SCP 125-320 / JU4H-UF54 / 108 - UL+FM

DIESEL DRIVEN FIRE PUMP SET

SUBMITTAL
JOB REPRESENTATIVE

ORDER NO. DATE


ENGINEER SUBMITTED BY DATE
CONTRACTOR APPROVED BY DATE

PUMP DESIGN DATA DIESEL ENGINE DESIGN DATA


NO. OF PUMPS: 1 ENGINE MAKE BY: CLARKE-UK
TAG: ENGINE MODEL: JU4H-UF54 108 kW @ 3000 RPM
CAPACITY: 1000 GPM 227 m³/h VOLTS: 220 HERTZ: 50 PHASE: 1
HEAD: 100 mWC FUEL TANK 1000 LITERS
LIQUID: WATER CONTROL PANEL DATA
TEMPERATURE: 90 ºC CONTROLLER MAKE BY TORNATECH
CONTROLLER MODEL GPD

MATERIALS OF CONSTRUCTION CERTIFICATION


CASING GG40 DUCTILE IRON UL LISTED FM APPROVED
IMPELLER GCuSn10-BRONZE
SHAFT AISI420 ST STEEL DIMENSIONS (mm)
WEAR RINGS RG 5 DNs DNd W L H
BEARINGS BALL BEARING 8" 5" - - -
SEALING SOFT GLAND PACK * Dimensions are approximated.
SCP 125-320 / JU4H-UF54 / 108 - UL+FM
Capacity 227,00 m³/h Impeller diameter 269 mm
Head 100,00 mWC Efficiency 63,7 %
Density 1,00 g/cm³ Power required 97,6 kW
Shut-off head 103,10 mWC Motor power 108 kW
NPSH required 3,15 mWC Speed 3000 rpm

100% 150%

269
0120324040 56789

96 
856 

-./012.34453676829:;<=>?@A6=<;26B>CBDE6DBA<:
8@D2
8FGHIJKLMNO6=JIF6BLPQRE6DQOJH68NRF
STTUVTWTXYZU[W\]X^Y_`]WU\]XUaTW_X`\bcYZUdX̀TUeb^fghUSfZ̀_UaYgT
ijkllmnopkqmlirstuouvkiw xyz{{|z
S}xVx~[U€U‚ƒh
{„ƒzU…†‡ˆ‰ˆŠ†…hU‰‹Vˆ‡Œ
nŽm‘’“”m“•–—m“˜™–

š™˜›mt˜m ¢™¦m§£Ž¨•–m
š™˜›mr™™œ˜m ¤Ž““‘Žmš™•–m ¥Ž£¦mw›m ¤Ž““‘Žm
ž–’Ÿ w mž•¡Ÿ ¢£›—mq“– ž“Ÿ žŽ’Ÿ ž“Ÿ
©|‚ {ª© SaeU‚‚«©‚‚ zz¬­‚© z®‚‚ ©‚‚
|‚‚ {ª© SaeU‚‚«©‚‚ z®¬­‚‚ z®‚‚ ©‚‚
|‚‚ ©ª{ SaeU‚‚«z|‚ z¬{„ ­‚‚‚ z­z
„|‚ ©ª{ SaeU‚‚«z|‚ ‚{¬{„ ­‚‚‚ z­z
„|‚ {ª© SaeU‚‚«©‚‚ ®®¬zƒ‚ z®‚‚ ©‚‚
‚‚‚ ©ª{ SaeU‚‚«z|‚ ®ƒ¬{z ­‚‚‚ z­z
‚‚‚ |ªƒ SaeUz|«­‚‚ ‚¬®‚ ­‚‚‚ z®‚
‚‚‚ ƒª| SaeUz|«­z‚ ‚¬„„ z®‚‚ z­z
‚‚‚ ƒª| SaeUz|«­®‚ „ƒ¬zƒƒ z®‚‚ ­©ƒ
z|‚ |ªƒ SaeUz|«­‚‚ ‚„¬ƒ® ­‚‚‚ z®‚
z|‚ ƒª| SaeUz|«­z‚ ®„¬„| z®‚‚ z­z
z|‚ ƒª| SaeUz|«­®‚ {|¬z„ƒ z®‚‚ ­©ƒ
|‚‚ |ªƒ SaeUz|«­‚‚ ‚¬ƒ| ­‚‚‚ z®‚
|‚‚ ƒª{ SaeU|‚«­‚‚ ®ƒ¬|| z®‚‚ z­z
|‚‚ ƒª{ SaeU|‚«­|| |‚¬z©z z®‚‚ ­z‚
z‚‚‚ {y‚ Sae©U|‚«{­‚ z©¬zzz |‚‚ z©{
z‚‚‚ ƒª{ SaeU|‚«­‚‚ ®©¬©® z®‚‚ z­z
z‚‚‚ ƒª{ SaeU|‚«­|| ­ƒ¬z­© z®‚‚ ­z‚
z‚‚‚ ‚ª{ Sae©U|‚«{­‚Ud ®|¬z­ |‚‚ z®‚
z|‚‚ ‚ª{ Sae©U|‚«{­‚Ud ƒƒ¬z |‚‚ z®‚
!""#2$%2&"%'"($%)%*3+4,,0 3"4
0120324040 56789

96 
856 
-... /.01 23456/7.81-.69 /:;<;/- /7.. ;=.
>?@A6BCD?AED6FG6;.;.<./<.:

HIE6?CCE?J?GKE6FL6?6KFMC?GNO@6G?ME6FJ6CJFDPKA6QG6AIQ@6D?A?R?@E6DFE@6GFA6QG6QA@ESL6?@@PJE6AI?A6CJFDPKA@6@F6QDEGAQLQED6I?TE6REEG
M?GPL?KAPJED6PGDEJ6B>O@69FSSFU<BC62EJTQKEV6WGSN6AIF@E6CJFDPKA@6RE?JQGX6AIE6B>6Y?JZ6@IFPSD6RE6KFG@QDEJED6AF6RE63EJAQLQED6?GD6KFTEJED
PGDEJ6B>O@69FSSFU<BC62EJTQKEV6[SU?N@6SFFZ6LFJ6AIE6Y?JZ6FG6AIE6CJFDPKAV
B>6CEJMQA@6AIE6JECJFDPKAQFG6FL6AIE6M?AEJQ?S6KFGA?QGED6QG6AIE6WGSQGE63EJAQLQK?AQFG6\QJEKAFJN6@PR]EKA6AF6AIE6LFSSFUQGX6KFGDQAQFG@^6/V6HIE6_PQDE
G̀LFJM?AQFGa6[@@EMRSQE@a63FG@AJPKAQFG@a6\E@QXG@a62N@AEM@a6?GD8FJ63EJAQLQK?AQFG@6bLQSE@c6MP@A6RE6CJE@EGAED6QG6AIEQJ6EGAQJEAN6?GD6QG6?6GFG<
MQ@SE?DQGX6M?GGEJa6UQAIFPA6?GN6M?GQCPS?AQFG6FL6AIE6D?A?6bFJ6DJ?UQGX@cV6;V6HIE6@A?AEMEGA6deECJQGAED6LJFM6AIE6WGSQGE63EJAQLQK?AQFG@6\QJEKAFJN
UQAI6CEJMQ@@QFG6LJFM6B>d6MP@A6?CCE?J6?D]?KEGA6AF6AIE6E0AJ?KAED6M?AEJQ?SV6̀G6?DDQAQFGa6AIE6JECJQGAED6M?AEJQ?S6MP@A6QGKSPDE6?6KFCNJQXIA6GFAQKE
QG6AIE6LFSSFUQGX6LFJM?A^6df6;.;.6B>6>>3d

!""#2$%2&"%'"($%)%*3+4,,0 4"4
EBITT - UL+FM

Approved Fire
Pump Sets

Construction Diesel Engines


The fire pump sets are being mounted and aligned with electric motor, Ebitt fire pumps are being directly connected through flexible coupling to
and/or diesel engine on a common base plate. The fire pump package the diesel engines manufactured by Clarke. All our approved fire pumps are
includes all pump fittings such as manometers, casing relief valve, and having UL Listed, FM Approved diesel engines with granted and guaranteed
automatic air release valve (for split-case models) to be supplied with continuous power ratings. The diesel engines conform to the requirements
approved electric and/or diesel fire pump controller. of NFPA 20 and specifically approved for fire pump application and service.
Diesel engines operate at a rated speed not exceeding the above RPM and
Our fire pump sets are being delivered as a package to be operated as for develop sufficient horsepower to drive the pump with reserve power.
Plug&Run type.
Internal Cooling System loop is included in our engine sets. The cooling
Pumps water supply for the heat exchanger is from the discharge of the pump,
taken off prior to the pump discharge valve. The pipe connection
Ebitt UL approved fire pumps are ideally developed and produced either includes four manual shut-off valves (including by-pass line), two
for small flows or high flows through well-designed compact packages. strainers, two pressure regulators, an approved and listed automatic
Ebitt-N series-End-Suction Fire pumps have back pull out design for solenoid valve, and a pressure gauge, piping and fittings are all fitted to
easy maintenance, self-venting center line discharge, and low NPSH the diesel engine as per NFPA 20 by Ebitt.
requirements. The pump construction is ductile iron body, bronze fitted
with packing. The shaft and sleeves are in AISI316 Stainless steel and be One set of double heavy duty lead acid batteries are being supplied
supported by thrust ball bearings, and radial roller bearing. by Ebitt mounted on the common baseplate of our engine-pump set
complete with battery cables.
Ebitt-SCP series-Double Suction, split-casing pumps are in-line designed,
space saving, easy maintenance horizontal type. Our split-case pumps are The fuel tank is produced and supplied by Ebitt according to NFPA 20
heavy-duty designed with replaceable wear rings and sleeves. Bearings recommendations complete with fill pipe, cap and level gauge to be
are mounted and can be replaced without opening pump case. Each delivered separately from pump-set with legs for floor mounting.
stuffing box is fitted with bronze gland and with a stuffing box extension
to facilitate the packaging rings removal. The pump construction is Minimum Fittings
ductile iron body, bronze fitted with packaging. The shaft and sleeves are
in AISI316 stainless steel and be supported by heavy-duty ball bearings All Ebitt fire pumps are being supplied with suction and discharge
and roller bearing. gauges, air release valve mounted on pumps. Our electric driven pump
sets are also having casing relief valves mounted on our pumps.
Electric Motor
Testing
Ebitt UL approved fire pump sets always have Totally Enclosed Fan Cooled
(TEFC) type of electric motors. Our motors in our sets have UL Listings, Ebitt fire pumps are being hydrostatically tested to a pressure recommended
IP55 protection class, and F insulation class. The voltages are in 50 Hz, 380 by UL. The fire pump is subjected to a performance test at a rated speed. Our
Volts and/or 415 Volts with Wye-Delta Starting type as in standard. pumps furnish not less than 150% of rated capacity at a pressure not less
than 65% of rated head. The shut-off head is not exceeding 140% of rated
head. Ebitt certified test curve is being supplied with the pump.

1097
Approved Fire Pump Sets

DOL Starting Fire Wye-Delta Starting Fire Pump Controller


Pump Controller Fire Pump Controller with ATS Integrated

Electric Fire Pump Controller


Ebitt fire pump set includes fire pump controller on its own base plate The controller displays last messages screen that will display up to 10.000
complete with wiring cables to the electric motor. All settings are being alarms/messages stored in the memory.
made in Ebitt factory as ready for use.
The controller has green status LED’s for power on, pump running,
Electric Fire Pump controller meets the requirements of the latest edition of local start, remote start, emergency start, deluge valve, interlock status,
NFPA 20 and is UL Listed, FM Approved. low pressure etc. And the controller has also red alarm LED’s for phase
reversal, phase failure, fail to start, undervoltage, overvoltage, low room
Ebitt electric fire pump controller has Wye-Delta Starting method as temperature, lock rotor trip, low suction pressure, etc.
standard and optional for other type of starting methods. Our controller
has a withstand ratings of 100.000 RMS symmetrical amperes, 380V, 415V, The microprocessor logic board is available with USB port for transference
etc. of message history, controller status, diagnostics, and statistics.
The controller includes a motor rated combination isolating switch and A solid-state 4-20 mA pressure sensor is included.
circuit breaker, mechanically interlocked and operated with a single
externally mounted handle. All relays are equipped with the plug-in type and all relay contacts
provided for phase reversal, phase failure, common alarm, pump run,
The isolating switch is rated to disconnect the motor load. and the common alarm and phase relays are energized under normal
The isolating switch/circuit breaker combination is mechanically conditions.
interlocked such that the enclosure door cannot be opened when
the handle is in the ON position except by a tool operated defeater An audible alarm buzzer, capable of being heard while the motor is
mechanism. operating, shall operate if fail to start. Hardware malfunction or any
common alarm condition exists.
The controller is complete with a 4 line by 40 character LCD display
mounted on a panel opening in the front door. The LCD display includes
system pressure, voltage and amperage readings, frequency, date, time,
set point, start/stop points, weekly test time and controller statistics screen
which includes run time, start/stop numbers, system voltage, frequency
and pressure recordings, etc.

1098
Approved Fire Pump Sets

Diesel Fire Pump


Controller

Diesel Fire Pump Controller


EBITT fire pumps set includes diesel fire pump controller on its own c) One NO/NC contact when the main switch is in the MANUAL or OFF
base plate complete with wiring cables to batteries and diesel engine position.
instrument panel. All settings are being made in EBITT factory as Ready for d) One SPTD contact indicating engine trouble. The engine trouble
use. condition is indicated on engine over speed, engine failure to start, low
Engine controller meets the requirements of the latest edition of NFPA 20 oil pressure, and high coolant temperature conditions.
and is UL listed, FM Approved.
A solid-state 4-20 mA pressure sensor is included.
The diesel engine controller incorporates the following components: A seven-day pressure recorder is provided.
Two independently functional battery charges, each having its own
power transformer rated for a maximum continuous charge current of A central annunciator and operator control panel is provided inside the
10 amperes. The charger has solid state electronic design with a semi- controller but visible and accessible through a breakable glass panel on the
conductor type rectifier and includes the following supervisory and safety enclosure door. This control panel incorporates all alarm and status pilot
features. light indicators, voltmeters and ammeters for battery charges and the four
positions main switch manual start push buttons, and combination Lamp
a) Current limiting in every charging mode test / Charger reset push button and the operational NORMAL/SILENCE
b) Over-current shut-off selector switch for pump room alarms.
c) Automatic selection of bulk or float charge by battery voltage sensing
d) Lower than 0,5 ampere trickle charge
e) Reverse voltage shut-off
f ) Dead cell detection
g) Over and under voltage alarm
h) Charger initiated battery failure alarm with signaling to prevent the use
of the defective battery during the engine starting cycle.

