Winding Applications 2020 PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

THE ART AND SCIENCE OF MEASURING

THE WINDING RESISTANCE OF


POWER TRANSFORMERS
Oleh W.Iwansiw, P.Eng
Technical Consultant - Eltel Industries

TWRM-10A ATWRM-25

This article describes many of the down and steady state conditions prevail.
techniques and problems that may be Most electrical engineers will recognize that
encountered when measuring resistance in the windings of most electrical power
the presence of inductance, especially as equipment such as motors, generators and
applied to measuring the winding resistance transformers have sizeable inductance
of Power Transformers. associated with the resistance of the
windings. When measuring the windings
1. RESISTANCE MEASUREMENTS: of such equipment, special techniques and
precautions need to be employed if accurate
Resistance of a conductor can be determined measurements are to result.
by dividing the voltage across the conductor
by the current flowing through it. This 2. MEASURING RESISTANCE
technique is employed when measuring ASSOCIATED WITH INDUCTANCE:
many resistance samples including the Electrical laws and principles tell us that
windings of transformers to be discusses when inductance and resistance are
here. It should be pointed out that such associated in a circuit, a transient will occur
resistance measurement assumes steady upon the application of power and that the
state conditions where the current through time constant of this transient will be equal
the sample remains steady and so does the to L/R seconds, where L is the inductance
voltage drop across it. This must be true in Henries and R is the Resistance in Ohms.
throughout the measurement period. Most To make measurements in such a circuit, a
professional knowledgeable in the field of time constant of several (5 to 9) time
electrical measurements will recognize that constants will be required to settle the circuit
if inductance or capacitance is associated before meaningful measurements of
with the resistance to be measured, a resistance can be undertaken. The number
transient will be generated on the of time constants required will depend on
application of voltage/current to the test the accuracy desired. 5 time constant will
sample. Accurate measurements of provide an accuracy of 1% and 9 time
resistance will not be possible in R/L/C constants will provide an accuracy of 0.1%,
circuits until the transient is allowed to die approximately.
1
The error in resistance measurements under transformers, being relatively large, this
unstable or transient condition is all due to transient typically controls the time required
the inductance which will have a voltage to complete a measurement on a delta
developed across it equal to V=L.di/dt, connected transformer.
where L is the inductance in Henries and
di/dt it the rate of change of current in It should be pointed out that this transient
amperes per second. In order to make an will occur regardless of which winding is
error-free measurement, the inductance tested (primary or secondary) and regardless
must be eliminated from the circuit or the of the measuring connection (phase-to-
current must remain perfectly steady. phase-to-neutral). The time constant of the
transient within the delta is proportional to
3. TRANSFORMERS:
the ratio of the inductance to resistance
It should be pointed out that the inductive within the delta circuit. This time constant
effects are more serious with large pieces of increases with the increase in the KVA
equipment as large pieces of equipment will rating of the transformer as well as with the
have a larger L/R time constant. The above efficiency of the transformer.
considerations assumed relatively linear
inductors, such as are associated with 5. SAFETY CONSIDERATIONS:
motors, generators or reactors. An
Most professional in the electric power field
additional complication occurs when
will recognise that there is a danger when
measuring the winding resistance of
testing inductive equipment using Direct
transformers. The core of the transformer
Current. The danger is due to the energy
comprises of a closed magnetic circuit and
that is stored in the inductance (E=1/2I.I.L).
therefore the winding exhibits a very large
This is the energy that must be applied to
inductance. The core must be fully or
the specimen upon initiation of the test. The
partially saturated in order to reduce the
same energy must be dissipated in a safe
high inductance and allow the current to
manner upon completion of the test and
flow.
before opening of the current circuit. Should
After the current is established one must still the current circuit be interrupted during the
wait several time constants before readings test, the store energy will be dissipated in a
can be taken. This time constant depends High Voltage arc. Such an arc may damage
on the ratio of the residual inductance of the test specimen, the test equipment or
the winding and the resistance of the cause injury or death to personnel. The safe
measuring circuit. dissipation of the energy cannot be stressed
enough. Safe ways of disposing of the stored
4. DELTA CONNECTED energy include, the shorting of the test
TRANSFORMERS: specimen (inductance) before disconnection,
the use of suitable surge or transient
Delta connected transformers present protectors, or by using electronic techniques.
special problems when their winding Shunt reactors due to their linearity store
resistance is to be measure. This problem is more energy than transformers and are
due to the transient current that will be therefore more dangerous.
established within the delta connection
during the initial transient (start-up) period. 6. DISCUSSION OF PROBLEMS:
As this current is coupled by transformer 6.1 INDUCTANCE WITH RESISTANCE
action to all the windings on the
transformer, it must be allowed to die down The inductance typically associated with the
before accurate measurement can be measurement of winding resistance of
accomplished. This transient is an power equipment to be measured causes a
additional complication when testing delta transient upon initiation. This transient

