Professional Documents
Culture Documents
07a - Instrument - Transformers - Tech - r8 401
07a - Instrument - Transformers - Tech - r8 401
Instrument Transformers
CTs and VTs
Instrument Transformers_r8 1
Power System Protection for Engineers – PROT 401
Instrument Transformers
Objectives
Instrument Transformers_r8 2
Power System Protection for Engineers – PROT 401
Current Transformers
Instrument Transformers_r8 3
Power System Protection for Engineers – PROT 401
Secondary
Winding with Ns
Turns
z CT Isolates Relay
from the HV System
Is z Drastically Reduces
h g Current
Ideally: Is = Ip / Ns
Relay
The initial problem was how to connect a low-voltage device to the high-voltage system and
have the ability to handle large fault currents (kilo-Amps). How can we make the relay
measure the currents flowing in the high-voltage system in order to detect these faults?
The solution consists of using a special type of transformer, called a current transformer.
The main parts of a current transformer are:
• Iron core
• Secondary winding
• Primary conductor
• External insulation
Some current transformers do not have a primary conductor. In those cases the primary is the
line or bus itself. Sometimes the core and its secondary winding are directly installed in the
bushing of the circuit breakers or transformers. These CTs are called “bushing CTs”.
Some current transformers may have a primary that consists of several turns. Typically there
are no more turns than the natural, which is equivalent to say that the primary number of
turns is 1.
The total load connected to the CT terminal (g and h in this case) is called “burden”.
Ideally, the secondary current of a CT is perfectly proportional to the primary current. It will
be shown later that in reality this is sometimes not true.
Instrument Transformers_r8 4
Power System Protection for Engineers – PROT 401
Instrument Transformers_r8 5
Power System Protection for Engineers – PROT 401
High-Voltage CT Example
Instrument Transformers_r8 6
Power System Protection for Engineers – PROT 401
Instrument Transformers_r8 7
Power System Protection for Engineers – PROT 401
CT Symbols
IP IP P1 P2
S1 S2
IS IS
ANSI IEC
IP
P1 P2 IP
K L
S1 S2
k l
IS IS
Some Countries VDE
These are the most common symbols used to represent current transformers. There are
some deviations, but the main shape of the symbols is essentially similar to what is
shown here.
Note that in all cases there are polarity marks. The following conventions are used to
mark the reference for AC currents:
• VDE: K, L, k, l
The ANSI polarity mark consists of a dot, a small circle, an “x”, or a small square (as
shown in the slide) drawn at each side of the transformer primary and secondary sides.
The convention establishes that current flowing IN the polarity mark of one winding
flows OUT the polarity mark of the other.
Instrument Transformers_r8 8
Power System Protection for Engineers – PROT 401
CT Common Connections
Ia Wye Ia Delta
Ib Ib
Ic Ic
Ics
Ibs
Ias-Ics
Ias Ires
Ics-Ibs
Ibs-Ias
These are the two of the most common connections of current transformers in three-
phase systems.
At the left, the “Y” connection provides the line currents at the secondary.
At the right, the “∆” connection, provides the difference currents (delta currents) to the
secondary loads.
Instrument Transformers_r8 9
Power System Protection for Engineers – PROT 401
The Current Transformer Ratio, CTR, expressed as a fraction, is the ratio between the
magnitudes of the primary and the secondary current for ideal working conditions of
the current transformer.
Instrument Transformers_r8 10
Power System Protection for Engineers – PROT 401
Volt-
Burden Impedance Amperes Power
Designation (Ohms) (at 5 A) Factor
B-1 1.0 25 0.5
B-2 2.0 50 0.5
B-4 4.0 100 0.5
B-8 8.0 200 0.5
The ANSI standard burdens are specified as impedances in Ohms with an angle of 60
degrees, i.e.:
The ANSI standard states that a CT of a given class will have 10%, or less, error when
operated at 20 times nominal current into the standard burden.
As an example, a C400 rated CT will exhibit 10%, or less, error with 100 amps
secondary current flowing into a 4 ohm burden. The CT must therefore be capable of
supporting a secondary voltage of at least 400 volts.