All relays are equipped with manual test buttons and ON-OFF status
indicators and terminal block to indicate the following engine conditions;

a) Two SPDT contacts for engine running condition.


b) One NO/NC contact when the main switch is in the AUTO position.

1099
® MODELS
JU4H-UF10 JU4H-UF20 JU4H-UF34 JU4H-UF40
JU4H-UF12 JU4H-UF22 JU4H-UFH0 JU4H-UF42 JU4H-UF52
FIRE PUMP ENGINES JU4H-UF14 JU4H-UF24 JU4H-UFH2 JU4H-UF50 JU4H-UF54

UK Purchased
FM-UL-cUL APPROVED RATINGS KW/BHP
JU4H RATED SPEED
MODEL 1470 1760 2100 2350 2600 2800 3000
UF10 31 41 38 51 41 55
UF12 41 55 44 59
UF14 52 70 53 71
UF20 45 60 50 67 54 72
UF22 54 72 56 75
UF24 60 80 62 83
UF34 78 104 86 115
UFH0 54 73 66 88 73 98
UFH2 73 98 74 99
UF40 70 94 78 105 79 106
UF42 79 106 79 106
UF50 59 79 82 110 97 130 95 127
UF52 95 127 95 127
UF54 108 145 108 145

SPECIFICATIONS
JU4H MODELS
ITEM
UF10/12/14 UF20/22/24 UF34 UFH0/H2 UF40/42 UF50/52/54
Number of Cylinders 4
Aspiration NA T
Rotation* CW
Weight – kg (lb) 413 (910) 424 (935)
Compression Ratio 17.6:1 17.0:1
Displacement – l (cu. in.) 4.5 (275)
Engine Type 4 Stroke Cycle – Inline Construction
Bore & Stroke – mm ( in.) 106 x 127 (4.19 x 5.00)
Installation Drawing D545
Wiring Diagram AC C07591
Wiring Diagram DC C07575
Engine Series John Deere 4045 Series

Abbreviations: CW – Clockwise NA – Naturally Aspirated T – Turbocharged


*Rotation viewed from Heat Exchanger / Front of engine
CERTIFIED POWER RATING ENGINE RATINGS BASELINES
• Each engine is factory tested to verify power and performance. • Engines are to be used for stationary emergency standby fire pump service only. Engines
are to be tested in accordance with NFPA 25.
• Although FM-UL ratings are shown at specific speeds, Clarke engines can be
applied at any intermediate speed. To determine the intermediate speed power; • Engines are rated at standard SAE conditions of 29.61 in. (752.1 mm) Hg barometer and
make a linear interpolation from the Clarke FM-UL
FM UL power curve.
curve Contact Clarke or 77°F
77 F (25
(25°C)
C) inlet air temperature [approximates 300 ftft. (91
(91.44 m) above sea level] by the
your Pump OEM Representative to obtain details. testing laboratory (see SAE Standard J 1349).
• A deduction of 3 percent from engine horsepower rating at standard SAE conditions shall
be made for diesel engines for each 1000 ft. (305 m) altitude above 300 ft. (91.4 m)
• A deduction of 1 percent from engine horsepower rating as corrected to standard SAE
FM conditions shall be made for diesel engines for every 10°F (5.6°C) above 77°F (25°C)
ambient temperature.

Page 1 of 11
® MODELS
JU4H-UF10 JU4H-UF20 JU4H-UF34 JU4H-UF40
JU4H-UF12 JU4H-UF22 JU4H-UFH0 JU4H-UF42 JU4H-UF52
FIRE PUMP ENGINES JU4H-UF14 JU4H-UF24 JU4H-UFH2 JU4H-UF50 JU4H-UF54

ENGINE EQUIPMENT
EQUIPMENT STANDARD OPTIONAL
Air Cleaner Direct Mounted, Washable, Indoor Service with Drip Shield Disposable, Drip Proof, Indoor Service Outdoor Type
Alternator 12V-DC, 42 Amps; with Poly-Vee Belt and Guard 24V-DC, 40 Amps; with Belt Guard
Exhaust Protection Blankets on Naturally Aspirated Models, Metal Guards on Manifolds
and Turbocharger on Turbocharged Models
Coupling Bare Flywheel Listed Driveshaft and Guard, UF10/12/14, UF20/22/24 – CDS10-
SC; UFH0/H2, UF40/42 – CDS20-SC; UF50/52/54 – CDS30-S1
Exhaust Flex Connection For NA Engines - Stainless Steel, Clamped, 3” Stainless Steel Flex, Clamped, 4” & 5”
For T Engines – Stainless Steel, Clamped, 4”
Flywheel Housing SAE #3
Flywheel Power Take Off 11.5” SAE Industrial Flywheel Connection
Fuel Connections Fire Resistant, Flexible, USA Coast Guard Approved, Supply and
Return Lines
Fuel Filter Primary Filter with Priming Pump
Fuel Injection System Stanadyne Direct Injection
Engine Heater 230V-AC, 1000 Watt 115V-AC, 1000 Watt
Governor, Speed Constant Speed, Mechanical
Heat Exchanger Tube and Shell Type, 4 BAR (60 PSI), BSP(F) Connections
Instrument Panel English and Metric, Tachometer, Hourmeter, Water Temperature,
Oil Pressure and Two (2) Voltmeters
Junction Box Integral with Instrument Panel; For DC Wiring Interconnection to
Engine Controller
Lube Oil Cooler Engine Water Cooled, Plate Type
Lube Oil Filter Full Flow with By-Pass Valve
Lube Oil Pump Gear Driven,
Driven Gear Type
Manual Start Control On Instrument Panel with Control Position Warning Light
Overspeed Control Electronic with Reset and Test on Instrument Panel
Raw Water Solenoid Operation Automatic from Fire Pump Controller and from Engine Instrument
Panel
Run – Stop Control On Instrument Panel with Control Position Warning Light
Run Solenoid 12V-DC Energized to Run 12V-DC Energized to Stop; 24V-DC Energized to Run; 24V-DC
Energized to Stop
Starters Two ((2)) 12V-DC Two ((2)) 24V-DC
Throttle Control Adjustable Speed Control, Tamper Proof
Water Pump Centrifugal Type, Poly-Vee Belt Driven

Abbreviations: DC –Direct Current, AC – Alternating Current, SAE – Society of Automotive Engineers, NA – Naturally Aspirated, T- Turbocharged, BSP(F) – British
Standard Pipe Thread (Female)

UK, Ltd. Fire Protection Products, Inc.


Grange Works, Lomond Rd., Coatbridge, ML5-2NN 3133 E. Kemper Rd., Cincinnati, Ohio 45241
United Kingdom United States of America
Tel +44-1236-429946 Fax +44-1236-427274 Tel +1-513-475-FIRE (3473) Fax +1-513-771-0726
www.clarkefire.com www.clarkefire.com

C133432 revJ Specifications and information contained in this brochure subject to change without notice.
12NOV14 Page 2 of 11
FIRE PUMP MODEL: JU4H-UF54
Heat Exchanger Cooled
Turbocharged
4.5L 4 Cylinder
115

110

108 108

105
104

100

95

91

90

85
1750 2000 2250 2500 2750 3000 3250
ENGINE SPEED - RPM
RESTRICTED:
USE ONLY FOR STAND-BY FIRE PUMP APPLICATIONS

ENGINE PERFORMANCE:
STANDARD CONDITIONS: (SAE J1349, ISO 3046)
77°F (25°C) AIR INLET TEMPERATURE NAMEPLATE kW (MAXIMUM PUMP LOAD)
29.61 IN. (751.1MM) HG BAROMETRIC PRESSURE
#2 DIESEL FUEL (SEE C13940)
THIS DRAWING AND THE IN- CREATED DATE CREATED
FORMATION HEREIN ARE OUR 05/19/04
PROPERTY AND MAY BE USED BY
OTHER ONLY AS AUTHORIZED BY
US. UNPUBLISHED -- ALL RIGHTS
ENGINE MODEL JU4H-UF54
RESERVED UNDER THE DRAWING NO. REV
KEN WAULIGMAN 27OCT06 COPYRIGHT LAWS. C131946 A

Page 3 of 11
JU4H-UF54
INSTALLATION & OPERATION DATA (I&O Data)
UK Produced
Basic Engine Description
Engine Manufacturer John Deere Co.
Ignition Type Compression (Diesel)
Number of Cylinders 4
Bore and Stroke - mm (in) 106 (4.19) X 127 (5)
Displacement - L (in³) 4.5 (275)
Compression Ratio 17.0:1
Valves per cylinder
Intake 1
Exhaust 1
Combustion System Direct Injection
Engine Type In-Line, 4 Stroke Cycle
Fuel Management Control Mechanical, Rotary Pump
Firing Order (CW Rotation) 1-3-4-2
Aspiration Turbocharged
Charge Air Cooling Type None
Rotation, viewed from front of engine, Clockwise (CW) Standard
Engine Crankcase Vent System Open
Installation Drawing D545
Weight - kg (lb) 424 (935)

Power Rating 2350 2600 2800 3000


Nameplate Power - kW (HP) 91 (122) 104 (139) 108 (145) 108 (145)

Cooling System - [C051001] 2350 2600 2800 3000


Engine Coolant Heat - kW (Btu/sec) 60.1 (57) 72.8 (69) 84.4 (80) 86.5 (82)
Engine Radiated Heat - kW (Btu/sec) 29.1 (27.6) 33.3 (31.6) 34.6 (32.8) 34.6 (32.8)
Heat Exchanger Minimum Flow
15°C (60°F) Raw H 20 - L/min (gal/min) 26.5 (7) 26.5 (7) 30.3 (8) 34.1 (9)
35°C (95°F) Raw H 20 - L/min (gal/min) 30.3 (8) 41.6 (11) 45.4 (12) 49.2 (13)
Heat Exchanger Maximum Cooling Raw Water
Inlet Pressure - bar (psi) 4.1 (60)
Flow - L/min (gal/min) 98.4 (26)
Typical Engine H20 Operating Temp - °C (°F)[1] 76.7 (170) - 87.8 (190)
Thermostat
Start to Open - °C (°F) 76.7 (170)
Fully Opened - °C (°F) 87.8 (190)
Engine Coolant Capacity - L (qt) 14 (14.8)
Coolant Pressure Cap - kPa (lb/in²) 68.9 (10)
Maximum Engine Coolant Temperature - °C (°F) 93.3 (200)
Minimum Engine Coolant Temperature - °C (°F) 71.1 (160)
High Coolant Temp Alarm Switch - °C (°F) 96.1 (205)

Electric System - DC Standard Optional


System Voltage (Nominal) 12 24
Battery Capacity for Ambients Above 0°C (32°F)
Voltage (Nominal) 12 [C07633] 24 [C07633]
Qty. Per Battery Bank 1 2
SAE size per J537 8D 8D
CCA @ -18°C (0°F) 1400 1400
Reserve Capacity - Minutes 430 430
Battery Cable Circuit, Max Resistance - ohm 0.0012 0.0012
Battery Cable Minimum Size
0-3.1m Circuit Length [2] 00 00
3.1m-4.1m Circuit Length [2] 000 000
4.1m-5.1m Circuit Length [2] 0000 0000
Charging Alternator Maximum Output - Amp, 40 [C071363] 55 [C071366]
Starter Cranking Amps, Rolling - @15°C (60°F) 225 [C07888/C07889] 250 [C07819/C07820]

NOTE: This engine is intended for indoor installation or in a weatherproof enclosure. 1Engine H 2O temperature is
dependent on raw water temperature and flow. 2Positive and Negative Cables Combined Length.
Page 1 of 2

Page 4 of 11
JU4H-UF54
INSTALLATION & OPERATION DATA (I&O Data)
UK Produced
Exhaust System 2350 2600 2800 3000
Exhaust Flow - m³/min (ft.³/min) 21.7 (768) 26.4 (934) 30 (1061) 33.8 (1193)
Exhaust Temperature - °C (°F) 609 (1129) 611 (1132) 607 (1124) 592 (1098)
Maximum Allowable Back Pressure - kPa (in H 20) 7.5 (30) 7.5 (30) 7.5 (30) 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in) [3] 102 (4) 102 (4) 102 (4) 102 (4)

Fuel System 2350 2600 2800 3000


Fuel Consumption - L/hr (gal/hr) 27.3 (7.2) 39 (10.3) 37.8 (10) 43.1 (11.4)
Fuel Return - L/hr (gal/hr) 34.1 (9) 36 (9.5) 37.5 (9.9) 39 (10.3)
Fuel Supply - L/hr (gal/hr) 61.3 (16.2) 74.9 (19.8) 75.3 (19.9) 82.1 (21.7)
Fuel Pressure - kPa (lb/in²) 20.7 (3) - 41.4 (6)
Minimum Line Size - Supply - in. .50 Schedule 40 Steel Pipe
Pipe Outer Diameter - mm (in) 21.5 (0.848)
Minimum Line Size - Return - in. .375 Schedule 40 Steel Pipe
Pipe Outer Diameter - mm (in) 17.1 (0.675)
Maximum Allowable Fuel Pump Suction Lift
with clean Filter - mH 20 (in H20) 0.8 (31)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - m (ft) 1.4 (4.5)
Fuel Filter Micron Size 2

Heater System Standard Optional


Engine Coolant Heater
Wattage (Nominal) 1000 1000
Voltage - AC, 1 Phase 230 (+5%, -10%) 115 (+5%, -10%)
Part Number [C122192] [C122188]

Air System 2350 2600 2800 3000


Combustion Air Flow - m³/min (ft.³/min) 7.3 (259) 8.9 (315) 10.3 (362) 11.7 (413)
Air Cleaner Standard Optional
Part Number [C03249] [C03327]
Type Indoor Service Only, Canister,
with Shield Single-Stage
Cleaning method Washable Disposable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - kPa (in H20) 2.5 (10) 2.5 (10)
Clean Air Cleaner - kPa (in H 20) 1.2 (5) 1.2 (5)
Maximum Allowable Temperature (Air To Engine Inlet) - °C (°F)[4] 54.4 (130)

Lubrication System
Oil Pressure - normal - kPa (lb/in²) 345 (50) - 655 (95)
Low Oil Pressure Alarm Switch - kPa (lb/in²) 138 (20)
In Pan Oil Temperature - °C (°F) 104 (220) - 118 (245)
Total Oil Capacity with Filter - L (qt) 14.7 (15.5)

Lube Oil Heater Optional Optional


Wattage (Nominal) 150 150
Voltage 240V (+5%, -10%) 120V (+5%, -10%)
Part Number C04431 C04430

Performance 2350 2600 2800 3000


BMEP - kPa (lb/in²) 1030 (150) 1060 (154) 1030 (149) 958 (139)
Piston Speed - m/min (ft/min) 597 (1958) 661 (2167) 711 (2333) 762 (2500)
Mechanical Noise - dB(A) @ 1m C131535
Power Curve C131946
3Based on Nominal System. Back pressure flow analysis must be done to assure maximum allowable back pressure is not exceeded. (Note:
minimum exhaust Pipe diameter is based on: 15 feet of pipe, one 90° elbow, and a silencer pressure drop no greater than one half of the maximum
allowable back pressure.) 4Review for horsepower derate if ambient air entering engine exceeds 77°F (25°C). [ ] indicates component reference part
number.