2
may have a time constant of 1 to 100 secs. 6.3 DELTA CONNECTIONS:
A delay of 5 to 10 time constants may be
Transformers with delta connected
required before a stable reading is obtained.
windings encounter an additional transient
This time constant may be effectively
and causes a delay due to the L/R time
reduced by suitable test equipment. This test
constant within the delta circuit. The test
equipment would provide additional circuit
person has little control over this time
resistance, thereby reducing the L/R ratio
constant except to try and modify the
i.e. Time Constant.
inductance by selecting a higher or lower
6.2 CORE SATURATION: test current. IT MUST NOT be
automatically assumed that a higher current
The measurement of transformer winding
will reduce the inductance. In fact when
resistance has an additional complication
testing the low voltage windings of a large
that of saturating the core to allow the
transformer, the inductance of the winding
current to flow in the winding. The typical
will increase with an increase in current, the
time required to saturate the core depends
current in such situations must be reduced
on the voltage rating of the transformer
or increased past the knee point to
winding being tested. Thus the test
effectively reduce the inductance. In
equipment must apply “volt seconds”
numerous test laboratories, the delta
equivalent to the rated voltage of the
connection is opened by means of a test link
winding before any appreciable current will
to facilitate the winding resistance
be established. The volt-seconds can be
measurement.
calculated by integrating the area under on
half cycle of the voltage and dividing this 7. PRACTICAL SUGGESTIONS AND
value by 2. Thus, a winding rated at 100KV SOLUTIONS:
at 50 Hz will be rated at approx 450 volt-
second while a 100KV, 60 Hz winding will 7.1 MEASURING MOTORS AND
have a rating of 375 volt-seconds, GENERATORS:
approximately. The 50 Hz winding will The measurement of motor and generator
need the application of 6 volts for 75 seconds winding should present little difficulty to the
before the current is established. The test person. Although the inductance of
saturation will occur much faster if a higher such equipment can be substantial, it can
voltage is applied. Thus only 15 seconds readily dampened by incorporating resistance
will be required if a voltage of 30 volts is in the test circuit to reduce the time constant
applied. of the start-up transient. Unless currents in
It must be pointed out that the above the order of 50 to 200 amperes are used the
calculations assume no residual flux energy stored in the circuit is modes and odes
not present a dangerous condition when
(residual magnetism) in the core of the test
terminating the test.
transformer. As the residual flux in a
transformer may be as high as 75% of the 7.2 USING DIGITAL MULTI-METERS OR
saturation flux density, the actual time for OHM-METERS:
the current flow may be 0.25 to 1.7 times
the calculated value. A variety of commercial digital multi-meters
or ohm-meters all using a “constant current
To reduce the time required to saturate the source” upto 1 amp will work well when
core of a high voltage winding, a large test used on small power transformers and
voltage is indicated. The use of a high test motor/generators. When the size of the test
voltage will automatically provide a higher specimen increases and the L/R ratio
resistance in the test circuit that reduces the increases, the constant current sources
L/R time constant. At the same time, the within these instruments become unstable
use of a higher voltage increases the VA and the instrument reading becomes
rating and complexity of the power supply. unstable. Instruments that use passive

