Professional Documents
Culture Documents
Fasteners Test Report DHBVN
Fasteners Test Report DHBVN
Fasteners Test Report DHBVN
ffi
IJ"ESN
trrr*s D ,s ltff*' suu rry-frstr nffifriil
12'2013
Specification No, CSC- 73'R'1 /BH/U H/P&D/20
Technical Specification for Hot Dip Galvanized Hexagonal Head Bolts and Nuts, Electro
Galvanized Spring Washers and Hot Dip Galvanized Step Bolts
1. SCOPE ..
1.1 This specification provides for design, manufacture, testing and manufacturer's works
before dispatch, supply and delivery of Hot Dip Galvanized Hexagonal Head Bolts
with
nuts, Electro Galvanized Spring Washers and Hot-Dip Galvanized Step Bolts for use
on
33 kV and above power transmission lines and substation structure in the State of
Haryana.
2. STANDARDS:
Spring
2.1 Hot Dip Galvanized Hexagonal Head Bolts with nuts, Electro-Galvanized Hexagonal
following
Washers and Hot Dip Galvanized Step Bolts shall comply in all respects with the
lndian Standards which shall mean latest revision, amendments / changes adopted and
published unless othenruise specified hereafter.
3 ts-10238
4 lS-1363 (All Parts) Elacf hexagon bolts, nuts & lock nuts (diameter 6 to 39 mm; ano
Black hexagon screws (diameter 6 to 24. mm)
5 S-1367 (All Parts) Techn'lcal supply conditions for threaded steel fasteners
6 5-4218 (All Pads) ISO metric screw threads
7 s-2633 Methods of testlgullglmity of coating on Zinc coateo antoes
B s-2614 methods for sampling of fasteners
I s-4072 Stcel
_--___. for snrino
_f-__,v washers
10 s-1586 &C scales) for steel'
11 s-6821 fi/clhnds for samolino non-threaded fasteners
12 rs-2016 Plain washers
W l}#hJttl
TII.Tf;fi. D fiIBYJIATL BIJTI $TA*tr trIEiIH
#*"
2.2 Material manufactured according to any other international and authoritative standards
which ensures an equal or better quality material than in the specification mentioned above,
shall also be acceptable. The salient points of differences between the standard adopted
and the Indian Standard Specifications referred above, or these specification shall be
brought out in a comparative statement to be attached with the tender. The specific
standard, to which the material quoted by the tenderer shall comply, shall be clear stated
3. CLIMATIC CONDITIONS
The equipmenUmateriat to be supplied against this specification shall be suitable fot
The equipment shall be for use in moderately hot and humid tropical climate, conducive to
C:\DocumentsAndSettings\Uhbvn\Desktop\12.03.2013.Doc Page3ofl-4
rrrtr Efuur Elfrdnnr ffi ftffdrsr ftrdrd .._.S-:;'
urr*R D*BFrIlr n*nt'*n* Br,rH InruJril rn6*H ,rpF*'swru
r_r-GhAl
G.l Nuts and Bolts shall have hexagonal head with threads conforming to clause B g of lS:
4218 (Par1-6) 1978'lSO metric Screw threads'with latest amendments for M 16 size botts
with nuts,
4.1,1 DIMENSIONS
The bolts shall be of product grade C as specified in lS: 1367 (Parl-2)-1979 ' Technical
supply conditions for threaded steel fasteners" (Part-2) for product grades and tolerances
(second revision).
4.1.3,1 The hexagonal nuts used with these bolts shall conform to the requirements of lS: 1363
(Part-3) 1984. The nuts shall be of property class 5 as specified in lS: 1367 (Part-6)-1980.
The proof stress for the nominal nuts size M 16 shall be 490 N/mmz,
4.1.3.2 Nuts shall be hot dip galvanized in accordance with clause 6 of lS: 12427-1988.
4.1,4 MECHANICAL PROPERTIES
4.1,4.1 The mechanical properties of bolts with conform to class 5.6 as specified in lS: 1367 (Part-
For Tensile, proof load and wedge loading tests, three threads only shall be exposed
between the grips. This is obtained by freely running the nut or fixture to the fullest extent
and then unscrewing the specimen three full turns. These tests are to be done after
chemically degalvanising the bolts,
Bolts having nominal length less than the 3 times the nominal diameter shall meet the
4,1.4,2 The shear strength and the testing for shear strength of the bolts shall be in accordance
4,1,5 FINISH
4.1.S.1 The bolt's heads shall be neatly finished and free from fins, scales and other defects. The
threads of nuts shall not be torn or rubbed and shall be of proper contour, Bolts and nuts
shall be completely inter-changeably. The bolts and nuts shall be hot dip galvanized in
accordance with the requirements of lS: 1367 (Part-13)-1983. The uniformity of zinc
4.1,5.2 Hot dip galvanized bolts and nuts shall be passivated by dipping, immediately after
galvanizing in a 0,15% Solution of Sodium dichromate with 0.5% concentrated sulphuric
acid maintained at a temperature more than 32oC to provide protection against wet storage,
i:LZ' 35|!tff] iltirt'*:tl3Tffi rength upto 10 times the diameter or the borts shourd be
manufactured by cold forging and thread rolling process to obtain good and reliable
mechanical properties and effective dimensional control. The shear strength of bolts for
5.6 grade should be 310-MPa minimum as per lS: 12427, bolts should be provided with
4.1.6,2T0 ensure effective in-process Quality Control it is essential that the rnanufacturer should
have all the testing facilities for test like weight of zinc coating, shear strength, other testing
facilities etc, in house. The manufacturer should also have proper Quality Assurance
System which should be in line with the requirement of this specification and lS: 14000
Quality System,
4.1.0.3 The permissible sudace discontinuities of the bolts shall conform to lS: 1367 (Part-9)-1979
'Technical supply conditions for threaded steel Fasteners' (second revision)'
4.16,4 The requirements which are not covered underthe standard lS:12427-1998, shall conform
to lS:1367 (Part-1) 1980 (Seconcl revision).
4,1.7 DESIGNATION
The bolts shall be designated by nomenclature, threaded size, nominal length and the
number of B.l.S standard. The letter N and W shall be added to the designation to indicate
C:\DocumentsAndSettings\Uhbvn\Desktop\12'03.201.3'Doc Page5ofl-4
Edtr trfur Ffraron ftrdr& ftraqur ftil-drff
single coil rectangular section confirming to lS: 3063-1972. The spring washers shall be
made from suitable steel according to 1S: 4072-1975 'specification for steel for spring
washers' (1st Revision) to meet with the requirements specified in clause 5 of lS: 3063-
1gT2. The surface of the washers shall be free from scale and burrs. The spring washers
shall be Electro-Galvanized. The washers shall be coiled without any kinks. The outer
edges may be slightly rounded or sharp, The ends of the washers shall not abut when
4.2.2 TYPES
The spring washers shall be of type-B Spring washers with flat ends
4.2.3 DIMENSIONS
and
Spring washers shall be designed by the normal size, type, the number of this standard
For example a single coil spring washer having a nominal size 16 type-B with Electro-
Spring washers after coiling shall be suitably heat treated, s0 as to result in the
finished
washer having hardness in the range of 13 to 50 HRC, when tested in accordance lS: 1586
' Methods for Rockwell hardness test (B and C scales) for steel (1st Revision),
C:\DocumentsAndSettings\Uhbvn\oesktop\12'03.2013.Doc Page6of14
Errq dfutrr EftHKrn ffi fuffror ftil-na
WLJ.Gfvt*l
wT*B Df,n$ilrt n*nt'*n*. BIIII firtr*r mfif;H
4.3 GENERAL TECHNICAL REQUIREMENTS FOR HOT DIP GALVANIZED STEP BOLTS
Step bolts conforming to lS: 10238-1982 shall be suitable for use on transmission towers
Each bolt shall be supplied with two hexagonal nuts and two plain washers of thickness
5+1/-0 mm. The hexagonal nuts to be used with step bolts shall conform to the
requirement given in lS: 1363-1967'Specification for black hexagonal bolts, nuts and lock
The plain washers used on these Step Bolts shall conform to the requirements of lS: 2016--.
