Professional Documents
Culture Documents
Tes-B-106.04-R0-Deluge System
Tes-B-106.04-R0-Deluge System
la
a.. fI.~~~~~1 ~~I
Q.
« Saudi ElectricityCompany
.....=
0::
w
0
a
C>
Q:
0
111-1-111.14
ReVisionno.0
en
z
0
(j) DELUGE SYSTEM
5
w
0::
Z
0
i=
Q.
Q:
0
en
w
a
PROPRIETARY INFORMATION
Q) This document contains proprietary information developed by and for exclusive use of Saudi Electricity
iii Company. Your acceptance of the document is an acknowledgement that it must be used for the identified
a
purpose/application and during the period indicated. It cannot be used or copied for any other purposes nor
released to others without prior written authorization of Saudi Electricity Company. Saudi Electricity Company
ci ...... N (') will not be responsible for misuse and/or misapplication, and any harm resulting therefrom. Saudi Electricity
Z
Company also reserves the right to take any necessary actions to protect its interest against unauthorized use.
ORIGINATED BY CERTIFIED BY APPROVED BY
~~
Engr. Khalaf M.AI-Ma'ashi Engr. Abdullah M. AI-Garni Engr. Saleh N. AI-Sohaibani
Division Manager, Department Manager, Executive Director,
Engineering Support Transmission Standards & Engineering & Projects
Specifications
Date of Approval: April 29, 2009
TABLE OF CONTENTS
1.0 SCOPE
5.1 General
5.2 Water Spray Systems for Horizontal Tanks
5.3 Water Spray Systems for Vertical Tanks
6.1 General
6.2 Deluge Valve
6.3 Fire Detection Equipment
6.4 Control and Indicating Equipment
6.5 Water Spray Nozzles
6.6 Piping
9.0 REFERENCES
1.0 SCOPE
This Transmission Engineering Standard establishes the minimum requirements for the
design, installation, tests and commissioning of deluge water spray system to be used in
Saudi Electricity Company (SEC) in Kingdom of Saudi Arabia.
Any conflicts between this Standard and other SEC Engineering Standards (TES), related
SEC Materials Standards Specifications (TMSS), SEC Standard Drawings and other
relevant Codes and Standards shall be resolved by the Fire Prevention Development
Division.
Any deviations or exceptions to the Standard that provide less than the minimum
requirements of this Standard shall require a written approval of the Fire Prevention
Development Division.
The system shall be a deluge type of water spray extinguishing system intended for
the protection of special hazards. The system shall be designed to deliver the water
spray that has a predetermined pattern, particle size, velocity, density and duration
over the protected area or equipment.
3.2.1 General
The fire detection and alarm system shall control the programmed automatic
actuation of the system.
a. The fire detection and alarm system shall employ fire detectors wired
in a dual-detector dependency. The operation of the fire detectors in a
dual-detector dependency and the alarm signaling system shall
operate as follows:
b. When flammable gas detectors are employed by the fire detection and
alarm system which controls the deluge system, the gas detection
system shall be designed to operate as follows:
3.3.1 Sources
The water supply for the deluge system shall be provided by any of the
following:
i. A listed fire water pump taking suction from a reliable public water
main. A listed O.S & Y shut-off valve and a check valve shall be
installed in the suction line connection to the public water mains.
ii. A listed fire water pump taking suction from a fire water storage tank.
The fire water storage tank shall comply with the applicable
requirements of NFPA 22, Water Tanks for Private Fire Protection.
The fire pump shall comply with the applicable requirements of
NFPA 20, Centrifugal Fire Pumps.
iii. The fire water storage shall be dedicated to the deluge system and the
quantity shall be adequate for a system operation of at least two
hours.
3.4.1 The water density required for deluge systems designed for cooling or
exposure protection are listed in the Table below:
3.4.2 The water density for deluge systems protecting pumps, compressors and
devices handling flammable liquids and gases shall not be less than 20.4
(l/min)/m2. The water spray shall be directed to impinge on the protected
equipment and the surrounding area where spills may accumulate. If the
equipment is located in an enclosed equipment room, the enclosed area shall
also be protected with water spray.
3.4.3 The water density for deluge systems protecting hazards listed in Section 4.1
shall be a minimum of 24.4 (l/min)/m2. The deluge system shall be installed
primarily to prevent the formation of potentially explosive air/fuel mixture by
utilizing the water spray to disperse gas formations resulting from leaks or
spills. The distribution piping and the spray nozzles shall be arranged in a
grid system similar to that of automatic sprinkler systems.
3.5.1 Adequate means shall be installed for the effective disposal or containment of
all liquids from the hazard area during the discharge of the deluge system.
Such provisions shall include any one or a combination of the following
methods:
a) Grading
c) Trenching
d) Diking
3.5.2 When the hazard area is an enclosed space, the drainage system shall be
provided by floor drains or trench drains discharging to an underground pipe
work.
3.5.3 The drainage and/or diking requirements of fuel storage tanks shall comply
with the applicable requirements of the Flammable and combustible Liquids
code, NFPA 30.