Page 2 of 2
C131271 Rev H
DP 15JAN14

Page 5 of 11
CLARKE
Fire Protection Products

JU4H, JU4R & JU6H, JU6R ENGINE MODELS


ENGINE MATERIALS AND CONSTRUCTION
Air Cleaner Fuel Pump
Type…………..………….. .. Indoor Usage Only Type…………………………Diaphragm
Oiled Fabric Pleats Drive…………………………Cam Lobe
Material……..…..…….………Surgical Cotton
Aluminum Mesh
Heat Exchanger (USA) - JU4H & JU6H Only
Air Cleaner - Optional Type…………………………Tube & Shell
Type…………………………. Canister Materials
Material……………………… Pleated Paper Tube & Headers……………Copper
Housing………………..……… Enclosed Shell…………………………Copper
Electrode……………………Zinc
Camshaft
Material………….………….. Cast Iron
Chill Hardened Heat Exchanger (UK) - JU4H & JU6H Only
Location…………...….…….. In Block Type…………………………Tube & Bundle
Drive……………….………..…Gear, Spur Materials
Type of Cam…………..….... Ground Tube & Headers……………Copper
Shell………..……………. Aluminum
Charge Air Cooler (JU6H-60,62,68,74,84, ADK0,
AD58, ADNG, ADN0, ADQ0, ADR0, AAQ8, AARG,
ADP8, ADP0, ADT0, AD88, ADR8, AD98, ADS0,
ADW8, ADX8, AD98 only) Injection Pump
Type……….. ..…………….Raw Water Cooled Type……………………….. Rotary
Materials (in contact with raw water) Drive…………………………Gear
Tubes……… ……………………90/10 CU/NI
Headers ……………………36500 Muntz Lubrication Cooler
Covers ……………………83600 Red Brass Type…………………………Plate
Plumbing ……………………316 Stainless Steel/ Brass
90/10 Silicone Lubrication Pump
Type…………………………Gear
Charge Air Cooler (JU6R-AA67, 59, 61, PF, Q7, RF, Drive…………………………Gear
S9, 83 only)
Type…...……………………Air to Air Cooled Main Bearings
Materials Type…………………………Precision Half Shells
Core…………………………Aluminum Material………………………Steel Backed-Aluminum Lined

Coolant Pump Piston


Type……….………………… Centrifugal Type and Material…………Aluminum Alloy with Reinforced
Drive……………………………Poly Vee Belt Top Ring Groove
Cooling………………………Oil Jet Spray
Coolant Thermostat
Type…………………………… Non Blocking Piston Pin
Qty…………………………… 1 Type…………………………Full Floating - Offset

Connecting Rod Piston Rings


Type…………………………… I-Beam Taper Number/Piston………………
3
Material……………………… Forged Steel Alloy Top………………………… Keystone Barrel Faced -
Plasma Coated
Crank Pin Bearings Second………………………Tapered Cast Iron
Type…………………………… Precision Half Shell Third…………………………Double Rail Type
Number……………………… 1 Pair Per Cylinder w/Expander Spring
Material……………………… Wear-Guard
Radiator - JU4R & JU6R Only
Crankshaft Type……………………… Plate Fin
Material……………………… Forged Steel Materials
Dynamic
Type of Balance……………… Core……………………… Copper & Brass
Tank & Structure……….. Steel
Cylinder Block
Type…………………………… One Piece with Valves
Non-Siamese Cylinders Type…….. …………………Poppet
Material……………………… Annealed Gray Iron Arrangement………… ……Overhead Valve
Number/Cylinder……………1 intake
Cylinder Head 1 exhaust
Type…….. ……………………Slab 2 Valve Operating Mechanism…… Mechanical Rocker Arm
Material……………………. Annealed Gray Iron Type of Lifter…………….. Large Head
Valve Seat Insert……………Replaceable
Cylinder Liners
Type…….. ……………………Centrifugal Cast, Wet Liner
Material………………..….… Alloy Iron Plateau, Honed

C13615 09OCT12 DSP


Page 6 of 11
Page 7 of 11
Page 8 of 11
JU4H-UF54
Stationary Fire Pump Engine Driver
EMISSION DATA
EPA 40 CFR Part 60

4 Cylinders
Four Cycle
Lean Burn
Turbocharged

500 PPM SULFUR #2 DIESEL FUEL


FUEL GRAMS / HP/ HR EXHAUST
RPM BHP (3) GAL/HR (4) CFM
NMHC NOx CO PM °F (°C)
(L/HR) (m3/min)
2800 145 10.6 (40.1) 0.20 3.48 0.70 0.11 1124 (607) 1061 (30.0)
3000 145 11.4 (43.2) 0.21 3.57 0.85 0.13 1098 (592) 1193 (33.8)

Notes:
1) 4045TF252 Base Engine Model manufactured by John Deere Corporation.
For John Deere Emissions Conformance to EPA 40 CFR Part 60 see Page 2 of 2.
2) The Emission Warranty for this engine is provided directly to the owner
by John Deere Corporation. A copy of the John Deere Emission Warranty can
be found in the Clarke Operation and Maintenance Manual.
3) Engines are rated at standard conditions of 29.61in. (7521 mm) Hg barometer
and 77°F (25° C) inlet air temperature. (SAE J1349)
4) PM is a measure of total particulate matter, including PM 10 .

CLARKE
FIRE PROTECTION PRODUCTS
3133 EAST KEMPER ROAD
C131870 REV.D CINCINNATI, OH 45241
01NOV 07 KRW PAGE 1 OF 2

Page 9 of 11
John Deere Power Systems
3801 W. Ridgeway Ave., PO Box 5100
Waterloo, Iowa USA 50704-5100

31 October 2007

Subject: Fire Pump Ratings – Conformance to EPA 40 CFR Part 60 (NSPS requirements)

All John Deere stationary fire pump engines conform to the requirements of 40 CFR Part 60. All such
engines include an emission label, stating the engine conforms to the requirements of 40 CFR Part 60. An
example of the emission label is show below:

This label applies to all of the following engine models, sold to Clarke Fire Protection, for use in stationary
fire pump applications:

All engines conforming to 40 CFR Part 60 (identified by emission label, as shown above) are covered under
the emissions warranty of 40 CFR Part 89.

Sincerely,

Kyle J. Tingle
Regional Sales Manager, JDPS
Page 2 of 2

Page 10 of 11
CLARKE
www.clarkefire.com Fire Protection Products

JU4H-UF54
FIRE PUMP DRIVER

NOISE DATA

Mechanical Engine Noise *


Octave Band
RPM BHP OVERALL 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz 16k Hz
dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)

2800 145 106.8 66.3 68.3 82.2 89.3 96.7 98.2 100.3 100.2 98.3 87.7

3000 145 107.9 67.8 69.9 81.0 90.3 98.5 100.3 99.7 101.2 99.6 87.7

Raw Exhaust Engine Noise **


Octave Band
RPM BHP OVERALL 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz 16k Hz
dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)

2800-3000 145 105.8 95.6 100.0 94.7 96.9 96.5 99.2 95.4 86.1 79.7

* Values above are provided at 3.3ft (1m) from engine block and do not include the raw exhaust noise.

** Values above are provided at 23ft (7m), 90° horizontal, from a vertical exhaust outlet and does not include noise created mechanically by the
engine.

The above data reflects values for a typical engine of this model, speed and power in a free-field environment.

Installation specifics such as background noise level and amplification of noise levels from reflecting off of surrounding objects, will affect the overall noise
levels observed. As a result of this, Clarke makes no guarantees to the above levels in an actual installation.