The plain washers shall be Hot dip Galvanized in accordance with the requirements of
lS:4759-1984 "Specification for Hot-Dip Zinc coating on structural steel and other allied
products" (Second-revision) except that the minimum value of the average mass of coating
The Step bolts & nuts shall be galvanized as specified in lS: 1367 (Pad-Xlll)-1982
'Technical supply conditions for threaded steel fasteners' Part-Xlll Hot Dip Galvanized
coating on threaded fasteners'. The length of step bolts shall be 175 mm in accordance
with lS: 10238-1982 (Amendment No.2). The dimensions of the nuts before galvanizing
shall be conforming to lS: 1363-1967. Plain washers shall be conforming to lS: 2016-1967.
The dimensions & tolerances for the step bolts shall be conforming to lS: 10238-1982
(Amendments No.2).
4.3.2 GRADE
supply condition for threaded steel fasteners Part-ll Product grades and tolerances'
(Second revision).
C:\DocumentsAndSettings\Uhbvn\Desktop\12.03,2013.Doc Page7ofL4
Ftrtr Efur Elfrartln ffi fud;ror ftrdrdr
"'4$;;'
ffiffi UTT,i$T D*ESHIF N*AYNN* BLIII TNTRJffi I{IEf;H ,ffinx.xswm
{...'"""
and tests methods for bolts, screws and nuts with full lodability (Second revision).
4,3.4 DESIGNATION
The step bolt shall be designated by size, length and number of BIS Starrdard.
For example a step bolt of size M 16 and length 175 mm with 2 nuts and2plain washers
Hardness Test, permanent set test and Twist-Test shall be carried on spring washers in
The step bolt shall not have any permanent set when subjected to the cantilever test as per
shall be accordance with lS: 2614-1969 'Methods for sampling of fasteners' (1st Revision).
6,2 Sampling size and acceptance criteria for Electro Galvanized spring washers shall be in
6,3 The method of sampling and acceptance criteria for Hot dip galvanized step bolts shall be
in accordance with lS:2614-1969 ' Methods for sampling of fasteners' (1st Revision),
6.4 The Hot dip galvanized hexagonal head bolts with nuts, electro-galvanized, spring washers
and hot dip-galvanized, step bolts offereci against this specification shall be subjected to all
the tests specified in the latest editions of the relevant Indian Standard Specifications as
referred in this specification and the test results shall conform therewith. Every test shall be
C:\DocumentsAndSettings\Uhbvn\Desktop\12.03.2013.Doc PageBof14
trfit E'fuur gfiraron fttildt futrdrrr ftil-dlil 'i" '
#g{.._.
UTT*R Dr*ESftI[ g^*8{*ilf,. BLIII IriTB.*tr r{r6*H -,Lry'HffiVru
ffiiffi
Ll-S$t'N
t,-.,/'
material,
7.0 INSPECTION --
all times to the works and all
7.1 The purchaser and its representatives shall have access at
hexagonal head bolts with nuts,
other places of manufacture, where the hot dip galvanized
8.1 The hot dip galvanized hexagonal head transmission tower bolts shall be marked with the
following symbols on the top surface of.the bolt head either embossed or identified as given
below:-
Minimum height of marking shall be 3.0 mm. When embossed, marking shall
project not less than 0.3 mm above the surface of the head and total head height (Head
plus marking) shall not exceed the specified maximum head height plus 0.4 mm,
8.2 Electro galvanized spring washers shall be packed in cartons of 500 or 1000 numbers.
Each carton containing the spring washers shall be marked with the manufacturer's name
8.3 Hot dip galvanized step bolts shall be marked and packed as specified in lS: 1367 (Part-
xvlll)-1 97e.
The tenderers are required to quote on per metric tonne rate basis for each size of bolt with
The quantity and delivery schedule shall be as per Annexure-l attached herewith.
1O.O GUARANTEEDTECHNICALPARTICULARS
The guaranteed technical particulars duly signed are required to be furnished by the Bidder
The materjal offered / received after the inspection by the authorized inspecting
Officer may again be subjected to the test for losses or any other parameters from any
testing house / in house technique of the Nigam having requisite capabilities and facilities.
the lot shall be rejected and bidder shall arrange to supply the within thirty (30) days of
C:\DocumentsAndSettings\Uhbvn\Desktop\12.03.2013.Doc Page10of14
ET{ Efuor €frstoTr ftffi fuffsr ftil-drff
penalty @
such detection at fiis cust including,to & fro transportation, In addition to this a
rb
Generral
Member
len
Cumrl\Mt csc
/N,l Pancl
P
\'-{. l
V*q
t,./
t
vl
1.
\
ANNEXURE-I
Nuts
ANNEXURE.II
nforming to ls:1367
art-6) property class 5
Sources of recei
Contents of Sulphur, Carbon and
ts'.12427-1988 lS:3063-1972
with lndian Standard No'
lS:2016-1967 lS: 10238-1982
ln respect of M16 X 40 N
lS 12427 or anY other
relevant lS as aPPlicable
ln respect of M16 X 300
N lS: 12427 or anY other
relevant lS as aPPli
Name
Designation ,....
Date .
Doc Page 13 of L4
C:\Docu ments And Settin gs\Uhbvn\Desktop\12'03'2013'
futr{sr ftildttr
'-rrtr Efunr
FftirTun fttu1'6qb
ffi
t
,"#:i
M-.l***
urr*R Df,Hsflffi n*nf*n*. gHLl v|ruf,ff FIfff,H ,il:'F5'=tir';
l"$#&thl
ANNEXURE.II
(Contd.)
G u A RA N T E E D TEc HN I co t t$Tt N I z E D s P R I N G -wA s H E R s
suLlff 3J 5i ifil1l;G#hvA
1. GENERAL
ffii''*Name
Place of Manufacture
ldentification Mark
2. SPECIFICTION AND STANDARD
Electro-G alvan ized SPri ng
Washers Galvanizing
3. SIZE
4, RAW MATERIAL
Grade
Type of Steel used
5, CHEMICAL COMPOSITION
Carbon
Phosphorous (Max.)
Sulphur (Max.)
Silicon (Max,)
Magnise
7 , PACKING DETAILS
Any other particulars as the tenders may line to give
Designation ..
Date
C:\DocumentsAndSettings\Uhbvn\Desktop\12.03'2013.Doc PageL4ofL4
SPECIFICATION NO. HSD/S-364/ST-163
OFFICE OF THE
Offil:l.: of Ik :
Chief l:.!w.inecr
. / .FiaIUlU!2. ..
mesurinc c:urrcnt lrlllL.ifnrttta'S fOt· uqe with low tem;ion ~ llha.qe 4 wire, wntthoul' mett":l'il
Ull:lwlt:u t?ll 41S V, 3 pltalle;: 4 wU.t~ 50 Hz. lIuliUly e;:io:lhc:J lIupply 8,yl>'(e;:m ali pea' IIhc;:uvle;: or
requirement mentioned in Appt-ndi" - A.
specification, the current tran.:.-formcrs shall comply \'tith the latest 'version of thc follo\\ing
Stnndal'ds :
frequency test voltage of3 kV (un.s.) for one ( 1 ) minute. The insuldtion material uscO in
:the c:r.s shall be of non-hygroscopic nature.
muumum diameter (if tbe ccntral opcni!'2 (if tbc Currcnt Tran~ionncrs 6hall bc in
accordancc with the appIOpriatc size of 'PVC eat.l~ to be used with the l!~eifie rating of
the CT.
