Professional Documents
Culture Documents
Chapter-1: 1.1. Overview The Project
Chapter-1: 1.1. Overview The Project
Chapter-1: 1.1. Overview The Project
I. INTRODUCTION
1
Design consideration of the hybrid filter for current compensation has been extensively
studied. A hybrid active filter with damping conductance was proposed to suppress harmonic
voltage propagation in distribution power systems [20]. Nevertheless, this method did not
consider the resonance between the passive filter and the line inductance. The fixed
conductance may deteriorate the damping performances. An ant resonance hybrid filter for
delta-connected capacitor bank of power-factor-correction applications was presented [21].
This circuit was limited to three single-phase inverters, and the filtering performance was not
considered. In addition, the hybrid active filter was proposed for the unified power quality
(PQ) conditioner to address PQ issues in the power distribution system [22]. Several case
studies of the hybrid active filter considering optimal voltage or current distortion were
conducted in [23]. In previous work, the authors have presented a transformer less hybrid
active filter to suppress harmonic resonances in the industrial power system [24], [25]. The
hybrid filter is constructed by a seventh-tuned passive filter and an active filter in series
connection. It operates as a variable conductance at harmonic frequencies according to the
voltage THD, so that harmonic distortion can be reduced to an acceptable level in response to
load change and power system variation.
Since the series capacitor is responsible for sustaining the fundamental component of
the grid voltage, the active filter is able to operate with a very low dc bus voltage, compared
with the pure shunt active filter [14], [20]. Hence, both the rated kVA capacity and the
switching ripples are reduced accordingly. Moreover, the proposed harmonic conductance is
able to avoid over current of the passive filter in the case of mistuning parameters. These
features will benefit practical applications. In this paper, we further present designing
consideration of the hybrid filter. A prototype circuit of the hybrid filter based on 220-V/10-
kVA system has been established to verify theoretic analysis, including steady-state
behaviour, transient response, and stability analysis. Thefiltering performance of the hybrid
filter is discussed considering X/R ratio and magnified variations of line impedance.
We also focus on filtering deterioration due to line resistance, voltage unbalance, and
capacitive filters in the power system. In many cases, an active power filter is designed to
compensate harmonic current produced by a specific non-linear load, in such a way that it
needs to measure the load current to be compensated [14], [26]. In this paper, the active filter
is designed as a harmonic conductance to suppress both harmonic resonance and harmonic
distortion by using inverter-side voltage and current measurements. Notice that it does not
require current information of the non-linear loads. Thus, this approach can be suitable in
power distribution networks in which the loads may be distributed along afeederin addition,
2
compensating fundamental reactive power due to unbalanced load is possible, but it is outside
the scope of this paper.
LITERATURE SURVEY:
This article described a harmonic analysis study that determined that the proposed
midfrequency welder would produce unacceptable voltage distortion on the utility electrical
distribution system, especially an adjacent manufacturing facility with extensive electronic
controls as well as on the house load associated with the midfrequency welder This knowledge of
the harmonics nature of the midfrequency welder load and effective harmonic mitigation methods
provided valuable data to the welder manufacturer so that changes could be made in the design
stage to achieve the utility criteria.
T.-L. Lee, Y.-C. Wang, and J.-C. Li,Design of a hybrid active filter for harmonics
suppression in industrial facilities,”
B. Singh, K. Al-Haddad, and A. Chandra, “A review of active filters for power quality
improvement,”
Active filtering of electric power has now become a mature technology for harmonic and
reactive power compensation in two-wire (single phase), three-wire (three phase without neutral),
and four-wire (three phase with neutral) AC power networks with nonlinear loads. This Project
presents a comprehensive review of active filter (AF) configurations, control strategies, selection
of components, other related economic and technical considerations, and their selection for
specific applications
3
1.3 OBJECTIVES OF THE PROJECT:
4
CHAPTER-2
ACTIVE FILTER
An Active Filter is a type of analog electronic filter, distinguished by the use of one or
more active components i.e. voltage amplifiers or buffer amplifiers. Typically this will be a
vacuum tube, or solid-state (transistor or operational amplifier).
Inductors can be avoided. Passive filters without inductors cannot obtain a high Q
(low damping), but with them are often large and expensive (at low frequencies), may
have significant internal resistance, and may pick up surrounding electromagnetic
signals.
The shape of the response, the Q (Quality factor), and the tuned frequency can often
be set easily by varying resistors, in some filters one parameter can be adjusted
without affecting the others. Variable inductances for low frequency filters are not
practical.
The amplifier powering the filter can be used to buffer the filter from the electronic
components it drives or is fed from, variations in which could otherwise significantly
affect the shape of the frequency response.
Sallen and Key, and VCVS filters (low dependency on accuracy of the components)
5
All the varieties of passive filters can also be found in active filters. Some of them
are:
High-pass filters – attenuation of frequencies below their cut-off points.
Low-pass filters – attenuation of frequencies above their cut-off points.
Band-pass filters – attenuation of frequencies both above and below those they allow
to pass.
Notch filters – attenuation of certain frequencies while allowing all others to pass.
Combinations are possible, such as notch and high-pass (for example, in a rumblefilter where
most of the offending rumble comes from a particular frequency), e.g. Elliptic filters.
For notch filters, the degree to which unwanted signals at the notch frequency must be
rejected determines the accuracy of the components, but not the Q, which is governed by
desired steepness of the notch, i.e. the bandwidth around the notch before attenuation
becomes small.
For high-pass and low-pass (as well as band-pass filters far from the centre frequency),
the required rejection may determine the slope of attenuation needed, and thus the "order" of
the filter. A second-order all-pole filter gives an ultimate slope of about 12 dB per octave
(40dB/decade), but the slope close to the corner frequency is much less, sometimes
necessitating a notch be added to the filter.
6
The allowable "ripple" (variation from a flat response, in decibels) within the passband
of high-pass and low-pass filters, along with the shape of the frequency response curve near
the corner frequency, determine the damping factor (reciprocal of Q). This also affects the
phase response, and the time response to a square-wave input. Several important response
shapes (damping factors) have well-known names:
Chebyshev filter – slight peaking/ripple in the pass band before the corner; Q>0.7071 for
2nd-order filters
Bessel filter – best time-delay, best overshoot response; Q=0.577 for 2nd-order filters
Elliptic filter or Causer filters – add a notch (or "zero") just outside the passband, to give a
much greater slope in this region than the combination of order and damping factor without
the notch.
7
CHAPTER-3
HARMONIC
3.1 HARMONIC
1. Some references refer to “clean” or “pure” power as those without any harmonics.
But such clean waveforms typically only exist in a laboratory. Harmonics have been
around for a long time and will continue to do so. In fact, musicians have been aware
of such since the invention of the first string or woodwind instrument. Harmonics
(called “overtones” in music) are responsible for what makes a trumpet sound like a
trumpet, anda clarinet like a clarinet.