3
circuitry (resistors) for controlling the test reduction would allow the bridge to be
current will work properly on all sizes of properly balanced and remain in balance
equipment from smallest to the largest. for a long time. The reading of the bridge,
These ”passive current sources” waste a lot however, would NOT BE CORRECT and
of power in resistors which convert voltage the error would depend on the magnitude
to current to stabiles the measurement of inductance associated with the sample
circuit. (winding) being measured.
7.3 KELVIN AND THOMPSON BRIDGES: Assuming that the 11kv winding of a 10
The traditional method of measuring low MVA transformer is being measured
resistance values has been the Kelvin or (winding resistance 30 milli ohms,
Thompson bridges. These bridges continue inductance about 5 Henries) the error in
to be used to date to measure the winding resistance measurement under the above
resistance of power equipment. When used conditions would be - 0.08 milli ohms or
to measure low resistance values, these 0.25%. It should be noted that the reading
bridges would be equipped with a battery will ALWAYS be lower under a falling
and an adjustable resistor to provide the voltage battery condition and that the error
bridge with excitation current. The exact becomes larger for a low-loss transformer
value or stability of the current is not (lower resistance and higher inductance)
important when making measurements on Calculations:
resistances using a bridge circuit.
R*I = 0.030 ohms * 12 amperes = 0.360 volts
However, when measuring the value of L*di/dt = 5 Henries * 0.0005 a/s = 0.0025
resistances associated with inductance, the volts
STABILITY of current is of great Error= 0.0025/0.36 = 0.0069 or 0.69%
importance. If the current is not stable, the
operator will determine a “fictitious” 7.4 VOLT-METER AMMETER METHOD:
resistance. This resistance will be stable over
a considerably long period of time and Many find it more convenient to use a shunt
provide the operator with a false impression and two milli voltmeters to measure the
that he has made an accurate measurement. resistance of a winding. By using quality
It is therefore very important to use digital voltmeters, one can make
electronic current stabilizers for the test measurements over a wide range of
current in addition to the usual current resistance provided that a suitable current
setting resistor. source and shunt are available. As this
method is very similar to the Kelvin bridge,
An e.g. of a typical “fictitious resistance” all the advantages, disadvantages and errors
measurement is as follows: that were discussed in section 7.3 are equally
applicable here including the “false
Assume a 12V battery source and a 1 ohm reading” examples.
current setting resistor that provides a test
current of 12 amperes. The battery voltage 7.5 THERMAL EMFs:
will fall continuously under the load of 12
As typical measurements discussed here
amperes and for our example we will
involve the measurements of DC millivolts,
assume a fall of 0.010 volt/min (this is a
it is important to take precautions against
good battery!). This means that the test
the introduction of thermal EMFs. This
current will also fall by 0.001 amperes/min.
means that ALL connection to be made are
This type of reduction in test current of
copper-to-copper. Quality instruments for
battery voltage would not be noticeable, as
this application will have copper binding
the battery would fall only to 11.400 volts
posts rather than the usual plated brass
from 12.000 volts after one hour of
terminals. Of extreme importance is the
operation. This continuous current
connection of the leads to the test specimen.

4
As these are typically made using clips, size transformers, this is very difficult to
ONE MUST use SOLID COPPER clips. Very obtain for large power transformers. The
large errors can be introduced by using cost for equipment for accomplishing this
“copper plated steel clips”, especially during on large power transformer is rather large
heat run situations where the bushing and those who are asking for it are not
terminals are hot. willing to pay the price.
7.6 SELECTION OF TEST CURRENT: Considering the measurement of winding
resistance after a heat run is one of the most
The statements by many in the industry is demanding application. The items that
that “the more current you apply, the faster require time are as follows:
the reading will stabiles”. Although this
may be true of many cases, this is NOT true a) Shutdown of heat run.
in all cases. For best results, the test current
b) Disconnection of heat run leads.
should be selected according to requirements
of the test specimen. Thus, when measuring c) Connection of TWRM-10 leads.
transformer winding resistance, it is d) Saturation of transformer and
desirable to use a current that is larger than stabilisation of resistance reading.
the excitation current for that winding. This
will tend to saturate the core and reduce ANSI C-57 specification allow 4 minutes of
the settling time for the measurement. The time between shut-down and the first
selected current should be less than 10% of resistance reading. This time is reasonable
the rated current for that winding, as for medium size transformers but becomes
excessive current will be heating up the unreasonable for the large transformers
winding and causing its resistance to being manufactured today. The test people
increase. A current of 10% will cause only are pressed for time so much that they design
1% of the normal heating of the winding. and procure high current shorting and
Caution should be exercised when selecting unshorting equipment for high current
the test current as some manufacturers claim windings, as these typically take the longest
that excessive DC excitation of the core to connect or disconnect.
produces undesirable stresses. These
stresses are similar to the stresses when a Anyway, allowing half of the allowable time
transformer is energized, saturates, and for tearing down the connections and
draws in-rush current. connecting the Ohm Meter, the remaining
Therefore it may be desirable to limit the test 2 minutes is typically sufficient for
current to 2-4 times the excitation current saturating even the largest transformers and
for the winding being tested. As the obtaining a reading with a TWRM-5.
excitation currents for larger transformers The exception to the 2 minute time would
are typically less than 1% of rated, one be delta connected transformers. As was
should consider test currents in the range explained in section 6.3 there is a transient
of 2-4% rated. This range would increase circulating current set up within the delta
for medium and small power transformers and this current must be allowed to decay
which draw a larger percentage of before accurate resistance readings can be
excitation current. taken. The time constant of this circuit
7.7 TIME REQUIRED FOR A depends on transformer characteristics and
MEASUREMENT: is relatively independent of test conditions.
It is this precise reason that some
There are some individuals in the industry manufacturers of large power transformers
who are asking for a time of only 30 seconds are providing “a delta link” which can open
to obtain a proper reading. Although this the delta circuit to avoid the transient
is readily possible for small or even medium condition within the delta for resistance
measurement.

