SCHEDULE A COMMON SUSBSTATION PARAMERTERS

----------------------------------------------------------------------------------------------------------------------------------------
SECTION A1: 132kV OUTDOOR SWITCHGEAR.

----------------------------------------------------------------------------------------------------------------------------------------

Location Amman

Altitude m <1000

Air Temperatures

Minimum °C -10

Maximum ( Design ambient temperature) °C 50

Maximum daily average °C 35

Humidity variation % 4-98

The climate In day Dry & Hot


In night Cold
Heavy
Pollution level (IEC 60815-1)
Airborne contamination
Isoceraunic level days/annum 15

Solar radiation w/sq.mm 1150

Insulator creepage distance mm/KV 35

Average annual rain fall mm 230

Wind velocity m/sec 50


Ice loading, radial thickness mm 10

Seismic condition Zone 2B accordance


Horizontal acceleration to Jordanian seismic code (latest
version)

NOTES: -

- All outdoor equipment must be suitable for live washing.


- Enclosures for all outdoor equipment can be of ceramic or polymer material.
- Required completion date (CFR) of the works in this contract should be earlier than 36
weeks from the date of issuing the letter of contract award.
- The color of all indoor panels if exist shall be as the existing.
- Tubular type or sectional type to be used wherever possible rather than lattice structure.