Instrument Transformers_r8 11
Power System Protection for Engineers – PROT 401
ZRELAY
Instrument Transformers_r8 12
Power System Protection for Engineers – PROT 401
Non-Linear Behavior
Without Hysteresis
φ φ
iE iE
If a certain ac voltage is applied to the secondary of a CT, the core is magnetized and
the flux density B has a non-linear relationship with the magnetic field intensity H,
according to the well-known law of magnetic material: Hysteresis Loop. The magnetic
field H is approximately proportional to the excitation current, and the magnetic flux is
proportional to the magnetic flux density. These relationships depend not only on the
material properties but also on the core dimensions (Cross Section A and Effective
Length L).
The slide shows the flux vs. exciting current curve which is similar to, and closely
related to, the B vs. H curve. The hysteresis is sometimes neglected, as shown in the
right half of the slide. The approximation is valid for some materials. In general, the
approximation serves to simplify the analysis.
Instrument Transformers_r8 13
Power System Protection for Engineers – PROT 401
Instrument Transformers_r8 14
Power System Protection for Engineers – PROT 401
IP
IS = − IE ; VS = IS (Rs + jXs ) + IS ZLOAD
NS
The general equivalent circuit is adapted to the current transformer as indicated in the
figure. Note the non-linear reactance used to represent the non-linear behavior of the
iron core. Note also that this reactance comes from the relationship between the induced
voltage VS and the excitation current iE.
As the flux limits of the CT are reached, the exciting current increases. As the exciting
current increases, the secondary current output is decreased, resulting in increased error.
As will be seen later, the secondary output current can be reduced to zero during
extreme saturation.
Instrument Transformers_r8 15
Power System Protection for Engineers – PROT 401
Log-Log plot
Vs
Saturation
Voltage Vsat
dφ
vs ≈ −Ns
dt
IE
This is the excitation curve in the form normally used in practice. The curve presents
the magnitude of the internal induced voltage VS as a function of the excitation current
IE.
Instrument Transformers_r8 16
Power System Protection for Engineers – PROT 401
45o
Vs
(Exciting
Voltage)
Log-Log Plot with
Square Decades
ANSI
Knee
Point
IE
The ANSI knee point voltage is defined geometrically in the excitation curve. When
plotted on equally spaced log-log axes, it is the point in the excitation curve where the
tangent is at 45° to the abscissa, for CTs with a non-gapped core. The knee point
voltage does not define the onset of saturation for the ANSI standard.
Instrument Transformers_r8 17
Power System Protection for Engineers – PROT 401
Vs
(Exciting
Voltage)
Log-Log Plot with
Square Decades
IEC
Knee Point
IE
The IEC knee point voltage is defined as the point of intersection of two lines in the
log-log plot. One line corresponds to the linear part of the CT curve, and the other
corresponds to the saturation voltage. The IEC knee point voltage is very close to the
onset of saturation, and is taken as equal to the onset of saturation.
The IEC knee point voltage correlates closely to the ANSI C Rating Voltage which will
be discussed in later slides.
Instrument Transformers_r8 18
Power System Protection for Engineers – PROT 401
z IEC
10% change in excitation voltage
causes 50% change in excitation
current
Near ANSI C rating
Instrument Transformers_r8 19
Power System Protection for Engineers – PROT 401
For a multiratio current transformer, manufacturers provide all the curves in the same
plot.
In the example shown, for the 2000/5 ratio, the ANSI knee point is approximately 200
Volts, and the full saturation voltage is close to 500 Volts.
Instrument Transformers_r8 20
Power System Protection for Engineers – PROT 401
CT Response to Sinusoidal Ip
φ
φ
iE t
vs
dφ
v s ≈ − Ns
dt
t
iE
When the CT works in the non-saturated area, the sinusoidal primary current produces
an approximately sinusoidal flux, induced voltage, and excitation current. This
excitation current is very small and the secondary current is very similar to the ideal
ratio current. Therefore, the error is very small.
Instrument Transformers_r8 21
Power System Protection for Engineers – PROT 401
t
iE
dφ
vs vs ≈ −Ns
dt
t
iE
If the load and the magnitude of the primary current are large enough to saturate the
CT, neither the flux nor the induced voltage are sinusoidal. The excitation current can
take large magnitudes and the resulting error will be large. The secondary current is
shown in the next slide.