C131535 revC 25APR13 dsp

Page 11 of 11
0123420303 567896
766689967
76
998!9" 7#

,-./012345567689:;<9=>7?@ABCD:E@9619FE9;D6G@<
H<EIE9F6J:=:E@9=<K6LE<;6MCAND
89:;<9=>7?@ABCD:E@9619FE9;D6G@<6H<EIE9F6J:=:E@9=<K6LE<;6MCAND
OPPQRPSPTUVQWSXYTZU[\YSQXYTQWS[PTSUV]^YZ_`a[\YSQbSc\SPaQXYTQdT\e\ScQO[U[\YSUTfQg\TPQh`Zia
jklmnopqrmopsmtuojurtvpsmtwxjuypkuw bz{|}}
R~€RbQ‚~ƒO
„‚…‚€dQ~d
†‚‡ˆ~WdRb‰Q…„}QŠ€€Q‹€W‡bdQƒW€Rd‚…
wroyokpovŒrvoypmluowplupysojrqrjpysoowy
m™š
vŽ’pŽ“p m™š yœp
Ž‘ j”‘•–—˜ ›s —œžŸ
 ‹¡¢]‹g£¡ ¡ }£ Š¤}£
¡ }} Š{££
¡ {£ Š¥££
¡ {£ ¤£££
 ‹¡¢]‹g|£ ¡ ¡| |¦{£
¡ }| Š|££
¡ }} Š¤}£
 ‹¡¢]‹g|Š ¡ }} Š¤}£
¡ }§ Š{££
 ‹¡¢]‹g|¡ ¡ }} Š¤}£
¡ }§ Š{££
¡ ¦£ Š¥££
¡ ¦| ¤£££
 ‹¡¢]‹gŠ£ ¡ {£ |¦{£
¡ {¦ Š|££
¡ ¦Š Š¤}£
 ‹¡¢]‹gŠŠ ¡ ¦Š Š¤}£
¡ ¦} Š{££
 ‹¡¢]‹gŠ¡ ¡ ¦Š Š¤}£
¡ ¦} Š{££
$77%&&'2 98 792 &86&9 8(8)14*31+ 1&10
0123420303 567896
766689967
76
998!9" 7#
, -. /-..
, -0 0...
12,34250. , 6, 786.
, 89 /7..
, -: /0:.
12,34250/ , -: /0:.
, -: /6..
12,34250, , -: /0:.
, -: /6..
, 7., /-..
, 77: 0...
12,34253- , 60 7,8.
, 80 786.
12,34253. , 80 786.
, -- /7..
, 9- /0:.
12,34253/ , 9- /0:.
, 99 /6..
12,3425,. , 9, 786.
, 7.: /7..
, 7.6 /0:.
12,3425,/ , 7.6 /0:.
, 7.6 /6..
12,3425:. , 89 7,8.
, 77. 786.
, 70. /7..
, 7/8 /0:.
12,3425:/ , 7/8 /0:.
, 7/8 /6..
12,3425:, , 7// /0:.
, 709 /6..
, 7,: /-..
, 7,: 0...
$77%&&'2 98 792 &86&9 8(8)14*31+ 0&10
0123420303 567896
766689967
76
998!9" 7#
,-./0-123 . 45 6.47
. 667 6487
,-.90-175 . :5 6487
. .3 ;677
. 2; ;:27
,-.90-166 . 2; ;:27
. 22<2 ;877
,-.90-16: . 2: ;:27
. 28<2 ;877
. 88<2 ;377
. 88<2 :777
,-.90-165 . 23<2 6487
. 8.<2 ;677
. 83 ;:27
,-.90-1;6 . 83 ;:27
. 47<2 ;877
,-.90-1;: . 47 ;:27
. 4;<2 ;877
. 48<2 ;377
. 43 :777
,-.90-1.7 . 5. 6487
. 672 ;677
. 678 ;:27
,-.90-1.5 . 678 6487
. 6;: ;677
. 664 ;:27
,-.90-126 . 665 ;:27
. 665 ;877
,-.90-12: . 668 ;:27
. 6:6 ;877
. 6:2 ;377
. 6:: :777
=>8/0-1?@.A 8 ;57 6487
$77%&&'2 98 792 &86&9 8(8)14*31+ *&10
0123420303 567896
766689967
76
998!9" 7#
,-./0123456 . 758 95:8
,-./01234;8 . <58 7988
,-./01234.8 . <5; 9:.8
. <.8 7988
,-./0123466 . <:; 9:.8
,-./01234=6 . <88 95:8
. 598 9:.8
,>./01234;8 . 7.; 9:.8
. 768 7988
. 76. 7<;8
,>./01234.7 . <88 7<;8
?1./012,8 . 998 9:.8
. 955 7988
. 956 7<;8
?1./012,7 . 956 7<;8
. 956 7.88
?1./012<8 . =5 95:8
. 958 9:.8
. 9.8 7988
. 9.8 7<;8
?1./012<7 . 9.8 7<;8
. 9.8 7.88
?1./012<5 . 9.8 7<;8
. 9.8 7.88
. 9.8 7688
. 9:; <888
?1./012@6 . 9<8 95:8
. 95= 9:.8
?1./012A6 . 9<. 95:8
. 9:; 9:.8
?1./012A8 . 9:; 9:.8
. 78: 7988
. 788 7<;8
$77%&&'2 98 792 &86&9 8(8)14*31+ 4&10
0123420303 567896
766689967
76
998!9" 7#
-./01.234 / 455 4675
/ 455 4/55
-./01.278 / 968 9:;5
/ 986 9;/5
-./01.275 / 968 9:;5
/ 986 9;/5
/ 495 4955
/ 495 4675
-./01.274 / 495 4675
/ 495 4/55
-./01.27: / 495 4675
/ 49/ 4/55
/ 49/ 4855
/ 49/ 6555
-./01.2/8 / 9;7 9:;5
/ 455 9;/5
-./01.2/5 / 9;7 9:;5
/ 455 9;/5
/ 4:5 4955
/ 4:5 4675
-./01.2/4 / 4:5 4675
/ 4:5 4/55
-./01.28: / 4:6 4675
/ 4:; 4/55
/ 47< 4855
/ 4;7 6555
-./01.2=>?5 / 9;6 9;/5
/ 9;6 4955
/ 9;6 4675
-./01.2=>?4 / 9;6 4675
/ 9;6 4/55
-./01.2=>?8 / 96/ 9:;5
/ 9;6 9;/5
$77%&&'2 98 792 &86&9 8(8)14*31+ ,&10
0123420303 567896
766689967
76
998!9" 7#
-./01.23456 / 787 9:/;
-./01.234<= / 77: 9:/;
-./01.234>; / 7/; 79;;
-./01.234?6 / 77; 9@:;
-./51.234A: / 9:; 9:/;
B?/01.234== / 7C; 9:/;
B</01.234@; / D9; 79;;
B?/01.234E= / 7@; 9@:;
-./51.23452 / 7@: 9:/;
-./51.234?2 / 7;D 9@:;
-./51.234>C / 787 79;;
-./51.234<: / 777 9:/;
-F/01.244/; / D/; 7D8;
-F/01.244=; / @77 9:/;
/ @;; 79;;
-./01.2C@ / 7C8 7=;;
/ D;; D;;;
-./01.234G; / 7CD 79;;
/ 7C8 7D8;
-./01.234G7 / 7C8 7D8;
/ 7C9 7/;;
-./01.234G= / 7/8 9:/;
/ 7:D 9C;;
B5=01.23486 = @8; 9@:;
B5=01.234/= = @C8 9:/;
B5=01.234/7 = @C: 9C;;
= 8;; 79;;
= 8;; 7D8;
B5=01.234@; = D=8 9@:;
= @/; 9:/;
= @:7 9C;;
= @C; 79;;
= @C; 7D8;
$77%&&'2 98 792 &86&9 8(8)14*31+ ,&10
0123420303 567896
766689967
76
998!9" 7#
-./01234567 / 869 7:;;
-./0123456/ / 889 :<9;
-=;012345>; :; 87; :<9;
:; 8?; 7:;;
-=;01234567 :; <77 7:;;
-=;0123456/ :; 98; :<9;
-=;0123459/ :; 877 :@<;
:; 8/< :<9;
-=;0123459; :; 9;; :6;;
:; 9:@ 7:;;
:; 9;9 7?8;
-=;.123459< :; @/: :@<;
:; 8?/ :<9;
-=;.1234586 :; 887 7:;;
-A70123458/ :7 <;; :@<;
-A70123458; :7 /;; :<9;
:7 /;; :6;;
:7 /;; 7:;;
-A7012345// :7 /<8 :<9;
-A70123459; :7 <78 :@<;
:7 /;8 :<9;
:7 //; 7:;;
-A70123456/ :7 /78 :@<;
:7 6/7 :<9;
:7 :;;; :6;;
-A701235567 :7 :;78 7:;;
9 @;; 7:;;
B2@.123;6 @ ?6 :<9;
@ @/ 7:;;
@ 87 7?8;
B2@.123:: @ 87 7?8;
@ 88C8 79;;
B2@.123:? @ 8? 7?8;
$77%&&'2 98 792 &86&9 8(8)14*31+ ,&10
0123420303 567896
766689967
76
998!9" 7#
, -./- 0.11
, ../- 0211
, ../- 3111
45,67589: , -2/- 9;.1
, .,/- 0911
, .2 03-1
45,675809 , .2 03-1
, ;1/- 0.11
45,675803 , ;1 03-1
, ;0/- 0.11
, ;./- 0211
, ;2 3111
45,6758,1 , :, 9;.1
, 91- 0911
, 91. 03-1
45,6758,: , 91. 9;.1
, 903 0911
, 99; 03-1
45,6758-9 , 99: 03-1
, 99: 0.11
45,6758-3 , 99. 03-1
, 939 0.11
, 93- 0211
, 933 3111
. 0;3 9:11
<=
>?@A@BC@DE?D@ACFGH@>CIJFCKA@CL?HM?DCAN@@>CFGDE@A
OXYX\]\ O^_X\]\
F^`RQ F^`RQ
DPTCPU AaRRQ F^`RQ AaRRQ F^`RQ
OPQRS VWSXYQRZ[ bZa\c MN bZa\c MN
45,d7581, , 03-1 -1 0.11 --
45,d7581, , 0.11 -- 0211 .1
45,d7581, , 0211 .1 3111 .1
$77%&&'2 98 792 &86&9 8(8)14*31+ +&10
0123420303 567896
766689967
76
998!9" 7#
-./01.234 / 3564 /3 7344 83
/ 7344 83 7984 88
-./01.237 / 7984 88 7644 8:
-./01.23/ / 7984 88 7644 8:
/ 7644 8: 7;44 54
/ 7;44 54 9444 53
-./01.274 / 3564 64 7344 65
/ 7344 65 7984 57
-./01.277 / 7984 57 7644 58
-./01.27/ / 7984 57 7644 58
/ 7644 58 7;44 ;4
/ 7;44 ;4 9444 ;9
-./01.294 / 3564 6/ 7344 5:
/ 7344 5: 7984 ;8
-./01.297 / 7984 ;8 7644 ;8
-./01.29/ / 7984 ;8 7644 ;8
/ 7644 ;8 7;44 34/
/ 7;44 34/ 9444 338
-./01.20; / 3/54 69 3564 59
-./01.204 / 3564 59 7344 ;;
/ 7344 ;; 7984 :;
-./01.207 / 7984 :; 7644 ::
-./01.2/4 / 3564 :/ 7344 348
/ 7344 348 7984 346
-./01.2/7 / 7984 346 7644 346
/ 3564 334 7344 394
-./01.28; / 3/54 5: 3564 334
-./01.284 / 3/54 5: 3564 334
/ 3564 334 7344 394
/ 7344 394 7984 375
-./01.287 / 7984 375 7644 375
-./01.28/ / 7984 377 7644 39:
/ 7644 39: 7;44 3/8
$77%&&'2 98 792 &86&9 8(8)14*31+ ,&10
0123420303 567896
766689967
76
998!9" 7#
, -.// 0,1 2/// 0,1
34,567834-, , -.// ,1 2/// ,1
34,567934-, , -.// ,1 2/// ,1
34,5678342, , -:// 21 -.// 1/
, -.// 1/ 2/// 1/
34,5679342, , -:// 21 -.// 1/
, -.// 1/ 2/// 1/
;<:567834:/ : 0=:/ 2,1 -0// 2:/
;<:567834>. : 0,=/ 2// 0=:/ ,0/
;?:5678341/ : 0=:/ -:1 -0// -./
: -0// -./ -21/ -.:
@7:5678;/ : 0=:/ 00/ -0// 0,,
: -0// 0,, -21/ 0,.
@7:5678;- : -21/ 0,. -:// 0,.
@7:56782/ : 0,=/ >, 0=:/ 0,/
: 0=:/ 0,/ -0// 0:/
: -0// 0:/ -21/ 0:/
@7:56782- : -21/ 0:/ -:// 0:/
@7:56782, : -21/ 0:/ -:// 0:/
: -.// 0:/ 2/// 0=1
@7:5678A. : 0,=/ 02/ 0=:/ 0,>
@7:5678B. : 0,=/ 02: 0=:/ 0=1
@7:5678B/ : 0=:/ 0=1 -0// -/=
: -0// -/= -21/ -//
@7:5678B- : -21/ -// -:// -//
@7:56781. : 0,=/ 02. 0=:/ 0.2
@7:56781/ : 0,=/ 02. 0=:/ 0.2
: 0=:/ 0.2 -0// -0/
: -0// -0/ -21/ -0/
@7:56781- : -21/ -0/ -:// -0/
@7:56781, : -21/ -0/ -:// -0:
: -.// -0: 2/// -0:
@7:5678:. : 0,=/ 0=1 0=:/ -//
$77%&&'2 98 792 &86&9 8(8)14*31+ 13&10
0123420303 567896
766689967
76
998!9" 7#
,-./0-1.2 . 3452 356 35.2 722
. 35.2 722 7322 742
. 7322 742 7862 742
,-./0-1.7 . 7862 742 7.22 742
,-./0-194 . 7862 748 7.22 745
. 7922 76: 8222 756
,-./0-1;<=9 . 3452 38. 35.2 358
,-./0-1;<=2 . 35.2 358 7862 358
,-./0-1;<=7 . 7862 358 7.22 358
,-.>0-1?;@: . 35.2 325 7322 38:
. 7322 38: 7862 343
,-.>0-1?;@3 . 7862 343 7.22 38:
,-.>0-1?;7: . 3452 :7 35.2 385
. 35.2 385 7322 366
. 7322 366 7862 368
,-.>0-1?;83 . 7862 368 7.22 363
,-.>0-1?;88 . 7922 349 7:.2 34.
. 7:.2 34. 8222 3.3
,-.>0-1?;A5 . 3452 379 35.2 34.
,-.>0-1?;=: . 35.2 352 7322 3.9
. 7322 3.9 7862 3..
,-.>0-1?;=3 . 7862 3.. 7.22 3.4
,-.>0-1?;B5 . 3452 384 35.2 357
,-.>0-1?;B: . 35.2 357 7322 727
. 7322 727 7862 3:8
,-.>0-1?;B3 . 7862 3:8 7.22 3:3
,-.>0-1?;65 . 3452 38. 35.2 392
,-.>0-1?;4: . 35.2 392 7322 726
. 7322 726 7862 722
,-.>0-1?;63 . 7862 722 7.22 723
,-.>0-1?;68 . 7922 724 7:.2 727
. 7:.2 727 8222 727
@C2/0-1?;D2 32 35.2 647 3:22 656
$77%&&'2 98 792 &86&9 8(8)14*31+ 11&10
0123420303 567896
766689967
76
998!9" 7#
,- ,.-- /0/ 1,-- /0/
23456789:0- 4 1,-- ;,1 1;/- ;,4
<74=6789:40 4 ,>0- ,0- ,04- ,./
<74=6789:/. 4 ,04- ,./ 1,-- 1;1
4 1,-- 1;1 1;/- 11?
<74=6789:4, 4 1;/- 11? 14-- 114
<74=6789:?; 4 1?-- 1;. ;--- 14-
2@-56789:A- ,- ,04- />1 ,.-- /0/
,- ,.-- /0/ 1,-- /0/
<7456789:B? 4 ,04- 14/ ,.-- 10;
<7456789:B- 4 1,-- 1.; 1;/- 1./
<7456789:B1 4 1;/- 1./ 14-- 1.,
<745678.> 4 1?-- 1./ ;--- ;--
CDEFG7HIDFJIGKLG1-,.6->6-/

BMJGDHHJDNDLOJGKPGDGOKQHDLRSEGLDQJGKNGHNKITOFGULGFMUEGIDFDVDEJGIKJEGLKFGULGUFEJWPGDEETNJGFMDFGHNKITOFEGEKGUIJLFUPUJIGMDXJGVJJL
QDLTPDOFTNJIGTLIJNG7CSEG8KWWKY67HG@JNXUOJZG[LWRGFMKEJGHNKITOFEGVJDNUL\GFMJG7CG]DN^GEMKTWIGVJGOKLEUIJNJIGFKGVJG_JNFUPUJIGDLIGOKXJNJI
TLIJNG7CSEG8KWWKY67HG@JNXUOJZG:WYDREGWKK^GPKNGFMJG]DN^GKLGFMJGHNKITOFZ
7CGHJNQUFEGFMJGNJHNKITOFUKLGKPGFMJGQDFJNUDWGOKLFDULJIGULGFMJG[LWULJG_JNFUPUODFUKLG2UNJOFKNRGETVJ̀OFGFKGFMJGPKWWKYUL\GOKLIUFUKLEaG,ZGBMJGbTUIJ
cLPKNQDFUKLdG:EEJQVWUJEdG_KLEFNTOFUKLEdG2JEU\LEdG@REFJQEdGDLIeKNG_JNFUPUODFUKLEGfPUWJEgGQTEFGVJGHNJEJLFJIGULGFMJUNGJLFUNJFRGDLIGULGDGLKL6
QUEWJDIUL\GQDLLJNdGYUFMKTFGDLRGQDLUHTWDFUKLGKPGFMJGIDFDGfKNGINDYUL\EgZG1ZGBMJGEFDFJQJLFGh=JHNULFJIGPNKQGFMJG[LWULJG_JNFUPUODFUKLEG2UNJOFKNR
YUFMGHJNQUEEUKLGPNKQG7ChGQTEFGDHHJDNGDID̀OJLFGFKGFMJGJiFNDOFJIGQDFJNUDWZGcLGDIIUFUKLdGFMJGNJHNULFJIGQDFJNUDWGQTEFGULOWTIJGDGOKHRNU\MFGLKFUOJ
ULGFMJGPKWWKYUL\GPKNQDFaGhjG1-1-G7CGCC_h

$77%&&'2 98 792 &86&9 8(8)14*31+ 10&10


Diesel Engines for Fire Pump Drivers
The diesel engines listed below are FM Approved as fire pump drivers for installations requiring internal combustion engine drive. The
stated rated horsepower represents power available to the pump at NFPA standard installation conditions, 300 ft (91 m) above sea
level and at 77°F (25°C). Allowances have been made for power consumption by accessories, normal engine wear and manufacturing
tolerances.
The engine selected for a particular installation should provide at least as much rated power as the maximum power requirement of
the pump to which it will be coupled.

Diesel Engines for Fire Pump Drivers, Liquid Cooled


The diesel engines shown in this section utilize raw water from the fire pump to cool the primary coolant of the engine via a heat
exchanger. The engine is then cooled by circulation of the primary coolant.