Fixing hmcKet~ shall he pro,,~dedfor
fixing the CTll on to any flat muface with the help ofhra.'lll QCreWllOf hoJlq aud nut'l. The
houscd in tcnninal block with se.aling cover of non-hygroscopic insulating rnatnial. Thc
tenninal block shall have sealing arrangement to prevent tunptrring. TIle name plate of the
CT should be embedded on the front of1he bo(ly bl-Having a hole pa.~sillg through name
pIale :md resin bott)· of CT for their se,Uing :iL the lime of testing in M&T bbor:llory. The
secondary leads of 1.5 melrc:s lenglh, fur each CT & each phase, willi proper imuli\tion
8. l\1.·\RKING EveryCurrentTr.:.p.sfonner
shallbe
indelibly aiid clearly marked- VYith the particulars mentioned in the m ; 2705 ( Part-I) and
IS : 2i05 ( Part-II) under Lhi:l hc;ad. Further, Lhe fi)lIuwing Khuuld he either marked
inddibly or punr,;hed on t:ar,;h CT :
i) Prope.rty ofDHDV1'-'L
9. mSTS
i) All tests shaH be made <It the place of manu!ilclUre u!lk:,~;
plIr-.;h;IS;';.
It)
the cost of the supplier. by an independent ,,!!cncy, whenever ther is ctispm,: F,>n,\Id:!I? [ile
iii) .~II the Type & Routine Tc.c;tRac;lqlccified in the IS : no,;
(Part - I & IT) 1992 shall be carried out in 3ccord3nce with the Indian Standards Referred
11. DRA\YlNGS &. LITERATURE The bidd~r .hall submit with his bid,
dimensioned drawings of the CTs along with the illustrative and descriptive literature. Any
other drawing, if required, by the purchaser shaD be supplied by the tenderer without any
,.
charges. Thc magm:lisaliun.curvc oflhc CT cure shall also be supplielllo the purchas<.:r by
The te.c.hnic
.•11 and g\~~rante,d
particulars f')r the CTs sMll be supplied in.the fOIDl. in Appendi.'t - B by the tenderer.
l
6j[1 for S.F../Planning &&Design,
C.E.iflbning
([l DIID\'NL,
~~ v \b,
Design,
IIisaf.
/ APPF.NDTX - A
T.T ring lype, epoxy reHin ca.'!l CT He!.'!.Each Het cumpriHing or three TlOH. similar
CTI') 8uilable lor indoor in.'$laIlalion lOr commercial melering purpose a:s per leclmical
details of the specific .•1tion<ienclose.d and of following rating.'i :
500/5
600/5
200/5
1500/5 A
300/5
800/5
400/5
looD/SA AA
J\
v)
iii)
iv)
vi)
vii)
ii)
"111)
APPENDL"{ - D
4. Rated Voltage
5. Current Transformer Data
6. I) fulled Primal)" Cum,;nl
v) AccuraCY Class
9. MOWlting Debils
10. OVerall Dimensions
11. Charactt:r:llic:l :
“TECHNICAL SPECIFICATION
FOR
11 kV CAPACITOR BANKS
&
ALLIED EQUIPMENT
OFFICE OF THE
CHIEF ENGINEER,
PLANNING, DESIGN AND
CONSTRUCTION, DHBVNL,
VIDYUT SADAN, VIDYUT NAGAR,
HISAR.-125005.
MONTH OF ISSUE
TECHNICAL SPECIFICATION FOR 11 KV SHUNT CAPACTORS
1 SCOPE:
The specification covers the design, manufacture, testing at manufacturer’s works before
despatch, supply and delivery F.O.R destination of the following equipment:
i) Capacitor banks complete with capacitor units provided with internal/external fuses and
internal discharge resistors, mounting racks arrangement, bus bar and connecting
material, post insulators and other accessories etc.
ii) Residual voltage transformer.
iii) 11 kV 400 Amps Line-cum-earth switch.
iv) Pedestal / structure of above equipment.
v) Terminal connectors for above equipment.
2. PARTICULARS OF THE SYSTEM :
The capacitor banks and RVT are required for use on 11 kV, 3 phase, 3 wire AC 50 Hz +/- 2.5
Hz solidly earthed system. Normally where 11 kV winding of power transformers are star
connected, the neutral shall be solidly grounded. The maximum short circuit level at the S/Stn.
is 18.4 KA, auxiliary supply available will be single phase 230 + 10% -20%, 415 Volt +10% -
20%, 3 phase AC & 220 Volt +/- 10% DC.
3 STANDARDS:
The shunt capacitor bank and associated equipment shall conform to the latest editions of
the following standards except to the extent explicitly modified in the specification and shall also
be in accordance with requirements of these specified:
a Capacitor IEC/871-1/87/IS-13925(Part-I) 1998
b Series Reactor IS-5553
c Internal Fuse IEC-593
d External Fuse IEC-549/IS-9402
e RVT ISS-3156 or respective IEC
f L&E Switch ISS-9921 or respective IEC
3 SERVICE CONDITIONS:
Equipment to be supplied against this specification shall be suitable for satisfactory
continuous operation under the following tropical conditions:
i Location In the Haryana State
ii Max. ambient air temp.(deg.C) 50
iii Min. ambient air temp.(deg.C) -2.5
iv Daily average air temp. (Deg. C) 35
v Average No. of Thunder strom days per 45
annum.
vi Max. relative humidity (%) 100
vii Min. relative humidity (%) 26
viii Average annual rain fall (mm) 900
ix Max. Wind pressure (kg/Sq.m) 195
x Max. Altitude above mean sea level(meters) 1000
xi Isoceraunic level (dyas / year) 45
xii Seismic level (horizontal acceleration) 0.3g
xiii Average No. of rainy days per annum. 120
NOTE : Moderately hot and humid tropical climate conditions to rust and fungus growth. The climate
conditions are also prone to wide variations in ambient condition. Smoke is also present in the
atmosphere. Heavy lightening also occurs during June to October.
i) 11 kV rating capacitor bank shall be made up of single group star connected bank
un-earth with a floating neutral connected by RVT (Residual Voltage
Transformers ) of ratio 11 kV /√3 –110/√3-190 Volt star/star/open delta to operate
protective relay.
ii) The protective scheme shall be by a two step relay one step current arranged as
follows:
If the failure of one or more units causes an over-voltage of less than 10%
tolerable on the other remaining healthy units, then the unbalance current shall
cause in the first step to sound an alarm. But, if more than the above number of
units fail, causing a voltage rise of more than 10% then the unbalance current
shall cause to trip and isolate the capacitor bank instantaneously.
iii) The per phase and individual star group rating shall be built by series parallel
combination of individual unit so as to achieve the desired bank rating. The
individual capacity rating shall be as per IS:13925 Part-I.
iv) All parallel units in one series group shall preferably be arranged in different tiers,
that is, one series group shall be duly insulated from one another by post
insulators adequate to withstand the voltage that may be impressed and shall be
sufficient to withstand even in case of total failure be duly insulated from the
earth potential by supporting post insulators.
v) Although the tolerances in the output rating of each individual units shall be as
per IS:13925. Yet it shall be ensured that in a completely assembled bank, the
departures from the nominal rating and within the specified tolerances values
shall not cause nuisance alarm or tripping since such alarm or tripping shall be to
meet only with the protective requirements specified.
vi) The tolerance in the output ratings shall not cause departures in the line currents
by that value specified in IS:13925. Besides it shall also be ensured that these
unsymmetrical current shall not cause unsymmetrical voltage rise, whether for a
short period or during prolonged operation.
vii) Individual units shall be designed to meet with the requirements of the
permissible overloads as specified as per IS:13925. Each unit shall also be
provided with internal discharging devices complying with the requirements of
IS.