As indicated in the figure, when the transformer is saturated, the flux wave shape
illustrates that the rate of change is almost zero. However, in the “linear”region the flux
can exhibit a very high rate of change, and therefore a very high induced voltage. This
produces the voltage peaks shown in the figure.
It is important to note that in the extreme saturation condition (infinite load impedance),
the peaks that appear in the induced voltage could be extremely large, even for
relatively low primary currents. These peaks represent dangerous overvoltages which
can damage the insulation of the secondary winding. This demonstrates why CTs
should never be left with the secondary open and the primary connected.
Instrument Transformers_r8 22
Power System Protection for Engineers – PROT 401
Pure
t Resistive
Load
ip /N (Ideal) i
s
t Z = R+jX
When a CT is saturated, the wave shape of the secondary current strongly depends on
the type of load connected. The figure shows two examples.
In the case of resistive load, as seen in the first diagram, the secondary current wave
shape has a “shark fin” appearance.
The second diagram’s wave shape is a representation of the distorted secondary current
for an impedance with resistance and reactance of similar magnitude.
In both cases, the rms value of the secondary current is considerably different than the
ideal one. Both the magnitude and angle errors may be unacceptable for protective
relaying applications.
Instrument Transformers_r8 23
Power System Protection for Engineers – PROT 401
There are several methods to determine the characteristics that a CT should have to
prevent saturation during fault conditions.
The standards organizations have established a set of rules which provide users with
enough information about the CTs so that they can be clearly specified to achieve the
appropriate performance.
Instrument Transformers_r8 24
Power System Protection for Engineers – PROT 401
z Metering Applications
z Protective Relaying Applications
Letter designation
Terminal voltage rating
Instrument Transformers_r8 25
Power System Protection for Engineers – PROT 401
The ANSI letter designations are C and T. The most common designation is C. The
leakage flux for this class of CT is negligible and therefore the performance can be
determined directly from the excitation characteristics.
A K rated CT is the same a C rated CT, except that the specified knee-point voltage is
at least 70% of the secondary terminal voltage rating.
T-rated CTs have appreciable flux leakage which requires the ratio error to be
determined by test.
Instrument Transformers_r8 26
Power System Protection for Engineers – PROT 401
Rs
g
IE
IP /Ns + IS
Ideal
IP /Ns VS ZLOAD
-
h
IP
IS = − IE ; VS = I S (Rs + ZLOAD)
NS
If the leakage is negligible, the CT equivalent circuit can be reduced to the one shown
in the figure.
Instrument Transformers_r8 27
Power System Protection for Engineers – PROT 401
The secondary terminal voltage rating is the minimum CT secondary voltage that the
CT will deliver when connected to a standard burden with 20 times nominal current
flowing and the ratio error is limited to 10%.
The voltage rating only applies to the full winding. The voltage rating of a CT tap is
directly proportional to the tap being used and the full winding capability. As an
example, if a C400 1200/5 CT is operated on the 600/5 tap, the voltage rating at 600/5
is 200 volts. This holds true only if the windings are fully distributed around the core.
The common ANSI standard voltage ratings are: 100, 200, 400, 800. For 5 amp CTs
this results in standard burdens of 1, 2, 4 and 8 ohms. The standard burden is often
considered purely resistive when used in calculations. The actual standard burden has a
power factor of 0.5 (i.e.. 60° characteristic angle).
Instrument Transformers_r8 28
Power System Protection for Engineers – PROT 401
VSTD = 20•IN•ZSTD
For IN = 5A Secondary:
C Class ZSTD(Ω) VSTD (V)
C100 1 100
C200 2 200
C400 4 400
C800 8 800
We can state this equation in terms of the standard values defined in C57.13.
Instrument Transformers_r8 29
Power System Protection for Engineers – PROT 401
Instrument Transformers_r8 30
Power System Protection for Engineers – PROT 401
The second method has been used by utility engineers and technicians when the CT
excitation curve has been available. Note that when using the excitation curve, the
secondary resistance of the CT must be included in the burden calculation since the
excitation curve is a plot of the induced voltage and not the terminal voltage.
Instrument Transformers_r8 31
Power System Protection for Engineers – PROT 401
The excitation curve can be used in combination with the Class C standard terminal
voltages to specify a CT.
In the example shown, for the 2000/5 ratio, full saturation voltage is close to 500 Volts,
and the CT has a secondary resistance of 0.7 Ohms.
