Multi Zone of Gas Detection- Integral Solenoid Drive - Integral Battery charger
The Module interfaces with conventional Gas The front fascia's of the main module has
detectors. the General LED fault indicators for:
DETAILED OPERATION
There are a number of pellistors available
The gas sensors the control panel has each with their own specific characteristics
been designed to monitor are Pellistor and applications. It is important to check
type that allow a bridge to be set up. the suitability for which the pellistors are
Each sensor has two elements. One is intended and the compatibility with the
open to the atmosphere and one is seal control equipment.
with special paint.
A Reference a Chart is available giving the
These elements are fitted into a housing relative values for other calibration gases
and this housing is fitted into a Stainless
Steel housing with a Sintered Stainless Upon receipt of an alarm the relevant
Steel filter with a pore density to Iso 2738. zone indicator will flash and outputs will
operate. Please refer to a typical:
The sensors are wired to the module with “EDS INSTALLATION” drawing
a 3 core cable, one core to each node. To attached.
the panel zone.
Various compatible sensors are
Pellistor available (compatibly should be checked
with the Sensor suppler before being
The detector head uses the standard purchased or connected).
pellistor elements. When a combustible
mixture surrounds the elements, the We have included an “Equivalent Gas
flameless catalytic burning produced on the Calibration Chart” to assist in setting up
surface raises the temperature, which in for alternate sensors.
turn changes the resistance. The re-
sistance of this pellistor is compared by the
Wheatstone Bridge circuit (which forms part
of the Gas detector module) to the
resistance of the second reference pellistor.
The reference element allows automatic
compensation for humidity, pressure and
temperature changes.
Typical Installation Diagram
Terminal Description.
Panel Set-up
When a new Sensor is connected to the main Battery Adjustment should be carried out with a
module it must be set-up correctly. Follow these fully charged battery connected, for a minimum of
steps: five minutes.
1. Before connecting the sensor ensure the
voltage on the terminal are less than 3V. The voltage on the battery should be measured
2. 31-33 or 34-36 with a multi-meter.
3. Connect the sensor three wires.
4. Adjust the voltage on the sensor to 2.4V The voltage on the battery should be between
using the Hd-V1 pot or Hd-V2 27.4 and 27.6 volts. The voltage is set by
5. Insert the Program jumper to allow the adjusting the multi-turn potentiometer mounted at
memory to be altered. the lower left of the main module, marked “BAT”.
6. Put the zone that is being set up into 2 x 12V 7AHr sealed lead acid batteries
isolate by pressing the Isolate Button on
the front facia. (Only one zone a a time).
7. Press the zero button then the gain Fuses are fitted to Main Module
button. Hold both until the bar on the
Various Fuses are fitted to the Main Module.
seven segment displays moves to thr top.
These are:
8. After a short while a nominal value of
1. Battery Fuse. 5 Amp.
approximately 50 should be displayed.
2. Solenoid Fuses F1 and F2. Nominally
9. Either set-up the second zone as above
1.6Amp.
using Zone 2 controls or simply remove
3. Other fuses are auto reset so they will
the programming jumper to inhibit any
recover after the load or short that caused
erroneous memory writes.
them to open circuit is removed. These
include
a. MF1 for Sounder and Beacon
b. MF2 for special use.
c. MF3 for Charger Overload
d. MF4 external +24V supply.
No action is needed on these resettable
fuses.
Jumper Description.
Non Latching Fire allow the Fire signal from the Fire
Panel to be Latched on rather than automatically
reset.
The Gas Sensor is screwed into one of the Junction Box entries.
Any spare junction box ports must have a plug fitted into it.
The sensor cab be mounted to be horizontal or vertically down. The cable entry
must not face upwards to that any rain water etc. does not trickle down the lead and
over time ingress into the junction box.
If the cable come down from above it should loop down so water can drain off. The
cable can then enter from the side or lower entry.
The Junction box should only be opened when it is certain there is no gas
hazard in the area. This can be checked with a hand held gas monitor.
Two zone Module and Two zone with two zone expansion
Equivalent Gas Calibration Chart
MAINTENANCE MAINS CABLING
Sensors should be kept clean and free from All Cables entering the Control Panel must
debris and contamination, Be via Cable glands.. Typically As show
below.
Sensors should be re-calibrated every 6
months depending on environment.
DO NO PAINT SENSOR OR HOUSING PANEL SITING
All screws should be checked to ensure they
are secure. The Control Panel must be sited inside the
building (Not suitable for mounting outside)
SPARES in a dry location where rain OR hose
cleaning will not wet the panel.
There are no Panel spare parts to be
changed. If found faulty it should be replaces Mains Power to the Panel should be from
with a complete spare module. the 10A fused isolator box sied as per CD
recommendations within 1M of the Panel.
Sensors should be replaced when it is no
longer possible to calibrate correctly. This can PANEL MUST BE EARTHED WITH PRO-
in some cases be as little as 6 months but in TECTIVE EARTH
most cases it will be several years.
Early Detection
EVER Systems
SHIELD LIMITED
Manufactured in UK
eds_shield@hotmail
12 Leigh Roadin
Manufactured Industrial
UK Park
Ramsgate,
12 Kent,
Leigh Road CT12 5EU,
Industrial UK
Park
+971(0)50 4399
Ramsgate, Kent,686
CT12 5EU, UK
+44(0)7767 354996
+971(0)50 4399 686
+44(0)7767 354996
www.Evershield-EDS.com
PANEL MOUNTING. CABLING
The panel should me fixed directly to a Sup- All Cables entering the Control Panel must
port Wall with 4 off No.10 fixing screws 60mm be via Cable glands.. Typically As show
long. They should be fitted into suitable wall below. No loose cables should be allowed.
fixings. Where any cores are not terminated these
should be tie-wrapped and secured away
The top two fixing holes are Key Hole type to from main panel cabling.
assist in levelling the panel. The Lowe two
Holes can be marked and drilled when the The Mains cable must be 1mm2 double
panel is hung on the top two screws. insulated:
DO NOT SITE PANEL IN DIRECT SUN- There are no Panel spare parts to be
LIGHT changed. If found faulty it should be replac-
es with a complete spare module.
The Panel must be mounted in a well ventilat-
ed room. The Panel may be mounted in Hi- Sensors should be replaced when it is no
Rise buildings at a height of less than 1000M. longer possible to calibrate correctly. This
The Panel MUST be used in a manner as de- can in some cases be as little as 6 months
scribed in this Manual. but in most cases it will be several years.
ALL cables must be suitably secured.
Sigo
EVERGas Equipment
SHIELD LIMITEDTrading LLC
Dubai, UAE in
Manufactured sales@sigogas.com
UK
12 Leigh Road Industrial Park
Manufactured in UK
Ramsgate,
12 Kent,
Leigh Road CT12 5EU,
Industrial UK
Park
+971(0)50 4399
Ramsgate, Kent,686
CT12 5EU, UK
+44(0)77674399
+971(0)50 354996
686
+44(0)7767 354996
www.Evershield-EDS.com