used for the works. Any alternative offer shall be submitted at the time of bidding.

Samples of the materials to be used shall be submitted to the Architect/Engineer for approval before
procurement and/or installation.

1.18 INTERPRETATION OF SPECIFICATION

Any queries regarding the interpretation of the specifications of the drawings may be addressed to the
Architect or Engineers in writing before submission of bid. The Contractor will be deemed to have
satisfied himself that he is able to comply in all respects with the plans and specification to a degree
acceptable to the Architect and Engineers.

1.19 MAINTENANCE AND DEFECTIVE LIABILITY PERIOD

The defective liability period shall be twelve (12) months starting from the date of satisfactory completion
of the work and formal acceptance of the work by the Owner.

If any defects or sign of deterioration occur to the said work within such period, the Contractor shall be
liable to make good all such defects at his own expense and to the satisfaction of the Architect and
Engineers. The period of maintenance of such repaired work shall be extended to a further three (3)
months.

1.20 SUBMITTAL REQUIREMENTS

A. All submittals shall be submitted within sixty (60) days from the issuance of notice to proceed.

B. Materials and equipment requiring samples, catalogue, data, shop drawing and manufacturer’s
certification shall be as indicated in the specification.
1
C. Material samples shall be fixed on 6mm ( /4 inch) thick plywood of sufficient size and fully labeled

D. Quantity of submittals shall be six (6) sets one (1) sepia prints for shop drawings and seven (7)
sets for catalogue data and manufacturer’s certification.

R.A.EUGENIO + PARTNERS Page 8 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

E. Submittals of the Contractor shall be reviewed and returned within a minimum 0f 21 days, each
stamped “REVIEWED” and “A”, “B”, or “C”, “ACTION”. The review actions are as follows:

“A” ACTION means that fabrication, manufacture or construction may proceed provided
submittal complies with the Contract Documents.

“B” ACTION means that fabrication, manufacture or construction may proceed provided
submittal complies with the Consultant’s notations and the Contract Documents. If, for
any reason, the Contractor cannot comply with the notations, the Contractor shall
resubmit as described for submittals stamped “C” ACTION.

“C” ACTION means that submittals does not comply with the Contract Documents and that
fabrication, manufacture or construction shall not proceed. Submittals stamped “C”
ACTION are not permitted on job site. Contractor shall make revisions and resubmit.

*** End of Section ***

R.A.EUGENIO + PARTNERS Page 9 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16:ELECTRICAL
SECTION 16030
INTERIOR WIRING SYSTEM

PART 1.00 – GENERAL

1.2 GENERAL REQUIREMENTS

Section 16000, “Electrical General Requirements”, applies t this section with additions and modification
specified herein. In the standards referred to herein, consider the advisory provision to be mandatory, as
though the word “shall” wherever it appears. Interpret reference in these standards to the “authority
having jurisdiction”, or words of similar meaning, to mean the Engineer.

1.3 SUBMITTALS

D. MANUFACTURER’S DATA

1. Wiring Devices (each type)


2. Conduit and Fittings (each type)
3. Insulated Conductors
4. Junction and utility Boxes
5. Panelbaord Circuit Breakers
6. Others as required

E. SHOP DRAWINGS

1. Panelboard (lighting and distribution panels)


2. Support details including hangers, brackets and clamps.
3. Others as required.

PART 2.00 - PRODUCTS

A. CONDUIT AND FITTINGS

1. Conduit in general shall be Intermediate Metallic Conduit (IMC) with an interior coating as
manufactured by “Panasonic”, “McGill” or approved equal.

2. Poly-vinyl-chloride (PVC) conduit shall be heavy wall, schedule 40, with factory made bends,
couplings and fittings “Atlanta”, “Moldex” or approved equal.
1
3. No conduits shall be used in any system smaller than 15 mm ( /2 inch) diameter electric
trade size, nor shall have more than four (4) 90 degree bends in any one run and where
necessary, pull boxes shall be provided as directed.

4. No wire shall be pulled into conduit until the conduit system is completed in all details, in the
case of concealed work until all rough plastering masonry has been completed, and in the
case of exposed work until the conduit work has been completed in every detail.

5. The ends of all conduits shall be tightly plugged to exclude plaster, dust and moisture while
the construction of building is in progress. All conduits shall be reamed to remove all burns.

R.A.EUGENIO + PARTNERS Page 10 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

6. All pipes and fittings on exposed work shall be IMC and be secured by means of metal clips,
which shall be held in place by means of machine screws. When running over

concrete surface, the screws shall be held in place by means of expansion sleeves. All pipes
on exposed work shall be allowed and all bends and offsets shall be avoided as much as
possible. Where necessary, conduit fittings shall be used. Conduits in all cases shall be run
perfectly straight and true, satisfactory to the Engineer. Conduits shall be supported at 1.50
meter interval maximum.

B. OUTLETS, BOXES AND FITTINS

1. At all outlets of whatever kind, for all system, there shall be provided a suitable fitting, which
shall be either a box or other device especially designed to receive the type of fitting to be
mounted thereon.

2. The Contractor shall consult with the Engineer as to the nature of the various fittings to be
used before installing his outlet fittings and shall conform strictly in the use of fittings to the
nature of the appliance to be mounted on them so that the work, when completed, will be a
finished design.

3. At all outlets on concealed conduit work provide galvanized pressed steel outlet boxes of
standard make. These boxes shall be in all cases standard and where such boxes are not
available on the market, fabricated boxes shall be provided by the Contractor at his own
expense. In general, boxes shall be at least 100mm in diameter, 53 mm deep and 2mm
minimum gauge.

4. All utility boxes intended for outlet devices shall be especially designed to receive the
particular type of device to be mounted and should be deep enough to accept and fit the
total number of conductors and device required.

5. Boxes shall be as manufactured by “Steel City”, “IMS” or approved equal.

6. In case of lighting fixtures, their outlet fittings shall be provided with suitable supports of size
and kind required by the lighting fixture to be hung. Fixture studs shall be 9 mm dia.

C. JUNCTION AND PULL BOXES

1. Junction and pull boxes, of code gauge steel, galvanized shall be provided as indicated or
as required for facilitating the pulling of wires and cables. Pull boxes in finished places shall
be located and installed with the permission and to the satisfaction of the Architect and
Engineers

2. All junction and pull boxes on exposed conduit work shall be provided with hubs for threaded
pipe entry and covers provided with hinged and provision for padlocking.

D. WIRES AND CABLES

1. All wires shall be copper, soft-drawn and annealed, 98% conductivity, smooth and true of a
cylindrical form and variation shall be within 1% of the actual size called for.

2. All wires and cable shall be as manufactures by “Phelps Dodge” or approved equal.

3. Wires and cables for power and lighting system shall be plastic insulated for 600 volts
working pressure type :THW” and “TW”.

R.A.EUGENIO + PARTNERS Page 11 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

4. THHN/THWN wires can be used for the same size of wires provided the allowable current
does not exceed that of TW/THW wires.
2
5. All wires 3.5 mm or larger shall be stranded copper.

6. Control leads for motors or lighting shall be or type “TW”.


2
7. For lighting and power system no wire smaller than 3.5 mm shall be used unless otherwise
indicated in the plan.

8. Color Coding:

Provide all service, feeder, branch, control and signaling circuit conductors. Color shall be
green for grounding conductors, and white for neutrals. The color of the ungrounded
conductors in different voltage system shall be as follows: Phase A - Red; Phase B -
Yellow; Phase C - Blue.

9. Splices and Termination Components

Connectors for wires o. 10 AWG and smaller shall be insulated pressure-type or twist-on
splicing connector (wire nut). Provide solderless terminal lugs on stranded conductors.

E. WALL SWITCHES AND PLATES

1. Wall switches shall be rated with ampere and voltage ratings required. Switches shall be for
flush mounting type and of the quite type, spring operated. The type of switches shall be
tumbler operation and the color, plating and appearance of wall plates shall be as selected
by the Architect. Appropriate samples shall be submitted prior to the purchase of wall
switches and faceplates. Switches and plates shall be as manufactured by “National”,
“Legrand” or “Bticino”.

2. Provide weather proof metal switch plate covers where indicated on plans.

3. All utility boxes intended for switch devices shall be specially designed to receive the
particular type of switch device to be mounted and should be deep enough to accept and fit
the total number of conductors required as per drawings.

F. WALL RECEPTACLES AND PLATES

1. Receptacle outlets shall be 15 Ampere, 250V, 3 prong and parallel grounded type. Locking
type and other special purposes receptacle outlets shall be as indicated in the drawings.
Wall receptacles and plates shall be as manufactured by “Panasonic”, “Legrand” or “Bticino”.

2. Appropriate weather proof fitting metal cast alloy boxes shall be provided for convenience
outlet where indicated to be weather proof.

3. Provide weather proof metal receptacle plate cover for each convenience receptacle outlet
indicated as weather proof.

4. Type and color of receptacle outlet and plates shall be as selected by the Architect.
appropriate samples of outlet and plates shall be submitted prior to purchase of devices.

5. All utility boxes intended for receptacle outlet devices shall be as specially designed to
receive the particular type of receptacle outlet device to be mounted and should be deep
enough to accept and fit the total number of conductors required as per drawings.

6. Receptacle with Ground Fault Circuit Interruption (GFCI) shall be rated 10A, 2P, 3 wire
grounding type, 220V parallel slot with 15milliampere current sensitivity.

R.A.EUGENIO + PARTNERS Page 12 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

G. PANELS AND CABINETS

1. Standard panels and cabinets, as much as possible shall be used and assembled on job. All
panels shall be dead front construction, furnished with trims for flush or surface mounting as
required. Cabinets shall be of code gauge steel with gutters as least 100 mm wide and wider
if necessary, and with door provided with concealed hinges and cylinder type lock and catch.
Two keys per panel shall be furnished. The trim for all panels shall be finished in industrial
grey over a coat of rust inhibitor.

2. Panels and cabinets shall be as manufactured by “T’sys Industrial Contrlols Inc.” LJ


Industrial Fabrication Inc.”, or approved equal. Manufacturer’s shop drawings shall be
submitted before manufacturing.

3. Lighting panels shall be equipped with branch air circuit breakers as required and mains as
noted on plans or panel schedule. All circuit breakers shall be “Schneider”, “ABB”, or
“EATON”.

4. Panelboard main bus work shall be ampacity rated to equal or exceed overcurrent protective
device immediately ahead of it. All buswork shall be properly secure to withstand available
short circuit forces at the location.

5. Distribution panels shall be of the same type as lighting panels except equipped with three
poles industrial branch circuit breakers of sizes, voltage ratings and interrupting capacity as
called for on plans. All circuit breakers for distribution and power panel shall be industrial
type model case circuit breakers.

6. All distribution and lighting panels shall be provided with permanent panel designation and
directory. Submit sample for approval of Engineer/Architect prior to fabrication. Panel
designation shall be similar to panelboard schedule and panel directory shall be provided
with circuit number, breaker rating, size of wire and conduit.

H. INDIVIDUAL BREAKERS AND SWITCHES

1. Provide individual circuit breakers, safety switches and disconnect switches where indicated
on plans. Voltage ratings shall be suitable in each case of service application. Enclosures
shall be General Purpose, NEMA Type 1, except where specifically noted on plans
assembled on panel cabinets.

All protective devices shall meet NEMA and Underwriter’s Laboratories, Inc. specifications.

2. Circuit breakers shall consist of a quick-make, quick break type entirely trip-free operating
mechanism with contacts, arc-interruption, and thermal-magnetic unit for each pole, all
closed in a molded-phenolic case. The thermal-magnetic trip unit shall provide time-delayed
overload protection, and in case of overload or short circuit current in any one pole. Circuit
breaker shall be trip indicating, with the tripped position of breaker handle midway between
“ON” and “OFF” positions.

3. Circuit breaker with ground fault circuit interruption shall be provided with “push to test”
button, visible indication of tripped condition and ability to detect a current imbalance of
approximately 5 milliamperes.

4. Current limiting type circuit breaker shall be no fuse type with minimum interrupting rating as
indicated in the drawings.

5. All circuit breaker shall be bolt-on type. Plug-in circuit breakers are not acceptable.

R.A.EUGENIO + PARTNERS Page 13 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

6. Circuit breakers shall be as manufactured by “Schneider”, “ABB” or “EATON”. All circuit


breakers rated above 225 amperes shall have interchangeable trip units. Unless otherwise
specified, minimum interrupting level for 380 volts circuit breakers shall be 5,000 amperes.

7. All single pole (1P) circuit breaker shall be rated at 220 volts or 400/230 volts, 240/120 volts
is not acceptable and 400 volts for three pole (3P) circuit breaker.

I. PANELBOARD BUSES

Support copper bus bars on bases independent of the circuit breakers. Main buses and back pans
shall be designed so that the breakers may be changed without machining, drilling or

tapping. Provide a separate ground bus marked with a green stripe along its front and bonded to
the steel cabinet for connecting grounding conductors.

3.1 INSTALLATION
3.2

A. GENERAL REQUIREMENTS

Electrical installations shall conform to the requirements of the Code and to the requirements
specified herein.

B. WIRING METHODS

Wiring method shall be insulated conductors installed in conduit, except where specifically
indicated or specified otherwise, or required by the code to be installed otherwise. An insulated
equipments grounding conductor shall be provided in all branch circuits, including lighting circuits.

C. CONDUIT INSTALLATION

Unless indicated otherwise, conceal, conduit within finished walls and floor. Install conduit panel
parallel with or at right angles to ceiling, walls and structural members where located above
accessible ceiling and where conduit will be visible after completion of project.

1. Where conduits rise through floor slobs the curved portion of bends shall not be visible
above the finished slab.

2. Conduit Support

Support conduit by pipe straps wall bracket, hangers, ceiling trapeze. Fasten by machine
screws, welded threaded studs, or spring-tension clamps on steelwork. Do not weld conduits
or pipe straps to steel structures. The load applied to fasteners shall not exceed one-fourth
of the proof test load. In partition of light steel construction, use sheet-metal screws.

3. Make changes in direction of runs with symmetrical bends or cast-metal fittings. Make field-
made bends and offsets with a hickey or conduit-bending machine. Do not install crushed or
deform conduits. Avoid trapped conduits. Prevent plaster, dirt, or trash from lodging in
conduits, boxes, fittings, and equipment during construction. Free clogged conduits of all
obstruction.

4. Install pull wires in empty conduits in which wire is to be installed. The pull wire shall be 2
mm2 (No. 14AWG) zinc-coated steel or plastic having not less than 90 kilogram (200 pound)
tensible strength. Leave not less than 300 mm of slack at each end of the pull wire.

R.A.EUGENIO + PARTNERS Page 14 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

5. Conduit Installed in Concrete Floor Slabs:

Locate so as not to adversely affect the structural strength of the slabs. Install conduit within
the middle one-third of the concrete slab. Space conduits horizontally shall not closer than
three diameters except at cabinet locations. Curved portions of bends shall not be visible
above the finish slab. Where embedded conduits cross expansion joints, provide suitable
watertight expansion fittings and bonding jumpers. Conduit larger than 25 mm trade size
shall be parallel with or at right angles to the main reinforcement; when at right angles to the
reinforcement, the conduit shall be close to one of the supports of the slab.