Instrument Transformers_r8 32
Power System Protection for Engineers – PROT 401
The quick estimate calculation does not consider the burden that is placed on the CT.
To calculate the voltage available, subtract the internal voltage drop from the secondary
exciting voltage obtained from the graph. The exciting voltage is read at the 10% error
point; that is, where the excitation current is 10 Amps.
The internal voltage drop is equal to the current (100 amps) times the winding
resistance (0.7 ohms).
The C rating is the voltage rating just below the calculated VB (Burden Voltage). This
CT would have a C400 rating.
Instrument Transformers_r8 33
Power System Protection for Engineers – PROT 401
15 VA Class 10 P 20
Accuracy Limit Current Factor
For Protection
Accuracy Class
Continuous VA
Instrument Transformers_r8 34
Power System Protection for Engineers – PROT 401
z 5 Amp CTs
Instrument Transformers_r8 35
Power System Protection for Engineers – PROT 401
Current Transformer
Performance
for a DC Current Component
Instrument Transformers_r8 36
Power System Protection for Engineers – PROT 401
If No Saturation Occurs
I ⎡ − RL t ⎤
− is = ⎢e − cos(ωt )⎥
N ⎣ ⎦
If no saturation occurs, the secondary current will be a perfect replica of the primary
current.
Instrument Transformers_r8 37
Power System Protection for Engineers – PROT 401
1
0
-1
0 1 2 3 4 5 6 7
Cycles
The plot shows the extreme error that is caused when a CT saturates. As can be seen,
the CT reaches saturation after approximately ¼ cycle. Once the waveform becomes
negative, the CT comes out of saturation and begins following the ratio current until the
next positive half cycle when it becomes saturated again.
Instrument Transformers_r8 38
Power System Protection for Engineers – PROT 401
-20
-30
-40
-50
0 1 2 3 4 5 6 7
Cycles
The error propagates beyond the relay filters and also beyond the phasor estimation
routines.
Most modern relays operate on the fundamental component of the measured current.
The upper plot shows the ideal current magnitude from a non-saturated CT; versus the
current from the saturated CT.
Instrument Transformers_r8 39
Power System Protection for Engineers – PROT 401
Required Vs
X
VS IF ZB 1
R
The equation shown in the slide is derived with the following procedure. First, start
with the volt-time integral for the case of resistive burden and asymmetric fault current:
R
t t − t
φ ⋅ N = − BAN = − ∫ vdt = − ∫ I F ⋅ Z B (cos ω t + e L
)dt =
0 0
⎛1 L − t L ⎞ I ⋅Z ⎛ R
⎞
⎜ sin ω t + ω L e ω L − ω L ⎟ =
R − ωt
= I F ⋅ Z B ⎜⎜ sin ω t + e L − ⎟⎟ = F B
⎜ R ⎟⎠
⎝ω R R⎠ ω ⎝ R
I ⋅Z ⎛ X − ωt X ⎞
R
= F B ⎜⎜ sin ω t + e X − ⎟⎟ ⇒
ω ⎝ R R⎠
⎛ X − Rωt X ⎞
BANω = I F ⋅ Z B ⎜⎜ − sin ω t − ⋅ e X + ⎟⎟
⎝ R R⎠
It can be shown that the maximum magnitude of the
function given above is
(BANω )max = I F ⋅ Z B ⎛⎜1 + X ⎞⎟
⎝ R⎠
But
(BANω )max = VS max
⎛ X⎞
VS max = I F ⋅ Z B ⎜1 + ⎟
⎝ R⎠
Instrument Transformers_r8 40
Power System Protection for Engineers – PROT 401
To Avoid CT Saturation
⎛ X⎞ I Z
20 ≥ ⎜1 + ⎟ ⋅ F ⋅ B
⎝ R ⎠ IN Z STD
We can also state equation in terms of the Standard Ratings values defined in C57.13.
Instrument Transformers_r8 41
Power System Protection for Engineers – PROT 401
Actual
ie
Desired
The formulas derived in the previous slides were obtained neglecting the iron core
hysteresis.
Modeling the whole phenomenon and determining the precise value of the secondary
current is an interesting task which is out of the scope of this course.
Another reason to consider a full offset wave when specifying a CT is that any residual
flux existing in the core due to previous fault conditions may cause the CT to saturate
sooner for a new fault condition.
