Transfer Pump Calculation
Transfer Pump Calculation
Transfer Pump Calculation
Pump Head :
Pump Head, H = static head + pressure required at outlet + pressure drop due
to friction in the piping
Where
Static Head = vertical distance between the furthest point and pump
discharge level
= 54.78 m - 51.53 m + 1.2 m
= 4.45 m
= 14.6 ft
Pressure required
at outlet = 7.5 m
= 24.6 ft
HR/1
AFC WCPU 2020 PERUNDING AZFAR
Pressure drop due
to friction = calculated as follows
Water Pipe Description No. of Equal Eff. 10% Head
Flow Size Item Length Length Safety Consume
(Igpm) (in) (ft) (ft) Factor (ft)
20 2 Static pipe - 180 256.7 282.4 5.67
Tee 1 3.3
Elbow 10 5
Strainer 2 10
Gate Valve 2 1.7
HR/2
AFC WCPU 2020 PERUNDING AZFAR