Clarke UK Ltd
Unit 1 Grange Works, Lomond Rd, Coatbridge ML5 2NN, United Kingdom
Listing Rated Power, Rated Power, Rated Speed, Certification
Product
Country hp kW r/min Type
United
JU4H-UF10 55 41 2350 FM Approved
Kingdom
United
JU6H-UFKAS0 260 194 2100 FM Approved
Kingdom
United
JU6H-UFKAPG 220 164 1470 FM Approved
Kingdom
United
DP6H-UFKA62 300 224 2350 FM Approved
Kingdom
United
DP6H-UFKA62 300 224 2100 FM Approved
Kingdom
United
DP6H-UFKA50 286 213 2350 FM Approved
Kingdom
United
DP6H-UFKA50 280 209 2100 FM Approved
Kingdom
United
DP6H-UFKA50 265 198 1760 FM Approved
Kingdom
United
DP6H-UFKA88 290 216 1760 FM Approved
Kingdom
United
DP6H-UFKA70 312 233 2100 FM Approved
Kingdom
United
DP6H-UFKA70 316 236 2350 FM Approved
Kingdom
United
DP6H-FMKA88 290 216 1760 FM Approved
Kingdom
United
DQ6H-UFKA98 410 306 1760 FM Approved
Kingdom
United
DP6H-UFKAX8 240 179 1470 FM Approved
Kingdom
United
DQ6H-UFKA98 300 224 1470 FM Approved
Kingdom
United
DQ6H-UFKA88 375 280 1760 FM Approved
Kingdom
United
DQ6H-UFKA60 360 268 2100 FM Approved
Kingdom
United
DQ6H-UFKA60 345 257 1760 FM Approved
Kingdom
United
DQ6H-UFKA50 340 254 2100 FM Approved
Kingdom

© 2007-2016 FM Approvals. All rights reserved. 1 of 29


United
DQ6H-UFKA48 240 179 1470 FM Approved
Kingdom
United
DQ6H-UFKA4G 290 216 1760 FM Approved
Kingdom
United
DQ6H-FMKA60 345 257 1760 FM Approved
Kingdom
United
DQ6H-UFKA40 309 231 2100 FM Approved
Kingdom
United
DQ6H-FMKA60 360 269 2100 FM Approved
Kingdom
United
DR8H-UFKA5G 450 336 1470 FM Approved
Kingdom
United
DR8H-UFKA68 495 369 1760 FM Approved
Kingdom
United
DR8H-UFKA62 497 371 1900 FM Approved
Kingdom
United
DR8H-UFKA62 500 373 2100 FM Approved
Kingdom
United
DR8H-UFKA62 500 373 2350 FM Approved
Kingdom
United
DR8H-UFKA40 385 287 1470 FM Approved
Kingdom
United
DR8H-UFKA40 460 343 1760 FM Approved
Kingdom
United
DR8H-UFKA40 472 352 1900 FM Approved
Kingdom
United
DR8H-UFKA40 490 365 2100 FM Approved
Kingdom
United
DR8H-UFKA40 490 365 2350 FM Approved
Kingdom
United
DS0H-UFKA68 522 389.5 1470 FM Approved
Kingdom
United
DS0H-UFKA68 587 438 1760 FM Approved
Kingdom
United
DS0H-UFKA60 614 458 2100 FM Approved
Kingdom
United
DS0H-UFKA60 606 452 2350 FM Approved
Kingdom
United
DS0H-UFKAN0 542 404 1760 FM Approved
Kingdom
United
DS0H-UFKAN0 575 429 2100 FM Approved
Kingdom
United
DT2H-UFKA58 700 522 1470 FM Approved
Kingdom
United
DT2H-UFKA50 800 596.5 1760 FM Approved
Kingdom
United
DT2H-UFKA50 800 596.5 1900 FM Approved
Kingdom
United
DT2H-UFKA50 800 596.5 2100 FM Approved
Kingdom
United
DT2H-UFKA20 700 522 1760 FM Approved
Kingdom
United
DT2H-UFKA20 700 522 2100 FM Approved
Kingdom
United
DR8H-FMKA5G 450 336 1470 FM Approved
Kingdom
United
DR8H-FMKA68 495 369 1760 FM Approved
Kingdom

© 2007-2016 FM Approvals. All rights reserved. 13 of 29


United
DR8H-FMKA62 497 371 1900 FM Approved
Kingdom
United
DR8H-FMKA62 500 373 2100 FM Approved
Kingdom
United
DR8H-FMKA62 500 373 2350 FM Approved
Kingdom
United
DS0H-FMKA68 522 389.5 1470 FM Approved
Kingdom
United
DS0H-FMKA68 587 438 1760 FM Approved
Kingdom
United
DS0H-FMKA60 614 458 2100 FM Approved
Kingdom
United
DS0H-FMKA60 606 452 2350 FM Approved
Kingdom
United
DT2H-FMKA40 655 488.5 1470 FM Approved
Kingdom
United
DT2H-FMKA40 770 574 1760 FM Approved
Kingdom
United
DT2H-FMKA40 758 565 2100 FM Approved
Kingdom
United
DT2H-UFKA60 725 541 1470 FM Approved
Kingdom
United
DT2H-UFKA60 805 600 1760 FM Approved
Kingdom
United
DT2H-UFKA60 880 656 2100 FM Approved
Kingdom
United
DT2H-UFKA98 825 615 1470 FM Approved
Kingdom
United
DT2H-UFKA98 982 732 1760 FM Approved
Kingdom
United
DT2H-UFKA98 1000 746 1900 FM Approved
Kingdom
United
DT2H-UFKA92 1025 764 2100 FM Approved
Kingdom
United
JU4H-UF04 50 37 2350 FM Approved
Kingdom
United
JU4H-UF04 55 41 2600 FM Approved
Kingdom
United
JU4H-UF04 60 45 2800 FM Approved
Kingdom
United
JU4H-UF04 60 45 3000 FM Approved
Kingdom
United
JU4H-UF10 51 38 2100 FM Approved
Kingdom
United
JU4H-UF10 41 31 1760 FM Approved
Kingdom
United
JU4H-UF12 59 44 2600 FM Approved
Kingdom
United
JU4H-UF12 55 41 2350 FM Approved
Kingdom
United
JU4H-UF14 59 44 2600 FM Approved
Kingdom
United
JU4H-UF14 55 41 2350 FM Approved
Kingdom
United
JU4H-UF14 71 53 3000 FM Approved
Kingdom
United
JU4H-UF14 70 52 2800 FM Approved
Kingdom

© 2007-2016 FM Approvals. All rights reserved. 14 of 29


United
JU4H-UF24 75 56 2600 FM Approved
Kingdom
United
JU4H-UF24 72 54 2350 FM Approved
Kingdom
United
JU4H-UF24 83 62 3000 FM Approved
Kingdom
United
JU4H-UF24 80 60 2800 FM Approved
Kingdom
United
JU4H-UF30 85 63 2350 FM Approved
Kingdom
United
JU4H-UF30 79 59 2100 FM Approved
Kingdom
United
JU4H-UF30 64 48 1760 FM Approved
Kingdom
United
JU4H-UF32 85 63 2600 FM Approved
Kingdom
United
JU4H-UF32 85 63 2350 FM Approved
Kingdom
United
JU4H-UF34 85 63 2600 FM Approved
Kingdom
United
JU4H-UF34 85 63 2350 FM Approved
Kingdom
United
JU4H-UF34 115 86 3000 FM Approved
Kingdom
United
JU4H-UF34 104 78 2800 FM Approved
Kingdom
United
JU4H-UF40 106 79 2350 FM Approved
Kingdom
United
JU4H-UF40 105 78 2100 FM Approved
Kingdom
United
JU4H-UF40 94 70 760 FM Approved
Kingdom
United
JU4H-UF42 106 79 2600 FM Approved
Kingdom
United
JU4H-UF42 106 79 2350 FM Approved
Kingdom
United
JU4H-UF44 106 79 2600 FM Approved
Kingdom
United
JU4H-UF44 106 79 2350 FM Approved
Kingdom
United
JU4H-UF44 140 104 3000 FM Approved
Kingdom
United
JU4H-UF44 135 101 2800 FM Approved
Kingdom
United
JU4H-UF50 127 95 2350 FM Approved
Kingdom
United
JU4H-UF50 130 97 2100 FM Approved
Kingdom
United
JU4H-UF50 110 82 1760 FM Approved
Kingdom
United
JU4H-UF52 127 95 2600 FM Approved
Kingdom
United
JU4H-UF52 127 95 2350 FM Approved
Kingdom
United
JU4H-UF54 139 104 2600 FM Approved
Kingdom
United
JU4H-UF54 122 91 2350 FM Approved
Kingdom

© 2007-2016 FM Approvals. All rights reserved. 15 of 29


United
JU4H-UF54 145 108 3000 FM Approved
Kingdom
United
JU4H-UF54 145 108 2800 FM Approved
Kingdom
United
JU4H-UF58 79 59 1470 FM Approved
Kingdom
United
JU4H-UF58 110 82 1760 FM Approved
Kingdom
United
JU4H-UFH0 73 54 1760 FM Approved
Kingdom
United
JU4H-UFH0 88 66 2100 FM Approved
Kingdom
United
JU4H-UFH0 98 73 2350 FM Approved
Kingdom
United
JU4H-UFH2 98 73 2350 FM Approved
Kingdom
United
JU4H-UFH2 99 74 2600 FM Approved
Kingdom
United
JU4H-UFH8 63 47 1470 FM Approved
Kingdom
United
JU4H-UFH8 73 54 1760 FM Approved
Kingdom
United
JU6H-UF30 140 104 1760 FM Approved
Kingdom
United
JU6H-UF30 160 119 2350 FM Approved
Kingdom
United
JU6H-UF30 160 119 2100 FM Approved
Kingdom
United
JU6H-UF30 94 70 1470 FM Approved
Kingdom
United
JU6H-UF32 160 119 2350 FM Approved
Kingdom
United
JU6H-UF32 160 119 2600 FM Approved
Kingdom
United
JU6H-UF34 160 119 2350 FM Approved
Kingdom
United
JU6H-UF34 175 131 3000 FM Approved
Kingdom
United
JU6H-UF34 160 119 2800 FM Approved
Kingdom
United
JU6H-UF34 160 119 2600 FM Approved
Kingdom
United
JU6H-UF50 183 137 1760 FM Approved
Kingdom
United
JU6H-UF50 138 103 1470 FM Approved
Kingdom
United
JU6H-UF50 210 157 2350 FM Approved
Kingdom
United
JU6H-UF50 210 157 2100 FM Approved
Kingdom
United
JU6H-UF52 210 157 2350 FM Approved
Kingdom
United
JU6H-UF52 210 157 2600 FM Approved
Kingdom
United
JU6H-UF54 210 157 2350 FM Approved
Kingdom
United
JU6H-UF54 216 161 3000 FM Approved
Kingdom

© 2007-2016 FM Approvals. All rights reserved. 16 of 29


United
JU6H-UF54 216 161 2800 FM Approved
Kingdom
United
JU6H-UF54 216 161 2600 FM Approved
Kingdom
United
JU6H-UF58 183 137 1760 FM Approved
Kingdom
United
JU6H-UF58 138 103 1470 FM Approved
Kingdom
United
JU6H-UF60 200 149 1760 FM Approved
Kingdom
United
JU6H-UF60 175 130 1470 FM Approved
Kingdom
United
JU6H-UF60 240 179 2350 FM Approved
Kingdom
United
JU6H-UF60 240 179 2100 FM Approved
Kingdom
United
JU6H-UF62 240 179 2350 FM Approved
Kingdom
United
JU6H-UF62 240 179 2600 FM Approved
Kingdom
United
JU6H-UF68 200 149 1760 FM Approved
Kingdom
United
JU6H-UF68 175 131 1470 FM Approved
Kingdom
United
JU6H-UF84 243 181 2350 FM Approved
Kingdom
United
JU6H-UF84 275 205 3000 FM Approved
Kingdom
United
JU6H-UF84 259 193 2800 FM Approved
Kingdom
United
JU6H-UF84 247 184 2600 FM Approved
Kingdom
United
JU6H-UFD0 110 82 1760 FM Approved
Kingdom
United
JU6H-UFD0 144 107 2100 FM Approved
Kingdom
United
JU6H-UFD0 148 110 2350 FM Approved
Kingdom
United
JU6H-UFD2 148 110 2350 FM Approved
Kingdom
United
JU6H-UFD2 148 110 2600 FM Approved
Kingdom
United
JU6H-UFG8 149 111 1760 FM Approved
Kingdom
United
JU6H-UFG8 130 97 1470 FM Approved
Kingdom
United
JU6H-UFKAQ8 227 169 1760 FM Approved
Kingdom
United
JU6H-UFKARG 252 188 1760 FM Approved
Kingdom
United
JU6H-UFM0 200 149 2350 FM Approved
Kingdom
United
JU6H-UFM0 175 131 1760 FM Approved
Kingdom
United
JU6H-UFM0 207 154 2100 FM Approved
Kingdom
United
JU6H-UFM2 200 149 2600 FM Approved
Kingdom

© 2007-2016 FM Approvals. All rights reserved. 17 of 29


United
JU6H-UFM2 200 149 2350 FM Approved
Kingdom
United
JU6H-UFM8 175 131 1760 FM Approved
Kingdom
United
JU6H-UFM8 136 101 1470 FM Approved
Kingdom
United
JW6H-UFAA80 400 298 2100 FM Approved
Kingdom
United
JW6H-UFAA80 422 315 1760 FM Approved
Kingdom
United
JW6H-UFAAM8 373 278 1760 FM Approved
Kingdom
United
JW6H-UFH8 330 246 1760 FM Approved
Kingdom
United
DR8H-UFKA98 556 415 1760 FM Approved
Kingdom
United
DR8H-UFKA92 596 444.5 2100 FM Approved
Kingdom
United
DS0H-UFKA98 650 485 1760 FM Approved
Kingdom
United
DS0H-UFKA92 722 538.5 2100 FM Approved
Kingdom
United
DS0H-UFKAM0 520 388 1760 FM Approved
Kingdom
United
DS0H-UFKAM0 530 395 2100 FM Approved
Kingdom
United
DT2H-UFKA88 875 652.5 1760 FM Approved
Kingdom
United
JU4H-UF20 60 45 1760 FM Approved
Kingdom
United
JU4H-UF20 67 50 2100 FM Approved
Kingdom
United
JU4H-UF20 72 54 2350 FM Approved
Kingdom
United
JU4H-UF22 72 54 2350 FM Approved
Kingdom
United
JU4H-UF22 75 56 2600 FM Approved
Kingdom
United
JU4H-UF28 48 36 1470 FM Approved
Kingdom
United
JU4H-UF28 60 45 1760 FM Approved
Kingdom
United
JU4H-UF50 79 59 1470 FM Approved
Kingdom
United
JU4H-UF50 110 82 1760 FM Approved
Kingdom
United
JU4H-UF50 130 97 2100 FM Approved
Kingdom
United
JU4H-UF50 127 95 2350 FM Approved
Kingdom
United
JU6H-UFAB76 225 168 2800 FM Approved
Kingdom
United
JU6H-UFABL0 173 129 1760 FM Approved
Kingdom
United
JU6H-UFABL0 173 129 2100 FM Approved
Kingdom
United
JU6H-UFABL0 173 129 2350 FM Approved
Kingdom