5. TROPICAL TREATMENT AND PAINT :
All corrodible parts and surfaces shall be of such material and shall be provided with
such paints or to other protective finish that no part of the installed equipment shall be
injuriously affected by the atmospheric moisture and heat.
6. INSTRUCTION PLATE AND MARKING:
All name plates, instruction plates, warning signs and any other marking what-so-ever in
the equipment and its parts and accessories shall be in English / Hindi using idioms,
works and meanings in current use in India.
In order to facilitate sorting and erection at site, every part of the plant and equipment,
shall be suitably marked, these marking shall corresponding to similar marks on the
assembly drawing.
7. EARTHING:
All metallic parts not meant to be connected to live circuits shall be earthed. All earthing
connections shall be of the bolt and clamp type secured with lock nuts:
8. RATING OF EQUIPMENT:
The rating of equipment and other particulars such as nominal system voltage, one
minute power frequency withstand voltage, standard impulse withstand voltage and
rating of banks / unit in KVAR, is as under:-
i) Nominal system voltage 11 kV
ii) a) Rated voltage of capacity banks 12.65 kV
b) Rated output of Capacitor banks at rated voltage 3000 KVAR
iii) Connection of capacitor bank. Single star
iv) Rating of Capacitor Units with external fuses 7.3 kV
200 KVAR
v) No. of units per bank with external fuses 15 Nos.
vi) Capacitor KVAR available at Nominal system voltage 2268 KVAR
(without series reactor)
viii) Insulation level
a) Impulse withstand voltage 75 kV (peak)
b) Power frequency withstand voltage 28 kV (rms)
9 (i) Type of Capacitors :
The Capacitors shall be of unit type suitable for outdoor installation having high
dielectric strength. Special attention shall be paid in design of the capacitors to
avoid any stresses due to expansion or contraction caused by large variation of
ambient temperature at site which may range from –2.5ºC to 50ºC. Scope of
supply of capacitor banks shall include capacitors unit / residual voltage
transformer, 11 kV Isolator with earth switch and all necessary supporting
framework pedestals, bus bar connections, fuse connecting clamps. Terminal
connector and accessories etc. required to complete / commission the bank. Each
capacitor units shall be self contained outdoor type, with a rating as specified in
clause 8 above. The capacitor shall be rated to operate at 50ºC upper limit of
temperature category as per Table –I under clause 4.1 of IS:13925/Part-I/1998 or
any other standards applicable. The capacitor shall be designed to withstand a
continuous 10% over voltage and each unit shall satisfactorily operate at 130% of
rated KVAR including factor of over voltage, harmonic current and
manufacturing tolerance. The bidder will furnish calculations to satisfy the above
aspect.
ii) Type of Dielectric / Paper used:
The bidder should only quote for non-PCB type impregnent as per international
norm.
10. PHYSICAL ARRANGEMENT OF BANK:
Each bank shall be connected in single star, neutral connected through a Residual voltage
transformer. The No. of parallel units in each series group should be large enough so that
failure of any one unit will not create an over-voltage of more than 10% on the remaining
units in parallel with it.
Detailed calculations regarding the voltage impressed upon the remaining parallel unit
when one or more units gets out of order in series group shall be attached with the bid.
The bidder shall provide fully dimensioned general lay out showing arrangement of
capacitor units, spacing, stacks and steps, with his bid. The dimension of each unit shall
also be shown. The bidder shall state total number of capacitor unit per bank. Number of
series groups per phase, & number of units in a parallel group shall be included in the
said general lay out.
11. MOUNTING RACK ASSY.AND MOUNTING STRUCTURE FOR CAPACITOR
BANK.
The mounting rack and pedestal shall be galvanised steel members with all galvanising
carried out after completion of cutting, drilling and punching. Mounting rack shall be
completed with rack insulators, hardware etc. for assembly into complete banks.
The height of mounting structure for capacitor banks shall be such that the minimum
clearance from live part to ground will be about 2.5 meters.
12. BUS BAR MATERIAL :
Suitable bus bar arrangement shall be proposed by the bidder and requisite quantity of
bus bar material shall be provided for the bank. The normal current rating and the short
time current rating of the bus may be specified.
All the interconnecting material necessary for the interconnecting the units in series,
parallel combination shall be supplied.
A warning instruction “DISCHARGE CAPACITORS BEFORE HANDLING” shall be
prominently marked in red.
13. FUSES :
Each capacitor unit shall be individually protected by explosion type fuse of suitable
rating and interrupting capacity so that a faulty capacitor unit shall be disconnected by
fuse.
The fuse shall be satisfactory for operation under the ambient condition. The fuse shall
have sufficient strength to withstand the mechanical stresses associated with their
location.
The following requirements for external type fuse shall be considered while selecting the
right size of fuse.
a) Ability to withstand the maximum discharge current from a healthy capacitor.
b) The fuse shall be capable of handling fault so as to avoid mechanical damage to
adjacent unit.
c) Discrimination between fuse protecting the faulty capacitor units and those
protecting healthy capacitor units.
d) The operated fuse shall have visual indication so that it can be deducted during
periodic inspection.
14. BUSHING:
Bushings shall be of porcelain and shall be jointed to the case by solder sealing or other
method which ensure as adequate permanent seal. Leads shall be brought out through
one piece porcelain bushing solder sealed to the case cover. Before final sealing the
entire assembly shall be vacuum impregnated with dielectric suitable for operation
application from –2.5ºC to 50ºC ambient temperature.
15 CONTAINER :
The container shall be made from sheet steel of thickness not less than 2 mm (14 SWG).
The outside of the capacitor containers and other structures should have smooth and tidy
look and should be quoted with weather proof, corrosion-resistant paint of grey shade.
The sheet container shall be suitably insulated from capacitor elements. Sufficient wall
insulation shall be provided.
16. LOSSES :
The capacitors offered should be built from best material obtainable and should develop
minimum losses.
For compression of various offers, equalisation charges on account of differences in
losses of capacitors in various offers shall be made at the rate of Rs. 66676/- per K.W.
Capacitor bank losses should be given at 50ºC. The successful bidder shall also be
penalised at the rate given, if during testing measured losses are found to be more than
the guaranteed losses.
17. DISCHARGED DEVICE :
Each capacitor unit shall be complete with suitable built in discharge resistors of
adequate thermal rating suitable for discharging the residual voltage to 50 Volt of less,
within 5 minutes ( preferably less than 5 minutes) after disconnection from the supply.
The recommendations of the bidders shall, however, be fully detailed out in the bid.
18. TERMINAL CONNECTORS :
Terminal connectors suitable for horizontal and vertical mounting and cable glands shall
be included in the scope of supply, wherever required.
19. RESIDUAL VOLTAGE TRANSFORMER :
The residual voltage transformer for the neutral voltage displacement relay shall be of
outdoor type naturally cooled, with a ratio of (11000/√3)/(110/√3)/190 Volt with VA
Burden of 100 and Accuracy class 3 as per IS:3156. It shall have primary connected in
star and secondary in open delta to energise neutral voltage displacement relay and to
discharge capacitor bank to voltage not exceeding 50 Volt in less than 5 minutes. All the
type tests report are required to be submitted along with bid in case already conducted.