6. Fasten conduits to sheet metal boxes and cabinets with two locknuts where required by the
Code, where insulated bushings are used, and where bushings cannot be brought into firm
contact with the box; otherwise, use at least a single locknut and bushing. Locknuts shall be
the type with sharp edges of digging into the wall of metal enclosures.

Install bushings on the ends of conduits and provide insulating type where required by Code.

7. Flexible connection of short length (maximum of 1.828 m) shall be provided for lighting
fixtures. Liquid-tight flexible conduit shall be used in wet location. A separate ground
conductors shall be provided across flexible connections.

D. BOXES, OUTLETS AND SUPPORT

Provide boxes in the writing or raceway systems wherever required for pulling of wires making
connections and mounting of devices of fixtures.

Boxes for metallic raceway shall be of the cast-metal hub type when located in normally wet
locations, when surface mounted on outside of exterior surfaces, when installed exposed up to 2
m above interior floors and walkways, ad when installed in hazardous areas. Boxes in other
locations shall be sheet steel. Each box shall have the volume required by Code for the number of
conductors enclosed in the box. Boxes for mounting lighting fixtures shall be not less than 100 mm
square (or octagonal), except that smaller boxes may be installed as required by fixture
configurations, as approved. Provide gaskets for cast-metal boxes installed in wet locations and
boxes installed flush with the outside of exterior surfaces. Fasten boxes and support: support
sheet boxes directly from the building structure or by bar hangers. Where bar hangers are used,
attach the bar to raceways on opposite sides of the box and support the raceway with an approved
type fastener not more than 600 mm from the box.

1. Boxes for use with raceway system shall not be less than the minimum size required by
Code of code-gage aluminum or galvanized sheet steel, except where cast-metal boxes are
required in locations specified above. Furnish boxes with common pull box; tag the feeders
to indicate clearly the electrical characteristics, circuit number and panel designation.

E. MOUNTING HEIGHTS

Mount panelboard, circuit breakers and disconnecting switches so that the height of the operating
handle at its highest position will not exceed 2 m from the floor. Mounted lighting switches 1.37 m
above finished floor, receptacles 0.30 m above finished floor, wall switches 1.4 m above finished
floor, intercom 1.4 m above finished floor. Measure mounting heights of wiring devices and outlets
to the center of device or outlet.

F. CONDUCTOR IDENTIFICATION

Provide conductor identification or tagging indicating its load or panel serve within each enclosure
or pull boxes where a tap, splice or termination or cable pulling is made.

R.A.EUGENIO + PARTNERS Page 15 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

G. SPLICES
2
Make splices in accessible locations Make splices in conductors 5.5 mm and smaller with an
2
insulated pressure type connector (wire nut). Make splices in conductors 8 mm and larger, with a
solderless connector and cover with an insulation material equivalent to the conductor insulation or
as indicated in the plan.

H. COVER AND DEVICE PLATES

Install with all four edges in continuous contact with finished wall surfaces without the use of mats
or similar devices. Plaster fillings will not be permitted. Plates shall be installed with an alignment
tolerance 0f 1.5 mm. The use of sectional type device plates will not be permitted. Plates installed
or as indicated shall in the plan.

I. GROUNDING AND BONDING

Ground all exposed non-current-carrying metallic parts of electrical equipment, metallic raceway
system and neutral conductor of wiring systems. Make ground connection at the main service
equipment or grounding grid. Make ground connection to buried ground rods on the exterior of the
building or as shown in the plan.

1. Grounding Conductor:

Provide an insulted, green-colored equipment grounding conductor in all feeder and branch
circuits.

2. Resistance:

The maximum resistance to ground of the grounding system shall not exceed 25 ohms
under normally dry conditions. Where the resistance obtained exceeds 25 ohms, contact
the Engineer for further instructions.

J. FIELD TEST

The Contractors shall provide all test equipment and personnel and submit written copies of all test
results. As an exception to requirements that may be stated elsewhere in the Contract, the
Engineer shall be given 5 working days notice prior to each test.

1. Devices Subject to Manual Operation:

Each device subject to manual operation shall be operated at least five times, demonstrating
satisfactory operation each time.

2. Test on 600-Volt Wiring

Test all 600-volt wiring to verify that no short circuits or accidental ground exist. Perform
insulation resistance tests on all wiring 14 mm 2 and larger using an instrument which applies
a voltage of approximately 500 volts to provide a direct reading of resistance; minimum
resistance shall be 250,000 ohms.

3. Grounding System Test:

Test the grounding system to assure continuity and the resistance to ground is not
excessive. Test ground wire for resistance to ground. Make resistance measurements in
normally dry weather, not less than 48 hours rainfall. Submit written results of each test to
the Engineer and indicate the resistance and soil conditions at the time the measurements
were made.
*** End of Section ***

R.A.EUGENIO + PARTNERS Page 16 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16: ELECTRICAL

SECTION 16510

LIGHTING FIXTURES

PART 1- GENERAL

1.01 Supply of lighting fixture for interior fit-out and common area as shown in the plan and necessary
documents as stated herein.

1.02 SUBMITTALS

A. Shop Drawing

1. Submit shop drawings showing all details, size and arrangement of parts and other pertinent
data. Clearly indicate the drawing number of fixture details used as reference in the
development of the shop drawings. Indicate finished dimensions and required clearance,
metal thickness and gauges, material finishes, electrical and mechanical connections,
fasteners, weld locations, joint locations, relationship to ceiling supports and provisions for
the work of others.

2. Provide listing on shop drawing containing the fixture type, manufacturer’s catalog number,
applied voltage, and lamp and ballast types. Manufacturer’s catalog cuts may be submitted
in lieu of shop drawings only if they contain sufficient detail and information to indicate
compliance with the specifications.

3. Coordinate lighting fixture shop drawings with the details to the architectural.

B. Samples

1. Submit for review one (1) working sample (complete with plug and cord for standard 220 volt
service) of each lighting fixture, complete with specified ballast and lamp(s), ready for
hanging and energizing. Samples are neither returnable nor included in quantities listed for
the Project. Where a fixture sample is submitted or requested, do not fabricate that fixture
type until sample is reviewed and approved.
2. Submit sample for any fixture offered in substitution for a specified fixture, according to
guidelines listed in item above.

C. Guarantees

1. Provide a written guarantee stating that each lighting fixture, finishes, and all component
parts, except ballast, shall be free from defects in materials or workmanship for a period of
one (1) year from date of final acceptance. Ballast shall be guaranteed for two (5) years.
Upon notification of such defects, within the guarantee period, provide the necessary repairs
or replacements at the convenience of the Owner without any additional cost.

2. Provide a written guarantee for twenty (20) years stating that semi-specular satin finish will
be guaranteed against discoloration. Upon notification of such premature discoloration
defects, within the guarantee period, provide the necessary replacements at the
convenience of the Owner without any additional cost.

D. Maintenance Manual: Submit two (2) copies of a bound maintenance manual, describing the
materials, tools required, replacement parts identification list and procedures for cleaning and

R.A.EUGENIO + PARTNERS Page 17 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

maintaining each type of lighting fixture. Include manufacturer’s data describing the materials and
finishes used in the work.

1.03 QUALITY ASSURANCE

A. Manufacturers: Manufacturers listed in the fixture schedule shall be assumed capable of supplying
the listed fixtures unless exceptions are set forth in their quotations. Any such exceptions shall
immediately be brought to the attention of the Owner, architect and Engineer. Manufacturers not
listed must be pre-qualified to bid as follows:

1. Experience: Manufacturer(s) shall not have less than five years experience in design and
manufacture of lighting fixtures of the type and quality shown. Pre-qualification submissions
must include a list of completed projects and dated catalog pages or drawings indicating
length of experience.

2. Prototypes: Manufacturer(s) shall also submit a prototype sample of each fixture for review.
Prototype samples shall be sufficiently detailed and operational to allow evaluation of
compliance with the salient features of the specification. Preliminary design or shop drawing
shall not be accepted in place of prototype samples.

3. The Owner, Architect and Engineer shall be the sole judges in determining whether the
prototype sample complies with the specifications, and shall reserve the right to disqualify
any bidders.

B. Standards

1. Except as modified by governing codes comply with the applicable provisions and
recommendations of the following:

a. Philippine Electrical Code (PEC).

b. National Electrical Code (NEC).

c. NEMA “Standard Publication No. LE-1 Fluorescent Luminaires”

2. Listing: Provide fixtures manufactured and listed in strict accordance with the appropriate
requirements of the National Electric Code (NEC) in compliance to UL, IEC, BPS and other
testing agency acceptable to local authorities having jurisdiction. Provide listings for each
fixture type, and the appropriate label or labels affixed to each fixture in a position concealed
from normal view.

1.04 PRODUCT HANDLING

A. Deliverer lighting fixtures, components and assemblies in fully sealed protective cartons and identified
as to contents. Protect fixtures from damage from any source. Provide removable protection as
required.

B. Instructions: Each lighting fixture shall be packaged with complete instruction and illustrations
indicating installation method.

B. Store materials in accordance with manufacturer’s instructions, properly protected from weather and
construction activities.

PART 2 PRODUCTS

R.A.EUGENIO + PARTNERS Page 18 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

2.01 MATERIALS

A. Standard with the manufacturer and complying with requirements of referenced standards.

2.02 FIXTURE FABRICATION, GENERAL

A. Provide lighting fixtures completely factory assembled, wired and equipped with necessary sockets,
ballast, wiring, shielding, reflector, channels, brackets, fasteners and other parts necessary to
complete the fixture installation.

B. Sheet Metal Work: Sheet metal work shall be free from tool marks and dents, and shall have
accurate angles bent as sharp as in compatible with the gauge and material of the required
metal. All intersections and joints shall be formed true, of adequate strength and structural rigidity
to prevent any distortion after assembly. All lighting fixture edges shall be free of all burns or sharp
spots.

C. Castings: Provide cast or extruded metal fixtures parts, of ample weight and thickness that
are closed grained, smoothly finished and buffed, rigid and free from imperfections, sand pits,
blemishes, scales, rust or discoloration. Provide for tolerance of shrinkage of the metal castings so
as to allow the finished castings to accurately fit in their designated locations.

D. Hinge door closure frames shall operate smoothly without binding. Fabricate allow installation
and/or removal without the use of tools. Hinge mechanism shall designed to preclude accidental
falling of hinged door closure frames during relamping operations and while secured in the
operating position.

E. Weld expose metal at joints, fill with compatible weld material, grind smooth and make free from
light leaks. Construct fixtures with the minimum number of joints. Fabricate unexposed joints
utilizing welding, brazing, screwing or bolting. Soldered joints are unacceptable. Do not utilized
self-tapping methods or rivets for fastening parts which require removal to gain access to electrical
components requiring service or replacement or for fastening any electrical components or their
supports. Weld ballast support studs, sockets, saddle studs an reflector support studs to fixture
body. Ventilate ballast compartments and firmly secure ballast to conducting metal surface.

F. Provide yokes, brackets and supplementary supporting members needed to mount lighting fixtures
to carrier channels or other suitable ceiling members.

G. Temperature: All fixtures and ballasts must operate within temperature limits of their design and
as specified by UL and IEC standard in the applications and mounting conditions specified
herein.

2.03 FIXTURE FABRICATION, SPECFIC ITEMS

A. Enclosures: Fabricate fixture enclosures with minimum 22 ga. Thick cold rolled sheet steel.
Enclosure may be constructed of other metals, provided they are equivalent in mechanical
strength and acceptable for the purpose.

B. Housings: Fabricate housing so that all electrical components are easily accessible and
replaceable without removing fixtures from their mountings, or altering adjacent construction.
Provide fixtures using bottom relamping unless otherwise noted.

C. Mounting Frames and Rings: If required for installation in specified ceiling system, provide
each recessed ad semi-recessed fixture with a mounting frame or ring compatible with ceiling

R.A.EUGENIO + PARTNERS Page 19 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

system in which they are to be installed. Frames and rings shall be one piece or constructed with
electrically-welded butt joints, and or sufficient size and strength to sustain the weight of the
fixture. Ceiling opening frames shall either be manufactured of non-ferrous metal or be suitably
rust=proofed after fabrication.

D. Spread Lens Fixtures: Each light fixture which has a spread lens shall contain lens orientation
locking devices to insure that lens orientation is not disturbed during future lamp replacement or
cleaning.

2.04 FIXTURE FINISHES

A. General: Remove scratches, abrasions, dents, die markings and other defects prior to finishing
operations. Perform this work in addition to finish treatment specified. Unless, otherwise noted,
colors and finishes shall be as selected by the Architect and Owner.

B. Shop Finishes
C.
1. White Powder Coated Surfaces: Apply white powder coated finishes smoothly. Finish shall
not be less than 7.5 mm thick of non-yellowing, white, vitreous porcelain enamel with a
reflectance of not less than 85% except as noted otherwise.

2.05 FLUORESCENT LIGHTING FIXTURES

A. General Constructions and Materials:Conform to UL or IEC which ever stringent. Housing end
plates, socket bridges, reflectors, wiring channels and ballast covers shall die formed of not less
than22 ga. cold-rolled steel unless otherwise specified.

B. Lamp holders shall be spring loaded.

C. Construct fixtures so that ballast may be serviced or replaced without removal of fixture housing.
Secure ballasts firmly in lighting fixtures to prevent vibrations.

2.06 FLUORESCENT BALLASTS

A. General:Ballasts within the same luminaire shall be from the same manufacturer. Ballast shall
comply to UL, IEC and ICC standard.

B. Relative light output (percentage of light emitted with reference tube and ballast) shall not be less
than 95%.
C.
C. Operating Environment: :Ballasts shall be designed and constructed to maintain a case
temperature not greater than 90 deg. C. when operated at an ambient room temperature of 50
deg. C. as tested in accordance with UL and CBM standards.

D. Electrical Characteristics:Ballast shall be designed for single frequency operation 60 Hz nominal,


and shall operate at the nominal voltages indicated on label, 220 volt. Provide ballasts suitable for
the electrical characteristics of the supply circuits to which they are to be connected, and which
are suitable for operating the lamps specified. Ballast shall be as manufactured by “Philips”,
“Thorn” or “Osram”.

2.07 LAMPS

A. Manufacturer: Lamp shall be as manufactured by “Philips”, “Thorn” or “Osram”. All lamps wattage
shall be as indicated in the plan.

B. If a specific manufacturer is noted in the schedule, only that manufacturer shall be acceptable.

R.A.EUGENIO + PARTNERS Page 20 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

PART 3 – EXECUTION

3.01 CLEANING

Prior to final acceptance by the Owner, clean lighting fixtures thoroughly with materials and method
recommended by the manufacturers. Clean fingerprints and smudges from the lenses. Replace broken
parts and replace lamps which are dim or have burned out.