© 2007-2016 FM Approvals. All rights reserved. 18 of 29


United
JU6H-UFABL2 173 129 2350 FM Approved
Kingdom
United
JU6H-UFABL2 173 129 2600 FM Approved
Kingdom
United
JU6H-UFABL8 136 101 1470 FM Approved
Kingdom
United
JU6H-UFABL8 173 129 1760 FM Approved
Kingdom
United
JU6R-UFKA67 170 127 1470 FM Approved
Kingdom
United
JU6R-UFKA67 195 145 1760 FM Approved
Kingdom
United
JU6R-UFKA59 195 145 1760 FM Approved
Kingdom
United
JU6R-UFKA59 232 173 2100 FM Approved
Kingdom
United
JU6R-UFKA59 228 170 2350 FM Approved
Kingdom
United
JU6R-UFKA61 228 170 2350 FM Approved
Kingdom
United
JU6R-UFKA61 226 168.5 2600 FM Approved
Kingdom
United
JU6R-UFKAPF 203 151 1470 FM Approved
Kingdom
United
JU6R-UFKAQ7 222 165.5 1760 FM Approved
Kingdom
United
JU6R-UFKARF 247 184 1760 FM Approved
Kingdom
United
JU6R-UFKAS9 252 188 2100 FM Approved
Kingdom
United
JU6R-UFKA83 239 178 2800 FM Approved
Kingdom
United
JU6R-UFKA83 260 194 3000 FM Approved
Kingdom
United
KA4H-UFKA24 45 33.5 3000 FM Approved
Kingdom
United
KA4H-UFKA24 45 33.5 2800 FM Approved
Kingdom

© 2007-2016 FM Approvals. All rights reserved. 19 of 29


SPECIFICATIONS FOR
MODEL GPD DIESEL ENGINE
FIRE PUMP CONTROLLER

1. STANDARD, LISTING AND APPROVAL


1 NFPA 20
2 UL (UL218 and CSA C22.2 No. 14)
3 FM Global (Class 1321/1323)
4 City of New York for fire pump service
2. MANUFACTURER AND MODEL
1 Tornatech model GPD
3. SEISMIC CERTIFICATION
1. Test Criteria
a. ICC-ES AC156
2. Building Code
a. IBC 2015
b. CBC 2016
c. OSHPD Special Seismic
Certification Preapproval – OSP
3. Seismic Parameters
a. ASCE 7-10 Chapter 13
4. ENCLOSURE
1 NEMA 2
2 Bottom conduit entry gland plate e. Cut-out and cut-in pressure
5. OPERATIONAL COMPONENTS settings
1 Hand-OFF-Auto selector switch f. Starter #1 and #2 rest or
installed behind lockable breakable cranking
cover. g. Engine stopped / running
6. TOUCH SCREEN OPERATOR INTERFACE h. Type of starting cause
1. 7.0” LCD color touch screen (HMI i. Fuel solenoid valve energized /
technology) operator interface not energized
powered by an embedded j. Timers counting
microcomputer with software PLC logic k. Hand-OFF-Auto selector
2. Keypad type pushbuttons: switch position
a. Crank from Battery #1 l. Actuation mode
b. Crank from Battery #2 m. Type of controller
c. Stop n. Method of shutdown
d. Run test o. Time and date
3. On-Screen Menu: p. Pump room temperature
a. Home (⁰F or ⁰C)
b. Alarms q. Digital pressure gauge
c. Configuration 5. System pressure selectable units of
d. History measure:
e. Service a. PSI
f. Manuals b. kPa
g. Language c. Bar
4. Shall graphically display: d. Feet of head
a. AC power present e. Meter of water
b. Charger #1 and #2 charging 6. Shall allow programming and display
mode of:
c. Battery #1 and #2 voltage and a. Cut-In and Cut-Out pressure
amperage settings
d. System pressure b. Minimum run period timer
c. Sequential start timer

GPD-SPE-003 Rev.0
SPECIFICATIONS FOR
MODEL GPD DIESEL ENGINE
FIRE PUMP CONTROLLER

d. Periodic test timer kk. Engine ECM fault


7. Shall allow selection of the language of ll. Engine low oil pressure
operation. mm. High raw water temperature
8. Shall allow on-screen viewing and nn. PLD low suction pressure
downloading of the corresponding oo. Engine Run
Operation Manual in the chosen pp. Main switch AUTO
language. qq. Pump room temperature (F or C)
7. COMMUNICATION PROTOCOL CAPABILITY rr. Periodic test
1. Modbus with TCP/IP frame format and ss. Main switch in HAND
shielded female RJ45 connector tt. Cranking cycle
8. STATE AND ALARM VISUAL INDICATORS uu. Main switch in OFF
1. Shall visually indicate and differentiate vv. AC Power available
the criticalness by color:
a. AC fail
b. DC fail 9. CRANK CYCLE
1 Crank from battery 1 for 15 seconds
2 Rest for 15 seconds
c. Battery fail 1, 2
3 Crank from Battery 2 for 15 seconds
d. Charger fail 1, 2
4 Shall repeat 3 times. Visual alarm “Fail
e. Engine trouble
TO Start” shall appear if the engine
f. Pump room trouble
does not start after the completion of
g. Controller trouble
this cycle.
h. Service required
10. PRESSURE AND EVENT RECORDING
i. Weak battery 1
1 Shall be capable of logging pressure
j. Weak battery 2
data and operational events with time
k. Loss of continuity with Contactor 1
and date stamp.
l. Loss of continuity with Contactor 2
2 Shall be able to display operational
m. Weekly test Cut-In not reached
events for the life of the controller, and
n. Weekly test check solenoid valve
display the pressure data in text and/or
o. Faulty pressure transducer
graphic form.
p. Low raw water flow
3 Data shall be retrievable and
q. Engine fail when running
downloadable to a flash memory disk
r. Engine fail to start
via the USB port accessible to the user
s. Engine overspeed
without having to open the controller
t. Low ambient temperature
door.
u. Pump on demand
a. All time statistics
v. Invalid Cut-In
(1) First start up
w. Overpressure
(2) On time
x. Underpressure
b. First and last service statistics
y. Battery 1 overvoltage
(1) First setup
z. Battery 2 overvoltage
(2) On time
aa. Water reservoir low
(3) Engine Statistics:
bb. Water reservoir high
(a) On time
cc. Fuel tank Leak
(b) Start count
dd. Low fuel level
(c) Last start time
ee. High fuel level
(4) Minimum, maximum, average
ff. Engine ECM in alternate position
system pressure
gg. Engine fuel injection malfunction
(5) Minimum, maximum, average
hh. Engine high temperature
pump room temperature
ii. Engine low temperature
(6) Jockey Pump controller
jj. Engine ECM warning

GPD-SPE-003 Rev.0
SPECIFICATIONS FOR
MODEL GPD DIESEL ENGINE
FIRE PUMP CONTROLLER

(a) On time
(b) Start count
(c) Last start time
11. PRESSURE SENSING - WETTED PARTS
1 Shall be supplied with a pressure
transducer (system) and run test
solenoid valve assembly rated for
500psi working pressure (calibrated at
0-300psi) and be externally mounted
with a protective cover
2 Pressure sensing line connection to the
pressure transducer shall be ½” FNPT
3 Provision for a redundant pressure
transducer shall be provided
12. SERVICE/FLOW TESTING CAPABILITIES
1 Shall have the capability of scheduling
maintenance reminders
2 Shall also have the capability of
inputting pump flow test data,
generate and display the pump curve
and store this information in memory
for the lifetime of the controller.
13. CONNECTION FOR EXTERNAL DEVICES
1 Manual remote start device
2 Automatic remote start device
3 Deluge valve start
14. DPDT DRY CONTACTS FOR REMOTE
INDICATION (8A – 250VAC):
1 Engine run
2 Main switch in HAND or OFF
3 Common controller trouble (fail safe)
4 Common engine trouble
(field re-assignable)
5 Common pump room alarm
(field re-assignable)
6 Field programmable
15. AUDIBLE ALARM
1 4” alarm bell rated for 85dB at 10ft
(3m)

GPD-SPE-003 Rev.0
Project:
Customer:
Engineer:
Pump Manufacturer:

Technical Data
Submittal Document
Model GPD
Diesel Engine Driven Fire Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

Note: The drawings included in this package are


for controllers covered under our standard
offering. Actual AS BUILT drawings may
differ from what is shown in this package.
February 2019
Technical Data
Model GPD Diesel Fire Pump Controller

Built to NFPA 20 (latest edition)


• UL218 - Fire Pump Controllers
Underwriters Laboratory (UL)
• CSA C22.2 No. 14 Industrial Control Equipment
Standard,
Listings, FM Global Class 1321/1323
Approvals and New York City Accepted for use in the City of New York by the Department of Buildings
Certifications Seismic Certification See page 5 for details
Optional
CE Mark Various EN, IEC & CEE directives and standards
Protection Rating
□ Standard: NEMA 2 (IP31)
Optional
□ NEMA 12 □ NEMA 4X-304 sst painted □ IP54
□ NEMA 3 □ NEMA 4X-304 sst brushed finish □ IP55
Enclosure □ NEMA 3R □ NEMA 4X-316 sst painted □ IP65
□ NEMA 4 □ NEMA 4X-316 sst brushed finish □ IP66
Accessories Paint Specifications
• Bottom entry gland plate • Red RAL3002
• Lifting Lugs • Powder coating
• Keylock handle • Glossy textured finish

Standard
Ambient □ 4°C to 40°C / 39°F to 104°F
Temperature Optional
Rating □ 4°C to 55°C / 39°F to 131°F
Controllers built in Dubai, UAE (Tornatech FZE) are supplied standard with 55°C rating.

AC □ 120V / 1ph / 60hz


□ 208V to 240V / 1ph / 50-60hz
DC □ 12VDC
General □ 24VDC
Grounding system • Negative
• Two independent fully automatic
Battery chargers • 10A continuous charge
• 500mA trickle charge
• Battery 1 & Battery 2 voltage
Electrical Reading • Battery 1 & Battery 2 charging amperage
• Charging mode
• Continuous system pressure display
Pressure Reading
• Cut-in and cut-out pressure setting
• Pressure readings with date stamp
• Event recording with date stamp
Pressure and
• Under regular maintained operation, events are stored in memory for the life of the controller.
Event Recorder
• Data viewable on operator interface display screen
• Downloadable by USB port to external memory device

This is a Marketing document. Please consult factory for more information.


February 2019 2
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPD Diesel Fire Pump Controller

• Pressure transducer and run test solenoid valve assembly for fresh water application
• Pressure sensing connection 1/2” Female NPT
Pressure sensing • Drain connection 3/8”
• Rated and calibrated for 0-500psi working pressure
• Externally mounted with protective cover
Audible Alarm 4” alarm bell - 85 dB at 10ft. (3m)
• Engine run • Periodic test
• Main switch AUTO • Cranking Cycle
Visual Indications • AC Power available
• Main switch in OFF
• Main switch in HAND • Pump room temperature (ºF or ºC)

Visual only
• Pump room trouble • Loss of continuity 1 • High pump room temperature
• Pump on demand • Loss of continuity 2 • ECM warning
• AC Failure • High fuel level • Weekly test cut-in not reached
• Charger 1 Failure • Fuel tank leak • Check weekly test solenoid
• Charger 2 Failure • PLD low suction pressure • Pressure transducer fault
• Weak battery 1 • High raw water temperature • Invalid Cut-In
• Weak battery 2 • Low pump room temperature • Service required
Visual & Audible • Battery 1 overvoltage
Alarms • Battery 2 overvoltage

Visual and Audible


• Engine trouble • Battery 1 Failure
• Controller trouble • Battery 2 Failure
• Engine low oil pressure • Engine fail to start
• Engine high temperature • Low fuel level
• Engine low temperature • ECM fault
• Engine overspeed • ECM SS in Alternate Position
• DC Failure • Fuel injection malfunction

DPDT-8A-250V.AC
• Engine run
• Common controller trouble
• Charger #1 & Charger #2 failure • Pressure transducer fault
• Common engine trouble
• High engine temperature • Battery #1 & battery #2 failure • Overspeed
• Fail to start • DC failure • Fail when running
Remote Alarm
• Fuel injection malfunction** • Loss of continuity (starter) #1 and/or #2 • Low oil pressure
Contacts
• ECM selector switch in alternate position*** • PLD low suction pressure
• Common pump room trouble (field re-assignable)*
• Low fuel level • Low pump room temperature • AC Failure
• High fuel level • High pump room temperature
• Fuel tank leak
• H-O-A selector switch in OFF or HAND
• Free (field programmable)*

*Except if option C13 is ordered. Tornatech reserves the right to use any of these four alarm points for special specific application requirements
**Applicable to electronic engines only.
*** Applicable to electronic engines only. Alarms when ECM selector switch on the engine is in alternate mode.

This is a Marketing document. Please consult factory for more information.


February 2019 Manufacturer reserves the right to modify this information without notice 3
Technical Data
Model GPD Diesel Fire Pump Controller

• Low fuel level


Terminals for
• Remote AUTOMATIC start
Field Connections
• Deluge valve start (re-assignable)
for External
• Fuel tank leak (re-assignable)
Devices
• High fuel level (re-assignable)
• Embedded microcomputer with software PLC logic
ViZiTouch V2 • 7.0” color touch screen (HMI technology)
Operator Interface • Upgradable software
• Multi-language
• Hand-Off-Auto
Selector Switch
• Behind lockable and breakable cover
• Start on pressure drop
Automatic Start
• Remote start signal from automatic device
• Crank 1 and Crank 2 start pushbuttons
• Run test pushbutton
Manual Start
• Deluge valve start
• Remote start from manual device
• 6 consecutive cycle attempts
Crank Cycle • 3 X 15s crank from battery 1 or 2 alternatively
Operation • 15s rest in between each crank attempt
• Manual with Stop pushbutton
Stopping
• Automatic after expiration of minimum run timer ****
• Minimum run timer ****(off delay)
Field Adjustable &
Timers • Sequential start timer (on delay)
Visual Countdown
• Periodic test timer
• Pressure
Actuation
• Non-pressure
Visual Indication
• Automatic
Mode
• Non-automatic
• Protocol: Modbus
Communication
• Connection type: Shielded female connector RJ45
Protocol
• Frame Format: TCP/IP
Capability
• Addresses: See bulletin MOD-GPD

Automatic Start Manual or Remote Start Run Test or Periodic Test


Alarm and High Coolant Alarm only Alarm only Shutdown
shutdown
schedule Low Oil Pressure Alarm only Alarm only Shutdown
Overspeed Shutdown Shutdown Shutdown

Wall Mount Floor Mount


Approx. shipping Approx. shipping
Approx. Shipping Approx. Shipping
Starting Voltage dimensions in inches dimensions in inches
Weight in Lbs (kg) Weight in Lbs (kg)
(mm) (mm)

12V.DC
32" l x 29" w x 16" h 32” l x 29” w x 26” h
85 (39) 115 (52)
(813 x 737 x 407 ) (813 x 737 x 661)
24V.DC

**** Automatic shutdown shall be approved by the AHJ.

This is a Marketing document. Please consult factory for more information.