Other wise all the type tests will have to be carried out free of cost in the presence of
DHBVN’S representative at the time of inspection.
20 11 kV 400 AMPS. LINE-CUM-EARTH SWITCH :
The isolator with earth switch shall be manually operated. Isolator should be provided
with ON and OFF indicators, arrangement for mechanical interlock and padlocking.
Isolator should be provided with auxiliary switches for their remote position indication on
the control panel. The isolator will be strictly as per ISS:9921. The supporting structures
are also required to be supplied for isolator, the rate may be quoted separately. All the
type test reports are required to be submitted along with bid in case already conducted
otherwise all the type tests will have to be carried out free of cost in the presence of
DHBVN’s representative at the time of inspection.
20(A) FITTINGS AND ACCESSORIES:
Any fittings or accessories which might have not being mentioned in the specification,
but which are usual or necessary for optional performance of the equipment are to be
provided by Contractor without extra cost. All equipment must be complete in all
respect, whether mentioned in the specification or not.
21. GUARANTEED DATA AND OTHER TECHNICAL PARTICULARS.
Guarantee and other technical particulars of capacitor banks, capacitor unit fuses, 11 kV
L&E switch and residual voltage transformer should be given in the form of guaranteed
technical particulars (Annexure-1). Any other particular considered by the supplier may
also be given in addition to those listed in the Appendices.
22 TESTS AND INSPECTION :
No material shall be dispatched without inspection and testing. The inspection may be
carried out by the purchaser at any stage of manufacture. The bidder shall grant free
access to the purchaser’s representative all (reasonable times during the manufacture of
equipment) covered by the specification.
Inspection and acceptance of any equipment under this specification by the purchaser
shall not relieve the supplier of his obligation of furnishing equipment. In accordance
with the specification and shall not prevent subsequent rejection, if the equipment is
found to be defective.
The supplier shall keep the purchaser informed in advance, about the manufacturing
programme. The supplier shall furnish to the purchaser works certificates at the time of
giving an inspection call for inspection.
22.1 TYPE TEST :
The equipment offered should be type tested. Type test report should not be more than
seven years old, reckoned from the date of bid opening in respect of the following tests,
carried out in accordance with ISS-13925/Part-I/98/IEC-871, from Govt./Govt. approved
test house, shall be submitted along with bid:
i) Thermal stability test.
ii) Partial discharge test.
iii) Self healing test.
iv) Impulse voltage best between terminals and container.
v) Capacitor discharge test.
vi) Endurance test.
The remaining type test report as per ISS-13925/Part-I/98/IEC-371 shall be submitted by
the successful bidder within three months from the date of placement of order. These
type test reports shall be from Govt. / Govt. approved test house and shall not be more
than seven years old reckoned from the date of placement of order. The failure to do so
will be considered as a breach of contract.
22.2 ROUTINE TESTS AND ACCEPTANCE TESTS :
All routine and acceptance tests as specified in relevant ISS/IEC of respective equipment
shall be carried out by the supplier in the presence of purchaser’s representative without
any additional payment.
22.3 ENDURANCE TESTING OF CAPAPCITOR UNIT :
The endurance test as per the procedure given in IEC-871.2 shall be conducted at CPRI
Bangalore test laboratory to ensure that the capacitor will withstand the service
conditions with a high degree of reliability. Test charges, if any, be quoted in the bid. In
case this test has already been got conducted on similar rating of units from of
Govt./Govt. approved Testing house, copies of test report shall be submitted by bidder
along with their bid. The purchaser reserves the right to carry out this test at Govt. Test
Agency on one or more units, if felt necessary.
23. DRAWINGS :
The bidder shall furnish one set of following drawings along with their bid to check the
suitability of their equipment:-
i) Outline general arrangement drawing of capacitor bank with detailed dimension
of capacitor bank / unit and structure with complete bill of material.
ii) Electrical layout drawing of Capacitor bank showing spacing of each equipment.
iii) Out line arrangement drawing of capacitor unit with detail dimension.
iv) Outline general arrangement drawing of 11 kV RVT and of 11 kV L&E switch.
v) Out line general arrangement drawing of 11 kV L&E switch and also its
schematic for electrical interlocking.
vi) Terminal connector drawings for Cap. Bank, RVT & L&E switch.
The successful bidder shall, within four weeks of placement of order, submit five sets of
final versions of all the above said drawings for purchaser’s approval. The purchaser shall
communicate his comments / approval on drawings to the supplier within a period of 4
weeks. The supplier shall, if necessary, modify the drawings and re- submit five copies
of the modified drawings for purchaser’s approval, within one week from the date of
purchaser’s comments. After receipt of purchaser’s approval the supplier shall, within
two weeks submit 20 prints along with reproducible of the approved drawings and
descriptive literature on capacitor & all allied equipments covered by the specification for
purchaser’s use.
23.1 The manufacturing of the equipment’s shall be strictly in accordance with the approved
drawings and no deviation shall be permitted without written approval of the purchaser.
23.2 Approval of drawings by purchaser shall not relieve the supplier of any of his
responsibility and liability for ensuring correctness and correct interpretation of the
drawings for meeting the requirement of the latest revision of applicable standard of
engineering, design and workmanship and latest revision of relevant standards at the time
of supply and purchaser shall have the power to reject any work or material which in his
judgement is not in accordance therewith.
24. DEPARTURE FROM SPECIFICATION :
Should the bidder wish to depart from the provisions of the specification either on
account of manufacturing practice or any other reasons, he should draw attention to the
proposed points of departure in his bid and submit such full information, drawing and
specification so that the merits of his proposal may be fully understood. The
specification shall be held binding unless the departure have been fully recorded as
required above.
25. PERFORMANCE :
The bidder shall submit details of similar static shunt capacitor banks and associated
equipment supplied by them which are in operation for the last three years along with
certificate from their customers in support of the satisfactory manufacture and operation
of the static shunt capacitor bank and associated equipment.
ANNEXURE ‘A’
GUARANTEED TECHNICAL PARTICULARS FOR SHUNT CAPACITOR & ALLIED
EQUIPMENT.
A SHUNT CAPACITORS
4. CAPACITOR BANKS :
i) Rated Voltage
ii) Maximum continuous over voltage
Rating as percentage of rated voltage.
iii) Nominal capacitance at 25ºC (Microfarad)
iv) Manufacturing tolerance on nominal ( +/- % )
capacitance value.
v) Variation of capacitance due to ( +/- % )
ambient temperature and load.
vi) Variation of capacitance due to ( +/- % )
loss of units / elements.
a) At alarm stage.
b) At trip stage.
vii) Number of unit in parallel per
phase per series section.
viii) Number of series section per phase.
ix) Connection symbol.
x) Rated output (KVAR)
xi) Rated current per phase ( Amp.)
xii) Withstand voltage of capacitor
Bank while switching ON/OFF. ( kV peak)
xiii) Power frequency withstand voltage (kV rms)
xiv) Creepage distance ( mm)
xv) Un-balance voltage in open delta of RVT
a) Under normal conditions
b) One Capacitor unit is out in a section
c) Two capacitor units are out in a section.
xvi) Total guaranteed losses at rated voltage (KW)
and frequency under stabilised condition.
xvii) Maximum residual voltage at the energisation (Volts)
xviii) Time taken in attaining the residual voltage. (Seconds)
xix) Annual Failure rate.