Electrical generators try to produce electric power where the voltage waveform has
only one frequency associated with it, the fundamental frequency. In the North America, this
frequency is 60 Hz, or cycles per second. In European countries and other parts of the world,
this frequency is usually 50 Hz. Aircraft often uses 400 Hz as the fundamental frequency. At
60 Hz, this means that sixty times a second, the voltage waveform increases to a maximum
positive value, then decreases to zero, further decreasing to a maximum negative value, and
then back to zero. The rate at which these changes occur is the trigonometric function called a
sine wave, as shown in figure 1. This function occurs in many natural phenomena, such as the
speed of a pendulum as it swings back and forth, or the way a string on a violin vibrates when
plucked.
8
The frequency of the harmonics is different, depending on the fundamental frequency.
For example, the 2nd harmonic on a 60 Hz system is 2*60 or 120 Hz. At 50Hz, the second
harmonic is 2* 50 or 100Hz.
In order to be able to analyse complex signals that have many different frequencies
present, a number of mathematical methods were developed. One of the more popular is
called the Fourier Transform. However, duplicating the mathematical steps required in a
microprocessor or computer-based instrument is quite difficult. So more compatible
processes, called the FFT for Fast Fourier transform, or DFT for Discrete Fourier Transform,
are used.
These methods only work properly if the signal is composed of only the fundamental
and harmonic frequencies in a certain frequency range (called the Nyquist frequency, which
is one-half of the sampling frequency). The frequency values must not change during the
measurement period. Failure of these rules to be maintained can result in miss-information.
For example, if a voltage waveform is comprised of 60 Hz and 200Hz signals, the FFT
cannot directly see the 200 Hz. It only knows 60, 120, 180, 240which are often called “bins”.
The result would be that the energy of the 200 Hz signal would appear partially in the 180Hz
bin, and partially in the 240 Hz bin. An FFT- based processor could show a voltage value of
115V at 60 Hz, 18 V at the 3rd harmonic, and 12 V at the 4th harmonic, when it really should
have been 30 V at 200 Hz.
9
These in-between frequencies are called “inter harmonics”. There is also a special
category of inter harmonics, which are frequency values less than the fundamental frequency
value, called sub-harmonics. For example, the process of melting metal in an electric arc
furnace can result large currents that are comprised of the fundamental, inter harmonic, and
sub harmonic frequencies being drawn from the electric power grid. These levels can be quite
high during the melt-down phase, and usually effect the voltage waveform.
10
Incorrect reading meters, including induction disc W-hr meters and averaging
type current meters.
Reduced true PF, where PF= Watts/VA.
Overheated transformers, especially delta windings where triple harmonics
generated on the load side of a delta-wye transformer will circulate in the
primary side. Some type of losses goes up as the square of harmonic value (such
as skin effect and eddy current losses). This is also true for solenoid coils and
lighting ballasts.
Zero, negative sequence voltages on motors and generators. In a balanced system,
voltage harmonics can either be positive (fundamental, 4th, 7th,.), negative (2nd,
5th, 8th...) or zero (3rd, 6th, 9th.) sequencing values. This means that the voltage at
that particular frequency tries to rotate the motor forward, backward, or neither
(just heats up the motor), respectively. There is also heating from increased
losses as in a transformer.
11
3.3 Where They Come From?
How this electricity is used by the different type of loads can have an effect on
“purity” of the voltage waveform. Some loads cause the voltage and current waveformsto
lose this pure sine wave appearance and become distorted. This distortion may consist of
Since this article is about harmonics, we will concentrate on those types of sources.
“The main sources of harmonic current are at present the phase angle controlled rectifiersand
inverters.” [3] These are often called static power converters. These devices take AC power
and convert it to another form, sometimes back to AC power at the same or different
frequency, based on the firing scheme. The firing scheme refers to the controlling mechanism
that determines how and when current is conducted. One major variation is the phase angle at
A typical such converter is the switching-type power supplies found in most personal
computers and peripheral equipment, such as printers. While they offer many benefits in size,
weight and cost, the large increase of this type of equipment over the past fifteen years is
Figure shows below how a switching-type power supply works. The AC voltage is
converted into a DC voltage, which is further converted into other voltages that the
equipment needs to run. The rectifier consists of semi-conductor devices (such as diodes) that
only conduct current in one direction. In order to do so, the voltage on the one end must be
greater than the other end. These devices feed current into a capacitor, where the voltage
value on the cap at any time depends on how much energy is being taken out by the rest of
12
When the input voltage value is higher than voltage on the capacitor, the diode will
conduct current through it. This results in a current waveform as shown in Figure 5, and
harmonic spectrum in Figure 6. Obviously, this is not a pure sinusoidal waveform with only a
60 Hz frequency component.
13
If the rectifier had only been a half wave rectifier, the waveform would only have every
other current pulse, and the harmonic spectrum would be different, as shown in Figure.
Fluorescent lights can be the source of harmonics, as the ballasts are non-linear inductors.
The third harmonic is the predominate harmonic in this case. (See Table 3) As previously
mentioned, the third harmonic current from each phase in a four-wire wye or star system will
be additive in the neutral, instead of cancelling out Some of the newer electronic ballasts have
very significant harmonic problems, as they operate somewhat like a switching power supply,
but can result in current harmonic distortion levels over 30%.
Low power, AC voltage regulators for light dimmers and small induction motors
adjust the phase angle or point on the wave where conduction occurs. Medium power
converters are used for motor control in manufacturing and rail road applications, and include
such equipment as ASDs (adjustable speed drives) and VFDs (variable frequency drives).
Metal reduction operations, like electric arc furnaces, and high voltage DC transmission
employ large power converters, in the 2-20MVA rating.
This type of 3-phase equipment may also cause other types of power quality
problems. When the semiconductor device is supposed to turn-off, it does not do so abruptly.
This happens under “naturally” commutated conditions, where the voltage that was larger on
the anode side compared to the cathode is now the opposite. This occurs each cycle as the
voltage waveform goes through the sine waveform. It also happens under “forced”
commutation conditions, where the semi-conductor device has a “gate”-type control
mechanism built in to it. This commutation period is a time when two semiconductor devices
14
are both conducting current at the same time, effectively shorting one phase to the other and
resulting in large current transients.
When transformers are first energized, the current drawn is different from the steady
state condition. This is caused by the inrush of the magnetizing current. The harmonics
during this period varies over time. Some harmonics have zero value for part of the time, and
then increase for a while before returning to zero. An unbalanced transformer (where either
the output current, winding impedance or input voltage on each leg are not equal) will cause
harmonics, as will over voltage saturation of a transformer.