3.02 Submission of computation confirming minimum illumination level of 500 lux.

*** End of Section ***

R.A.EUGENIO + PARTNERS Page 21 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16: ELECTRICAL

SECTION 16164

PANELBOARDS

PART 1 – GENERAL

1.1. GENERAL REQUIREMENTS

Section 16000, “Electrical General Requirements”, applies to this section with additions and modifications
specified herein. In each of the standard referred to herein, consider the advisory provisions to be mandatory,
as though the word “shall” wherever it appears. Interpret reference in these standards to the “authority having
jurisdiction”, or words of similar meaning, to mean the Engineer.

1.2. DESCRIPTION OF WORK

Supply of enclosed circuit breaker, distribution and lighting panelboard. Type of mounting, quantity and
rating of branch circuit breaker shall be as shown on panelboard schedule.

1.3. SUBMITTALS

A. MANUFACTURER’S DATA and SHOP DRAWING

1. Submit detailed shop drawing including dimensions, gutter spaces, size and rating of
busbar.

2. Others as required

2.1. PANELBOARDS AND CABINETS

A. Standard panels and cabinets, as much as possible shall be used and assembled on job. All
panels shall be dead front construction, furnish with trims for flush or surface mounting as
required. Cabinet shall be of code gauge steel and with door provided with heavy duty concealed
hinges and cylinder type lock and catch. Two keys per panel shall be furnished. The trim for all
panels shall be finished in industrial grey enamel over a coat of rust inhibitor.

B. Manufacturer’s shop drawings shall be submitted before manufacturing.

C. Lighting panels shall be equipped with branch air circuit breakers as required and mains as noted
on plans or panel schedule. All circuit breakers shall be UL listed.

D. Panels and cabinets shall be as manufactured by “T’sys Industrial Controls Inc.”, “LJ Industrial
Fabrication, Inc.”. Manufacturer’s shop drawings shall be submitted before manufacturing.

E. Panelboard main bus work shall be ampacity rated to equal or exceed overcurrent protective
device immediately ahead of it. All bus work shall be properly secured to withstand available short
circuit forces at the location.

F. Distribution panels shall be equipped with two or three poles air circuit breakers of sizes, voltages
ratings and interrupting capacity as called for on plans. All circuit breaker shall be industrial type
molded case circuit breakers.

R.A.EUGENIO + PARTNERS Page 22 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

G. All distribution and lighting panels shall be provided with permanent panel designation and
directory. Submit sample for approval of Engineer/Architect prior to fabrication. Panel designation
shall be similar to panelboard schedule and panel directory shall be provided with load
designation, circuit number, breaker rating, size of wire and conduit.

H. Minimum space for wire bending at terminal of panel.

Rating of Circuit Breaker Top (mm) Bottom (mm) Sides (mm)


30AT to 70AT 100 100 100
100AT to 125AT 150 125 100
150AT to 225AT 225 200 200
250AT to 400AT 325 275 200
500AT to 1200AT 375 300 250

2.2. INDIVIDUAL BREAKERS AND SWITCHES

A. Provide individual circuit breakers, safety switches and disconnect switches where indicated on
plans. Voltage ratings shall be suitable in each case of service application. Enclosures shall be
General Purpose, NEMA Type 1, except where specifically noted on plans or assembled on panel
cabinets.

All protective devices shall meet NEMA and Underwriter’s Laboratories, Inc. specifications.

B. Circuit breakers shall consist of a quick-make, quick-break type entirely trip-free operating
mechanism with contacts, arc-interrupter, and thermal magnetic trip unit for each pole, all enclosed
in a molded-phenolic case. The thermal-magnetic trip unit shall provide time-delayed overload
protection, and in case of overload or short circuit current in any one pole. Circuit breaker shall be
trip indicating, with the tripped position of breaker handle midway between “ON” and “OFF”
positions. Provide voltage transient surge suppression to main circuit breaker as indicated in the
riser diagram.

C. Circuit breaker with ground fault circuit interrupter shall be provided with “push to test” button,
visible indication of tripped condition and ability to detect a current imbalance of approximately 5
milliamperes.

D. Current limiting type circuit breaker shall be no fuse type with minimum interrupting rating as
indicated in the drawings.

E. All circuit breaker shall be bolt-on type. Plug-in circuit breakers are not acceptable.

F. Circuit breaker shall be as manufactured by “ABB”, “GE” or “Square D”. All three pole (3P) circuit
breaker shall have minimum voltage rating of 400 volts while all single pole (1P) circuit breaker
shall have minimum voltage rating of 220 volts. 240/120 volts for single pole circuit breaker is not
acceptable. All circuit breakers rated above 225 amperes shall have interchangeable trip units.
Unless otherwise specified, minimum interrupting level for 220 volts circuit breakers shall be 5,000
amperes.

2.3. PANELBOARD BUSES

Support copper bus bars on bases independent of the circuit breakers. Main buses and back pans shall
be designed so that the breakers may be changed without machining, drilling or tapping. All busbars shall
2
have a density of 1000A/in . Provide separate ground bus marked with a green stripe along its front and
bonded to the steel cabinet for connecting grounding conductors.

*** End of Section ***

R.A.EUGENIO + PARTNERS Page 23 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16: ELECTRICAL

SECTION 16400
LOW VOLTAGE SWITCHBOARD

PART 1.00 GENERAL

1.1 GENERAL RQUIREMENTS

Under this section of the specifications, the contractor shall supply and install the low voltage switchboard
as described herein and as shown in the drawings.

1.2 SUBMITTAL

A. MANUFACTURER’S DATA:

1. Main Circuit Breaker


2. Circuit Breakers
3. Enclosures

PART 2.00 PRODUCTS

2.1 LOW VOLTAGE SWITCHBOARD

A. The low voltage switchboard shall consist of two (2) metal enclosed indoor assembly rated 600
volts AC and arranged for service on a 240 volts, 3-phase, 3 wire line, with ground bus.

B. CONSTRUCTION

1. The Low Voltage Switchboard (LVSB) shall consist of completely enclosed, self-supporting
vertical structures bolted together to form one sheet metal enclosure. It shall be provided with
front and rear channels. The ends, top and rear shall be covered with removable, screw-on-steel
plate not less than 12 gauge. Switchboard shall include all protective devices and equipment as
listed with necessary interconnection, instrumentation and control wiring, terminal blocks, and
mechanical type solder less connector for terminals.

2. Protective devices shall have individual drawers or compartments, and necessary bus connection
straps. Devices shall be modular-sized and so arranged as to be individually removable and
readily interchangeable. Each device shall be provided with cardholder and card for identification.

3. Bus bar shall be tin plated copper with ampere rating 10% higher than the main breaker ampere
rating. It shall be mounted on insulator supports on high impact, non-tracking, and high quality
insulation material and adequately braced to withstand the mechanical forces exerted during
short circuit conditions.

R.A.EUGENIO + PARTNERS Page 24 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

Branch circuit bushing shall connect directly to the bus structure. All bushings shall be arranged
so as not to obstruct straight-in wiring to the protective devices. All bus work shall consist of
sufficient copper to limit temperature rise to 60 degree Centigrade at an ambient of

40 degree centigrade temperature. Bus bar shall be insulated and color coded from the devices
so that only exposed energized parts will be at point of connection to devices.

4. Bus structure shall be arranged to permit future extension. It shall be mounted on insulator
supports of high impact, non-tracking, and high quality insulation material and adequately braced
to withstand the mechanical forces exerted during short circuit conditions up to 65.000 amperes
RMS symmetrical short circuit at 400 volts. Bus bars shall be silver plated copper and rated as
shown on single line diagram. Branch circuit bushing shall connect directly to the bus structure.
All bushings shall be arranged so as not to obstruct straight in wiring to the protective devices All
bus work shall consist of sufficient copper to limit temperature to 40 degree C ambient
temperature.

5. Small wiring, necessary fuse blocks and terminal blocks within each vertical structure shall be
furnished as needed. All control and metering conductors shall be marked and color coded for
proper identification.

6. All hardware’s shall have protective finish.

7. Metal surfaces shall be chemically cleaned and treated. Chemical treatment shall provide a bond
between paint and metal surfaces and help prevent entrance of moisture and formation of rust
under the paint film.

The vertical structure shall be finished in ASA No. 49 medium-light-gray, the hinge doors over the
protective devices on the front in ASA No. 61 light grey.

8. LVSB supports for anchoring and for providing proper alignment shall be furnished and installed
on the floor or par by others.

9. A ground bus shall be furnished secured to each vertical structure and shall extend the entire
length of the low voltage switch board. Grounding terminals shall be provided.

10. Where space provisions only for future breaker is called for, all studs, copper work and provisions
for mounting the breaker shall be provided so that when breaker is added, no additional parts or
changes to the structure on bus work is required.

11. LVSB outgoing feeders shall be top or side exit.

12. Engraved metal nameplates shall be provided for each device. The letters or numerals on the
nameplate shall be a minimum of 5mm in height with light colored, enameled characters on a
dark background. The legend on the strips shall be so composed as to clearly indicate the name
of the feeder and/or panelboard and/or equipment served by the protective devices, etc.

13. Bases, frames and channels of the switchboard which come in contact with concrete shall be
corrosion resistant and shall be fabricated of hop dip galvanized steel.

R.A.EUGENIO + PARTNERS Page 25 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

C. CIRCUIT BREAKERS

1. The main and branch circuit breakers shall be power breaker type. Ratings of circuit breakers
including devices shall meet NEMA and Underwriter’s Laboratories, Inc. specifications.

2. The main circuit breakers shall be insulated case (hybrid) draw-out type, electrically and
mechanically operated. All main circuit breakers shall be provided with adjustable continuous

ampere setting, adjustable long time delay setting, adjustable short time delay pick-up, adjustable
instantaneous pick-up and adjustable ground-fault pick-up. Necessary current transformers,
breaker actuators, batteries and charger rectifier shall be included.

3. Feeder breakers shall be air or molded case, manually operated, each with direct acting inverse
time characteristics and instantaneous overcurrent devices.

4. All insulated case (hybrid) circuit breakers shall be provided with adjustable continuous ampere
setting, adjustable long time delay setting, adjustable short time delay pick-up, adjustable
instantaneous pick-up and adjustable ground fault pick-up.

5. All circuit breaker shall be 3-pole, rated 30,000 RMS symmetrical minimum interrupting rating, at
400V unless noted otherwise on plans or schedule. Trip ratings shall be as shown on the one-line
diagram.

6. Circuit breakers shall be as manufactured by Schneider, Mitsubishi, Fuji, ABB or approved equal.

7. All circuit breakers rated above 1000 amperes shall have built-in (integral) ground fault protection.

PART 3.00 EXECUTION

3.1 GENERAL

A. Install the switchboard as indicated on the project drawings, the approved shop drawings and as
specified herein in the presence of the equipment supplier representatives.

B. TOUCH-UP PAINTING

Touch-up all surfaces as required with paint and procedures approved by the manufacturer of the
switchboard.

C. SWITCHBOARD CONCRETE PAD

Mount the switchboard on concrete pad. The top of the concrete pad shall be approximately
150mm (6.0 in.) above the finished floor. Edges above floor shall have a 12mm (0.5 in.)
chamfered. The slab shall be of adequate size to project at least 100mm (4.0 in.) beyond the
equipment.

3.2 FIELD TESTS AND INSPECTIONS

R.A.EUGENIO + PARTNERS Page 26 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

A. ACCEPTANCE CHECKS, SETTINGS AND TEST

Perform all tests and inspections in accordance with the manufacturer’s recommendation and the
latest IEEE standards unless specified otherwise. Perform work in a careful and safe manner so
as not to endanger personnel or equipment. Perform tests in such a way as to obtain information
about the performance of the breakers and wiring together as a unit, as well as separately.
Except where specified otherwise, give the Engineer at least five (5) working days advance notice
of the dates and times for all checks, settings, inspections and tests.

B. ACCEPTANCE CHECKS AND TESTS: Include the following:

1. Compare actual connections with wiring diagrams. If differences are found, determine if
errors is in diagram or in actual wiring and correct as necessary..

2. Inspect all devices, equipment, and other materials for damage or maladjustment caused
by shipment or installation.

3. Assure that tightness of bolted bus joint is in accordance with manufacturer’s


recommendations (use calibrated torque wrench).

4. Perform all mechanical operator and contact alignment tests in breakers and operating
mechanics is accordance with manufacturer’s recommendation. Make adjustments as
necessary.

5. Measure breaker contact resistance and perform minimum pick-up voltage tests on all
trip and closing coils. Make adjustments as necessary to stay within manufacturer’s
acceptable range.

6. Remove wedges, ties, and blocks installed by the manufacturer to prevent damage
during shipment.

7. Check all circuit breakers in accordance with manufacturer’s instruction.

8. Verify minimum resistance to ground of all grounding systems.

9. Verify meter connections and ensure calibration.

C. FOLLOW-UP VERIFICATION

Upon completion of all acceptance checks, settings, and tests, the Contractor show by
demonstration in service that all circuits and devices performing their intended function. Circuit
breakers shall be tripped by operation of each protective device. Test shall be such that each
item will perform its function not less than three (3) times.

*** End of Section ***

R.A.EUGENIO + PARTNERS Page 27 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16: ELECTRICAL

SECTION 16123

BUSWAY

PART 1.00 – GENERAL

1.4. GENERAL REQUIREMENTS

Section 16000, “Electrical General Requirements”, applies to this section with additions and modifications
specified herein. In each of the standard referred to herein, consider the advisory provisions to be
mandatory, as though the word “shall” wherever it appears. Interpret reference in these standards to the
“authority having jurisdiction”, or words of similar meaning, to mean the Engineer.

1.5. Description of Work

A. Supply of busway system complete in every aspect as shown in the riser or as required necessary
to complete the installation for system operation.

1.6. Submittals

A. Manufacturer’s Data and Shop Drawing

1. Submit detailed shop drawing including dimensions and spacing.


2. Others as required

PART 2.00 – PRODUCTS

2.1. Busway

A. General

1. Furnish and install a complete low impedance pre-fabricated busway distribution system as
shown on the plans.

2. Busway shall be rated at 400 volts, 3-phase, 4-wires with 50% capacity integral ground bus
as manufactured by “Schneider”, “Powerbox, “Megatron” or approved equal.

3. The ampere ratings, approximately footage, fitting, proposed route, etc. are shown on the
plans. The electrical Contractor shall be responsible for the exact routing of the busway and
to coordinate with the other trades for possible conflict in layout. Final field measurements
shall be made by the Supplier/Contractor prior to release of the busway for fabrication.

B. Short Circuit Rating and Tests

1. The short circuit rating of the busway shall be determined according to U.L. standards. This
rating must be based upon actual test at the rated short circuit current.

C. Basic Construction

1. Housing

R.A.EUGENIO + PARTNERS Page 28 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

a) The busway housing shall be constructed of code gauge steel and aluminum to
reduce hysteresis and eddy current losses and shall be provided with a suitable
protective finish of ANSI 49 gray epoxy paint.

b) The busway housing shall be totally enclosed non-ventilated for protection against
mechanical damage and dust accumulation.

c) The totally enclosed housing shall be manufactured by the busway manufacturer.