B- R.V.T. :
i) Name of the manufacturer / country.
ii) Type
iii) Rated voltage (kV)
iv) VA Burden Winding 1,Winding 2.
v) Connection
vi) Accuracy class.
a) Protection winding:
C- INSULATORS :
1. Make
2. Type
3. Reference standard.
4. Rated voltage.
5. No. of poles.
6. Rated normal current.
7. Rated peak withstand current. (KA)
8. Rated short time current for 1 sec. (KA)
9. i) 1.2/50 Micro-seconds impulse
withstand voltage positive
and negative polarity.
a) Across the isolating distance (kV rms)
b) To earth and between poles. (kV p)
ii) One minute power frequency
withstand voltage.
a) Across the isolating distance (kV rms)
b) To earth and between poles (kV rms)
10 Type of isolator.
11 Creepage distance.
12 Weight of complete isolator.
13 Type of operating mehanism.
14 Number of auxiliary contacts provided.
15 Total weight.
16 Overall dimensions.
ANNEXURE -’B’
SCHEDULE OF REQUIREMENT
SERVICE CONDITIONS:
The equipments to be supplied against this specification shall be suitable for
satisfactory continuous operation under the following tropical conditions.
Cores are stripped and brushed with neutral grease before setting up for crimping.
2
1.3 Type Tests and number of test samples.
For each of the specified tests, the number of samples as well as the test
sequences shall be :
1. Crimping ability – 2 pcs
2. Tensile Test – 2 pcs
3. Voltage Test – 2 pcs
4. Electrical Ageing Test – 6 pcs
5. Climatic Test – 2 pcs
Unless otherwise specified, tests shall be carried out at an ambient temperature
between 15 C and 35 C in a room whose relative humidity ranges between 25%
and 75% .
1.6 Requirements
The connector is type test approved if the tests results are satisfactory for all
samples. A retest is allowed only if the failure of a samples results from a wrong
installation or a cable failure.
Procedure
Crimping of the joint sleeve or terminal lug on the relevant cores(s) shall be carried
out using dies of a 9mm width with minimum compression strength 50KN.
Requirement
The two half-dies shall be in contact, which means that a 0.05mm thick guage
cannot be inserted between the half-dies.
Procedure
Connection shall be carried out using 9 mm wide dies with face to face distance of
17.3 +0.1 /-0.2 mm . The minimum strength to be applied is given in the table
below. The length of the cores shall be as given below.
3
The assembly is submitted to a tensile strength applied to the conductor. The
strength shall be increased at a rate between 1000N/min and 5000 N/min up to :
- for phases : 50% of the minimum load. This strength shall be applied for 1
min.
- for Neutral messenger : 65% of the minimum breaking load of the
messenger shall be applied for 1 hour.
- In both cases, the strength shall then be increased up to the minimum load
indicated above, and released.
1.10.1 Procedure
The samples are submitted to the climatic ageing test according to NFC 20-540
with following details :
- 6 weekly cycles are required at the enclosure temperature (70+2)0 C.
- As far as possible, the samples are installed so that the core is in an
horizontal plan and the lamp in a vertical plan. These two plans intersect in
the middle of the lamp and in the middle of the sample. The core is
orthogonal to the described vertical plan (see Figure 3).
1.10.2 Requirements
After the climatic ageing cycles and after a period of at least 24 h but not
exceeding 72 h at the laboratory atmosphere, the following tests are carried out :
a. Joint sleeves
The joint sleeves and the adjacent parts of core horizontally disposed are
covered without mechanical stress by 1 cm to 2 cm of metallic balls with
1.3mm to 1.7mm diameter. After at least 1 min. a 6kV voltage test is carried
out for 1 min between the core conductors and the metallic balls. The a.c.
voltage is applied to a rate of approximately 1 k V/s. The voltage generator
shall trip for a leakage current of (10.0 +5) mA.
b. No flashover shall occur (tripping of voltage generator).
4
1.10.3 Electrical ageing test
Procedure
Test procedures are defined in NF C 33-004
Class A : If the cross-section is greater than or equal to 35mm2.
Class B : If the cross-section is lower than 35mm2
Over currents are applied on connecting equipment installed on core of cross
section greater than or equal to 35mm2 only.
The test loops are set up as per type A as defined in NFC 33-044..
1.11 Marking
Each device unit shall bear permanently
- the trade mark or the logo of the manufacturer.
- the crimping position and order.
- The length to be stripped
- Size to be used
5
6. Endurance test under mech and thermal stress has been excluded due to
likely difficulty in testing in India.
This may be included after obtaining feedback from CPRI etc.
7. Corrosion test is not applicable for sleeves as per NFC 3-021, and is
therefore excluded
8. Acceptance tests are based on the requirements of NFC 33-021, but
sampling plan for Visual, dimensional and materials tests is proposed by
author of this proposal.
Typical Drawing:
6
______________________________________________________________________
TECHNICAL SPECIFICATION
FOR
Outdoors types Distribution Transformers of
i.e (25 kVA to 100 kVA) with CSP (completely self protected)
features
Page 1 of 27
1
______________________________________________________________________
1. Scope:
This specification covers, engineering, manufacture, assembly, stage testing,
inspection and testing before supply, ready to use besides delivery at site of oil immersed,
naturally cooled 3 phase 11 kV/433-250 V completely self protected Distribution
Transformers for outdoor use along with metallic enclosure housing LV bushing & MCCB
(if provided) with sealing facility.
1.1. It is not the intent to specify completely herein all the details of the design and
construction of equipment. However the equipment shall conform in all respects to
high standards of engineering, design and workmanship and shall be capable of
performing in continuous commercial operation upto the Bidder’s guarantee, in
manner acceptable to the purchaser, who will interpret the meanings of drawings
and specification and shall have the power to reject any work or material which, in
his judgment is not in accordance therewith. The offered equipment shall be
complete with all components necessary for their effective and trouble free
operation. Such, components be deemed to be within the scope of Bidder’s supply
interceptive of whether those are specifically brought out in this specification and /
or the commercial order or not.
1.2. Standard Ratings:
The standard Ratings shall be 25, 63 and 100 kVA.
2. STANDARDS:
2.1. The material shall conform in all respects to the relevant Indian /International
standard Specification, with latest amendments thereof some of them are listed below:
Title India standard International&
Internationally
recognized standard
Specification for power Transformer ISS-2026/1977 IEC 76
outdoor distribution Transformer ISS-1180
upto including 100 KVA
Specification for Copper wire rod IS-12444 ASTM B-49
Page 2 of 27
2
______________________________________________________________________
The bidder shall use ISS, however, where this standard is not available
corresponding IEC may be followed.
Material conforming to ISS or the internationally accepted standards, which
ensure equal or higher quality than the standards mentioned above, would also be
acceptable. In case the Bidders who wish to offer material conforming to the standards,
salient points of difference between the standards adopted and the specific standards
shall be clearly brought out in relevant schedule. Four copies of such standards with
authentic English translations shall be furnished along with the other.
3. SERVICE CONDITIONS:-
The Distribution Transformers & other equipment/material to be supplied against
this specification shall be suitable for satisfactory operation under the following climatic
Conditions as per IS-2026 (Part-I) latest revision
i) Location At various locations in the
state of Haryana
ii) Maximum ambient temperature (oC) 60
iii) Minimum ambient air temperature (oC) -5
iv) Maximum average daily ambient temperature 40
(oC)
v) Maximum yearly weighed average ambient 32
temperature (oC)
vi) Maximum altitude above mean sea level (m) 1000
vii) Minimum Relative Humidity (%) 26
viii) Maximum Relative Humidity (%) 95
ix) Average no of Rainy days/ year 120
x) Average annual rainfall 900 mm
xi) Maximum wind pressure 195 kg/m sq.