Like any power quality investigation, the search can begin at the equipment effected
by the problem or at the point-of-common-coupling (PCC), where the utility service meets
the building distribution system. If only one piece of equipment is affected (or suspected), it
is often easier to start the monitoring process there. If the source is suspected to be from the
utility service side (such is the case when there is a neighbouring factory that is known to
generate high harmonics), then monitoring usually begins at the PCC.
The phase voltages and currents, as well as the neutral-to-ground voltage and neutral
current should be monitored, where possible. This will aid in pinpointing problems, or
detecting marginal systems. Monitoring the neutral will often show a high 3rd harmonic
value, indicating the presence of non-linear loads in the facility.
If the source is suspected to be from the utility service side (such is the case when
there is a neighbouring factory that is known to generate high harmonics), then monitoring
usually begins at the PCC.This will aid in pinpointing problems, or detecting marginal
systems. Monitoring the neutral will often show a high 3rd harmonic value, indicating the
presence of non-linear loads in the facility.
15
3.4 How do you find them?
Hand-held harmonic meters can be useful tools for making spot checks for known
harmonic problems. However, harmonic values will often change during the day, as different
loads are turned on and off within the facility or in other facilities on the same electric utility
distribution system. This requires the use of a harmonic monitor or power quality monitor
with harmonic capabilities (such as shown in Figure 8), which can record the harmonic
values over a period of time.
Typically, monitoring will last for one business cycle. A business cycle is how long it
takes for the normal operation of the plant to repeat itself. For example, if a plant runs three
identical shifts, seven days a week, then a business cycle would be eight hours. More
typically, a business cycle is one week, as different operations take place on a Monday, when
the plant equipment is restarted after being off over the weekend, then on a Wednesday, or a
Saturday, when only a Skeleton crew may be working.
Certain types of loads also generate typical harmonic spectrum signatures that can
point the investigator towards the source. This is related to the number of pulses, or paths of
conduction. The general equation is h = (n * p) +/- 1, where h is the harmonic number, n is
16
any integer (1,2,3,) and p is the number of pulses in the circuit, and the magnitude decreases
as the ration of 1/h (1/3, 1/5, 1/7, 1/9,). Table 4 shows examples of such.
17
Table 5. Note how the limit decreases at the higher harmonic values, and increases with
larger ratios.
For voltage harmonics, the voltage level of the system is used to determine the
limits, as shown in Table 6. At the higher voltages, more customers will be effective,
hence, the lower limits.
The European Community has also developed susceptibility and emission limits for\
harmonics. Formerly known as the 555-2 standard for appliances of less than 16 A, a more
encompassing set of standards under IEC 1000-4-7 are now in effect.
18
try to balance the system better. Neutral conductors should be properly sized according to the
latest NEC-1996 requirements covering such. Whereas the neutral may have been undersized
in the past, it may now be necessary to run a second neutral wire that is the same size as the
phase conductors. This is particularly important with some modular office partition-type
walls, which can exhibit high impedance values. The operating limits of transformers and
motors should be de-rated, in accordance with industry standards from IEEE, ANSI and
NEMA on such. Use of higher pulse converters, such as 24-pulse rectifiers, can eliminate
lower harmonic values, but at the expense of creating higher harmonic values.
19
CHAPTER-4
NONLINEAR LOADS
4.1 NONLINEAR LOADS
Due to the changes in the operating conditions and the rapid growth of advanced
power conversion devices, electronics equipment, computers, office automation, air-
conditioning systems, adjustable speed heating ventilation can cause current distortions. This
is due to increase in harmonics drastically. According to the Electric Power Research (EPR)
in 1995, 35-40% of all electric power flows through electronic converters. This is expected to
increase to 85% by the year 2012 [11]- [15]. All these devices are named as non-linear loads
and become sources of harmonics. The simple block diagram in Fig.2 illustrates the current
distortion problem due to harmonic at low voltage levels.
Fig.2 shows that the voltage waveform at the Point of Common Coupling (PCC) is distorted due
to harmonic current generated by the power electronic or non-linear load. The measurement results for
the several modems set of non-linear based on Figure 2 is tabulated in Table.1 [11]
20
Table.4.1 The measured results for the modern set of nonlinear loads
In this paper a survey is done for various non-linear loads to know the levels of
harmonics present in each load. These surveys are generally conducted with the objectives
such asIdentify the trends of harmonic distortion level present in the system, Identify the
future trends of metering in the presence of non-sinusoidal current and voltage waveforms.
And increased awareness and concern for customer's quality of service. Here various loads
and its harmonics are studied in detail.
4.1 A. Rectifiers
Rectifiers are the basic load employed in every system. Rectifiers are used to convert
AC to DC current, while converting due to the involvement of thyristors (non-linear load)
produces harmonics. It consumes the current in the circuit and which at last will have dc
output with ac components (i.e. harmonics). This distorted current also leads to distortion in
line voltage. Total harmonic distortion in line current in single phase rectifier is 88.81%. But,
three phase diode rectifiers have total harmonic distortion of 52.84% [16]. Comparison of the
line-current waveforms shows that the line current in a single-phase rectifier contains
significantly more distortions compared to a three-phase rectifier.
A 3 phase, six pulse (per cycle) converter produces the 5th, 7th, 11th, 13th, 17th, etc.,
and contains no harmonic lower than the 5th; for a 12-pulse converter the lowest is the 11th
harmonic [17]. These are represented below in Table4.2.
21
Generally lower order harmonics are significant and most dominant one is 3rd harmonics
in rectifier [18] - [21].
B. Fluorescent lamps
Recent governmental initiatives of a number of countries to ban selling of
incandescent light bulbs have brought some attention on the question of the quality of current
drawn by energy saving lamps. Energy saving lamps requires considerably smaller amounts
of active power than incandescent lamps when they have the same luminous flux. On the
other hand, due to their non-linear characteristics, energy saving lamps injects harmonic
currents into the network. That creates a concern that a very high penetration level of these
types of lamps may increase the overall voltage harmonic distortion considerably
1. In order to compare the different harmonic behaviour of the various ceiling light the
current total harmonic distortion (ITHD) has been also calculated with many
measurements [23]. The results are shown in Table.4.3.
22
In order to inform utilities how current distortion varies among today’s CFLs, EPRI
(Electric Power Research Institute) carried out extensive testing in its lab. Fig.3illustrates the
spread of input total harmonic current distortion for the 51 samples of CFLs that were used in
the project. These CFLs were purchased off-the-shelf from retail establishments where end
users commonly shop for CFLs. From the figure one can see that the ITHD ranges from 20 %
to 170 %. The trend among this sample set is higher ITHD as the majority of the CFLs tested
had ITHD above 100 [24]- [27].