Instrument Transformers_r8 42
Power System Protection for Engineers – PROT 401
CT Simulations
Instrument Transformers_r8 43
Power System Protection for Engineers – PROT 401
CT Simulations
z C800
z 2000/5
Full ratio
z ZB = 0.5 pu
z X/R = 12
85.2° line
Instrument Transformers_r8 44
Power System Protection for Engineers – PROT 401
(1 + X/R)•IF•ZB = 20
X/R = 12
ZB = 0.5 pu
Instrument Transformers_r8 45
Power System Protection for Engineers – PROT 401
(1 + X/R)•IF•ZB = 50
X/R = 12
ZB = 0.5 pu
Instrument Transformers_r8 46
Power System Protection for Engineers – PROT 401
(1 + X/R)•IF•ZB = 20
with 0.5 pu Remanent Flux
The conditions required to avoid CT saturation are met in this simulation. However,
50% remanent flux has been included. Now, the CT shows signs of saturation after
approximately 1.3 cycles.
Instrument Transformers_r8 47
Power System Protection for Engineers – PROT 401
Summary
Instrument Transformers_r8 48
Power System Protection for Engineers – PROT 401
Other CT Considerations
Instrument Transformers_r8 49
Power System Protection for Engineers – PROT 401
Other CT Ratings
z Continuous
ANSI
1.0, 1.33, 1.5
2.0, 3.0, 4.0
z Short-Time
Mechanical
Thermal
The ANSI standard defines a continuous thermal current rating that is based on 30° C
average ambient air temperature. The rating factor is a multiple of the rated secondary
current that the CT can support on a continuous basis without experiencing any
damage.
The short-time mechanical and thermal ratings are not independent. The short-time
mechanical rating is the rms value of the ac component of an asymmetrical primary
current wave that the transformer is capable of withstanding with the secondary
winding shorted.
The 1 second short-time thermal rating is the rms symmetrical primary current that can
be carried for 1 second, with the secondary winding shorted, without exceeding the
limiting temperature. Generally, the limiting temperature is 250° C for copper and 200°
C for aluminum conductors.
If the 1 second rating is independent of core saturation and the primary current is
symmetrical, the short-time thermal rating for any time, up to 5 seconds, can be
determined by dividing the 1 second rating by the square root of the specified number
of seconds. For example, the 3 second rating is equal to the 1 second rating divided by
the square root of 3, or 58% of the 1 second rating.
Instrument Transformers_r8 50
Power System Protection for Engineers – PROT 401
H1 XX
1
1
H2 X2
FrequencyininHertz
Frequency Hertz
The frequency response of current transformers is generally very flat around 100%.
The CT starts to lose precision for frequencies over 10 kHz. This indicates that for
normal relay applications (with interest in the 60 Hz component) the CT behavior is
very good. However, for relay applications which require of the fault current high
frequency components, the CT response must be carefully evaluated.
Instrument Transformers_r8 51
Power System Protection for Engineers – PROT 401
CT Application Notes
1200
Effective Rating = ⋅ 800 = 480
2000
Instrument Transformers_r8 52
Power System Protection for Engineers – PROT 401
CT Application Notes
Delta-connected CTs
Three-phase fault use the sum of the three
CT leads
Instrument Transformers_r8 53
Power System Protection for Engineers – PROT 401
CT Application Notes
Instrument Transformers_r8 54
Power System Protection for Engineers – PROT 401
CT Application Notes
⎛ X⎞ I Z
20 ≥ ⎜ 1 + ⎟ ⋅ F ⋅ B
⎝ R ⎠ IN Z STD
z IN = Primary CT Rating if IF is in Primary
Amps
z IN = Secondary CT Rating if IF is in
Secondary Amps
z ZSTD = Standard Burden Based on the C
Rating or the Effective C Rating,
Depending on Selected CT Ratio
The formula is based on the ANSI standards and includes the effect of the decay rate. It
also assumes full offset. While the ANSI standard says that there will be 10%, or less,
error at 20 times nominal current, it does not account for any remanent flux. Therefore,
the formula provides margin for remanent flux.
As an example, using an X/R ratio of 12 with a fault current and burden such that the
calculation equals 20, the CT will saturate after approximately 1.5 cycles with full
offset and 50% remanent flux.