The equipment shall be for safe operation in moderately hot and humid tropical
climate, conducive to rust and fungus growth.
4. PRINCIPAL PARAMETERS:-
The transformers shall be suitable for outdoor installation with three phase
50 Hz, 11 KV system in which the neutral is effectively earthed and they should be
suitable for service under fluctuations in supply voltage upto plus 10 to minus 15%.
Sr. No. Item
1 Continuous rated 25 KVA 63 KVA 100 KVA
capacity
2 System voltage 12.5 KV 12.5 KV 12.5 KV
(max.)
3 Rated voltage HV 11 KV 11 KV 11 KV
4 Rated voltage LV 433-250 V 433-250 V 433-250 V
5 Line current HV 1.31 A 3.306 A 5.25 A
6 Line current LV 33.33 A 84.0 A 133.0 A
7 Frequency 50c/s +5% 50c/s +5% 50c/s +5%
8 No. of phases Three Three Three
9 Connection HV Delta Delta Delta
10 Connection LV Star Star Star
(Neutral (Neutral (Neutral
Brought Brought Brought
out) out) out)
11 Vector group Dyn-II Dyn-II Dyn-II
12 Type of cooling ONAN ONAN ONAN
13 changing Not Not Not
arrangement applicable applicable Applicable
Page 3 of 27
3
______________________________________________________________________
5. TECHNICAL REQUIREMENTS:
5.1. MATERIAL – CRGO METAL
5.1.1. The core shall be stack / wound type generally of high grade rolled grain
annealed steel lamination having low loss and good grain properties, coated
with hot oil proof insulation, bolted together and to the frames firmly to
prevent vibration or noise. The complete design of core must ensure
permanency of the core losses with continuous working of the transformers.
The value of the maximum flux density allowed in the design and grade of
lamination used be clearly stated in the offer.
The bidder should offer the core for inspection and approval by the purchaser
during manufacturing stage. Bidder’s shall give notice for inspection with the
following documents as applicable as a proof towards use of prime core material.
5.1.1.1. Invoice of the supplier
5.1.1.2. Mills Test Certificate
5.1.1.3. Packing List
5.1.1.4. Bill of Loading
5.1.1.5. Bill of entry certificate to customs
5.1.2. Core clamping for CRGO Stacked core.
5.1.2.1. MS channel shall be used on top and bottom
5.1.2.2. Core channel on LV side to be reinforced at equidistance, if
holes/cutting is done for LT lead in order to a avoid bending of
channel.
5.1.2.3. MS channel shall be painted with varnish or oil resistant paint
5.1.2.4. Clamping & Tie-rods shall be made of HT steel and shall be
parkarised.
Page 4 of 27
4
______________________________________________________________________
Page 5 of 27
5
______________________________________________________________________
Page 6 of 27
6
______________________________________________________________________
The above losses are maximum allowable and here would not be any
positive tolerance. Bids with higher losses than the above specified values would be
treated as non-responsive.
Bidders are requested to quote the price as FOR destination on standard
losses. The Bid will be evaluated on the basis of standard losses instead of Equated
capitalized cost. No benefit of low losses to the bidder in case the losses are less than
standards losses at any time.
5.5.1. Percentage Impedance:
The value of Impedance of transformer at 75 Deg. C shall be 4.5% subject to the
tolerance specified in the standard IS: 2026-1977.
5.5.2. Temperature rise
The temperature rise over ambient shall not exceed the limits described below:
i) Top oil temperature rise measured by thermometer: 35 deg. C
ii) Winding temperature rise measure by resistance: 40 deg. C
Bids not meeting the above limits of temperature rise will be treated as non-responsive.
5.6. PENALTY FOR NON PERFORMANCE:
5.6.1. Purchaser reserves the right to reject any transformer during the test at
supplier’s works, if it is found that actual measured losses are more than the
values quoted by the bidder
5.6.2. Transformer with temperature rise and impedance beyond the Guaranteed
values.
5.6.2.1. Purchaser reserves the right to reject any transformer during the test at
supplier’s works, if the temperature rise exceeds the guaranteed values.
5.6.2.2. Purchaser reserves the right to reject any transformer during the test at
supplier’s works, if the impedance values differ from the guaranteed values including
tolerance.
5.6.2.3. Purchaser also reserves the right to retain the rejected transformer and take it
into service until the Bidder replaces it with a new transformer at no extra cost.
The delivery as per contract will be counted when the new transformer as per
specification is provided by the manufacture.
5.7. INSULATION MATERIAL:-
5.7.1. Material:-Electrical grade insulation Kraft papers and press Boards of standard
should be used. For the use standard material the names of following firms have been
approved.
Sr. No. Name of insulating Name of the firms
material
1 Press board a. Senapathy whitely
b. Raman Board
2 Craft paper a. Ballarpur
b. Padamjee
c. Triveni
d. M/s Skytouch Tapes Ltd., Mumbai.
e. M/s KLIM Enterprises, Mumbai.
f. M/s Vijaya Mercantile Ltd. New
Delhi.
g. M/s Badri Enterprises, New Delhi.
Page 7 of 27
7
______________________________________________________________________
5.7.2 All spacers, axial wedges / runners used in windings shall be made of
pre-compressed pressboard-solid, conforming to type B 3.1 of IEC 641-3-
2. In case of cross-over coil winding of HV all spacers shall be properly
sheared and dovetail punched to ensure proper locking. All axial wedges/
runners shall be properly milled to dovetail shape so that they pass through
the designed spacers freely. Insulation shearing, cutting, milling and
punching operations shall be carried out in such out in such a way, that
there should not be any burr and dimensional variations.
5.8. TANK:- The rectangular transformer tank can be with radiator
fins/rounded or elliptical cooling tubes. The main tank of the
transformers shall be made of good quality steel having a minimum
thickness of sides of the tanks 3.15 mm and a minimum thickness of
5.0 mm for top and bottom plates. The tank shall be capable of
withstanding a pressure up to 0.8 kg/cm2 and (-) 0.3 kg/cm2 for 30
minutes and 10 minutes respectfully. The word “UHBVNL/DHBVNL
PROPERTY” shall be engraved on the top cover plate and side of
the tank body. No negative tolerance shall be allowed.
5.8.1. For Rectangular plain tank:-
5.8.1.1. The transformer tank shall be of robust construction rectangular in
shape and shall be built up of tested MS sheets.
5.8.1.2. The internal clearance of tank shall be such that, it shall facilitate easy
lifting of core with coils from the tank without dismantling L.V bushings.
5.8.1.3. All joints of tank and fittings shall be oil tight and no bulging should
occur during service. The tank design shall be such that the core and
windings can be lifted freely. The tank plate shall be of such strength
that the complete transformers when filled with oil may be lifted bodily
by means of lifting lugs. Inside of tank shall be painted with varnish/
Hot oil.
5.8.1.4. Manufacturer should carry out all welding operations as per relevant
ASME standards and submit a copy of the welding procedure
qualifications and welder performance qualification certificates to the
customer.
Page 8 of 27
8
______________________________________________________________________
5.8.1.5. The four walls of the tank shall be made of Two ‘’L’’ shaped sheets
(without joints) fully welded at the corners from inside so that the joint is
stronger due to V-shape welding fillet and also outside of the tank for
withstanding a pressure of 0.8 kg/cm2 for 10 minutes.
