EVER SHIELD

LIMITED

Ever Shield Limited


Sigo Gas
EVER Equipment
SHIELD LIMITED
Sigo
EDS Multi-Channel Gas Monitoring
Control Panel
Marketed under the Shield trade name
Using the latest micro-controllers the Sigo
EDS panels offers detection up to 144 zones.
Seven Segment or Liquid Crystal Displays give visual indication of gas levels on each

Multi Zone of Gas Detection- Integral Solenoid Drive - Integral Battery charger

The Module interfaces with conventional Gas The front fascia's of the main module has
detectors. the General LED fault indicators for:

Conventional Detectors are connected by 3 Battery


cables. One from the Passive half of the Mains
bridge the second from the active side of the Sounder
bridge and the third cable from the centre of Gas Supply Button Switch with On/Off LEDs
the half bridge. Sprinkler Button Switch with On/Off LEDs
LEDs for:
The other half of the bridge is on the module. Power On
An operational amplifier measures the offset Alarm 1
induced by sensing gas. This is then digitised Alarm 2
and fed to the logic on the module. External Alarm
Sounders On
The digital information us used to set the 7 Gas Pressure Fault
segment displays to display the %LEL (Lower General Fault.
Explosive Limit) of the gas and to give two With Main Button Switches for:
alarm output. Accept—Steady LEDs
Evacuate-Turn Sounders on.
These outputs are shown on LEDs on the Silence– Turn Sounders off.
front plate. Alarm levels are normally set at Reset—to restore system to normal.
15% (Alarm 1) and 30% (alarm 2) Zonal indications of:
Gas Concentration (LEL)
Alarm relay outputs are available to operate Alarm 1
external equipment typically building Alarm 2
management systems Fault
Other functions available on Panel some versions.
Alarm In causes the Gas Solenoid Drive to be
de-energised and The Sprinkler Solenoid Repeated for all channel if multi zone panel.
Drive to be energised.
Technical Specification

DETAILED OPERATION
There are a number of pellistors available
The gas sensors the control panel has each with their own specific characteristics
been designed to monitor are Pellistor and applications. It is important to check
type that allow a bridge to be set up. the suitability for which the pellistors are
Each sensor has two elements. One is intended and the compatibility with the
open to the atmosphere and one is seal control equipment.
with special paint.
A Reference a Chart is available giving the
These elements are fitted into a housing relative values for other calibration gases
and this housing is fitted into a Stainless
Steel housing with a Sintered Stainless Upon receipt of an alarm the relevant
Steel filter with a pore density to Iso 2738. zone indicator will flash and outputs will
operate. Please refer to a typical:
The sensors are wired to the module with “EDS INSTALLATION” drawing
a 3 core cable, one core to each node. To attached.
the panel zone.
Various compatible sensors are
Pellistor available (compatibly should be checked
with the Sensor suppler before being
The detector head uses the standard purchased or connected).
pellistor elements. When a combustible
mixture surrounds the elements, the We have included an “Equivalent Gas
flameless catalytic burning produced on the Calibration Chart” to assist in setting up
surface raises the temperature, which in for alternate sensors.
turn changes the resistance. The re-
sistance of this pellistor is compared by the
Wheatstone Bridge circuit (which forms part
of the Gas detector module) to the
resistance of the second reference pellistor.
The reference element allows automatic
compensation for humidity, pressure and
temperature changes.
Typical Installation Diagram
Terminal Description.

1– 4 Terminals are special functions. Do not


connect before consultation with the Design
Office.

5 and 6 supply low signal to Local Sounder and


Beacon. +24V is supplied from Terminal 7
Maximum Rating 36V 0.5A

Terminals 8 and 9 are open normally and closes


on Gas Alarm. Maximum rating 36V at 0.5A

10 and 11 allow the Fire panel to shut the gas off


in the event of a fire alarm. Should only be
connected to volt free contact

12 and 13 Do not connect.

14 and 15 for connection of Sprinkler Flow switch


to sound alarms an cut off gas.