Modifications of busway manufacturer to make it totally enclosed by other than the
busway manufacturer voids the U.L. manifest. Busway so modified is unacceptable.

2. Joint

a) The busway joint shall be of the one-bolt type which utilizes a high strength steel
bolt(s) and belleville washers to maintain proper pressure over a large contact
surface area.

b) The bolt shall be torque indicating fully insulated and at ground potential.

c) The bolt shall be two-headed design to indicate when proper torque has been applied
and require only a standard long handle wrench to be properly activated.

d) Access shall be required to only one side of the busway for tightening joint bolts.

e) On busway 800A and above, it shall be possible to remove any joint connection
assembly to allow electrical isolation or physical removal of a busway length without
disturbing adjacent busway lengths.

3. Bus Bars

a) Bus bars shall be Tin Plated Aluminum.

b) Each bus bar shall be insulated with Class B rated epoxy powder coated materials or
130°C polyester film (mylar).

c) The temperature rise at any point in the busway shall not exceed 55°C rise above
ambient temperature when operating at rated load current.

d) Bolt feeder and plug-in busway (800A and above) shall be o sandwich construction,
meaning no air gap shall exist between bus bars except at plug-in opening and joints.

e) An integral ground bus shall be furnished which will electrically connect together all
equipment connected to the bus duct.

4. Support of Busway

a) Hanger spacing shall not exceed manufacturer’s recommendation.

b) Indoor feeder and plug-in busway shall be approved for hanger spacing of up to 10’0”
for horizontally mounted runs. Outdoor feeder busway shall be approved for spacing
of up to 5’0” for horizontally or vertically mounted runs.

5. Underwriter’s Laboratories Listing

R.A.EUGENIO + PARTNERS Page 29 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

a) All straight lengths, fittings and plug-in units shall be U.L. listed.

b) This listing shall include mounting of the busway in any position (i.e. horizontal,
flatwise, edgewise and vertical) without derating.

D. Quality

All busway products shall be manufactured in a facility which is Quality Systems Registered by
Underwriter’s Laboratories.

PART 3 – EXECUTION

3.1 INSTALLATION

Electrical installations shall conform to the requirements of the Code and to the requirements specified
herein.

*** End of section ***

R.A.EUGENIO + PARTNERS Page 30 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16: ELECTRICAL

SECTION 16401
AUTOMATIC TRANSFER SWITCH

PART 1.00 GENERAL

1.1 GENERAL REQUIREMENTS

A. General requirements include those specified in Section 16000 “Electrical General Requirements”
and as specified herin.

B. Provide Automatic Transfer Switch (ATS) for generator power supply system and included in the
supply of Low Voltage Switch board (LVSB) with accessories, auxiliary equipment and associated
work as specified.

C. The ATS shall consist of breaker or solenoid operated, molded case switches, interlocks, micro
processor control an logic circuits, voltage sensors, together with the necessary wires, fuses and
accessories, to automatically provide continuous electric power for the duration of any failure of
the normal utility power supply.

D. Provide ATS consisting of voltage sensors, frequency monitor, timers, control and logic circuits
together with all wiring, fuses and accessories needed the automatic start-stop of generator set.

E. QUANTITY AND EXPERIENCE

All materials and parts of the ATS shall be new and unused. Each component shall be of current
manufacture from a firm regularly engaged in the design and production of such equipment. Units
and components offered under these specifications shall be covered by the manufacturer’s
standard war guarantee on new equipment.

F. PARTS AND SERVICE

Bids shall be accepted only on ATS which can be properly maintained and serviced without
causing the purchaser either to carry expensive parts stock or to be subject to the inconvenience
of long periods of interrupted service because of lack of available parts.

G. The system shall be designed, assembled, tested and shipped by one manufacturer as the
generator set so that there is one source of supply and responsibility on all components supplied
with the system.

H. All equipment shall be designed, assembled and tested to conform to applicable standards of
ASA, IEEE, ASME, ASTM and NEMA or VDE and DIN.

R.A.EUGENIO + PARTNERS Page 31 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

1.2 SUBMITTALS

A. MANUFACTURER’S DATA

1. ATS

2. Microprocessor Control Panel

B. SHOPDRAWINGS AND CALCULATIONS

1. Drawings for the automatic transfer switch including certified electrical ratings, general
component arrangements and detail wiring and equipment drawings.

2. Electrical elements, schematics and wiring diagrams, including details of the interlocking system
and control logic circuits.

C. CERTIFIED TEST REPORTS

1. Components shop tests

2. System operation and control tests.

D. MANUALS

Provide three sets of operation and maintenance manual for equipment. Identification symbols for
all replaceable parts and assemblies shall be included. Information in manuals shall be
comprehensive specific.

PART 2.00 PRODUCTS

2.1 AUTOMATIC TRANSFER SWITCH

A. Automatic transfer switch (ATS) shall be provided for the generator power supply system. The
automatic transfer switch shall be coordinated with manufacturer of the standby AC power
generator to maintain system compatibility and local service responsibility for the complete
standby power system.

B. The Automatic Transfer Switch (ATS) shall be stand along type and part of the LVSB suitable for
use on all types of loads.

C. The ATS shall be UL 1008 for load transfer application and shall be as manufactured by ASCO or
approved equal.

R.A.EUGENIO + PARTNERS Page 32 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

D. The ATS shall be double throw, operated by solenoid power drive contacts equipped with ARC
chute/splitter and self clean contacts. The arching contacts shall operate first before the main
contacts open.

E. All accessories and parts shall be front accessible for ease of maintenance or removal.

F. Transfer switch shall have withstood, closing and interrupting ratings sufficient for the voltage
employed and the available short circuit at the point of application.

G. Automatic Transfer Switches (ATS) shall be breaker or solenoid type operated, mechanically held
and electrically operated with inherent interlocked construction with rating as shown on plan
240V, 3-phase, 3 wire plus ground wire.

H. The ATS shall be provided with two (2) normally open and two (2) normally closed auxiliary
switches operated by the emergency contactor for interfacing with other equipments as required
in the electrical plans.

I. The ATS microprocessor control panel shall be composed of the following:

1. Closed differential voltage sensing on all phases of normal source. Pick-up voltage
adjustable from 85 percent to 100 percent of nominal and drop out shall be adjustable
from 75% to 98% pick up voltage.

2. Adjustable voltage sensing of emergency source from 90 percent to 100 percent pick-up
of nominal.

3. Adjustable time delay from 0.5 to 6 seconds to override momentary normal source
outages to delay transfer switch and engine starting signals.

4. Adjustable time delay from 0 to 5 5 minutes for controlled timing of load transfer to
emergency.

5. Adjustable time delay from 0 to 5 5 minutes for controlled timing of load transfer to
emergency.

6. Signal lights for source availability, switch positions and gold flashed contacts for low
voltage engine start signals.

7. Control panels time delay shall be field set to better than 50 msec accuracy without tools.

J. The following operation shall be controlled by the ATS:

1. Upon loss of normal power, phase failure, or voltage drop of 25%, the ATS shall
automatically start the engine-generator set after a 2 second time delay and after an
additional time delay of 6 seconds the ATS shall automatically transfer loads from normal
to standby supply.

R.A.EUGENIO + PARTNERS Page 33 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

2. Upon return of normal power, while loads are on standby supply, the ATS maintain
supply to such emergency loads from the generator set for a duration of 60 seconds after
which if normal supply is continuous, the ATS shall transfer emergency loads back to
normal power. If normal power fails again, within 60 seconds duration, no transfer shall
take effect.

3. After transferring to normal power, the diesel generator set shall stopped automatically
after a time delay of 10 to 15 minutes. Timer shall be adjustable.

4. The ATS shall be providing with capability for testing purposes by simulating power
failure condition. Selector switch shall be provided for ENGINE TEST, SYSTEM and
TRANSFER TEST, READY and OFF conditions.

PART 3.00 EXECUTION

3.1 INSTALLATION

A. Installation shall conform to the requirements of the Code.

B. Testing:

1. The ATS shall receive the manufacturer’s standard factory testing prior to delivery.

2. Prior to acceptance of the installation, equipment shall be tested on-site together with the
generator set without any failure to show it is free of any defects, and be subjected to full
load test or that load which is available at the jobsite. Should failure occur during the
testing, the Contractor shall rectify deficiencies and shall repeat testing procedure at his
own expense and to the satisfaction of the Owner.

3. On completion of the installation, testing shall be performed by a factory-trained supplier


of dealer representative. Operating and maintenance instruction books shall be submitted
to the Owner and a procedure explained to the Owner’s operating personnel.

4. The ATS together with the LVSB and Generator set shall be tested to the satisfaction of
the Owner and the Engineer.

*** End of Section ***

R.A.EUGENIO + PARTNERS Page 34 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16: ELECTRICAL

SECTION 16208

DIESEL ENGINE GENERATOR SET

PART 1.00 – GENERAL

1.7. INTENT OF SPECIFICATION

The Owner shall secure for the purchaser a standby diesel generator set on the latest commercial type and
designed as specified herein.

1.8. GENERAL REQUIREMENTS

A. Materials and workmanship - All materials and parts of the generator set shall be new and unused.
Each component shall be of current manufacturer from a firm regularly engaged in the design and
production of such equipment. Units and components offered under these specifications shall be covered
by the manufacturer’s standard warranty or guarantee on new machines.

B. Warranty - Equipment furnished under this section shall be guaranteed against defective parts of
workmanship under terms of the manufacturer and dealer’s standard warranty.

C. Test - The generator set shall receive the manufacturer’s standard factory load testing. Prior to
acceptance of the installation, equipment shall be tested to show it is free of any defects and will start
automatically and be subjected to full load test, or that load which is available at the job site.

D. Start-up and Instructions - on completion of the installation, a factory trained dealer service
representative shall perform start-up. Operating and maintenance instruction books shall be supplied
upon delivery of the unit and procedures explained to operating personnel.

E. Specifications and Drawings - The bidders shall furnish information showing manufacturer’s model
numbers, dimensions and weights fir the generator set, engine fuel consumption and other major auxiliary
equipment. Proposed deviations from the specifications shall be stated in the bid. The successful bidder
shall submit copies of pertinent drawings and wiring diagrams for approval.

F. Manufacturer - The unit shall be factory assembled and tested by engine manufacturer and shipped to
the job site by his authorized dealer having parts and service facility in the area. The generator set shall
be as manufactured by “Caterpillar”, “Cummins” or approved equal.

1.3. SUBMITTAL

A. Manufacturer’s Data

1. Diesel engine driven electric generator set


2. Generator Control Panel
3. Engine Muffler
4. Storage Battery
5. Battery Charger
6. Fuel Day Tank

R.A.EUGENIO + PARTNERS Page 35 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

B. Certified Test Reports


1. Diesel engine factory test
2. Generator factory test

C. Manuals - Provide five sets of operation and maintenance manual for equipment.
Identification symbols for all replaceable parts and assemblies shall be included. Information in
manuals shall be comprehensive and specific.

PART 2.00 – PRODUCTS

2.1. GENERATORSETCHARACTERISTICS

A. Rating @ 60 Hertz, 1800 RPM

Power rating @ 0.80 pf with fan –600 kW

The specified standby kW rating shall be for continuous electrical service during interruption of the
normal utility source.

B. Voltage - The generator output voltage shall be 400 volts, 3-phase, 4 wires, 60 hertz nominal.

C. Engine

D. Type - The engine shall be water-cooled in-line or Vee-type for stroke cycle compression ignition
diesel. It shall meet specifications when operating in No.2 domestic burner oil. Diesel engines
requiring premium fuels will not be considered. The engine shall be equipped with fuel, lube, oil,
and intake air filters; lube oil coolers, fuel transfer pump, fuel priming pump, water pump and
radiator. The engine governor shall maintain frequency regulation not to exceed 3% (1.8 Hertz)
from no load to full rated load.

E. Mounting - unit shall be mounted on a structural steel sub-base shall be provide with suitable
vibration isolators.

F. Safety Device - Safety shut-off for high water temperature, low oil pressure, over speed, and
engine over crank shall be provided.

2.2.GENERATOR

A. Type - The generator shall be three-phase, 60 hertz, single bearing synchronous type with
brushless exciter and built to NEMA standards. Class F installation shall be used in the stator and
rotor, and both shall be further protected with 100& epoxy impregnation and an overcoat of
resilient insulating material to reduce possible fungus and/or abrasiondeterioration. Generator shall
incorporate reactive drop compensation for parallel operation and also include a thermal protector
for parallel operation and also include a thermal protector for generator protection against low
power factor loads.

B. Regulator- A generator mounted volts per hertz type regulator shall be provided to match the
characteristics of the generator and engine. Voltage regulation shall be +2% from no load to full
rated load, readily accessible voltage drop, voltage level and voltage gain controls shall be
provided. Voltage level adjustments shall be a minimum of +5%. The solid state regulator module
shall be shock mounted and epoxy encapsulated for protection against vibration and atmospheric
deterioration.

R.A.EUGENIO + PARTNERS Page 36 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

2.3. COOLING SYSTEMS

A. Radiator- An engine mounted radiator with blower type fan shall be sized to maintain safe
operation at 180-220°F maximum ambient temperature. The radiator shall be equipped for a duct
adapter flange. Airflow restriction from the radiator shall not exceed 0.5” W.G. Contractor shall
provide ductwork with flexible connecting section between radiator duct flanges and exhaust
damper.

2.4. DAY TANK

A. Day Tank - The day tank shall be floor mounted and has a capacity of 8 hours operation.

2.5. EXHAUST SYSTEM

A. Exhaust silencer -Provide a critical or residential type silencer including flexible exhaust fitting for
remote amounting, properly sized and installed, according to the manufacturer’s recommendation.
The installing contractor shall provide mounting. Silencer shall be mounted so that the engine does
not support its weight. Exhaust pipe size shall be sufficient to ensure that measured exhaust
backpressure does not exceed the maximum limitations specified by the generator set
manufacturer.

B. Insulation- The muffler and all indoor exhaust pipe shall be lagged by the installing contractor to
maintain a surface temperature not to exceed 150°F. The installation shall be installed so that it
does interfere with the flexible exhaust fitting.

2.6. AUTOMATIC STARTING SYSTEM

A. Starting Motor - A 12 volts DC electric starting system with positive engagements drive shall be
furnished.

B. Automatic Controls - Fully automatic generator set start-stop controls in the generator control
panel shall be provided. Controls shall provide shutdown for low oil pressure, high water temperature,
over-speed, over crank, and one auxiliary contact for activating accessory items. Controls shall
include 130 second single cranking cycle limit with lockout.

C. Batteries - A 12 volts lead-acid battery set of the heavy-duty diesel starting type shall be provided.
The battery set shall be of sufficient capacity to provide for one and one half minutes total cranking
time without recharging and will be rated no less than 170 amp-hours. A battery rack and necessary
cables and clamps shall be provided.