5
8. TWRM-10 a) Connect the winding equipped with
The Eltel TWRM-10 is a second generation the on-load tap changer contacts to the
instrument designed especially for TWRM-10 for measurement.
measuring the winding resistance of b) Energise the instrument and obtain a
transformers, inductors and other electrical reading.
equipment. The TWRM-10 uses current
electronic technology to provide a regulated c) Operate the tap changer over its full
output current of upto 10A in a smaller size range, up and down, while watching the
and lower weight than the TWRM-5. The indication of the instrument.
TWRM-10 provides, many of the features
asked by the users of TWRM-5. d) If the instrument continues to operate
after the up-down cycle of the tap changer,
Some of its salient features are :
the tap changer operation is proper.
Test currents of 10, 1, 0.1, and 0,01 Amperes
Resistance ranges of 1.9999 milli ohms to e) The instrument will shut down
1999.9 ohms immediately when a contact of the tap
changer is operated incorrectly i.e. causes a
Resolution of 0.1 micro ohms break-before-make operation.
Two measuring inputs
Provides a safe shut-down system 9. ATWRM-25
Provides protection against inductive The Eltel ATWRM-25 is a high current,
kickback digital direct reading Automatic
With the additional resolution, the TWRM-10 Transformer Winding Resistance Meter. It
is ideal for measuring winding resistance during is designed to measure the DC resistance of
heat run in factory tests. Without additional circuits associated with large Inductances.
weight the TWRM-10 is as portable as its It is specifically designed to measure the
predecessor the TWRM-5. resistances of highly inductive transformer
windings very quickly and accurately. The
8.1 TAP CHANGER APPLICATION:
operation of the instrument is micro-
The design features of the TWRM-10 processor controlled and is fully automatic.
ATWRM-25 makes the instrument
especially useful in checking the proper The ATWRM-25 test set can measure the
operation of on-load tap changers on power winding resistance of any transformer- small
transformers. The protection circuit of the or very large, distribution or power, single
TWRM-10/ATWRM-25 automatically or Three Phase, star, delta or zig-zag
shuts down the instrument if the circuit is connected. There are four independent
interrupted even for a few microseconds. measuring channels which can be used to
This features is used for checking the proper, simultaneously measure the DC resistance
make-before-break, operation of the tap
of upto four windings at the same time.
changer. The following procedure is used:
OTHER PRODUCTS
Automatic Transformer Ratio Meters. Automatic 12KV Capacitance & Tan Delta Test Set. Automatic CT/VT Test Sets
& Systems. Automatic Tan Delta & Resistivity Test sets for Transformer Oil. Digital Micro Ohm Meters with built in 100A. source
Relaying Current Transformer Analyser. Transformer Loss Measurement Systems.

ELTEL INDUSTRIES An ISO 9001 - 2008 Certified Company


SCROLL JUNE 2013

311 EMBASSY CENTRE, CRESCENT ROAD, BANGALORE-560 001, INDIA


TEL. : 91-80-22255467, 22205686, 22284253, 22284298 FAX : 91-80-22252733
E-mail: marketing@eltelindustries.com Web site: http//www.eltelindustries.com
Works : Plot No. 39, KIADB Industrial Area, Veerapura, Doddaballapur, Bangalore – 561 203, INDIA
TEL : 91-80-27630366, 27630367, 27630368, 9686693047/48 FAX : 91-80-27630351
CHENNAI : 044-24339075 GURGAON : 0124-2460619, 09311542530 KOLKATA: 09830067236, 033-24765536, 09331094257
MUMBAI : 022 - 21713579, 09325885244 VADODARA : 09327757574 (SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE)

You might also like