4.1 Deluge systems are suitable for the protection of the facilities listed below:
a) Storage tanks, vessels and equipment (pumps and compressors) handling the
following materials:
3) Petrochemical products.
4.2 Reference shall be made to the following standards for guidelines in the use of
deluge systems:
5.1 General
The design of a deluge system for exposure protection purposes involves basically
the determination of the system water demand, i.e. discharge rates and duration of
protection, and the provision of a nozzle lay-out configuration to deliver complete
water spray coverage and density to the protected equipment or area.
A detailed survey of the tank and its installation shall be conducted to obtain
the following information:
Tank diameter, D
Tank shell length, L
Tank end height, h
b) Contents of Tank
πD 2
Flat End Ae =
4
(D 2 + h 2 )
Spherical End Ae = π
4
D 2
Hemi Spherical End Ae = π
2
If there are appendages to the tank which may increase the basic area
of coverage, estimate the water required to protect these appendages
using the required shell density.
Qa1 = Aa1 x d
Qa = Qa1 + Qa2……
QL = AL x dL
The total amount of water required shall be the sum of the water for
the shell, both ends, the appendages and the supports.
QTOT = Qs + Qe + Qa + QL
30 0.43
60 1.20
90 3.00
120 8.00
140 19.40
NOTE: Overspray will occur for tank diameters smaller than those
indicated above.
a) Nozzle Direction
Nozzles protecting the tank shell shall be pointed directly at the tank.
Nozzles protecting the tank end shall be pointed directly at the ends
except in the case of flat surfaces. In the case of vertical flat surfaces,
the nozzle shall be pointed down approximately 10 degrees. Nozzles
protecting supports shall be located at the point where the tank
protection will not cover the support and shall point down the length
of the support.
c) Number of Nozzles
d) Support Nozzles
For each design area divide the water required by the number of
nozzles discharging into the design area.
Qarea
Q ≡
R NumberOfNozzles
QR = k / PN
Where K, a constant, is the discharge coefficient of the selected
nozzle.
a) Tank Diameter, D
b) Top height, h
c) Shell Height, H
d) Shell Density Required, d
e) Leg density Required, dL
1. Find the height (L) and number (N) of the shell design areas.
The total shell height shall be divided into two or more areas
such that the height of the upper area is one-third the height of
the lower areas. The height of the lower areas shall not exceed
3.7 meters
c) Other considerations
The design area equals the area of the top plus the upper shell
design area.
The total water required for the top equals the design area for the top
times the required density.
Qt = At x d
For smooth tanks the design area will be the same for each ring. For
tanks with appendages or obstructions, design areas may differ. (See
Figure 4-2.)
As1 = π DL
Water required equals design area times required density for each
ring. In the case of smooth tanks, water demand will be the same for
each ring.
Qs1 = As1 x d
Qs = Qs1 + Qs2 +……
If there are appendages to the tank which may increase the basic area
of coverage, estimate this area and multiply by the required density to
obtain the additional water required. There are appendages to the tank
which may increase the basic area of coverage, estimate this area and
multiply by the required density to obtain the additional water
required.
Qa1 = Aa1 x d
Qa = Qa1 + Qa2 +……..
The water required for each leg equals the design area of the leg times
the required density.
QL1 = AL1 x dL
QL = QL1 + QL2 +……..
Total water required equals the sum of the water demand for the top,
bottom, all rings all legs, and all appendages.
QTOT = Qt + Qb + Qa + QL
The shell rings shall be located so that the water spray will
impinge at the top boundary of each shell design area. Nozzles
in each successive rings hall be staggered. The number of
nozzles required for each ring shall be determined in
accordance with Table 4-2.
Rundown will occur over the top of spherical top tank and
over the vertical shell. There will be little or no rundown over
the bottom.
For each design area divide the water required by the number of
nozzles discharging into the design area.
6.1 General
6.1.1 All equipment, devices and associated accessories of the deluge system shall
be listed for their intended applications by accredited testing organizations or
laboratories acceptable to SEC, such as the Underwriters Laboratories Inc.
(UL) and the Factory Mutual Research Corp. (FM).
6.1.2 All equipment and devices shall be designed to function properly in the
temperature range 0˚C to 55˚C and a relative humidity of 100 percent.
6.1.3 Depending on the system design, the fire alarm system operating voltage
shall be either 24V or 12V dc, All electrically operated components such as
fire detectors, remote indicators, solenoid valves, audible and visible alarm
devices, pressure switches and valve supervisory switches shall have
electrical rating compatible with the system operating voltage.
6.2.1 Construction
The valve body which may either be 90˚ pattern or straight flow pattern, shall
be of cast iron with cast bronze trim and shall be designed for a minimum
working pressure of 1207 kPa (175 psi) and hydrostatically tested to 2413
kPa (350 psi). The valve shall have standard flanged ends, 125 lb class,
conforming to ANSI B15.5, except for valve size 63 mm which shall have
threaded ends. The valve shall comply with the applicable requirements of
UL 260, Dry Pipe and Deluge Valves for Fire Protection.