D. Battery Charger – A current limiting battery charger shall be furnished automatically recharge
batteries. Charger shall float at 2.17 volts per cell and equalize at 2.33 volts per cell. It shall include
overload protection, silicon diode full wave rectifiers, voltage surge suppressers, DC ammeter, and
fused AC input. AC input voltage shall be the same as generator output voltage. Amperage output
shall be no less than 5 amperes.

2.7. GENERATOR CONTROL PANEL

A. Type – A generator mounted NEMA 1 type vibration isolated dead front 14 gauge steel control panel
shall be provided. The generator control panel shall consist of separately mounted freestanding type
metal enclosed switchgear, with all protective devices, instrumentation, and control wiring as listed,
terminal blocks and solderless connectors for terminals. It shall be completely assembled, wired and
tested at the factory and shall conform to the applicable standards of ASA, IEEE and NEMA, or VDE
and DIN.

R.A.EUGENIO + PARTNERS Page 37 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

B. Equipment – Electronic Digital panel shall contain, but not limited to the following equipment.

Voltmeter, 3½”, 2% accuracy

Ammeter, 3½, 2% accuracy

Ammeter/Voltmeter phase selector switch

Frequency meter, 3½, dial type

Automatic starting controls as specified in 9.2

Panel illumination lights and switch

Voltage level adjustment rheostat

Engine oil pressure gauge

Engine water temperature gauge

Dry contacts for remote alarms wired to thermal strips

Faults indicators for low oil pressure, high water temperature, over speed and over crank

Four position function switch, “auto”, “manual”, “off/reset”, and “stop”

2.8. GENERATOR CIRCUIT BREAKER

A. Type – The generator molded case conduit breaker of adequate capacity shall be installed as a load
circuit interrupting and protection device. It shall operate both manually for normal switching function
and automatically during overload and short circuit conditions. The tripping unit of each pole shall
have elements providing inverse time delay during overload conditions and instantaneous magnetic
tripping for short circuit protection. The circuit breaker shall be standard established by Underwriter’s
Laboratories, National Electric Manufacturer’s Association, and National Electrical Code.

2.9. AUTOMATIC TRANSFER SWITCH (Included in Emergency Switchboard)

A. An automatic transfer switch (ATS) shall be provided and shall be coordinated with manufacturer of
the standby AC power generator to maintain system compatibility for the complete standby power
system.

B. The transfer switch shall be free-standing type suitable for use on all types of loads. ATS shall be
installed in-line with the normal low voltage switchboard and emergency low voltage switchboard as
shown in the plan, and connected to the main buses of switchboards.
.
C. All accessories and equipment shall be front accessible for ease of maintenance or removal.

D. Components of the operating mechanism shall be front insulated or electrically dead.

R.A.EUGENIO + PARTNERS Page 38 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

E. Components of linkage and handles in operating mechanism shall be ruggedly constructed and not
subject to deterioration.

F. Transfer switch shall be withstood, closing and interrupting ratings sufficient for the voltage employed
and the available short circuit at the point of application.

G. Automatic transfer switch (ATS) shall be breaker type, fixed typed, mechanically and electrically
interlocked rated as indicated in the plan, 3P, 60Hz, 400 volts, 3-phase, 4-wires, 65kA symmetrical at
400 volts interrupting capacity.

H. The following operation shall be controlled by the ATS

1) Upon loss of normal power or phase failure ATS shall immediately automatically start the engine-
generator set after time delay of 10 seconds the ATS shall automatically transfer loads from
normal to standby supply. Timer shall be adjustable.

2) Upon return of normal power, while loads are on standby supply, the ATS shall maintain supply
to such emergency loads from the engine generator set for a duration of 60 seconds after which
if normal power supply is continuous, the ATS shall transfer emergency loads back to normal
power. If normal power fails again, within 60 seconds duration, no transfer shall be affected.

3) After transferring to normal power, the diesel generator set shall be stopped automatically after a
time delay of 10 to 15 minutes.

4) The ATS shall be provided with capability for testing purposes by simulating power failure
condition. Selector switch shall be provided for ENGINE TEST, SYSTEM and TRANSFER
TEST, and READY conditions.

5) ATS circuit breaker devices shall be capable of being operated manually.

PART 2.00 – EXECUTION

A. All equipment and auxiliaries shall be delivered to the site.

B. Installation of all supplied equipment by the contractor shall be supervised by the Manufacturer’s
Qualified Representativeshall be present at all times while the equipment are being installed and
tested.

2.1 TESTING

Perform the following tests on the generator set system provided. The Engineer who shall witness the
testing shall be given 5 working days notice prior to each test. The supplier/Contractor shall provide
all test equipment, fuel and personnel and submit written copies of all test results for the following.

A. Factory Tests

The engine-generator shall be subject to the manufacturer’s standard run-in conditioning test.
Following the run-in tests, test the engine-generator set at rated speed and voltage for 8 hours of
continuous operation with 2 hours each at 50,75, and 80 percent of rated load, consecutively, .8
power factor. Determine generator frequency, phase current and voltage then record at 15 minute
intervals. Run tests on the voltage regulator to determine the variation of terminal voltage under

R.A.EUGENIO + PARTNERS Page 39 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

conditions of constant load, and under conditions of abrupt load changes to determine the maximum
voltage change during the surging period and the time required. Factory test shall also be performed
to demonstrate compliance with 15% maximum voltage change during the surging period and the
time required. Factory test shall also be performed to demonstrate compliance with 15% maximum
voltage dip at 100% step load.

B. Field Tests and Inspections

The equipment supplier perform all field tests and trial operations, and conduct all field inspections.
Field tests shall be the same as for factory tests.

*** End Section ***

R.A.EUGENIO + PARTNERS Page 40 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16 – ELECTRICAL

SECTION 16400

PAD MOUNTED TRANSFORMER

PART 1.00 GENERAL

1.1 GENERAL DESCRIPTION

A. These specifications cover requirements for three-phase, pad-mounted, liquid filled, self-cooled,
loop-feed, dead front, 60 Hz distribution transformers.

B. These transformers are to be used to supply three phase power loads from an underground
system. Ratings of these transformers are indicated on Plans.

PART 2.00 PRODUCTS

2.1 ELECTRICAL FEATURES

A. KVA AND VOLTAGE RATINGS

1. The transformer shall be three phase, 60 Hz, pad mounted, self-cooled. The transformer
ratings shall be as follows:

KVA - 1000KVA
Phase - 3
Frequency - 60 Hz
Primary Voltage - 19.92/34.5KV
Secondary Voltage - 230/400V
Cooling - ONAN
Brand - Schneider, ABB or Cooper

2. Primary shall delta connected and secondary grounded wye connection.

3. The temperature rise of the transformer winding shall be for 65 deg.C. The transformer
shall be capable of carrying 100% nameplate KVA rating at 65 deg. C. average winding
temperature rise in a 40 deg. C ambient temperature

B. TAPS

1. Primary taps for the 36KV units shall be full capacity with a minimum of 2-2.5% above
and 2-2.5% below rated voltage.

2. The de-energized tap changer control must be externally operable with a hot-stick. The
preferable location for the control is the primary compartment.

R.A.EUGENIO + PARTNERS Page 41 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

C. INSULATION LEVELS

1. Impulse rating of the high voltage winding must be equal to the basic impulse level
specified by ANSI for liquid filled distribution transformers of the same voltage class,
without the use of supplemental surge arresters.

a) For 36KV class insulation level shall be 150KV BIL.

2. Impulse rating of the low voltage winding must be 30KV for 400 volts.

D. IMPEDANCE VOLTAGE

The transformers shall be guaranteed to have an impedance of 5.0%-6.0%.

Variations from the guaranteed values shall be in accordance with ANSI 57, 12.00.

E. PRIMARY SWITCHING

An internal, liquid-immersed, manually and group operated, single-phase, four position load
break switch shall be provided for each transformer for disconnecting incoming lines to
completely isolate the transformer from a looped primary system.

The switch must be capable of switching 200A to permit sectionalizing the looped system. The
switch handle shall be located in the primary compartment and must be hot-stick operable.

F. OVERCURRENT PROTECTION

Primary shall be a combination of current limiting fuses and expulsion fuses coordinated to
provide full range protection with the explosion fuse, clearing high-current faults up to 42,000
amperes asymmetrical.

1. The expulsion fuses shall be liquid-immersed, bayonet-type and shall be suitable for field
replacement using standard hot-stick. Drip-shield shall be provided under the bayonet
fuse.

2. The current limiting shall be liquid-immersed, internal block mounted and shall not be
suitable for field replacement.

G. CURRENT-CARRYING CAPABILITIES

The minimum current-carrying capabilities of components for looped primary cable systems shall
be 200 amperes (continuous) and 10,000 amperes asymmetrical (momentary).

2.2 CONSTRUCTION FEATURES

A. TANK AND TERMINAL COMPARTMENT

The transformer shall be deadfront compartmental type consisting of transformer tank with high
and low-voltage cable terminating compartment assembled as an integral unit for mounting a pad.

R.A.EUGENIO + PARTNERS Page 42 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

1. There shall be no exposed screws, bolts, or other fastening devices which are externally
removable.

2. There shall be no openings through which foreign objects such as sticks, rods, or wires
might contact live parts.

3. The high-voltage and low voltage compartments shall be located side-by-side separated
by a steel barrier, with the high-voltage compartment on the left when facing the unit.
Access to high-voltage side shall only be after the door to the low-voltage compartment
has been opened.

4. The high-voltage compartment shall have sufficient space to contain elbow type, sully
shielded gapless surge arresters.

5. The compartment shall have hinged doors equipped for latching in the open position. To
facilitate making connections and permit cable pulling, the doors and compartment hood
shall be removable. Removable door sill on compartments shall be provided to permit
rolling or skidding of unit into place over conduit studs in foundation. Hinge assemblies
shall be stainless steel.

6. The compartment doors must be capable of being secured with a single padlock having a
minimum of 3/8” diameter shackle. In addition, the access doors shall be secured by a
captive recessed stainless steel pentahead bolt.

7. Facilities for jacking, rolling, lifting, and mounting shall be provided.

8. The instruction nameplate shall be stainless steel and shall be attached in the low-
voltage compartment using non-corrosive rivets or screws. It shall be readable with
cables in place. In addition to other nameplate data, the high-voltage BIL shall be
included.

9. Transformers shall be of sealed-tank construction with a welded main cover. A bolted-


tamper resistant handhole shall be provided in the tank cover for access to internal
connections. Provisions for tank grounding shall be supplied in both high-voltage and
low-voltage compartments.

B. HIGH VOLTAGE BUSHINGS

Separable insulated high-voltage bushings shall be provided for use with load elbow-terminator in
looped primary cable system.

1. The bushing shall be one-piece, three phase rated, load break design as per ANSI/IEEE
Standard 386. Elbow and bushing shall be produced by the same manufacturer.

2. The bushings shall be identified H1A, H2A, H3A and H1B, H2B, H3B, and shall be
arranged as per ANSI C57.12.25.

3. The high voltage side neutral point shall be brought out through a separate bushing for
grounding.

4. Dust caps over bushings shall be provided for shipping and storing.

R.A.EUGENIO + PARTNERS Page 43 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

5. Brackets for stand-off parking bushings shall be provided adjacent and horizontal to each
bushing.

C. LOW-VOLTAGE BUSHINGS

Insulated low-voltage bushings shall be provided and arranged for vertical take-off:

1. Bushings for all units shall have tinned spade type terminals with 6-hole NEMA drillings.

2. The neutral connection of the low voltage winding shall be brought out on an insulated
bushing and connected to the ground pad in the low-voltage compartment with a
removable ground strap. The ground strap shall be sized for the rating of the transformer
and connected to the neutral bushing by means other than the mounting holes available
on the spade. The ground strap shall be adequately sized and connected for maximum
conduction.

3. Bushings shall be identified X1, X2, and X3 and X0 for the neutral.

D. PROTECTIVE FINISH AND MARKING

1. Unit to be painted Munsell green 7.5 GY 2.95/2.1. Paint to be applied to a minimum


thickness of 3 mils on all exposed surfaces and on cabinet interior. Rust-proofing shall be
applied to all surfaces that are in contact with the pad.

2. KVA and voltage rating shall be painted of 1” minimum height, on the inside of the hinged
door, readable with the door in open position. In addition, each transformer shall be
identified on the over case with 1” minimum height KVA rating and serial number.

E. ACCESSORIES

The following accessories shall be provided on all units

1. Drain valve.

2. Filling plug.

3. Liquid level plug.

4. A pressure relief device which is capable of both manual and automatic operation shall
be installed above the liquid on all transformers. The pressure relief device shall be
installed so that when operated, will vent toward the ground and not straight out. All
pressure relief devices shall be equipped with an eye for hotstick operation.

The pressure relief devices shall automatically vent gradually upon a pressure build-up
0.00315 kg/mm 2 (4.5 psig) and immediately reseal after the pressure is expelled.

2.3 INSULATED LIQUID

The insulating liquid to be used shall be high fire point type. In no case shall PCB or other harmful
substances be used as insulating fluid.

R.A.EUGENIO + PARTNERS Page 44 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

PART 3.00 EXECUTION

3.1 TESTS AND INSPECTION

The transformer shall be subjected to production tests in accordance with the applicable standards used.
Both high and low-voltage windings of the transformer shall be impulse tested without surge protective
equipment of any kind connected on the transformer.

Claims to short-circuit capability shall be supported by short-circuit test reports. Satisfactory tests on a
representative transformer of a given general design will be considered sufficient evidence of the
capability of the basic design to comply with short-circuit requirements. Short-circuit testing shall be done
with zero external impedance.

The any significant movement or distortion of the windings during short-circuit test will cause a change in
the impedance of the transformer, an impedance test shall be made on the transformer, before and after
the completion of the short-circuit test. To assure comparable results, it is essential that the temperature
and resistance of the windings be obtained at the same time of the impedance tests to permit comparison
of the impedance values on a common temperature basis. If the change in impedance exceeds 7-1/2
percent, the transformer will be presumed to have failed the short-circuit test.

However, if the impedance change is within this 7-1/2 percent limit. The transformer will be given the
following tests to assure that the unit is still serviceable:

A. Excitation Loss Test]

B. Impulse Test

C. Applied Potential Test

D. Induced Potential Test

These tests shall be made in accordance with American Standards C57.12 requirements for new
transformers. If the transformer passes these tests satisfactorily, it shall be assumed to have withstood
the prescribed short-circuit test. Claims to loading capability shall be supported b Thermal Evaluation Test
reports and Temperature Rise Test reports. The thermal Evaluation Test and Temperature Test shall be
made in accordance with the latest revisions of ANSI C57.100 and ANSI C57.12.90, respectively.
Satisfactorily tests on representative transformer of a given general design will be considered sufficient
evidence of the capability of the basic design to comply with loading requirements. The Owner reserves
the right to inspect fully all phases of manufacture of these transformers and to witness the tests to be
done to ensure that the manufacturer complies with the specifications. Any item found not to be in
accordance with the specifications will be rejected and replaced with an acceptable item at no extra cost
to the Owner. Inspection by the Owner does not relieve the manufacturer from complying with the
specifications or release him from warranty.