Instrument Transformers_r8 55
Power System Protection for Engineers – PROT 401
Exercise
2000/5
g h Fault
ZLEAD ZLEAD
0.5 Ω 0.5 Ω
Fault Data:
ZRELAY IF = 12 kAφ-G
X/R = 11
0.1 or 1.0 Ω
Problem:
The maximum external fault current for the line shown above is 12 kA for a phase-to-
ground fault with an X/R of 11. The current transformation ratio is 2000:5. The one
way CT lead resistance is 0.5 Ω.
Assume you can use two types of relays, one with 1 Ohm impedance and the other with
an impedance of 0.1 Ohms. Assume that the leads and the relay are purely resistive.
If you were specifying the CT rating, what would you select for each relay in order to
avoid CT saturation?
Instrument Transformers_r8 56
Power System Protection for Engineers – PROT 401
Exercise Solution
ZRELAY = 1.0 Ω
Instrument Transformers_r8 57
Power System Protection for Engineers – PROT 401
Exercise Solution
ZRELAY = 0.1 Ω
Instrument Transformers_r8 58
Power System Protection for Engineers – PROT 401
Voltage Transformers
Instrument Transformers_r8 59
Power System Protection for Engineers – PROT 401
Magnetic Voltage
Transformers
Instrument Transformers_r8 60
Power System Protection for Engineers – PROT 401
+ +
Vp Np Ns Vs LOAD
- -
Vs N s
Ideally : =
VP N p
Instrument Transformers_r8 61
Power System Protection for Engineers – PROT 401
VT Equivalent Circuit
Referred to the Secondary Side
+ IE +
Vp Np Ns Vs
Non-
- Linear -
Ideal
Instrument Transformers_r8 62
Power System Protection for Engineers – PROT 401
150%
Primary
Voltage
100%
Normal Operating
Range
50%
0%
Exciting Current
In some systems (depending on the neutral grounding) there could be large steady-state
overvoltages on the sound (healthy) phases for a single-phase to ground fault.
V bf ≈ C g Vbn 1 ≤ C g ≤ 1.73
Where:
Instrument Transformers_r8 63
Power System Protection for Engineers – PROT 401
VT Wye Connection
A
B
C
a
b
c
Instrument Transformers_r8 64
Power System Protection for Engineers – PROT 401
VT Delta Connection
A
B
C
a
b
c
Instrument Transformers_r8 65
Power System Protection for Engineers – PROT 401
a
b
c
Instrument Transformers_r8 66
Power System Protection for Engineers – PROT 401
3V0
Instrument Transformers_r8 67
Power System Protection for Engineers – PROT 401
W 12.5 0.10
X 25 0.70
M 35 0.20
Y 75 0.85
Z 200 0.85
ZZ 400 0.85
Instrument Transformers_r8 68
Power System Protection for Engineers – PROT 401
Limits of Ratio
Accuracy Limits of Power
Correction
Class Factor (Lagging)
Factor
Instrument Transformers_r8 69
Power System Protection for Engineers – PROT 401
110
108
106 Curve Burden
(1)
104 (1) 15 k Ω
102 (2) 75 Ω
100
90
100 500 1000 5000 10000 20000
Frequency in Hertz
Instrument Transformers_r8 70
Power System Protection for Engineers – PROT 401
Capacitive Voltage
Transformers (CVT)
Instrument Transformers_r8 71
Power System Protection for Engineers – PROT 401
CVT Structure
Line Voltage
L Compensating
Reactor Step-Down
C1
Transformer
C2 Relay
Voltage
DWG: 6049-DH01
Instrument Transformers_r8 72
Power System Protection for Engineers – PROT 401
Ferroresonance-Suppression Circuits
Step-down Transformer
Tansformer Secondary
Relay Voltage
L
GAP
Secondary
Step-Down
C Lf Rf
Passive
Active DWG: 6049-DH02
Instrument Transformers_r8 73
Power System Protection for Engineers – PROT 401
Instrument Transformers_r8 74
Power System Protection for Engineers – PROT 401
Instrument Transformers_r8 75
Power System Protection for Engineers – PROT 401
Instrument Transformers_r8 76
Power System Protection for Engineers – PROT 401
Instrument Transformers_r8 77