In fact, arc furnaces may be the most prominent harmonic producers because of their
great capacity lumped together at one place. Using a program developed in MATLAB, based
23
on a Fourier analysis of the time-domain waveforms, the Total Harmonic Distortion (THD) is
computed at the PCC and Arc Furnace (Table.4 and Table.5). Results are presented in
percentage of the 50 Hz component.
The content of harmonics which is dominant is 2nd, 3rd, 4th, 5th, 6th and 7th. The
waveform of the electric current is badly distorted containing a large number of higher order
harmonics [30] – [32]
D. Television
Television receivers have power supplies which create current harmonics. Whilst the
harmonic current levels are small in magnitude, the cumulative effect of large numbers of
receivers can be significant. One way to examine the effect of television receivers on network
harmonic levels is to monitor harmonic levels during periods of increased television viewing
[33]
In this a television is served by the small wall outlet. The corresponding current
spectra are given in Table.6. Because of phase cancellation; the current flowing through the
wall outlet has lower THD.
24
The problem of the 3rd-harmonic tuning of the television horizontal-deflection circuit
has been examined experimentally, as well as theoretically. A well-known method is to use
the 2-8th harmonic to obtain good pictures without ringing oscillations and with high fly back
pulses. The resonant-frequency ratio recommended by this method, however, seemed to show
some discrepancies with empirically determined conditions. As this problem isdirectly related
to the quality of television pictures, the optimal conditions to attain good results have been
sought by television manufacturers.
E. Personal computers
Computer loads and systems are being increasingly used in all industrial, commercial
and residential sectors. The nature of these loads is such that they not only draw distorted
current from the source, but can significantly distort the supply voltage waveformcausing
disruption in system performance. The SMPS used in computer loads draw highly distorted
current from the source. Significant amount of odd harmonics including triples are present.
The THD observed in personal computers is shown in Table4.7
25
system design, whether new or an expansion to an existing system, must be analysed to
ensure that it is safe, reliable, meets the present objective, and permits expansion for future
needs. This chapter outlines the system planning considerations and provides guidelines.
References [S1] and [S2] provide guidelines for planning and designing a reliable power
system.
26
Provide operations and maintenance instructions, such as built-in wiring and
interlocking diagrams.
Install emergency lighting for the safety and safe exit of personnel during power
outage.
27
Plant Main Substation
High-voltage power from the utility is stepped down in the plant main substation for
the primary distribution system. The electrical and non-electrical items include:
Non-electrical:
Gantry for terminating incoming and outgoing transmission lines, support structures,
equipment foundation, perimeter fence, control building, grounding, underground oil
containment, etc.
Electrical items:
Power transformers, circuit breakers, disconnect switches, instrument transformers,
reactors, capacitors, power and control cable, protection and control, communications,
lighting, heating, etc.
28
Primary Distribution System
This includes distribution from the plant main substation or generating station to the
primary load centres or switchgear located in different plant facilities. A radial system with
two feeders to each area is used for greater reliability. The following voltage levels can be
considered as a guide:
In-Plant Generation
In-plant generation is used when one of the following conditions is present:
Continuous load is the kVA vector sum of active and reactive power
Motor starting kVA is at a very low power factor.
29
Non-linear loads such as a variable-frequency drive (VFD) are present. Since the generator is
designed for a sinusoidal load with a 5% harmonic distortion, the kVA rating needs to be de-rated
or the design altered for higher distortion factors.
Apply resistance grounding for the generator neutral. (This subject is covered in chapter 4.)
Power Supply for Monitoring and Control Systems
Power supply for monitoring and control systems shall be reliable, unaffected by
voltage dip or sag and transients, and shall meet the requirements of load characteristics
including voltage, frequency, and harmonics. An uninterruptible power supply (UPS) is
required for electronic, analogue, and digital control and monitoring systems. This consists of
a rectifier to convert AC source to DC, battery, inverter, and static transfer switch. Normal
AC power for control is through the inverter, which is filtered, regulated, and isolated from
system disturbances. Typical no redundant and redundant UPS systems are shown in figs. 2.2
and 2.3, respectively.
30
Fig4.6 Redundant UPS
In a non-redundant UPS, one charger and one inverter are used. In a redundant UPS,
two chargers, two inverters, and an alternated AC source from an emergency or standby
diesel generator are used to maintain the power supply under multiple contingencies.
Distribution Types
Distribution systems commonly used in industrial plants are briefly described here.
Simple Radial
The simple radial system (fig. 2.4) has no redundancy and can be used where loss of
power for an extended period is not detrimental to the process.
31
Expanded Radial
The expanded radial scheme (fig. 2.5) is an expansion of the above and has been used
in many industries. The industrial power system at medium voltage (2.4 to 34.5 kV) is low-
resistance (100–400 A) grounded, and power cable (insulated) is used for distribution.
The majority of the faults with cable systems starts as a line-to ground fault and
escalate to a three-phase fault if not cleared within a reasonable time. On a line-to-ground
fault, the fuse will either not see the fault current or will take a long time to melt. However,
32
the ground-fault relay at the switchgear set at about 5% will trip the feeder breaker. The
power is lost in a large area, and a longer time is required to detect and isolate the fault.
Primary Selective
In the primary selective arrangement (fig. 2.6), two primary feeders are brought to
each substation transformer. Half of the transformers are connected to each of the two
feeders. Each primary feeder is designed to carry the entire load. Though the problem caused
by the line-to-ground faults is the same as with the expanded radial system, the power to the
load centres can be restored quickly by transferring to the alternate feeder. Though the
problem caused by the line-to-ground faults is the same as with the expanded radial system,
the power to the load centres can be restored quickly by transferring to the alternate feeder.
Secondary Selective
The secondary selective arrangement (fig. 2.7) can be achieved between two single
transformer stations or double-ended stations by using a tie-circuit breaker. For low-voltage
systems, the tie breaker is normally kept in open position, and an interlock between the main
and the tie prevents paralleling of the transformers. An electrically operated manual transfer
scheme can be used to close the tie breaker for a few cycles before tripping the selected main
breaker. This scheme permits a planned shutdown of one transformer or primary feeder
without dropping any load.
However, the fault level may exceed the equipment rating during this brief period.
Because both low-voltage buses are in an energized state, the possibility of developing a fault
during this period is remote. For medium-voltage systems, the tie breaker may operate in
normally open or normally closed position. However, the relaying becomes more complex
with parallel operation. The preferred and a commonly used arrangement is to operate the
system with the tie breaker open and provide an auto- or manual-transfer scheme. The
application of an auto-transfer scheme is common in thermal power plants.