3.2 GUARANTEE

The manufacturer shall guarantee that the transformer furnished under this specification shall be free
from inherent defects in design, workmanship and materials. The guarantee period shall be twelve (12)
month from the date of service or eighteen (18) months after receipt by any authorized Owner’s

R.A.EUGENIO + PARTNERS Page 45 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

representative, whichever comes first. Winning bidders shall submit the name of their authorized
workshop where untanking/dissection and repair of under warranty units with valid warranty claims can be
done. If any part becomes defective within the guarantee period, the transformer shall be
untanked/dissected at the authorized workshop within one (1) month from the notice of the Owner. Units
covered by valid warranty claims shall be repaired or replaced by the suppliers within three (3) months
upon receipt of the Owner’s evaluation results. The guarantee period for any repaired or replacement part
shall be twelve (12) months from the date of service of such repaired or replacement part. Manufacturer
will be advised as to the date the equipment is placed in service. Taxes, duties, banking and handling
charges, that may be incurred in connection with the replacement and/or repair of the defective parts,
wrong shipments or delivery of any part due to omission from original delivery, which otherwise would not
be incurred by the Owner shall be paid by the supplier. Charges, including freight charges, to be incurred
for the return of wrong shipment, rejects, etc., shall also be supplier’s account.

3.3 SUBMITTALS

1. Technical Catalogues for Transformers


2. Dimension Drawings
3. Technical Catalogues for Accessories
4. Cable Termination Instruction Book

*** End of Section ***

R.A.EUGENIO + PARTNERS Page 46 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

SECTION 16402

UNDERGROUND ELECTRICAL WORKS

PART 1.00 – GENERAL

1.01 GENERAL REQUIREMENTS:

A. The Contractor shall furnish and install complete underground electrical system which includes
manholes as shown in the drawings.

B. Section 16000, “Electrical General Requirements”, applies to this section with additions and
modifications specified herein.

1.02 SUBMITTAL:

A. SHOP DRAWINGS OR MANUFACTURER’S DATA FOR:

1. Conduits

2. Manholes, Frame and Covers

3. Service boxes, Frame and Covers

B. CERTIFICATES OF COMPLIANCE:

1. Material and Equipment:

Provide manufacturer’s statement certifying that the product supplied meets or exceeds
contract requirements.

2. Workmen’s Competence:

Thirty days before the scheduled splicing/ termination, submit certificate of competency
which include experiences, trainings and completed jobs of all key personnel for this
work.

PART 2.00 – PRODUCTS

2.01 CONDUIT:

A. Conduit for incoming high voltage cable shall be high impact-resistant polyvinyl chloride conduit
(PVC) schedule 40.

2.02 PULL WIRE:

Shall be plastic having a tensile strength of 90 kilogram.

R.A.EUGENIO + PARTNERS Page 47 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

2.03 GROUND RODS:

Shall be copperclad steel with diameter of 20mm by 3m long unless otherwise indicated.

2.04 METAL FRAME AND COVERS:

Shall be steel plate with sizes shown in the drawing.

PART 3.00 – EXECUTION

3.01 UNDERGROUND DUCT:

Shall be constructed of conduit encased in concrete as shown on the drawing. Separate conduit by a
minimum concrete thickness of 75mm.

A. The top of the concrete envelope shall be a minimum of 450 mm below grade, except under
roads and pavement, where concrete envelope shall be a minimum of 600 mm below grade.

B. Duct banks shall have a continuous slope downward toward underground structures and away
from buildings with a minimum pitch of 75MM in 30M. Except at conduit risers, changes in
direction of runs exceeding a total of 10 degrees, either vertical or horizontal, shall be
accomplished by long sweep bends having a minimum radius of curvature of 900 mm sweep
bends may be composed of one or more curved or straight sections or combinations thereof.

Manufactured bends shall have a minimum radius of 450 mm for use with conduits of less than
75 mm in diameter and a minimum radius of 900 mm for ducts of 75 mm in diameter and larger .
Excavate trenches along straight lines from structure so the elevation can be adjusted, if
necessary, to avoid unseen obstruction.

C. Terminate conduits in end-bells where ducts enter underground structures. Stagger the joints of
the conduits by rows and layers to strengthen the duct bank. Provide plastic or precast concrete
duct spacers that interlock vertically and horizontally. Spacer assembly shall consist of base
spacers, intermediate spacers, and top spacers to provide a completely enclosed and locked-in
duct bank. Install spacers per manufacturer’s instructions, but provide a minimum of two spacer
assemblies per 3 M of duct bank. Before pouring concrete, anchor duct bank assemblies to
prevent the assemblies from floating during concrete pouring. Anchoring shall be done during
concrete pouring.

Anchoring shall be done by driving reinforcing rods adjacent to every other duct spacer assembly
and attaching the rod to the spacer assembly.

D. As each section of a duct bank is completed from structure to structure, a testing mandrel not less
than 300 MM long with a diameter 6 MM less than the inside diameter of the conduit shall be
drawn through each conduit, after which a stiff-bristled brush, having the diameter of the conduit
shall be drawn through until the conduit is clear of earth, sand, and gravel particles. Conduit plugs
shall then be immediately installed.

R.A.EUGENIO + PARTNERS Page 48 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

E. New conduit indicated as being unused or empty shall be provided with plugs on each end.
Provide a plastic pull rope having 90 MM of slack at each end of unused or empty conduits.

F. Connections to Service Boxes:

Duct bank envelopes connecting to underground structures shall be flared to have an enlarged
cross-section at the manhole entrance to provide additional shear strength. The dimensions of
the flared cross-section shall be larger than the corresponding manhole opening dimensions by
not less than 300 MM in each direction.

The perimeter of the duct bank opening in the underground structure shall be flared toward the
inside or keyed to provide for a positive interlock between the duct bank and the wall of the
structure. Vibrators shall be used when this portion of the envelope is poured to assure a seal
between the envelope and the wall of the structure.

G. Partially Completed Duct Banks:

During construction wherever a construction joint is necessary in a duct bank, prevent debris
such as mud, sand, and dirt from entering ducts by providing suitable conduit plugs. Fit concrete
envelope of back into the envelope and a minimum of 600 MM beyond the end of the envelope.

Provide one 12mm dia bar in each corner, 75 MM from the edge of the envelope. Secure corner
bars with two 10 mm dia. Ties, spaced approximately 300 MM. Restrain reinforcing assembly
from moving during concrete pouring.

3.02 MANHOLES:

Shall be poured in place concrete construction as specified herein.

A. Metal Frames and Covers:

Frames and covers of steel shall be welded by qualified welders in accordance with standard
commercial practice. Steel covers shall be rolled-steel floor plate having an approved anti slip
surface.

B. Pulling-in irons shall be steel bars bent as indicated and cast in the walls and floors.

Alternatively, pipe sleeves may be precast into the walls and floors where required to accept U-
bolts or other types of pulling-in devices possessing the strengths and clearances stated herein.
The final installation shall be made permanent.

C. Cable rack arms shall be steel or malleable iron and shall be of the removable type. Insulators
shall be dry-process glazed porcelain. The metal portion of racks shall be zinc-coated after
fabrication. Cable racks, including rack arms and insulators, shall be sufficient to accommodate
the cables. Racks in power manholes shall be spaced not more than 3 feet apart, and each
manhole wall shall be provided with a minimum of two racks. Methods of anchoring cable racks
shall be as follows:

1. Provide a 12 mm diameter by 200 mm long anchor bolt with 75 mm cast in structure wall
with protrusion of threaded portion of bolts. Provide 12 mm steel square head nut on

R.A.EUGENIO + PARTNERS Page 49 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

each anchor bolts. Coat threads of anchor bolt with white lead immediately prior to
installing nuts.

2. Provide concrete channel insert with a minimum load rating of 800 pounds per foot. Insert
channel shall be steel of the same length as “vertical rack channel”; channel insert shall
be cast flush in structure wall. Provide 75 mm steel nuts in channel insert to receive 16
mm diameter by 75 mm long steel, square head anchor bolts.

3. Provide concrete “spot insert” at each anchor bolt location, cast flush in structure wall.
Each insert shall have minimum 800-pound load rating. Provide 16 mm diameter by 75
mm long steel, square head anchor bolt at each anchor point. Coat threads of anchor
bolts with white lead immediately prior to installing bolts.

D. Field Painting:

Frames, covers, and gratings not buried in masonry shall be cleaned of mortar, rust, grease, dirt
and other deleterious materials, and coated with bituminous paint. Steel frames not buried in
masonry and steel covers shall be cleaned of mortar, dirt and grease by an approved blasting
process. Surfaces that cannot be cleaned satisfactorily by blasting shall be cleaned to bare metal
by wire brushing or other mechanical means.

Surfaces contaminated with rust, dirt, oil, grease or other contaminants shall be washed with
solvents until thoroughly cleaned. Immediately after cleaning, surfaces shall be coated with a
pretreatment coating or a crystalline phosphate coating. As soon as practicable after the
pretreatment coating has dried, treated surfaces shall be coated with zinc chromate primer and
synthetic exterior gloss enamel.

E. Excavating, Backfiring, and Compacting:

Excavate underground structures to depths indicated. If hard material is encountered, the


provisions of the contract respecting an adjustment for changed conditions shall apply, subject to
the requirements of notification there under being given.

Hard material shall be defined as solid rock; firmly cemented unstratified masses; conglomerate
deposits possessing the characteristics of solid rock not ordinarily removed without systematic
drilling and blasting; or any boulder, masonry, or concrete (except pavement) exceeding .68 cubic
meter in volume.

1. Excavated materials not required or suitable for backfill shall be removed from the project
site. Provide sheeting and shoring as necessary for protection of work and safety of
personnel. Remove water from excavation by pumping or other approved method.

2. Backfilling around structures shall consist of earth, sand-clay, or sand and gravel, free
from large clods of earth or stones over 25 mm in size. Backfill materials shall be placed
symmetrically on all sides in loose layers not moistened, if necessary, and compacted
with mechanical or hand tampers to 90 percent compaction.

3. Backfilling Trenches:

Place backfill not more than 150 mm thick, and compact each layer. Backfilling shall
progress as rapidly as the construction, testing, and acceptance of the work permits.

R.A.EUGENIO + PARTNERS Page 50 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

Backfill shall be free from roots, wood scrap material, and other vegetable matter and
refuse.

3.03 FIELD TESTS:

As an exception to requirement that may be stated elsewhere in the Contract, notify the Engineer in
writing at least two (2) working days prior to test. Furnish labor, equipment, and incidentals required for
testing. Correct defects in the work provided by the Contractor and repeat tests until the work is in
compliance with Contract requirements.

Show by demonstration in service that circuits and devices are in good operating condition. Tests shall be
such that item of control equipment will function not less than five times.

END OF SECTION

R.A.EUGENIO + PARTNERS Page 51 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16: ELECTRICAL


SECTION 16100
GROUNDING SYSTEM

PART 1.00 – GENERAL

A. The Contractor shall furnish and install complete grounding system as shown in the drawings.

B. Grounding system shall include ground wires, ground rods, and clamps, connectors, grounding
buses, ground wells and auxiliary ground wire taps as shown in the drawings.

C. Equipment Grounding:

The grounded neutrals of the secondary distribution system shall be supplemented by an


equipment grounding system to properly safeguard the equipment and personnel. The equipment
grounding system shall be installed so that all metallic structures , enclosures, raceways, junction
boxes, outlet boxes, cabinets, machine frames, portable equipment and other conductive items in
close proximity with electrical circuits operate continuously at ground potential and provide a low
impedance path for possible ground fault currents. The systems shall comply with the Philippine
Electrical Coe, modified as indicated on the drawings and/or as specified.

1.9. SUBMITTALS

A. MANUFACTURER’S DATA

1. Ground Rods

2. Ground Clamps

3. Ground Wires

4. Connectors

PART 2.00 – PRODUCTS

2.1. GROUND WIRE

Shall be bare copper stranded, with sizes as shown in the drawings and shall be of cylindrical form and
variation shall be within 1% of the actual size called for:

2.2. GROUND BUS

Ground bus shall be solid copper with size as indicated in the drawing.

2.3. GROUND RODS

Shall be copperclad steel with a diameter of 20 mm by 3000 mm long unless otherwise specified.

R.A.EUGENIO + PARTNERS Page 52 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

2.4. GROUND CLAMPS AND CONNECTORS

Shall be solderless compression or bolted type and shall be bronze.

PART 3.00 – EXECUTION

A. Locations of ground rods and ground wells are shown on the plans.

B. The main transformer, generator set and switchboard shall be connected to the grounding system
as shown on the plans.

C. Test the grounding system to assure continuity and the resistance to ground is not excessive.
Make resistance measurement in normally dry weather, not less than 48 hours after rainfall.
Submit written results of each test to the Engineer for approval.

*** End of Section ***

R.A.EUGENIO + PARTNERS Page 53 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16: ELECTRICAL

SECTION 16601

LIGHTNING PROTECTION SYSTEM

PART 1.00 - GENERAL

1.10. GENERAL REQUIREMENTS

A. Section 16000 “Electrical General Requirements”, applies to this section, with modifications and of
the actual size called for.

1.11. SCOPE OF WORK

G. The Contractor shall furnish and install a complete lightning protection system as specified and as
shown on the drawing.

H. The building lightning protection system shall include roof mounted field generating air terminals,
grounding conductors, clamps, conduits and auxiliary equipment as required for complete and
operational lightning protection system.

1.12. SUBMITTAL

A. Manufacturer’s Data

Data shall be sufficient to show conformance to specified requirements.

B. Shop Drawings

Include dimensions, accessories, installation and construction details.

PART 2.00 – PRODUCTS

A. Field Emission (or Early Streamer) Air Terminal shall be used.

B. Insulated copper lightning carrier cable shall be surface mounted and clamp to roof slab.
Down conductor shall be routed in 50 mm diameter PVC conduits to be exposed or embedded in
concrete columns or walls. Down conductor shall be supplied by the same manufacturer of the
lightning terminals and compatible with it.

C. Ground rods shall be clad steel with a diameter of 20mm by 3 meters long.

D. Lightning strike counter shall be provided by the same manufacturer as the air terminal.

R.A.EUGENIO + PARTNERS Page 54 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

PART 3.00 – EXECUTION

3.1 INSTALLATION

A. Installation shall be in accordance with the Code and requirements specified or indicated in the
drawings.

B. Maintain horizontal or vertical runs of ground wires and ensures that all bends have at least 200
mm radius and an angle of any bed shall not less than 90 degrees.

C. Lightning carrier cable and down conductor shall be supported every 1.50 meters on center using
fabricated copper clamps, bolted to roof slab with plastic expansion sleeves.