February 2019 4
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPD Diesel Fire Pump Controller

Seismic
TRU Compliance, LLC
Certification TWEI Project No.: 15014
A Tobalski Watkins Affiliate
Company
Mounting
Rigid wall mounting
details
Seismic
Building Test Seismic AFLX-H ARIG-H AFLX-V ARIG-V
Certification
Code Criteria Parameters
SDS z/h IP
Seismic IBC
Information ICC- 2.0 1.0 1.5 3.20 2.40 1.33 0.53
2015, ASCE 7-10
ES
CBC Chapter 13
AC156 3.2 0.0 1.5 3.20 1.28 2.13 0.85
2016

RRS for Nonstructural Components Testing


10.0
Spectral Response Acceleration (g)

1.0

0.1
0.1 1.0 10.0
Frequency, f (Hz)

Horiz. Level 1 Vert. Level 1

Notes:
• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016.
• OSHPD Special Seismic Certification Preapproval (OSP)

This is a Marketing document. Please consult factory for more information.


February 2019 Manufacturer reserves the right to modify this information without notice 5
Technical Data
Model GPD Diesel Fire Pump Controller

A1 Periodic test alarm contact (DPDT) Engine block heater circuit - 6KW max
C7A (same voltage as battery charger primary)
A2 Overspeed alarm contact (DPDT) Confirm power rating of block heater
Non pressure actuated controller w/o pressure trans-
A3 Low oil pressure alarm contact (DPDT) C9 ducer and run test solenoid valve
A4 High coolant temperature alarm contact (DPDT) C13 Louver activation circuit (battery power specific)
A5 Failure to start alarm contacts alarm contact (DPDT) Delayed automatic start on AC power failure
C14 (factory set at 15 minutes)
A6 Battery 1 & 2 failure alarm contact (2 x DPDT)
C15 Low zone pump control function
A7 Charger 1 & 2 failure alarm contact (2 x DPDT)
C16 Middle zone pump control function
A8 AC failure alarm contact (DPDT)
C17 High zone pump control function
System overpressure alarm contact (For engines with
A9 PLD) (DPDT) Lockout/interlock circuit from equipment installed inside
C19 the pump room
A11 Extra controller trouble alarm contact (DPDT)
Pressure transducer and run test solenoid valve for
A12 Extra engine trouble alarm contact (DPDT) D4 fresh water rated for 0-500psi (for factory calibration
purposes only)
Additional engine alarm contact (DPDT)
Ax Pressure transducer and run test solenoid valve for sea
(specify function) D6 water rated for 0-500PSI
B1 Low fuel level alarm contact (DPDT) Low fuel level float switch supplied as separate item
D7A (1-1/4”)
B2 Water reservoir level low alarm contact (DPDT)
Low fuel level float switch supplied as separate item
D7B
B3 Water reservoir empty alarm contact (DPDT) (1-1/2”)
High fuel level float switch supplied as separate item
B4 Low pump room temperature alarm contact (DPDT) D8A (1-1/4”)
B5 High fuel level alarm contact (DPDT) High fuel level float switch supplied as separate item
D8B (1-1/2”)
Low system (discharge) pressure alarm contact
B6 (DPDT) D9A Anti-condensation heater & thermostat
B7 Low suction pressure alarm contact (DPDT) D9B Anti-condensation heater & humidistat
B8 Pump on demand alarm contact (DPDT) D9C Anti-condensation heater & thermostat & humidistat
B9 Fuel tank leak alarm contact (DPDT) Low suction pressure transducer for fresh water rated
D11 at 0-300PSI with visual indication and alarm contact
B10 Main relief valve open alarm contact (DPDT)
Low suction pressure transducer for sea water rated at
D11A 0-300PSI with visual indication and alarm contact
B11 Flow meter loop valve open alarm contact (DPDT)

B12 Water reservoir level high alarm contact (DPDT) D12 Tropicalization

B13 High pump room temperature alarm contact (DPDT) D25 Mounting stand

Additional pump room alarm contact (DPDT) (specify D25A Mounting stand SST- 304 painted
Bx function)
D25B Mounting stand SST- 304 brushed finish
C5 CE Mark with factory certificate
D25C Mounting stand SST- 316 painted
Nickel – cadmium battery chargers (Battery data sheet
C6 required) D25D Mounting stand SST- 316 brushed finish
Engine block heater circuit - 3KW max
C7 (same voltage as battery charger primary) D26 Combined low and high fuel level float switch (1-1/4”)

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

This is a Marketing document. Please consult factory for more information.


February 2019 6
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPD Diesel Fire Pump Controller

D26A Combined low and high fuel level float switch (1-1/2”) L01 Other language and English (bilingual)

D27 Fuel level probe (2”) Level indication L02 French

D28A Field programmable I/O board - 5 Input / 5 output L03 Spanish


Redundant pressure transducer for fresh water rated L04 German
D30 for 0-500PSI
Redundant pressure transducer for sea water rated for L05 Italian
D31 0-500PSI
L06 Polish
D32 Modbus with RTU frame format and RS485 connection
L07 Romanian

L08 Hungarian

L09 Slovak

L10 Croatian

L11 Czech

L12 Portuguese

L13 Dutch

L14 Russian

L15 Turkish

L16 Swedish

L17 Bulgarian

L18 Thai

L19 Indonesian

L20 Slovenian

L21 Danish

L22 Greek

L23 Arabic

L24 Hebrew

L25 Chinese

Additional Options:

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

This is a Marketing document. Please consult factory for more information.


February 2019 Manufacturer reserves the right to modify this information without notice 7
Technical Data
Model GPD Diesel Fire Pump Controller

ViZiTouch V2 Operator Interface


®

PMS 295 PMS 361 Noir

Home

2 3

9
5 6 7 8

1 - Color touch screen 3 - Screen protector


2 - Onscreen menu 4 - Power LED (3 colors)
• HOME page 5 - CRANK 1 button
• ALARM page 6 - CRANK 2 button
• CONFIGURATION page 7 - STOP button
• HISTORY page 8 - RUN TEST button
• SERVICE page 9 - USB port
• MANUAL page
• LANGUAGES page

This is a Marketing document. Please consult factory for more information.


February 2019 8
Manufacturer reserves the right to modify this information without notice
Diesel Engine Fire Pump Controller Model:GPD
12Vdc or 24Vdc Negative Ground
Dimensions Built to the latest edition of the NFPA 20 standard

27" [684] 9 5/8" [245]


26" [661] 8 5/8" [220]
23 5/8" [600] 1/2" [12]
7 7/8" [200] 22 1/8" [562]

See Notes
28 7/8" [732] 27 1/2" [700]
29 7/8" [757]
20 1/4" [514]

SV1 PT1

2 7/8" [73]

6 7/8" [174]

- Controller standard without mounting stand.


- Order option D25 if mounting stand required.

20 1/2" [520] 13 1/8" [333]

23 5/8" [600]
Sensing Line Connection - 1/2 " F.NPT

Drain - 3/8 " M.TUBE


23 3/8" [594]

9 1/6" [233] 4 1/2" [115] 7 1/8" [182]

3 1/3" [84] 10 7/8" [275]


Notes: 1 1/4" [31]
13 1/8" [333]
- Standard: NEMA 2
- Standard paint : textured red RAL 3002.
- All dimensions are in inches [millimeters].
- Center of ViZiTouch screen: 20-1/4" [514] from bottom (no feet).
- Bottom conduit entrance through removable gland plate recommended.
- Use watertight conduit and connector only.
- Protect equipment against drilling chips.
- Door swing equal to door width.
- Seismic mounting to be rigid wall only.

Drawing for information only. Projection


Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
1. Revised logo 18/06/18 GPD-DI700 /E
0. First issue 18/11/16 CDL
2018 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Diesel Engine Fire Pump Controller Model:GPD
12VDC or 24VDC Negative Ground
Wiring schematic Built to the latest edition of the NFPA 20 standard
2
1
NO Black - +
Controller Trouble
NO
C C J36 J50 Red
AB1
(Fail Safe) TB1 AB
NC NC
2
1

NO NO
J37 Brown SV1
Engine Run / Louver Activation Circuit C C
TB2 J24
SV
Blue
VMB1
NC NC
2
1

NO NO
C J38
Main Switch in HAND or OFF C
TB3 +
NC NC
J16 AI5
2
1 -
NO NO I/O
Engine Trouble C J39
C +
TB4
NC NC
J14 AI4
2
1 -

COM
NO NO

DI5

DI4
Pump Room Alarm C J40
C +
TB5
NC
NC J15 AI3
2 30 32 31
1 -
NO NO
C J42
(Field Programmable) C
TB6 +
NC
NC J17 AI2
-
SS1 H
OFF
A
Red
+
White
PT1
Low Fuel Level IN1 J18 AI1
- Black AUTO
Remote Auto Start J1* IN2
HAND
Deluge Valve Start J2* IN3 J25 53
J44 VIN
54
Fuel Tank Leak IN4

High Fuel Level IN5 J20 UP

DOWN
J8
MP+
J35
MP-

ECM Selector Switch in Alternate Position 301 301


J4 24V in
Fuel Injection Malfunction 302 302 24V out

Electronic Control Module Warning 303 15


303
BC1

BOOST
B1+ B1
16
Electronic Control Module Fault 304 304 B1- B2
J103 J106 17
CF1 Com
PLD Low Suction Pressure

ALARM
305 305 18 NO
High Raw Water Temperature 310 310 NC

Low Raw Water Flow 311 311 BATT. SUPPLY

+ - L N
19
Low Engine Temperature 312 312
BC2
BOOST

B2+ B1
B2-
20 B2
J107 63 11 13 54
Energize to Start Solenoid 1 1 CF2
21 Com
ALARM

22 NO
Engine Run 2 2
NC
Overspeed 3 3
BATT. SUPPLY
Low Oil Pressure 4 4 + - L N

High Engine Temperature 5 5 62


62
Battery 1 6 6 J104 6
6 CB3 83 11 14 54

Battery 2 8 8 63
63
Start Contactor 1 9 9 11
J105 11
Start Contactor 2 10 10

11 11 83
Ground 83
Ground 11 8
11 8
82 CB4
Energize to Stop Solenoid 12 12 DB1 82

Legend
53 54 AB Alarm Bell
BC Battery Charger
CB Circuit Breaker

IS1 CB2 DB Diesel I/O Board

53 F Filter
14
1L L' IS Isolating Switch
L
CB1 J Jumper
120-240 VAC
50-60Hz F1 13
PT
SS
Pressure Transducer
Selector Switch
1N
N 54 SV Solenoid Valve
E N' VMB ViZiTouch Main Board

Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
* Remove jumper to use this feature Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC 2 Revised logo 18/06/18
Dpt of Building
Approved 1 Corrected SS1 inputs 16/01/17 GPD-WS700 /E
0 First issue 10/11/16 CDL
2018 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Diesel Engine Fire Pump Controller Model:GPD
12VDC or 24VDC Negative Ground
Layout Built to the latest edition of the NFPA 20 standard

Designation Description
BC1-BC2 Battery Charger #1 and #2
CB1-2 Magnetic Breaker 1 Pole 10 A
CB3-4 Magnetic Breaker 1 Pole 16 A
DB1 I/O Diesel Board
F1 Filter
IS1 Isolating Switch

SS1 Lockable 3 Position Selector Switch


VMB1 ViZiTouch Main Board

BC1

VMB1

BC2
F1
54

0 - OFF 0 - OFF 0 - OFF 0 - OFF

SS1

IS1
DOWN
UP
AB

SV

AI5

AI4

AI3

AI2

AI1

24V in

CF1

CF2
-

B1-

B2-
+

B1+

B2+
VIN

24V out

62

63

83

82
6

DB1
NO

NO

NO

NO

NO

NO
NC

NC

NC

NC

NC

NC
C

C
2

MP+
IN1

IN2

IN3

IN4

IN5

MP-

10

11

11

12
301

302

303

304

305

310

311

312
NO

NO

NO

NO

NO

NO

2
3

8
9
NC

NC

NC

NC

NC

NC
C

C
1

Front Door Layout Internal Layout

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
1 Revised logo 18/06/18 GPD-LY700 /E
0 First issue 21/11/16 CDL
Diesel Engine Fire Pump Controller Model:GPD
12VDC or 24VDC Negative Ground
Terminal Diagram Built to the latest edition of the NFPA 20 standard
Power Supply Remote Alarm Terminals (DB1)
Terminals Wire Size: Terminals Wire Size:
14 - 6 AWG 24 - 12 AWG
3.9 Nm 0.5 Nm

120-240 VAC L
50-60Hz Normally closed
2

N Opens to alarm
NO

Normally open C

Controller Trouble Closes to alarm NC


J36
(Fail Safe)
Normally open
1
TB1
NO
Normally closed Closes to alarm C
Opens to alarm
Engine Connections (DB1) NC

Normally open
2

NO
Energize to Start Solenoid Closes to alarm
1 1 Engine Run Normally closed C

Engine Run
Opens to alarm NC
J37
2 2
Normally open
1
TB2
NO
Overspeed Louver Activation Circuit Normally closed Closes to alarm
3 3 C
Opens to alarm NC
Low Oil Pressure
4 4
Normally open
2
High Engine Temperature
5 5 NO
Normally closed Closes to alarm C
Battery 1 Opens to alarm
6 6 J104 NC
J38
Main Switch in HAND or OFF
Normally open
1
Battery 2 TB3
NO
8 8 Closes to alarm
Normally closed C
Start Contactor 1 Opens to alarm
9 9 NC

Start Contactor 2
Engine Terminal Strip

10 10 Normally open
2

NO
Ground Normally closed Closes to alarm C
11 11
Opens to alarm NC
Engine Trouble ** J39
Ground
Normally open
1
11 11 TB4
NO
Normally closed Closes to alarm
Energize to Stop Solenoid C
12 12 Opens to alarm NC

Normally open
2
ECM Selector Switch in Alternate Position
301 301 NO
Normally closed Closes to alarm
C
Fuel Injection Malfunction Opens to alarm
302 302 NC
J40
Pump Room Alarm **
Normally open
1
TB5
Electronic Control Module Warning NO
303 303
Normally closed Closes to alarm C
Electronic Control Module Fault Opens to alarm NC
304 304

PLD Low Suction Pressure J103


Normally open
2
305 305
NO
Normally closed Closes to alarm
High Raw Water Temperature C
310 310 Opens to alarm NC
(Field Programmable) J42
Normally open
1
Low Raw Water Flow TB6
311 311 NO
Normally closed Closes to alarm C
Low Engine Temperature
312 312 Opens to alarm NC

Field Connections (DB1)


Terminals Wire Size:
24 - 12 AWG
0.5 Nm

Low Fuel Level IN1 All wiring between the controller and diesel engine shall be stranded
(NFPA20)
Remote Auto Start J1* IN2

Deluge Valve Start ** J2* IN3


J25 Wiring between controller and engine (terminals 301, 302, 303, 304, 305,
Fuel Tank Leak ** IN4
310, 311, 312, 2 ,3 ,4 ,5) must be #14AWG as minimum.