Sparing Transformer
The sparing transformer scheme (fig. 2.8) is used where several low-voltage
transformer stations of the same capacity are installed in one area. The load is transferred to
the spare transformer upon the loss of any unit in the system. This minimizes the spare
transformer capacity
33
Fig4.8 Secondary selective
4.4. Plant Power Demand and Load Estimateof Power Demand and Energy
Cost
Estimates of power consumption, power demand, and total power cost are carried out
during the project feasibility stage and during the contract negotiations with the power utility.
The results of the power cost study, the power consumption of utilization equipment, and the
approximate location of equipment is required for system planning and sizing the electrical
equipment. The plant power demand, power cost, electrical load estimate in different areas,
and selection of major electrical equipment can be made using the following approach.
34
Energy consumption based on the plant output and operating hours
Power demand for each facility and net demand for the plant
Monthly and yearly power cost consisting of energy cost and demand charge:
An example illustrating the method for estimating the power requirement and power
demand for an alloy steel plant producing 60,000 tons/year of finished product is given in
tables 2.1 and 2.2, respectively. A plant producing Fe Cr (ferro chromium) operates 24 hours
per day and 365 days per year, whereas the operating period for other plant facilities depends
on the production requirement. These tables provide the plant operating period for each
facility, including the number of shifts per day and number of days per week. Load factors
and coincidence factors are based on past experience with similar plants. Table 2.1 has been
used to estimate the energy consumption and maximum power demand for each facility and
total plant. Table 2.2 shows the plant facilities arranged in groups based on their operating
period and shifts, which helps in organizing the plant operations and estimating plant
manpower requirements. Tariff as agreed with the power utility:
Estimate of power cost: Power demand (based on a 30-min period) as derived from
table 2.1 = 39,200 MW Energy consumption per year = 166.3 × 106 kWh Energy
consumption per month = 13,860 × 103 kWh (based on an average 730 h) Energy cost per
month = $0.04 × 13,860 × 103 = $554,400 Demand charge per month = $6.0 × 39,200 =
$235,200 Total power cost per month = $789, 600
35
Typical Demand Factors for Utilization Equipment Typical demand factors for
utilization equipment are given in table 2.3. Total Power Demand = ∑ (Equipment Rating
× Demand Factor) added space between equipment and rating.
36
4.5Voltage Considerations
The most common (preferred) system and utilization voltages used in the United
States and Canada for industrial power systems are given in table 2.4. The power supply
frequency is 60 Hz. Reference [S1] provides the voltages and their ranges. For utilization
equipment, the voltage variation is defined in the relevant standards.
The steady-state voltage drop is caused by the variation in utility power supply and by
voltage drop in the transformer and feeders connected to the utilization equipment. The
spread from the utility power supply is generally remedied by utilizing main step-down
transformers with load tap changers. The electrical safety codes, NEC and CSA, have
specified the allowable voltage drop at the maximum load current; these are 5% for feeders
and 3% for branch circuits. The steady-state voltage drop can be calculated or estimated
using one of the following methods
Formula
Where
37
X = sum of the reactance component in the circuit, ohms A commonly used formula for
percent voltage drop is
Ampere-foot Method
This method can be used in computing the voltage drop in low-voltage feeders and branch
circuits that have not been included in load-flow runs. In this method, the load current is
multiplied by the one-way cable length to get the value in ampere-feet. The voltage drop can
be read from the graphs in ref. [1] or estimated from the tables in ref. [11] against the cable
size. The conductor size can be increased or the load can be fed from a different bus to reduce
the voltage drop. Table 2.7, extracted from ref. [11], can be used for estimating voltage drop
in a three-phase system with the load current at 0.8 power factor
Load Flow
This is a system planning and study activity, and it is covered in chapter 3. The output
files provide bus voltage summary for light or no load, full load, and contingency operations.
The output files also highlight the bus voltage when it is in violation of the specified range.
The transformer voltage spread or voltage drop from no load to full load is reduced by
adjusting the transformer taps.
Voltage Flicker
The voltage changes of a transient nature, such as turning loads on and off, which last
only a short duration, are generally referred to as voltage flicker. The rapid voltage
fluctuations affect the light output from incandescent lamps, which can irritate the human
eye. Flicker-limit curves adopted by IEEE and used by many power utilities in North
America are shown in fig. 2.9 [S1]. These curves are the composite of the flicker on
incandescent lamps studied by General Electric Co., Kansas City Power and Light Company,
T&D Committee, Detroit Edison Company, and West Pennsylvania Power Company
Flicker is divided into four groups based on their frequency of occurrence:
Cyclic flicker:
38
Is that resulting from periodic voltage fluctuations, the range of frequency of fluctuation
is 10 per second to 2 per second. Reciprocating compressors and pumps, arc furnaces, and
automatic spot welders fall into this category
Fig. Range of observable and objectionable voltage flicker vs. time (From IEEE 1993,
IEEE Recommended Practice for Electric Power Distribution for Industrial Plants
(IEEE
Red book), chap. 2. With permission.)
Cyclic low frequency: The frequency of fluctuation ranges from 2 per second to 12
per minute. Arc welders, drop hammers, saws, and manual spot welders fall into this
category.
Non-cyclic frequent: The frequency of fluctuation ranges from 12 per minute to 1 per
minute. Hoists, cranes, single elevators fall into this category.
Non-cyclic infrequent: The frequency of fluctuation ranges from 1 per minute to 3 per
hour. Motor starting falls into this category
The utilization of equipment that may cause voltage flicker in industrial power plants is
summarized here:
Starting of large motors: Starting of large synchronous or induction motors draws four
to seven times their rated current at a very low factor (0.10 to 0.3). The highly
inductive current causes a voltage dip that may exceed the flicker limit. This can be
remedied by utilizing an assisted starting method.