The valve shall be sized in accordance with the design flow and frictional
loss criteria established by the system hydraulic calculations. The
recommended valve sizes for given flow rates are indicated in Table 6-1
below.
(NOTE: The valve size selected from Table 6-1 is preliminary and shall be
verified from the listing of the deluge valve approved for the installation).
6.3.1 Ultraviolet flame detectors listed and approved for outdoor applications shall
be used for monitoring storage tanks containing combustible liquids and
gases.
b) The control unit shall provide supervision of all fire detection circuits,
alarm and indication circuits, extinguishing release circuits and power
supplies. In addition, the control unit shall provide supervision of
ground faults and open circuits in all field wiring.
d) The control unit shall be equipped with the following control devices:
1) A "Reset" switch for resetting the control unit from the alarm
of fault condition to normal condition. The operation of the
"RESET" shall restore the system to normal supervisory
condition.
6) A "Lamp Test" switch for testing all fire, fault and function
lamp indicators. The operation of this momentary type switch
shall turn on simultaneously all LED lamp indicators.
f) The control unit shall have provisions for inter-facing with the main
fire alarm control panel and/or the remote manned central station
(SEC Power Control Center).
g) The control unit shall have nominal input power supply rating of
220V/127V, ac, single phase, 60 hertz, transformed and rectified to
24 or 12V dc.
The release and drain lines shall be fabricated of 25 mm nominal pipe size
copper tubing, type K, conforming to ASTM B88 with brazed wrought
copper fittings conforming to ANSI B16.22.
The alarm signaling system for a deluge system shall include at least tow
audible alarm circuits to indicate the "Alarm" and "Discharge" modes of the
extinguishing system. The following audible alarm devices shall be used to
indicate a distinctive signal for each level of alarm:
The audible alarm devices shall be compatible with the control and
indicating unit and shall comply with the applicable requirements of
UL 464, Audible Signal Appliances. The audible alarm devices shall
be wired in supervised class B circuits.
The deluge system shall be provided with a shut-off valve installed in the
riser upstream of the deluge valve. The valve shall be an outside screw and
yoke gate valve listed for fire protection service in accordance with UL 262.
The gate valve shall be of cast iron body with bronze trim and shall be
designed for a working pressure of 1207 kPa (175 psi).
6.5.1 Construction
The spray nozzles shall be of the open type directional discharge nozzles
fabricated of corrosion resistant materials such as cast brass or aluminum.
Spray nozzles with interchangeable inserts to vary the spray angle shall be
employed for flexibility in the nozzle arrangement. The spray nozzle shall
have standard 20 mm NPT threaded connection. The nozzle orifice size shall
not be less than 6.35 mm.
The nozzle body shall be clearly marked with the model number and the size
of the inlet connection. The nozzle insert shall be marked with the spray
angle, k-factor and the model number. Nozzle inserts with more than one
model number may be used interchangeably with either type of nozzles
indicated.
The listed performance charts or tables of the proposed nozzle type shall be
consulted to evaluate the nozzle discharge characteristics (discharge rate,
distance of throw, spray pattern, operating pressures) and determine its
suitability for an intended deluge system application.
6.6 Piping
6.6.1 Materials
b) For nominal pipe sizes 90 mm and smaller the pipe fittings shall be
galvanized malleable iron threaded fittings, class 150, and
conforming to specification ANSI.3. For nominal pipe sizes 110 mm
and larger, pipe fittings shall be standard weight welding fittings
conforming to ANSI B16.9.
e) Flanges shall be forged steel, ASTM 105, flat face, class 150 lb and
conforming to ANSI.
6.6.2 Welding
Field welding shall comply with the applicable requirements of NFPA 51B,
Welding and Cutting Processes.
b) All pipe hanger equipment and accessories shall comply with the
requirements of UL 203, Pipe Hanger Equipment for Fire Protection
Service.
Table 6 – 2
6.6.4 Painting
All pipe work excluding valves shall be painted as per TES-H-107.01 and
color coded as per TES-H-107.02.
7.1 All electrical equipment wiring associated with the fire detection and alarm system
shall be listed and approved by SEC.
7.2 The electrical installation of the fire alarm system shall comply with the applicable
requirements of Article 760 of the National Electrical Code, NFPA 70.
7.3 All fire detector circuits, extinguishing release circuits and audible appliance circuits
shall use mineral insulated copper-sheath cables (MICC).
The deluge piping shall be subjected to a field hydrostatic test pressure of 1379 kPa
(200 psi) for at least 2 hours.
The functional tests of the fire detection and alarm equipment shall be conducted as
per TES-B-106.01. The functional tests shall include the following:
A full flow discharge test with water shall be conducted to check operational
reliability of the system, including the speed of response of the system and the
effectivity of the water spray coverage.
9.0 REFERENCES
T I T L E PUBLICATION