High Fuel Level ** IN5

Wiring between controller and engine (terminals 12 [rated at 10A or 22A for
20 seconds] 1, 9, 10 [rated at 10A]) must be stranded #10AWG as minimum.
Network Connection (VMB1)
Shielded Female Connector RJ45

Wiring between controller and engine (terminals 6, 8, 11 [rated at 30A]) must


be stranded and sized according to distance.
Modbus TCP/IP

Drawing for information only.


* Remove jumper to use this feature Manufacturer reserves the right to modify this drawing without notice.
** Re-assignable Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
1 Revised logo 18/06/18 GPD-TD700 /E
0 First issue 10/11/16 CDL
Diesel Engine Fire Pump Controller Model:GPD
12VDC or 24VDC Negative Ground
Louver Connection Built to the latest edition of the NFPA 20 standard

Located in Controller
Engine Run Alarm Contacts

C-NO C-NC

Normally open Normally closed


Closes to alarm Opens to alarm

NO
NO
J37
C
TB2
C
NC
NC

M
Louvers Motor

Power Supply from a Reliable


External Power Source
(See NFPA20-2016 11.3.2 & A 11.3.2)

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved
1 Revised logo 18/06/18 GPD-TD701 /E
0 First issue 10/11/16
11/12/2017 QYZS.EX3971 - Pump Controllers, Fire

QYZS.EX3971
Pump Controllers, Fire
Page Bottom

Pump Controllers, Fire

See General Information for Pump Controllers, Fire

TORNATECH INC EX3971


#132
7075 PLACE ROBERT-JONCAS
ST LAURENT, QC H4M 2Z2 CANADA

Fire Pump Controllers: Models AF, AFP, AFR, AFY, ATF, ATR, ATP or ATY followed by C or N, followed by additional suffixes. All of the above
controllers are suitable for use on circuits capable of delivering high fault currents. The withstand ratings are as follows:

Max Short Circuit


Current RMS
Circuit Breaker Max V AC Symmetrical Amps

MZMH6-63, MZMH6-100, 208; 240 25000; 42,000

MZMH6-160, MZMH6-250

MZMH6-63, MZMH6-100, 480 65,000

MZMH6-160, MZMH6-250

The controllers provided with Automatic Transfer Switches are suitable for use on circuits capable of delivering high fault currents. The withstand
rating of the normal power source side is determined by the transfer switch as indicated below:

Max Controller Short Circuit


ASCO Transfer Switch Withstand Rating

9403704 22KA, 480 VAC Max

94031004 22KA, 480 VAC Max

94032604 35KA, 480 VAC Max

The withstand ratings for the alternate power source side will be dependent upon the ratings of the external circuit breaker provided. But in no
case will they exceed those of the normal power source side.

Models AL or AL1 followed by additional suffixes.

All of the above controllers are suitable for use on circuits capable of delivering high fault currents. The withstand ratings are as follows:

Max Short Circuit


Current RMS
Circuit Breaker Max V AC Symmetrical Amps

NZM6B-63, 480 25,000

NZM6B-100, NZM6B-160

The controllers provided with automatic Transfer Switches are suitable for use on circuits capable of delivering high fault currents. The withstand
rating of the entire controller is determined by the transfer switch as indicated below:

ASCO Transfer Switch Max Controller S. C. Withstand Rating

9403704 22KA, 480 VAC Max

94031004 22KA, 480 VAC Max

94032604 25KA, 480 VAC Max

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYZS.EX3971&ccnshorttitle=Pump+Controllers,+Fire&objid=10… 1/5
11/12/2017 QYZS.EX3971 - Pump Controllers, Fire
The withstand ratings for the alternate power source side will be dependent upon the ratings of the external circuit breaker provided. But in no
case will they exceed those of the normal power source side.

Authorities having jurisdiction should be consulted in all cases.

Model FPD Series controller for engine-driven centrifugal fire pumps.

Models FPA, FPP, FPR, FPS, FPV, FPW, FPY, VPA, VPR, and VPS may be followed by additional suffixes. The withstand ratings are as follows:

Withstand Ratings of Controllers Without Transfer Switch:

Short Circuit Withstand Ratings


(Ampere Symmetrical)

OPTIONAL
VOLTAGE STANDARD HIGH

200 to 480 V 100,000A RMS 150,000A RMS

575 to 600 V 50,000A RMS 100,000A RMS

Models ATG , ATU, VPG or VPU. The controllers provided with Automatic Transfer Switches are suitable for use on circuits capable of delivering
high fault currents. The withstand rating of the normal power side is the same as the withstand ratings of controllers without transfer switches.
The withstand rating of the alternate power side is determined by the transfer switch as indicated by the following tables:

Withstand ratings of controllers with 120 A Tornatech Inc. Transfer Switch

200-208V 230-240V 380-416V 440-480V 600V


50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 60Hz Withstand
Rating (A)
MAX HP MAX HP MAX HP MAX HP MAX HP

40 40 — — — 65,000

— — 60 75 — 25,000

— — — — 100 18,000

Withstand Ratings For Controllers with Ascolectric Transfer Switches

Withstand
Rating Specific**
Transfer 200-208V 230-240V Withstand
Switch 50/60 Hz 50/60 Hz Time Rating
(A) Max HP Max HP (A) (Cycles) (A)

100 30 30 10000 1.5 22000

150 50 50 1000 1.5 22000

400 150 150 35000 3 42000

600 N/A N/A 50000 3 65000

** Tested and found suitable for 100kA

Withstand Ratings for Controllers with Ascolectric Transfer Switches, Continued

Withstand Rating
Transfer 600V Specific Withstand
Switch 60 Hz Time Rating
(A) Max HP (A) (Cycles) (A)

100 75 10000 1.5 N/A

150 150 1000 1.5 N/A

400 400 22000 3 N/A

600 N/A N/A N/A N/A

Model ATU or VPU: Normal Power Side: Same as withstand rating of controller without transfer switch.

Alternate Power Side: Same as withstand rating of controller without transfer switch.

Model FPL: Limited Service controllers with withstand ratings as follows:

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYZS.EX3971&ccnshorttitle=Pump+Controllers,+Fire&objid=10… 2/5
11/12/2017 QYZS.EX3971 - Pump Controllers, Fire

Short Circuit Withstand Ratings of Limited Service Controllers Without Transfer Switches

OPTIONAL
VOLTAGE STANDARD HIGH

200 to 480 V 25,000 A RMS 65,000 A RMS

575 to 600 V 18,000 A RMS 25,000 A RMS

Model LTG, GLG: Automatic transfer switch for connection to a generator set.

Model LTU: Automatic transfer switch for connection to a 2nd utility.

Withstand ratings of Controller with transfer switch Model FPAT (Tornatech):

Model LTG: Normal Power Side: Same as withstand rating of controller without transfer switch.

Alternate Power Side: Withstand rating only applies when the generator
set is protected by a molded case circuit breaker

TRANSFER SWITCH 200-480 V WITHSTAND RATING


AMPERES H.P. AMPERES

120 30 25,000

TRANSFER SWITCH 600 V WITHSTAND RATING


AMPERES H.P. AMPERES

120 30 18,000

Model LTU: Normal Power Side: Same as withstand rating of controller without transfer switch.

Alternate Power Side: Same as withstand rating of controller without transfer switch.

Withstand ratings of controller with transfer switch Model 940 (Ascolectric):

Model LTG: Normal Power Side: Same as withstand rating of controller without transfer switch.

Alternate Power Side: Withstand rating only applies when the generator set is protected
by a molded case circuit breaker not exceeding the ampere rating of
the transfer switch.

Withstand Rating
Transfer 200-480 V Specific Withstand
Switch A Max HP A Time Rating A

120 30 10,000 1.5 22,000

Withstand Rating
Transfer 600 V Specific Withstand
Switch A Max HP A Time Rating A

120 30 10,000 1.5 N/A

Model LTU: Normal Power Side: Same as withstand rating of controller without transfer switch.

Alternate Power Side: Same as withstand rating of controller without transfer switch.

Models CPA, CPP, CPR, CPS, CPV, CPW, CPY, may be followed by additional suffixes. The withstand ratings are as follows:

Withstand ratings of controllers without transfer switch:

Short circuit withstand ratings (ampere symmetrical)

voltage standard optional

200 to 480 V 100 kA 150 kA

575 to 600 V 50 kA 100 kA

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYZS.EX3971&ccnshorttitle=Pump+Controllers,+Fire&objid=10… 3/5
11/12/2017 QYZS.EX3971 - Pump Controllers, Fire
Model CPU - The controllers provided with automatic transfer switches are suitable for use on circuits capable of delivering high fault currents.
The withstand rating of the normal power side and the alternate power side is the same as the withstand ratings of controllers without transfer
switches.

Model CPU

Short circuit withstand rating for alternate power circuit with transfer switch (RMS Symmetrical)

V Standard High (optional)

200 to 480 V 100 kA 150 kA

575 to 600 V 50 kA 100 kA

Model GPD Series controller for engine-driven centrifugal fire pumps.

Overcurrent Protection Panels, Model OPD; may be followed by a number 200 through 575 with - or /; followed by a number 200 through
600 with /; followed by a number 10 through 500 with /; followed by 1 or 3 with /; followed by 50 or 60 or 50/60. - These panels provide
separate overcurrent protection and disconnect to comply with NFPA 70 Article 695.4(B)(2)(a) and 695.4(B)(3) and NFPA 20 Article 9.2.3.1,
9.2.3.4, and 9.2.3.4.1.

Short Circuit Withstand Ratings, A Symmetrical

V Standard High (Optional) High Capacity

200-480 25,000 35,000 to 65,000 150,000

575-600 18,000 20,000 to 25,000 50,000 to 100,00

Battery chargers, BCE10, followed by 12 or 24, followed by 120 or 220.

Fire pump controllers, horsepower rated, Models GPA, GPAe, GPP, GPR, GPS, GPV, GPY, GPYe or GPW; may be followed by a number 110
through 575 with - or /; followed by a number 200 through 600 with /; followed by a number 1 through 500 with /; followed by 1 or 3 with /;
followed by 50 or 60 or 50/60.

Fire pump controllers, kilowatt rated, Models GPA, GPAe, GPP, GPR, GPS, GPV, GPY, GPYe or GPW; followed by -400/; followed by a number
0.75 through 315 with kW/; followed by 3 with /; followed by 50 or 60 or 50/60.

Transfer switch, horsepower rated, Model GPU; may be followed by a number 110 through 575 with - or /; followed by a number 200 through
600 with /; followed by a number 1 through 500 with /; followed by 1 or 3 with /; followed by 50 or 60 or 50/60.

Transfer switch, kilowatt rated, Model GPU; followed by -400/; followed by a number 0.75 through 315 with kW/; followed by 3 with /;
followed by 50 or 60 or 50/60.

Withstand ratings of normal power circuit for GPA, GPAe, GPP, GPR, GPS, GPV, GPY, GPYe and GPW controllers with or without
gpu transfer switch.

Short Circuit Withstand Ratings for normal power circuit with or without transfer switch, A Symmetrical

V Standard High (Optional) +

200-480 100,000 150,000

575-600 + 50,000 100,000

+ - Not applicable to controllers that use NOARK Power Components.

Limited service fire pump controllers, kilowatt rated, Models GPL; followed by -400/; followed by a number 0.75 through 315 with kW/;
followed by 3 with /; followed by 50 or 60 or 50/60.

Limited service fire pump controllers, , kilowatt rated, Models GPL; followed by -400/; followed by a number 0.75 through 315 with kW/;
followed by 3 with /; followed by 50 or 60 or 50/60.

Limited service transfer switch, for connection to a second utility, horsepower rated, Model GLU; may be followed by a number 110 through
575 with - or /; followed by a number 200 through 600 with /; followed by a number 1 through 500 with /; followed by 1 or 3 with /; followed
by 50 or 60 or 50/60.

Limited service transfer switch, for connection to a second utility, kilowatt rated, Model GLU; followed by -400/; followed by a number 0.75
through 315 with kW/; followed by 3 with /; followed by 50 or 60 or 50/60.

Withstand ratings of normal power circuit for GPL controller with or without GLU transfer switch.

Short Circuit Withstand Ratings for normal power circuit with or without transfer switch, A Symmetrical

V Standard High (Optional)

200-240 65,000 -

380-480 25,000 65,000

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYZS.EX3971&ccnshorttitle=Pump+Controllers,+Fire&objid=10… 4/5
11/12/2017 QYZS.EX3971 - Pump Controllers, Fire
575-600 18,000 25,000

Click here to view the Colombia Market Access Certification

Last Updated on 2017-02-09

Questions? Print this page Terms of Use Page Top

© 2017 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=QYZS.EX3971&ccnshorttitle=Pump+Controllers,+Fire&objid=10… 5/5
Certificate of Compliance
This certificate is issued for the following:

CONTROLLERS FOR LOW VOLTAGE ELECTRIC MOTOR DRIVEN FIRE PUMPS


MODEL GPx and GPxFM SERIES

Prepared for:
TornaTech Inc
7075 Pl Robert-Joncas, #132
St Laurent, QC H4M 2Z2
Canada

Manufactured at:
TornaTech Inc TornaTech Europe SPRL
7075 Pl Robert-Joncas, #132 Avenue Sabin 3
St Laurent, QC H4M 2Z2 1300 Wavre
Canada Belgium

FM Approvals Class: 1321/1323

Approval Identification: 0003032642 Approval Granted: July 1, 2010


Approval Identification: 0003040606 Approval Granted: November 5, 2010
Approval Identification: 0003041613 Approval Granted: May 17, 2011
Approval Identification: 0003042367 Approval Granted: November 4, 2011
Approval Identification: 0003047451 Approval Granted: January 15, 2013
Supersedes original Certificates of Compliance.

Said Approval is subject to satisfactory field performance, continuing Surveillance Audits, and strict conformity to the
constructions as shown in the Approval Guide, an online resource of FM Approvals.

To verify the availability of the Approved product, please refer to www.approvalguide.com

June 13, 2013


Richard B. Dunne Date
Group Manager – Fire Protection
FM Approvals
1151 Boston-Providence Turnpike
Norwood, MA 02062

FM Approvals HLC
04/13