16 and 17 Gas Pressure switch allows pressure


to be monitored. If too high it shuts off gas. Low
gives fault. Terminals 14 to 17 should only be
connected to volt free contacts

Terminals 18 to 26 are volt free contacts for the


specified function. Maximum rating 36V at 1A

27 and 28 supply to Gas Solenoids. Normally on


when no gas sensed. Maximum Rating 36V 1A

29 and 30 supply to the Sprinkler Solenoid. Off


when no gas sensed. The operation may be
overridden by front of panel switches.
Maximum Rating 36V 1A

31, 32 and 33 are for connecting the gas sensor


for Zone 1. Sensor Max Rating 5VDC 0.5A

34, 35 and 36 are for connecting the second gas


sensor if a two zone panel. Sensor Max Rating
5VDC 0.5A
Power Terminal Description.

Terminals 1 & 2 supply voltage for external relays


etc. if required. Max Rating 36VDC 1A

3 and 4 allow connection of 2 x 12V 7AHr sealed


lead acid batteries giving nominal 24VDC. Battery
fused at 5A

Terminals 5 & 6 allow connection of a 10,000 uF


50V capacitor to compensate for solenoid surge if
required.

Terminals 7 to 10 allow connection of the Mains


transformer with two 19V AC windings.
Ensure correct phasing before applying power.

Terminal 11 allows connection of earth/ ground


input where this is monitored for fault.

Panel Set-up

Sensor Initial Set-up Battery Adjustment

When a new Sensor is connected to the main Battery Adjustment should be carried out with a
module it must be set-up correctly. Follow these fully charged battery connected, for a minimum of
steps: five minutes.
1. Before connecting the sensor ensure the
voltage on the terminal are less than 3V. The voltage on the battery should be measured
2. 31-33 or 34-36 with a multi-meter.
3. Connect the sensor three wires.
4. Adjust the voltage on the sensor to 2.4V The voltage on the battery should be between
using the Hd-V1 pot or Hd-V2 27.4 and 27.6 volts. The voltage is set by
5. Insert the Program jumper to allow the adjusting the multi-turn potentiometer mounted at
memory to be altered. the lower left of the main module, marked “BAT”.
6. Put the zone that is being set up into 2 x 12V 7AHr sealed lead acid batteries
isolate by pressing the Isolate Button on
the front facia. (Only one zone a a time).
7. Press the zero button then the gain Fuses are fitted to Main Module
button. Hold both until the bar on the
Various Fuses are fitted to the Main Module.
seven segment displays moves to thr top.
These are:
8. After a short while a nominal value of
1. Battery Fuse. 5 Amp.
approximately 50 should be displayed.
2. Solenoid Fuses F1 and F2. Nominally
9. Either set-up the second zone as above
1.6Amp.
using Zone 2 controls or simply remove
3. Other fuses are auto reset so they will
the programming jumper to inhibit any
recover after the load or short that caused
erroneous memory writes.
them to open circuit is removed. These
include
a. MF1 for Sounder and Beacon
b. MF2 for special use.
c. MF3 for Charger Overload
d. MF4 external +24V supply.
No action is needed on these resettable
fuses.
Jumper Description.

Jumpers GH1 allows for the module to initially be set


up without a gas sensor connected. Remove for
normal operation.

Jumpers GH2 allows for the module to initially be set


up without gas sensor two (if applicable) connected.
Remove for normal operation.

Gas pressure jumpers allows setup without pressure


switch connected

Crds jumper allows additional G2 modules to be


connected to the pane. Refer to G2 manual).

Non Latching Fire allow the Fire signal from the Fire
Panel to be Latched on rather than automatically
reset.

GasSol and Sprinkler Sol jumpers give a dummy load


for Panel setup. Remove for normal Operation.

This Jumper must be inserted ONLY when any


function is being programmed. Must be removed for
normal operation.

This jumper is fitted to Enable Relay operation.

This jumper is fitted to Enable Panel Sounder


operation.
Equipment.
Each Sensor if fitted into the Exp Junction box.

The Gas Sensor is screwed into one of the Junction Box entries.

Any spare junction box ports must have a plug fitted into it.

The sensor cab be mounted to be horizontal or vertically down. The cable entry
must not face upwards to that any rain water etc. does not trickle down the lead and
over time ingress into the junction box.

If the cable come down from above it should loop down so water can drain off. The
cable can then enter from the side or lower entry.

The Junction box should only be opened when it is certain there is no gas
hazard in the area. This can be checked with a hand held gas monitor.