39
Arc furnace: An electric arc furnace is a problem load for the network, especially
during the period when the scrap metal is converted into molten steel for refining. The
meltdown period lasts about 70 to 90 minutes, followed by the refining period. The
refining period lasts between 0.5 and 2.0 hours, depending on the quality of the
finished steel. The characteristics of the meltdown period are:
For an optimum arc, the active power must be at 0.707 power factor. The circuit
constants for maximum arc power are: Optimum current I0 = 1.45 × I, where I is the rated
rms current Short-circuit current, ISC = 1.58 × I0 = 2.3 × I Power factor for maximum arc =
0.707 Power factor during short circuits = 0.25
Frequently recurring short circuits occur at the electrodes; two phases are generally
short-circuited, and one phase is with no current. The frequent short circuits during the
meltdown period cause voltage fluctuations in the power system at a frequency of about four
to seven times per second. The rapid change in current during meltdown period causes
voltage flicker. The furnace is connected to a dedicated bus, and a static VAR compensator is
utilized to eliminate the flicker (fig. 2.10). The voltage flicker for an arc furnace is defined as
a short-circuit voltage depression (SCDV) and can be estimated using the formula:
where MWF = the furnace rating in MW MVASC = the three-phase fault level at the point of
common coupling. The recommended short-circuit voltage depression is SCDV < 1.9% for
systems where lamps are at 230 V SCDV < 2.5% for systems where lamps are at 120 V
40
Fig4.10. Power system for an arc furnace
Electric shovels:
Mining operations using electric shovels cause problems for the power distribution
system. A typical duty cycle lasts about 25 to 30 s. This includes digging, hoisting, swinging
back to the truck, dumping in the truck, and swinging back to the pit. The power drawn from
the system is about 200% of the equipment rating during digging and hoisting periods, and
there is some regeneration during lowering and stopping. Power system design and
equipment rating must take the duty cycle into consideration, and voltage flicker must be
checked to ensure that the limits are not exceeded.
Other loads:
These include electric welders, electric shovels and strippers, heavy rolling, etc. The
system must be studied to check whether the voltage fluctuations exceed the flick limit, and if
they do, corrective measures must be taken accordingly.
Voltage Sag and Threshold Voltage
A voltage sag is defined as a decrease in rms voltage of 0.1 to 0.9 P.U. at the power
frequency for a duration of 0.5 cycles (8.3 ms) to 1.0 min. The threshold voltage is the critical
voltage at which the equipment stops working; for example, a starter coil may drop out at 0.6
per-unit (P.U.) voltage, and a variable-frequency drive may trip at 0.8 to 0.85 P.U. voltage.
Disturbances such as faults on utility transmission or distribution systems cause momentary
voltage dips or voltage sags. The utilization equipment in the plant may trip or stop
functioning if the voltage sag is below the equipment threshold voltage. Sag response curves
have been published in ref. [S15]. The following measures
can help to survive such voltage dips or provide ride through≅ capability:
41
Higher pull-out torque for synchronous motors and field-forcing capability
Lower threshold voltage for control system, drives, monitoring, etc.
Uninterruptible power supply (UPS) for critical control and monitoring
42
CHAPTER-5
RESONANCE
5.1 Resonance
43
Examples
One familiar example is a playground swing, which acts as a pendulum. Pushing a
person in a swing in time with the natural interval of the swing (its resonant frequency) will
make the swing go higher and higher (maximum amplitude), while attempts to push the
swing at a faster or slower tempo will result in smaller arcs. This is because the energy the
swing absorbs is maximized when the pushes are "in phase"with the swings natural
oscillations, while some of the swings energy is actually extracted by the opposing force of
the pushes when they are not.
Resonance occurs widely in nature, and is exploited in many man made devices. It is
the mechanism by which virtually all sinusoidal waves and vibrations are generated. Many
sounds we hear, such as when hard objects of metal, glass, or wood are struck, are caused by
brief resonant vibrations in the object. Light and other short wavelength electromagnetic
radiation is produced by resonance on an atomic scale, such as electrons in atoms. Other
examples are:
Timekeeping mechanisms of modern clocks and watches, e.g., the balance wheel in a
mechanical watch and the quartz crystal in a quartz watch
44
Shattering of a crystal wineglass when exposed to a musical tone of the right pitch (its
resonant frequency)
Electrical resonance of tuned circuits in radios and TVs that allow radio frequencies
to be selectively received
reed receiver
frequency meters
Orbital resonance as exemplified by some moons of the solar system's gas giants
Material resonances in atomic scale are the basis of several spectroscopic techniques
that are used in condensed matter physics
Electrical resonance
Electrical resonance occurs in an electric circuit at a particular resonant frequency
when the impedance of the circuit is at a minimum in a series circuit or at maximum in a
parallel circuit (or when the transfer function is at a maximum).
Optical resonance
An optical cavity, also called an optical resonator, is an arrangement of mirrors that
forms a standing wave cavity resonator for light waves. Optical cavities are a major
component of lasers, surrounding the gain medium and providing feedback of the laser light.
They are also used in optical parametric oscillators and some interferometers. Light confined
in the cavity reflects multiple times producing standing waves for certain resonant
frequencies. The standing wave patterns produced are called "modes". Longitudinal modes
differ only in frequency while transverse modes differ for different frequencies and have
different intensity patterns across the cross-section of the beam. Ring resonators and
whispering galleries are examples of optical resonators that do not form standing waves.
Different resonator types are distinguished by the focal lengths of the two mirrors and
the distance between them; flat mirrors are not often used because of the difficulty of aligning
them precisely. The geometry (resonator type) must be chosen so the beam remains stable,
i.e., the beam size does not continue to grow with each reflection.
45
Resonator types are also designed to meet other criteria such as minimum beam waist
or having no focal point (and therefore intense light at that point) inside the cavity. Optical
[13]
cavities are designed to have a very large Q factor; a beam will reflect a very large number
of times with little attenuation. Therefore the frequency line width of the beam is very small
compared to the frequency of the laser. Additional optical resonances are guided-mode
resonances and surface Plasmon resonance, which result in anomalous reflection and high
evanescent fields at resonance. In this case, the resonant modes are guided modes of a
waveguide or surface Plasmon modes of a dielectric-metallic interface. These modes are
usually excited by a sub wavelength grating.
Orbital resonance
In celestial mechanics, an orbital resonanceoccurs when two orbitingbodies exert a
regular, periodic gravitational influence on each other, usually due to their orbitalperiods
being related by a ratio of two small integers. Orbital resonances greatly enhance the mutual
gravitational influence of the bodies. In most cases, this results in an unstable interaction, in
which the bodies exchange momentum and shift orbits until theresonance no longer exists.
Under some circumstances, a resonant system can be stable and self-correcting, so that the
bodies remain in resonance. Examples are the 1:2:4 resonance of Jupiter's moons Ganymede,
Europa, and Io, and the 2:3 resonance between Plutoand Neptune. Unstable resonances with
Saturn's inner moons give rise to gaps in the rings of Saturn. The special case of 1:1
resonance (between bodies with similar orbital radii) causes large Solar System bodies to
clear the neighborhoodaround their orbits by ejecting nearly everything else around them; this
effect is used in the current definition of a planet.