3.2 FIELD TEST

A. Test the grounding system to assure the continuity and that the resistance to ground is not
excessive.

*** End of Section ***

R.A.EUGENIO + PARTNERS Page 55 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16: ELECTRICAL


SECTION 16160
TESTING

PART 1.00 – GENERAL

A. The Contractor shall provide any material, equipment and labor required, and make such tests as
specified in the various Electrical Power and Lighting Systems and as deemed necessary to show
proper execution of the work in the presence of the Engineer.

B. Any defects or deficiencies discovered as a result of such tests shall be corrected at the expense
of the Contractor without additional cost to the Owner.

C. After the installation is completed and properly adjusted, and at such time as the Engineer may
direct, the Contractor shall conduct operating tests. The various equipment and systems shall be
demonstrated to operate in accordance with the requirements of the Contract Documents. Tests
shall be performed in the presence of the Engineer. The Contractor shall provide electric power,
instrument and personnel necessary for performing the various tests.

D. Contractor shall engage the services of a recognized independent testing laboratory (hereinafter
referred to as testing laboratory) to perform tests herein specified.

E. Testing laboratory shall provide all materials, equipment, labor and technical supervision to
perform such tests.

F. It is the intent of these tests to assure that all electrical equipment is operational within industry
and manufacturer’s tolerances.

G. Upon completion of the tests noted in these specifications, a label shall be attached to all serviced
devices. These labels shall indicate date serviced and the service company responsible and the
name of the Electrical Contractor.

H. Tests shall determine suitability for continued reliable operation.

I. Division of Responsibility:

1. Contractor shall perform routine insulation resistance, continuity an rotation tests for all
distribution and utilization equipment prior and in addition to tests performed by the testing
laboratory.

2. Contractor shall supply suitable and stable source of test power to test laboratory at each
test site. Testing laboratory shall specify requirements.

3. Contractor shall notify testing laboratory when equipment becomes available for acceptance
tests. Work shall be coordinated to expedite to project scheduling.

4. Contractor shall supply complete set of electrical plans, specifications and any pertinent
change orders to the testing laboratory prior to commencement of testing.

5. Testing laboratory shall notify the Engineer prior to commencement of any testing.

R.A.EUGENIO + PARTNERS Page 56 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

6. Testing laboratory shall be responsible for implementing all final settings and adjustments on
protective devices and tap changes in accordance with specified values.

7. Any system material or workmanship which is found defective on the basis of acceptance
tests shall be reported directly to the Engineer.

8. Testing laboratory shall maintain written record of all tests and upon completion of project,
assemble and certify final test report.

1.1. INSPECTION AND TEST PROCEDURES

A. Cables – Low Voltage (600 Volts and Less)

1. Visual and Mechanical Inspection:

a) Cables to be inspected for physical damage and proper connection in accordance with
single line diagram.

b) Cable connection shall be torque tested to manufacturer’s recommended values.

2. Electrical Tests:

a) Perform insulation resistance test on each cable with respect to ground and adjacent
cables.

b) Perform continuity tests to ensure proper cable connection.

3. Test Values:
1
a) Insulation resistance tests shall be performed at 1000 volts D.C. for one-half ( /2)
minute.

b) When insulation resistance must be determined with all switchboards, panelboards,


fuse holders, switches and overcurrent devices in place.

B. Circuit Breakers

1. Visual and mechanical Inspection:

a) Circuit breaker shall be check for proper mounting, conductor size and feeder
designation.

b) Operate circuit breaker to insure smooth operation.

c) Inspect case for cracks of other defects.


d) Check tightness of connection with torque wrench in accordance with manufacturer’s
recommendations.

2. Electrical Tests:

a) Contact resistance shall be measured.

b) Time-current characteristics test shall be performed by passing three hundred percent


(300%) rated current through each pole separately. Trip time shall be determined.

R.A.EUGENIO + PARTNERS Page 57 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

c) Instantaneous pickup current shall be performed by run-up or pulse method. Clearing


times should be within four (4) cycles or less.

d) Insulation resistance shall be determined pole-to-pole, across pole-to-ground. Test


voltage shall be 1000 volts D.C.

3. Test Values:

a) Contact resistance shall be compared to adjacent poles and similar breaker.


Deviations of more than fifty percent (50%) shall be investigated.

b) Insulation resistance shall not be less than fifty (50) megaohms.

C. Metering and Instrumentation

1. Visual and Mechanical Inspection:

a) Examine all devices for broken parts, indication of shipping damage and wire
connection tightness.
b) Verify meter connections in accordance with single line meter and relay diagram.

2. Electrical Test:

a) Calibrate all meters at mid-scale. Calibration instruments shall have precision no more
than fifty percent (50%) of the instrument being tested.
b) Calibrate watt-hour meters to one-half percent (1/2%).
c) Verify all instrument multipliers.

D. Grounding System

3. Visual and Mechanical Inspection:

Inspect ground system for compliance with plans and specifications.

4. Electrical Tests:

Perform ground continuity test between main ground system and equipment frame system
neutral and/or desired neutral point. This test shall be made by passing a minimum of (10)
amperes D.C. current between ground reference system and the ground point to be tested.
Voltage drop shall be measured and resistance calculated by voltage drop method.

a) Perform insulation resistance tests phase-to-phase and phase-to-ground with switch in


both source positions.

*** End of Section ***

R.A.EUGENIO + PARTNERS Page 58 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16: ELECTRICAL


SECTION 16720
FIRE DETECTION AND ALARM SYSTEM

PART 1.00 – GENERAL

1.13. General Requirements

The work includes furnishing of labor, materials, tools and equipment necessary for and incidental to the
installation of a complete for operation and usable standard system conforming to the applicable
requirements of NFPA except as modified herein. Materials and equipment to be furnished under this
Contract shall be essentially the current design products of one manufacturer regularly engaged in the
production of such equipment.

A. The system shall be a semi addressable closed circuit, electronically-supervised, non-coded, Fire
Detection and Alarm System capable of control and monitoring 800 minimum addressable points.

B. The system shall include but not limited to Fire Alarm Control Panel (FACP) with trouble buzzer
and lights, manual stations, alarm speaker with strobe light, automatic detectors, interface
addressable modules, stand-by batteries, telephone and emergency voice evacuation system.

C. The system shall be wired as Class A System throughout for the risers only and preferably with
two (2) pairs of wires.

D. The system shall comply with the applicable provisions of NFPA, local building codes, and meet all
the requirements of the local code enforcing authorities. The system shall be listed, labeled or
approved by Underwriter’s Laboratories, Inc.

E. Installation of the system shall be governed by the provisions of the latest edition of the Philippine
Electrical Code and existing rules and regulations of the locality and other governing agencies.

F. All materials and equipment to be furnished shall be essentially the standard products of a single
manufacturer regularly engaged in the production of such equipment.

1.14. Qualifications of Installer

A. Prior to the installation, the Contractor shall submit data for the approval of the Engineer which will
show that he has successfully install fire alarm systems of the same type and design as specified
herein, or that he has a firm contractual agreement with a sub-contractor having such required
experience. The data shall include the names and the locations of at least two (2) installations
where the Contractor or the Sub-Contractor referred to above, has installed such systems. The
Contractor shall indicate the type and the design of these systems and certify that these systems
have performed satisfactorily in the manner intended for a period of not less than 18 months.

B. Manufacturer’s Representative

The services of a qualified manufacturer representatives or technician, experienced in the


installations and operation of the type system being provided shall be furnished to supervise the
testing, including the final testing, adjustment of the system and instructions.

R.A.EUGENIO + PARTNERS Page 59 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

1.3. Submittals

Submittals shall be a complete set; partial submittals are not acceptable. Six copies of complete
submittals shall be provided. Items for which the submittal; “ELECTRICAL GENERAL REQUIREMENTS”
apply are as follows:

A. Manufacturer’s Data

Each item supplied shall be clearly identified on each sheet.

1. Control Panel
2. Storage Batteries
3. Battery Charger
4. Cabinets
5. Manual Pull Station
6. Heat Detector
7. Addressable Interface Module
8. Smoke Detector
9. Emergency Voice Evacuation System
10. Fire Alarm Bell with strobe Light

B. Shop Drawings

1. Control Panel interior wiring diagrams.

2. Point to Point diagrams showing the points of connection and terminals used for all electrical
field connection in the system.

3. Installation drawings showing locations and layout of all fire alarm equipment, electrical
power supply panels, wring counts and conduit runs from the control panel to all associated
equipment.

C. Operation and Maintenance Manuals: All System Components

Operating instructions shall include thorough training procedures and recommended testing
frequency for each item. Maintenance instructions shall include complete trouble-shooting
manuals.

D. As-Built Drawings

As-built drawings shall show installed conduits and exact locations of all installed equipment.

E. Spare Parts

1. 5% of each type of detector provided


2. Five (5) complete set of system keys

1.4. System Function Requirements

A. Upon actuation of any manual station detectors, automatic detectors or flow switches, an audible
alarm shall sound at the FACP continuously, a tone generated alarm with pre-recorded message
shall sound at the floor level in alarm condition as well as one floor above and below.

The LCD display at the FACP shall indicate in alphanumeric the area in alarm.

R.A.EUGENIO + PARTNERS Page 60 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

All operation shall remain in the alarm mode until the manual station, automatic detector is
recorded to normal and the FACP reset, upon which all systems including auxiliaries return to
normal operation.

B. The system shall be electronically supervised for all signal initiating circuits, alarm signal sounding
circuits, battery supply circuits and low stand-by battery voltage. Supervision shall also be
provided for loss normal power supply. Any ground fault and open-circuit condition in any of the
above circuits shall cause an audible trouble signal to sound continuously until the system is
restored to normal at the central control panel or until the signal is silence by a cut-off switch.

On operating this cut-off switch, a trouble-indicating lamp will light to indicate that the trouble signal
is cut-off. Upon connection of the trouble conditions and when the system is restored to normal,
the trouble signal shall sound again to indicate cut-off by restoring the switch to its normal position
and at the same time, extinguishing the trouble indicating lamp.

Open circuits or ground faults shall not cause false alarm on the system.

A separate alarm and trouble lamp shall be provided for each zone alarm initiating circuit at the
control panel.

C. All signal initiating circuits, signal indicating circuits and trouble signal circuits shall operate on 24
VDC. The main operating power shall be 220 volts AC from building supply mains transformed
through a two-winding isolation type transformer and rectified to 24 volts DC. An auxiliary power
supply operation of the system in the event of failure of the AC shall be provided. The auxiliary
power supply consists of rechargeable storage batteries, and battery charger. The batteries shall
re-charge automatically upon restoration of the AC power supply. Transfer from normal to
emergency to normal power. Transfer from automatic shall not cause transmission of false alarm.

PART 2.00 – PRODUCTS

2.1. Fire Alarm and Control Panel (FACP)

A. The FACP shall contain a mimic board face cover with an LCD text display which will indicate the
location of the alarm by means of illuminated alphanumeric text signaling module and power
supply.

B. The FACP shall be solid state design with full capability for sensing automatic detectors, and
manual stations and have the provision for integrating with a security system.

C. The FACP shall be completely programmable equipped with a panel mounted alphanumeric LCD
text display for fire, fault and reset events showing the date and time with the zone and loop
numbers.

D. The FACP shall have a key operated lock and the case itself shall be protected to detect any
unauthorized attempt at operating it at anytime whether or not the system is in the secure or
access mode o operation.

E. The FACP shall be capable to operate remote annunciators, computers and printers.

F. The control panel will be powered from a 220 volt, 60 cycle source and will contain all necessary
equipment to constantly charge the battery to ensure its full capacity at all times. In the event
power failure from the 220 volts, 60 cycle source, the battery will automatically provide power for
the system and the unit shall contain all devices necessary to accomplish automatic changeover
and shall be accomplished automatically without causing the unit to transmit an alarm. When the
emergency power source is no longer able to supply the necessary energy, the unit will sense this

R.A.EUGENIO + PARTNERS Page 61 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

condition and automatically transmit an alarm to the alarm receiver. If the primary power source is
restored before the battery has been de-energized, the unit will automatically recharge the battery
to its full capacity at the proper rate upon resumption of the primary power source.

2.2. Standby Power

A. Standby system auxiliary power supply capable of operating the FACP smoke detectors and fire
alarm indicating units shall be provided. Upon failure of primary Emergency power, the system will
automatically switch to auxiliary power supply without causing a false alarm. Systems that require
any manual intervention to re-start on switch over to batteries or return to primary power shall not
be acceptable.

2.3. Detectors

A. Heat Detectors - Rate of Rise

Detectors shall operate to cause an alarm when subjected to temperature greater than 135°F or
when the temperature rises at rate of 15°F per minute. Detector shall be provided with red LED
lamp to indicate detector is activated. Detector shall be ceiling type design for semi-flush mounting
as indicated in the plans. Detectors shall be supported independently of wiring connection.

B. Smoke Detectors

Automatic smoke detectors shall be designed for detection of abnormal smoke densities by the
photoelectric principle and shall have a time delay (to prevent false alarm), rate compensation
circuit to increase detection sensitivity upon rapid build up of smoke. The detector shall operate on
a multiple cell concept using a light emitting diode light source. Failure of the LED shall not cause
an alarm condition but shall operate the detector-indicating lamp. Detectors shall contain a red
LED which glows when it is activated.

PART 3.00 – EXECUTION

3.1. Test during Installation

The following test shall be conducted by the Contractor during installation of wiring and system
components. Any deficiency pertaining to these requirements shall be corrected by the Contractor prior to
final functional and operational tests of the system.

A. Ground Resistance

The resistance of each connection to ground shall be measured and shall not exceed 10 ohms.

B. Dielectric Strength and Insulation Resistance

The dielectric strength and the insulation resistance of the system interconnecting wiring shall be
tested by means of an instrument capable of generating 500 volts direct current and equipped to
indicate leakage current in 100 megaohms. For the purpose of this test, the instrument shall be
connected between each conductor and ground at the control panel and of the line, with the other
extremity open circuited and all series connected devices in place. The system shall withstand the
test without breakdown and shall indicate a resistance of not less than 500,000 ohms, the
measurement being taken after an electrification of not more than one minute with a direct current
potential of not less than 100 volts or more than 550 volts.

R.A.EUGENIO + PARTNERS Page 62 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

3.2. Test Upon Completion

Upon completion of the installation, the system shall be subjected to complete functional and operational
test in place of each detector. When all required corrections have been accomplished, the system shall
be re-tested and the Engineer notified of readiness for final inspection. At this time any and all required
test shall be repeated and any defectscorrected until the system is found to be acceptable. The
Contractor shall furnish all instrument, labor and materials required, for the test, and a qualified technician
to conduct the test.