Gas Kitchen Addressable Detection Panel


Sensor Gas
Sensor

Two zone Module and Two zone with two zone expansion
Equivalent Gas Calibration Chart
MAINTENANCE MAINS CABLING
Sensors should be kept clean and free from All Cables entering the Control Panel must
debris and contamination, Be via Cable glands.. Typically As show
below.
Sensors should be re-calibrated every 6
months depending on environment.
DO NO PAINT SENSOR OR HOUSING PANEL SITING
All screws should be checked to ensure they
are secure. The Control Panel must be sited inside the
building (Not suitable for mounting outside)
SPARES in a dry location where rain OR hose
cleaning will not wet the panel.
There are no Panel spare parts to be
changed. If found faulty it should be replaces Mains Power to the Panel should be from
with a complete spare module. the 10A fused isolator box sied as per CD
recommendations within 1M of the Panel.
Sensors should be replaced when it is no
longer possible to calibrate correctly. This can PANEL MUST BE EARTHED WITH PRO-
in some cases be as little as 6 months but in TECTIVE EARTH
most cases it will be several years.

Early Detection
EVER Systems
SHIELD LIMITED
Manufactured in UK
eds_shield@hotmail
12 Leigh Roadin
Manufactured Industrial
UK Park
Ramsgate,
12 Kent,
Leigh Road CT12 5EU,
Industrial UK
Park
+971(0)50 4399
Ramsgate, Kent,686
CT12 5EU, UK
+44(0)7767 354996
+971(0)50 4399 686
+44(0)7767 354996
www.Evershield-EDS.com
PANEL MOUNTING. CABLING
The panel should me fixed directly to a Sup- All Cables entering the Control Panel must
port Wall with 4 off No.10 fixing screws 60mm be via Cable glands.. Typically As show
long. They should be fitted into suitable wall below. No loose cables should be allowed.
fixings. Where any cores are not terminated these
should be tie-wrapped and secured away
The top two fixing holes are Key Hole type to from main panel cabling.
assist in levelling the panel. The Lowe two
Holes can be marked and drilled when the The Mains cable must be 1mm2 double
panel is hung on the top two screws. insulated:

BEFORE any drilling the Chassis should be Line: Brown


removed from the panel by loosening the 4 Ground: Green/Yellow
fixing screws. Do not remove these screws as Neutral: Blue
the chassis has key hole slots for easy remov-
al and re-fitting. The chassis should be placed We suggest Gas Sensors are wired so that
in a safe location and protected from any dirt different colours are used for each poll of
ingress. each sensor. Repeated for each additional
sensor.
The Panel should be powered from an exter-
nal Fused, Switched Mains Supply and the All Cabling MUST comply with Local Au-
Mains and Earth connections Tested for con- thority or Civil Defence requirements.
tinuity with Main Building Supply (230VAC +/-
10%, Line Earth and Neutral) 50-60 HZ The Panel should have the inner and outer
door closed when not attended. A key lock
The Panel can easily be carried to its installa- is supplied for the outer door which should
tion location just prior to fixing within the build- be used to stop any un-authorised access
ing as detailed above. The Panel should not to the panel.
be sited above 500M with an ambient temper-
ature range of 0 deg. to 45 deg. Celsius.
Humidity range: 0% RH to 95% RH SPARES

DO NOT SITE PANEL IN DIRECT SUN- There are no Panel spare parts to be
LIGHT changed. If found faulty it should be replac-
es with a complete spare module.
The Panel must be mounted in a well ventilat-
ed room. The Panel may be mounted in Hi- Sensors should be replaced when it is no
Rise buildings at a height of less than 1000M. longer possible to calibrate correctly. This
The Panel MUST be used in a manner as de- can in some cases be as little as 6 months
scribed in this Manual. but in most cases it will be several years.
ALL cables must be suitably secured.

Sigo
EVERGas Equipment
SHIELD LIMITEDTrading LLC
Dubai, UAE in
Manufactured sales@sigogas.com
UK
12 Leigh Road Industrial Park
Manufactured in UK
Ramsgate,
12 Kent,
Leigh Road CT12 5EU,
Industrial UK
Park
+971(0)50 4399
Ramsgate, Kent,686
CT12 5EU, UK
+44(0)77674399
+971(0)50 354996
686
+44(0)7767 354996
www.Evershield-EDS.com