All nuclei containing odd numbers of nucleons have an intrinsic magneticmoment and
angular momentum. A key feature of NMR is that the resonant frequency of a particular
substance is directly proportional to the strength of the applied magnetic field. It is this
feature that is exploited in imaging techniques; if a sample is placed in a non-uniform
46
magnetic field then the resonant frequencies of the sample's nuclei depend on where in the
field they are located. Therefore, the particle can be located quite precisely by its resonant
frequency. Electron paramagnetic resonance, otherwise known as Electron Spin Resonance
(ESR) is a spectroscopic technique similar to NMR, but uses unpaired electrons instead.
Materials for which this can be applied are much more limited since the material needs to
both have an unpaired spin and be paramagnetic.
The Mossbauer effect is the resonant and recoil-free emission and absorption of
gammaray photons by atoms bound in a solid form. Resonance in particle physics appears in
similar circumstances to classical physics at the level of mechanics and quantum fieldtheory.
However, they can also be thought of as unstable particles, with the formula above valid if
the is the decay rate and replaced by the particle's mass M. In that case, the formula
comes from the particle's propagator, with its mass replaced by the complex
number . The formula is further related to the particle's decayrate by the optical theorem.
LC circuits
Resonance of a circuit involving capacitors and inductors occurs because the
collapsing magnetic field of the inductor generates an electric current in its windings that
charges the capacitor, and then the discharging capacitor provides an electric current that
builds the magnetic field in the inductor. This process is repeated continually. An analogy is a
mechanical pendulum.
At resonance, the series impedance of the two elements is at a minimum and the
parallel impedance is at maximum. Resonance is used for tuning and filtering, because it
occurs at a particular frequency for given values of inductance and capacitance. It can be
detrimental to the operation of communications circuits by causing unwanted sustained and
transient oscillations that may cause noise, signal distortion, and damage to circuit elements.
Parallel resonance or near-to-resonance circuits can be used to prevent the waste of electrical
energy, which would otherwise occur while the inductor built its field or the capacitor
charged and discharged. As an example, asynchronous motors waste inductive current while
synchronous ones waste capacitive current. The use of the two types in parallel makes the
inductor feed the capacitor, and vice versa, maintaining the same resonant current in the
circuit, and converting all the current into useful work.
Since the inductive reactance and the capacitive reactance are of equal magnitude,
ωL = 1/ωC, so:
47
where ω = 2πf, in whichfis the resonance frequency in hertz, L is the inductance in henries,
and C is the capacitance in farads when standard SI units are used.
The quality of the resonance (how long it will ring when excited) is determined by its
Qfactor,which is a function of resistance. A true LC circuit would have infinite Q, but all real
circuits have some resistance and smaller Q and are usually approximated more accurately by
an RLC circuit.
RLC circuit
An RLCcircuit (or LCR circuit) is an electricalcircuit consisting of a resistor, an
inductor, and a capacitor, connected in series or in parallel. The RLC part of the name is due
to those letters being the usual electrical symbols for resistance, inductance and capacitance
respectively. The circuit forms a harmonic for current and resonates similarly to an LC
circuit. The main difference stemming from the presence of the resistor is that any oscillation
induced in the circuit decays over time if it is not kept going by a source. This effect of the
resistor is called damping. The presence of the resistance also reduces the peak resonant
frequency. Some resistance is unavoidable in real circuits, even if a resistor is not specifically
included as a component. A pure LC circuit is an ideal that exists only in theory.
There are many applications for this circuit. It is used in many different types of
oscillatorcircuits. An important application is for tuning, such as in radio receivers
ortelevisionsets, where they are used to select a narrow range of frequencies from the ambient
radio waves. In this role the circuit is often referred to as a tuned circuit. An RLC circuit can
be used as a band-pass filter, band-stop filter, low-pass filter or high-pass filter. The tuning
application, for instance, is an example of band-pass filtering. The RLC filter is described as
a second-order circuit, meaning that any voltage or current in the circuit can be described by
a second-order differential equation in circuit analysis.
The three circuit elements can be combined in a number of different topologies. All
three elements in series or all three elements in parallel are the simplest in concept and the
most straightforward to analyse. There are, however, other arrangements, some with practical
importance in real circuits. One issue often encountered is the need to take into account
48
inductor resistance. Inductors are typically constructed from coils of wire, the resistance of
which is not usually desirable, but it often has a significant effect on the circuit.
BLOCK DIAGRAM:
Fig. 5.2. Proposed HAFU in the industrial power system and its associated control.
(a)Circuit diagram of the HAFU.
(b) Control block diagram of the HAFU
A. Harmonic Loop
B. Fundamental Loop
In this paper, the q-axis is aligned to a-phase voltage. Since the passive filter is
capacitive at the fundamental frequency, the passive filter draws fundamental leading
current from the grid, which is located on the d-axis. The proposed inverter produces slight
fundamental voltage on the d-axis, which is in phase with the fundamental leading current.
Therefore, the control of dc bus voltage is able to be accomplished byshows the harmonic
voltage drop on the passive filter due to the compensating current of the HAFU [20], where
Ih represents the maximum harmonic current of the active filter, and the voltage drop on
filter resistance Rf is neglected. As can be seen, a large filter capacitor results in the
reduction of the required dc voltage. On the other hand, the filtercapacitor determines
reactive power compensation of the passive filter at the fundamental frequency. Thus, the
dc voltage v d c can be determined based on this compromise. Note that the compensating
current should be limited to ensure that the hybrid filter operates without undergoing
saturation,
50
C. Current Regulator
The current command i is consisted of i h and i f. Based on the current command
i and the measured current i, the voltage command v can be derived by using a proportional
controller as follows:
v = K.i − i
(3)
where Kc is a proportional gain. According to the voltage command v , space-vector
pulse width modulation (PWM) is employed to synthesize the required output voltage ofthe
inverter. Fig. shows the model of the current control. The computational delay of digital
signal processing is equal to one sampling delay T, and PWM delay approximates to half
sampling delay T/2. Hence, the proportional gain Kc can be simply evaluated fromboth
open-loop and closed-loop gains for suitable stability margin and current tracking
capability.
Note that PI parameters need to be tuned for required response and stability. For example,
the proportional gain can be tuned for transient behaviour, and the integral gain is responsible
for suppressing the steady-state error. The band width should be lower than one-tenth of the
cut-off frequency of the current loop to assure stable allowable level
51
CHAPTER-6
SIMULATION RESULTS
Figs. show the grid voltagee, the source currentis, the filter currenti, and the load
currentiLfor NL1=1.8 kW and NL2 = 2.8 kW, respectively. When the HAFU is in the OFF
state, the HAFU becomes a passive filter. Since the resonant frequency between the passive
filter Lf−Cf and line inductance Ls is close to the fifth harmonic frequency, fifth harmonic
distortion one, is, if are significantly amplified as shown in Figs. 9(a) and 10(a). As can be
seen, the passive filter loses its filtering functionality and even causes excessive harmonic
current in is or harmonic voltage one. It is worth noting that the resonant frequency could be
shifted toward the lower frequency due to the existence of the leakage inductance of the
transformer.