*** End of Section ***

R.A.EUGENIO + PARTNERS Page 63 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

DIVISION 16: ELECTRICAL

SECTION 16727

CLOSED CIRCUIT TELEVISION SYSTEM

1.0 GENERAL REQUIREMENTS

A. The system shall consist of but not limited to indoor CCTV, a digital video management
microprocessor-based video processor, multiplexer and recorder. Designed to operate with color
composite video signals, the device shall complex and multiplex video images with the minimum
16 cameras and store them in the unit’s image database. It shall provide a variety of multiple- and
single camera display options, optional operator selected activity target settings, playback, optional
image enhancement tools and several alarm/event triggered response options. The unit shall
provide operator definable live filters to record and trigger alarm events when the light level
change, a motion is detected or a perimeter is crossed. The unit shall provide operator-definable
filters to search image database for light changes, motion and perimeter violations, as well as
camera, date/time and filter settings, and then display a list of matching video segments. It shall
provide for simultaneous recording, playback, transmitting, database searching and archiving. All
display features shall be available from an on-screen interface. Some features shall also be
available from an optional manufacturer-specific camera control device. All programming features
shall be available from an on-screen programming interface. The unit shall provide for network
operation a manufacturer-specific software application.

B. All materials and equipment to be furnished shall be the standard products of a single
manufacturer regularly engaged in the production of such equipment and shall be listed by
Underwriter’s Laboratories, Inc., CE, or shall be in conformance to established standards other
than those of the United States.

C. Equipment lists presented here shall summarize the main content of the system and are not
intended to be exhaustive. The Contractor shall be responsible for ensuring that a complete
working system is provided.

D. All equipment must be propriety, generally available products. This is to ensure that the future
extensions to the system may be carried out by any installing Company extending the controls by
adding cards, cages, etc.

E. Color camera shall be of 1/3” CCD format with microlens on each pixel for high sensitivity. Minimum
illumination shall be 1 lux or better. Horizontal resolution shall be 330 lines or better. Lens shall be
standard, wide angle, super wide, telephoto, motorized zoom lens. Lens shall be made of glass and
shall be C or CS mount type and must be the same brand as the camera.

2.0 PERFORMANCE SPECIFICATIONS

A. Digital Video Recorder

The digital video management system will meet the following operating requirements or approved
equivalent.

1. Video Format

Color (input and output) : NTSC

R.A.EUGENIO + PARTNERS Page 64 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

2. Alarm

Includes programmable alarm input and output, motion detection and pre-alarm.

3. Display

Display output shall available from the SVGA adapter at 16.7 million colors, mouse-
selectable buttons with indicator lights for display controls. Display shall be simultaneous-
multiple display corresponding to the maximum number of cameras.

A standard mouse input device shall be provided to operate the on-screen program features.
The mouse input port shall be a small round PS/2 style connector.

4. Record Options

Record mode shall be a selectable Linear or Continuous. Record method can be selectable
from either “Record All Cameras All the Time” or “User Defined Schedule or Settings”.

Archive method shall be selectable from Archive in Background (Online), Offline and No-
Archive. Image quality shall be selectable from minimum compression for playback
resolution. Record Rate will range from 60ips, 45ips, 30ips, 15ips, 7.5ips, 2.5ips, 1ips,
(images per second) in real time. Record Resolution will be at least 320x240 for compressed
image quality.

5. Digital Image/Zoom Capability

The unit shall allow operator selection and display of stop-action or frozen images of any
stored image while in playback mode. As an option, the unit shall allow magnification of a
display image up to a factor of 16 times its original size.

Optional playback tools shall provide the means to enhance any stored image for display or
output to an attached printer. This selection of tools shall include image enhancement,
image sharpening, brightness and contrast control, and hue and saturation/lightness control.

6. Database Browsing

Images stored in the database shall be identified to allow search and retrieval by type of event or
image. Searches shall be specified by alarm, camera number, date/time, event type (i.e., video
loss) or filter (optional). Search result shall be provided in a scrollable list to allow selection for
display.

7. Components

a. Main Monitor

Principal display output shall be available from the SVGA adapter capable a resolution of
800x600 pixels to a 21” Monitor display. The SVGA output port shall be a standard DB15-S
connector.

Main monitor output to a standard television or other video device shall be provided using
composite and S-Video connectors. The output connection for composite video shall be a

R.A.EUGENIO + PARTNERS Page 65 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

standard RCA style connector. The output connection for S-Video shall be a standard S-
Video style connector.

b. Diskette Drive

Image transfer or system software update shall be available through an internal 1.44 MB,
3.4”, half-height, IDE controlled floppy disk drive. The unit shall allow the use of
enhancement tools on the loaded image.

c. Hard Drives

Equipped IDE Hard disk and the capacity shall be expandable to handle a capacity of 16
cameras recording for 90 days recording in real time at 30 image per second per camera.

d. Network Interface

Supports 10BASE-T (10Mbps) and 100BASE-TX (100Mbps) network operation.


Network connectivity shall be available through an RJ-45 network port on the rear panel.

e. Modem Card

Supports 56 kb dial-up communications for remote management. This shall be available


through a connector on the rear panel.

f. Printer

A printer output shall be available through a parallel port.

An optional data export accessory pack shall give the user the ability to identify previously
recorded video segments and copy them to a removable media drive. Writable CD devices shall
be supported.

a. CD-RW/DVD-RW Drive-CD-RW/DVD-RW internal drive, 51/4”, half-height, using 74 minute


(650 MB) or 80 minute (700 MB) rewriteable CDs or DVD-RW Disc.

1 1
b. Digital Audio Tape Drive- DDS-4 internal tape drive, 5 /4”, half-height (3 /2”, half-height with
adapter kit)

c. Digital Audio Tapes- with a minimum of 120-meter DDS-2 (4.0 GB)

8. Power Supply

Input : 230VAC, Single Phase, 60 Hz,

9. Environmental Requirements

Temperature : Minimum of 5-40° C (41-104° F)

Humidity : Minimum of 5-95% RH non-condensing

R.A.EUGENIO + PARTNERS Page 66 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

Altitude (operating) : 0-3,048 meters (0-10,000 feet)

with tape drive : 0-2,133 meters (0-7,000 feet)

Tilt : Maximum of 15 degrees.

Real panel connectors and controls shall be labeled indicating the intended origin or intended
destination of the input or output available at each connector, or the associated feature controlled.

B. Camera
1
The camera must incorporate a /3-inch CCD array with interline transfer and Digital Signal
Processing (DSP) to produce no less than 330 TV lines of resolution. The CCD array active pixel
count must be no less than 510 (H) x 492 (V) for NTSC and 500 (H) x 582 (V) for PAL.

The camera must produce usable video at 0.91 lux and provide an automatic electronic shutter
and automatic gain control to assure it will operate in a wide range of lighting conditions using
manual iris lenses. The camera must accept either C or CS mouth lenses without the use of an
adapter ring.

On third inch general purpose color digital CCD camera shall meet the following operating
requirements:

1. Operational
1
Imager : Interline transfer /3-inch CCD array
Video Output : 1.0 Vp-p / 75 Ohm, composite
Active Pixel Count
NTSC : 510 (H) x 492 (V) pixels
PAL : 500 (H) x 582 (V) pixels
Minimum Scene Illumination : 0.91 lux (F1.2 lens)
Horizontal Resolution : 330 lines
Light Compensation Modes
NTSC : 1/60-1/100,000 sec
PAL : 1/50-1/100,000 sec
Auto Iris Drive : DC or EE-type
Backlight Compensation : On/Off selectable
Aperture Correction : Yes
Synchronization Modes : Internal/Line-lock with phase adjust
White Balance : Auto or Manual Modes
Geometric Distortion : None
S/N Ratio : 50 dB

2. Controls

AES : On/Off
BLC : On/Off
Back Focus : Adjustment ring, with lock
Auto Iris : DC/EE-type, switchable
DC Iris : Level Control
AGC : On/Off
Synchronization : Internal/Line Lock
White Balance : Auto/Manual

R.A.EUGENIO + PARTNERS Page 67 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

3. Electrical

AC Voltage : 24 VAC (+33%, -15%), 50/60 Hz


DC Voltage : 12 VDC (+15%, -10%)

4. Mechanical

Lens Mount : C or CS type

5. Environmental

Temperature : -10° to 50°C (14° to 122°F)


Relative Humidity : 90% (non-condensing)

6. Regulatory
FCC : Part 15, Class B
UL : UL2044
CE : EN50082-1, EN55022, EN60950,
EN50130-4

3.0 STANDARDS AND REQUIREMENTS

A. NTSC standard documents-EIA Recommended Standards RS-170 and RS-170A.

B. EMC (Emissions and Immunity)

1. FCC Part 15b, Class A: Conducted and Radiated Emissions


2. EN50130-4 (1996): Immunity Requirements for Components of Fire, Intruder and Social
Alarm Systems
3. EN55022 (1995): Conducted and Radiated Emissions
4. EN61000-3-2 (1995): Power Line Harmonics
5. EN61000-3-3 (1995): Power Line Flicker
rd
C. Safety- UL1950, CUL1950, 3 edition; EN60950 (1992), Amendments 1, 2, and 3

D. PEC, NEC and other applicable code standards.

The digital video management system video input and video output signal shall conform to RS-170 and
RS-170A standards.

4.0 SUB-CONTRACTING

No part of the contract may be sub-contracted to any other company or individuals without the express
written permission of the Customer. Unless specified to the contrary, it is assumed that all works will be
carried out by the Contractor’s direct labor.

If it is intended to sub-contract any part of the design or installation, this must be made clear in the tender
submission and the name of the sub-contractor(s) must be provided. The Customer reserves the right to
accept or reject nominated sub-contractors.

5.0 ACCESS EQUIPMENT

R.A.EUGENIO + PARTNERS Page 68 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

The Contractor shall be responsible for providing all access equipment necessary to enable safe
installation of all high level equipment and cabling.
6.0 HEALTH AND SAFETY ON SITE

The Contractor will be expected to comply with all health and safety requirements issued by the Customer
and the local governments codes. It is the Contractor’s responsibility to provide all access equipment
required to complete the installation in accordance with good safety practices.

7.0 COMPLIANCE WITH REGULATIONS

All electrical works herein shall be done with the accordance with the provisions of the latest edition of the
Philippine Electrical Code, the laws and ordinances of the local code enforcing with good safety practices.

8.0 COMPLIANCE WITH SPECIFICATION

All tenderers must include a statement that the system proposed and price complies with this
specification. Variations and suggestions for changing or improving the system shall be listed and priced
separately.

The tenderer is required to verify at site existing equipment/system and shall provide detailed system
design architecture information to demonstrate offered system hardware and system is compatible with
the existing system and will able to operate according to this document or contract. He will be deemed to
have done this before preparing his proposal and any subsequent claims on the ground of inadequate or
inaccurate information will not be entertained.

9.0 INDEMNITY AND INSURANCE

The Contractor shall indemnify and keep indemnified the Customer against the injury to, or death of, any
person, and loss of, or damage to, any property arising out of or in consequence of the Contractors
obligations under the contract and against all actions, claims, demands, proceedings, damages, costs,
charges and expenses in respect thereof. For all claims against which the Contractor is required to
insure, the insurance cover shall be a minimum of 1 million or such greater sum as the Contractor may
choose in respect of any one incident.

The Contractor will be expected to produce evidence of sufficient insurance cover to meet these
requirements before any work is carried on site.

10.0 MODIFICATIONS AND VARIATIONS

No modifications or variations to the contract will be permitted without the written consent of the Electrical
consultant and authorized bank representative.

The Contractor shall notify the supervising Consultant immediately if any unforeseen circumstances are
encountered during the course of the Contract which may require modifications or variation and shall
await instructions before proceeding with any part of the Contract which may be affected.

11.0 PRE-ASSEMBLY AND TESTING

All equipment is to be pre-built and tested at the contractor’s premises before being delivered to site. All
equipment function herein, recording equipment, controls etc., are to be assembled and prove to the
satisfaction o the client’s representative before being delivered to site.

12.0 TESTING AND COMMISSIONING

A. Practical Completion

R.A.EUGENIO + PARTNERS Page 69 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

When the contract is considered to be complete, Practical Completion will be effective after thirty
consecutive days of uninterrupted, fault free operation.

B. Warranty Period

The Contractor will repair, correct, or replace any defect of any nature that may occur for a period
of twelve months from the date of the issue of the Certificate of Practical Completion. To this end,
The Contractor will attend site within 1 hour of the fault being reported. The defect will be corrected
without undue delay at the contractor’s expense and to the satisfaction of the engineers. The
period of maintenance of such repaired work shall be extended to a further 3 (three) months. To
this end, the Contractor will hold sufficient stock of spares to allow speedy repair or replacement of
equipment. Waiting for manufacturers to replace or repair equipment will not be acceptable.

The Contractor will provide the employer with details of telephone and fax facilities for reporting
such defects. The warranty is to include for full maintenance of video recorders or cameras in
accordance with the manufacturer’s’recommendations.

The Contractor will have in operation a system whereby all service visits are recorded on a multi-
part form, a copy of which will be left on site. The form will record the date and time of the fault
being reported, the nature o the reported fault, the date and time of the visit and the actual fault
together with the remedial work carried out.

C. Maintenance

The Contractor shall submit a full schedule of maintenance to be carried out on the system during
the warranty period and under subsequent maintenance contracts.

13.0 OPERATING INSTRUCTIONS

On completion of the contract, before the issue of Certificate of Compliance, the Contractor will provide a
full set of manuals and operating instructions, this to include comprehensive descriptive brochures and
technical manuals for all equipment forming part of the contract. It should include as-fitted wiring and
schematic diagram.

An A4 laminated sheet is to be provided with short form operating instructions on one side, and a site
diagram showing camera locations and pre-set positions on the other.

14.0 TRAINING

Training shall be provided by the tenderer free of charge to the assigned personnel; for proper operation
of equipment.

*** End of Section ***

R.A.EUGENIO + PARTNERS Page 70 of 72


IMERIAL ERA MANSION July 16, 2018
Pasay City, Metro Manila Revision:00

SECTION 16760

TELEPHONE SYSTEM

PART 1.00 – GENERAL

A. The telephone system shall consist of an interior system of conduits, outlet boxes, junction boxes, and
terminal cabinets, as shown on the plans. The complete conduit systems shall be ready for use by others
who will install wires and equipments.

B. The Main Distribution Frame (MDF), telephone instruments, telephone distribution cables, terminal
blocks, communication data panel, face plate and operator consoles are supplied and installed by others.

PART 2.00 – PRODUCT

A. CONDUITS

Conduits shall be Polyvinyl Chloride (PVC) conduit with a minimum diameter as indicated under Section
16050 “Interior Wiring System”.

B. BOXES:

Shall be as indicated under Section 16050 “Interior Wiring Systems”.

C. TERMINAL CABINETS:

Shall be code gauge construction provided with SNAP catch and brass lock. All cabinets shall be keyed
alike. Each cabinet shall be provided with 20 mm thick wood backboard.

PART 3.00 – EXECUTION

3.01 INSTALLATION WORKS:

A. The conduit installation works shall be carried out by this Contractor. Conduit installation shall be
as indicated under Section 16050 “Interior Wiring Systems”.

B. Any tools or equipment required for the installation shall be provided free of charge by the
Contractor and shall remain his property.

END OF SECTION

R.A.EUGENIO + PARTNERS Page 71 of 72

You might also like