After the start of the HAFU, the harmonic distortion is clearly improved as shown in
Figs. 9(b) and 10(b). The THD of e is reduced to 2.0% with G* = 0.97 p.u. for NL1 and G* =
3.05 p.u. for NL2, respectively. The THD of isis also improved below 5% in both cases.
Tables IV and V summarize THD data of e, is, and i, iL measured by a PQ analyser (HIOKI
52
3196). High-order harmonics (>13) are not included here due to insignificance. Seventh
harmonic voltage distortion is increased after the HAFU is started. This is because the HAFU
emulates conductance for all harmonic frequencies. This feature can be used to avoid the
overloading of the passive filter at the tuned (seventh) frequency. We also observe that fifth
harmonic component of load current iL is slightly increased. This may result from
improvement of the fifth voltage distortion one.
The detailed results indicate that the proposed HAFU is able to suppress harmonic
resonances and to reduce harmonic distortion. More importantly, the HAFU only consumes
470 VA, which is approximately 4.7% of the system rating or 16.7% of NL2. Obviously, the
required kVA rating of the filter is significantly reduced, in comparison with the use of a pure
shunt active power filter.
Fig9a: Line voltage e, source current is, load current iL, and filter current i in the case of NL1
initiated. X-axis: 5 ms/div. (a) HAFU is off. (b) HAFU is on.
After the start of the HAFU, the harmonic distortion is clearly improved as shown in
Figs. 9(b) and 10(b). The THD of e is reduced to 2.0% with G* = 0.97 p.u. for NL1 and G* =
3.05 p.u. for NL2, respectively. The THD of isis also improved below 5% in both cases.
Tables IV and V summarize THD data of e, is, and i, iL measured by a PQ analyser (HIOKI
3196). High-order harmonics (>13) are not included here due to insignificance. Seventh
harmonic voltage distortion is increased after the HAFU is started. This is because the HAFU
emulates conductance for all harmonic frequencies. This feature can be used to avoid the
overloading of the passive filter at the tuned (seventh) frequency. We also observe that fifth
53
harmonic component of load current iL is slightly increased. This may result from
improvement of the fifth voltage distortion one.
The detailed results indicate that the proposed HAFU is able to suppress harmonic
resonances and to reduce harmonic distortion. More importantly, the HAFU only consumes
470 VA, which is approximately 4.7% of the system rating or 16.7% of NL2. Obviously, the
required kVA rating of the filter is significantly reduced, in comparison with the use of a pure
shunt active power filter.
Fig9b: Line voltage e, source current is, load current iL, and filter current i in the case of NL1
initiated. X-axis: 5 ms/div. (a) HAFU is off. (b) HAFU is on.
54
Fig10: Line voltage e, source current is, load current iL, and filter current i in the
case of NL2 initiated. X-axis: 5 ms/div.
a. HAFU is off.
b. HAFU is on.
Fig10: Line voltage e, source current is, load current iL, and filter
current i in the case of NL2 initiated. X-axis: 5 ms/div.
a. HAFU is off.
b. HAFU is on.
Fig. shows the transient waveforms ofG*, THD ofe, andvdcas the non-linear load is
changed by a stepped increase from NL1 to NL2 at T. Large non-linear current will result in
large voltage distortion one. Due to the proposed tuning control, the conductance command
G* is increased to 3.05 p.u. to draw more harmonic current shown in Fig. 11(b) in order to
maintain voltage THD at 2%. Fig. 11(a) also demonstrates vdc is well controlled to 50 V to
ensure proper operation of the active filter. Additionally, time-domain simulations have been
carried out to compare filtering performances between current
55
Transient response when the non-linear load is increased at T.
(a)Waveforms of vdc, Voltage THD, G . X-axis: 100 ms/div; Y -axis: vdc(V),
G (1.21p.u./div), and THD (1.25%/div). (b) Current waveforms
Single-Phase Load:
Fig. Test results are summarized in Table VI. Voltage distortion of e is reduced from
4.6% to 3.0% with conductance command G* = 0.5 p.u. Since the passive filter is tuned at the
seventh-order harmonic frequency, the proposed hybrid filter is not able to suppress third-
order harmonic distortion effectively for single-phase non-linear load. In this case, the
passive filter might be tuned at fifth-order harmonic frequency to improve filtering
performance for third-order harmonic.
56
fig:HAFU is on for single-phase non-linear load.
(a) Terminalvoltage. (b) Source current. (c) Filter current. (d) Load current
57
VII. CONCLUSION
This paper presents hybrid active filter to uppers harmonic resonances in industrial
power systems. The proposed hybrid filter is composed of a seventh harmonic-tuned passive
filter and an active filter in series connection at the secondary side of the distribution
transformer. With the active filter part operating as variable harmonic conductance, the
filtering performances of the passive filter can be significantly improved. Accordingly, the
harmonic resonances can be avoided, and the harmonic distortion can be maintained inside an
acceptable level in case of load changes and variations of line impedance of the power
system. Experimental results verify the effectiveness of the proposed method. Extended
discussions are s summarized as follows.
Large line inductance and large non-linear load may result in severe voltage distortion.
The conductance is increased to maintain distortion to an acceptable level.
Line resistance may help r educe voltage distortion. The conductance is decreased
High-frequency resonances resulting from capacitive filters is possible to be suppressed
by the proposed method.
I n case of unbalanced voltage, a band-rejected filter is needed to filter out second-order
harmonics if the SRF is realized to extract voltage harmonics.
58
REFERENCES
non-linear loads-three case histories,”IEEE Trans. Ind. A p p ., vol. 41, no. 1, pp.
59
systems with power factor correction equipment,”IEEE Trans. Power Electron.,
vol. 16, no. 6, pp. 821–827, Nov. 2001.
13. V. Varma and B. Singh, “Design and implementation of a current controlled
parallel hybrid power filter,”IEEE Trans. Ind. Appl., vol. 45, no. 5, pp. 1910–1917,
Sep./Oct.2009.
14. H. Akagi, S. Srianthumrong, and Y. Tamai, “Comparison in circuit configuration
and filtering performance between hybrid and pure shunt active filters,” in Conf.
Rec.38th IEEE IAS Anna. Meeting, 2003, pp. 1195–1202.
15. C.-S. Lam, W.-H. Choi, M.-C. Wong, and Y.-D. Han, “Adaptive DC-link voltage-
controlled hybrid active power filters for reactive power compensation,”IEEE
Trans.Power Electron., vol. 27, no. 4, pp. 1758–1772, Apr. 2012.
60