5.8.1.6. The tank shall be reinforced by welded angle on all the outside walls
on the edge of the tank to form two equal compartments. Permanent
deflection when the tank without oil is subject to a vacuum of 525 mm
of mercury for rectangular tank and 760 mm of mercury for round tank,
shall not be more than 4 mm in accordance with clause 22.5 of IS:1180
(Part-I/1989) upto 750 mm length and 6mm upto 1250 mm length. The
tank shall further be capable of withstanding a pressure of 0.8 kg/cm2
(g) and a vacuum of 0.3 kg/cm2 (g) without any deformation.
5.8.1.7. The radiators can be of tube type or fin or pressed type steel type to
achieve the desired cooling to limit the specified temperature rise. The
transformer shall be capable of giving continuous rated output without
exceeding the specified temperature rise Bidder shall submit the calculation
sheet.
5.8.1.8. Lifting lugs: 4 Nos. welded heavy duty lifting lugs of MS flat 8 mm thick
(min) suitably reinforced by vertical supporting flat welded edgewise below
the jug on the side wall.
5.8.1.9. Pulling lugs: 4 Nos. of welded heavy duty pulling lugs of MS plate 8
mm thick (mm) shall be provided to pull the transformer horizontally.
5.8.1.10. Top cover fixing bolts of G.I adequately spaced and 6mm Neoprene
bonded cork gaskets conforming to IS 42332 part-II shall be placed
between tank and cover. The bolts outside tank shall have 2 flat washers &
one spring washer.
5.8.1.11. Pressure release value as standard fitment shall be provided on the top
of tank of transformer which should operate at a pressure of 0.3 to 0.5 kg/cm2.
5.8.2. CONSERVATOR: -
On Transformers of ratings upto 100 KVA with rectangular plain tank
the provision of conservators is optional with the clarification that:-
• the transformer with conservator shall comply with IS: 1180 Part-I (Non
sealed type)
• the transformers without conservator shall comply with IS:1180 Part-II
(Sealed type)
When a conservator is provided oil gauge and the plain or
dehydrating breathing devise shall be fixed to the conservator which shall also be
provided with a drain plug and a filling hole (1¼”) normal size thread) with cover.
The capacity of a conservator tank shall be designed keeping in view the total
quantity of oil and its contraction and expansion due to temperature variations, In
Page 9 of 27
9
______________________________________________________________________
addition the cover of main tank shall be provided with an air release plug to enable
air trapped within to be released, unless the conservator is so located as to
eliminate the possibility of air being trapped within the main tank.
The inside diameter of the pipe connecting the conservator to the
main tank should be within 20 to 50 mm and it should be projected into the
conservator so that its end is approximately 20 mm above the bottom of the
conservator so as to create a sump for collection of impurities. The minimum oil
level (corresponding to -5 deg C) should be above the sump level.
5.9. SURFACE PREPARATION & PAINTING.
5.9.1. General
5.9.1.1. All paints shall be applied in accordance with the paint manufacturer’s
recommendations. Particular attention shall be paid to the following:
5.9.1.1.1. Proper storage to avoid exposure as well as extremes of
temperature.
5.9.1.1.2. Surface preparation prior to painting.
5.9.1.1.3. Mixing and thinning.
5.9.1.1.4. Application of paints and the recommended limit of time intervals
between coats.
5.9.1.1.5. Shelf life for storage.
5.9.1.2. All paints when applied in a normal full coat, shall be free from runs,
sags, wrinkles, patchiness, brush marks or other defects.
5.9.1.3. All primers shall be well marked into the surface, particularly in areas
where painting is evident, and the first priming coat shall be applied as
soon as possible after cleaning. The paint shall be applied by airless
spray according to manufacture’s recommendations. However,
whenever airless spray is not possible, conventional spray be used with
prior approval of purchaser.
5.9.1.4. The supplier shall prior to painting nameplates, lettering gauges sight
glasses, light fittings and similar such items.
5.9.2. Cleaning and Surface preparation
5.9.2.1. After all machining, forming and welding shall been completed, all steel
work surfaces shall be thoroughly cleaned of rust, scale, welding slag or
spatter and other contamination prior to any painting.
5.9.2.2. Steel surfaces shall prepared by Short blast cleaning or Chemical by
Seven Tank process including Phosphating to the appropriate quality.
5.9.2.3. The pressure and volume of the compressed air supply for blast cleaning
shall meet the work requirement and shall be sufficiently free from all water
contamination to ensure that the cleaning process is not impaired.
5.9.2.4. Chipping, scraping and steel wire brushing using manual or power driven
tools cannot remove firmly adherent mill-scale shall only be used where
Page 10 of 27
10
______________________________________________________________________
Page 11 of 27
11
______________________________________________________________________
5.10. BUSHINGS:
5.10.1. The bushings shall conform to the relevant standards specified and shall
be outdoor. The bushing rods and nuts shall be made of brass material 12 mm
diameter for both HT & LT. The HT bushings shall be fixed to the transformers on
side with straight pockets and in the same plane or the top cover but LT bushing
shall be provided on the side of the tank. The tests as per latest IS 2099 and
IS7421 shall be conducted on the transformer bushings.
Page 12 of 27
12
______________________________________________________________________
5.10.2. For 11 KV, 17.5 KV class bushings shall be used and for 0.433 KV, 1.1KV
class bushings shall be used. Bushings of plain shades as per IS-3347 shall
be mounted on the side of the Tank and not on top cover.
5.10.3. Dimensions of the bushings of the voltage class shall conform to the
Standards specified.
5.10.4. A minimum phase to phase clearance of 75 mm for LV (upto 1.1 KV
bushings) and 255 mm for HV bushings shall be obtained with the bushing
mounted on the transformer.
5.10.5. The bushings shall be fixed on sides with pockets in the same plane and
not on the top cover. Arcing horns or lightning arrestors shall be provided on
HV bushings.
5.10.6. Brazing of all inter connections; jumpers from winding to bushing shall have
cross section larger than the winding conductor. All the Brazers shall be
qualified as per ASME, Section-IX.
5.10.7. The bushings shall be of reputed make supplied by those manufacturers
who are having manufacturing and testing facilities for manufacture of
insulators.
5.10.8. The terminal arrangement shall not require a separate oil chamber not
connected to oil in the main tank.
5.10.9. The LV bushings & micro-processor based MCCB with time current
characteristics in compliance with IS:6600 (if provided) shall be housed
within the metallic enclosure with sealing arrangement so as to avoid any
possibility of tapping of supply from the bushing terminal. The enclosure
shall be made with sheet metal of thickness not less than 2mm and powder
coated. Enclosure shall have provision for pad locking arrangements.
5.11. Terminal connectors: The HV bushing stems shall be provided with suitable
terminal connectors so as to connect the jumper without disturbing the bushing
stem. Connectors shall be with eye bolts so as to receive 55 mm2 conductors for
HV. Terminal connectors should must be type tested as per IS : 5561.
5.12. Terminal markings
High voltage and Low voltage phase windings shall be marked both in the
terminal boards inside the tank and on the outside with capital letter IU, IV, IW and
low voltage winding for the same phase marked by corresponding small letter 2u,
2v, 2w. The neutral point terminal shall be indicated by the letter 2n.Neutral
terminal to be brought out and connected to local grounding terminal by an
Earthing strip.
5.13. FITTINGS:
The following standard fittings shall be provided.
5.13.1. Rating and terminal marking plates non-detachable
5.13.2. Ear thing terminal with lugs -2Nos.
Page 13 of 27
13
______________________________________________________________________
Page 14 of 27
14
______________________________________________________________________
Bolts or studs shall not be less than 6 mm in diameter except when used for
small wiring terminals.
All nuts and pins shall be adequately locked. Wherever possible bolts
shall be fitted in such a manner that in the event of failure of locking resulting in the
nuts working loose and falling off, the bolt will remain in position.
All ferrous bolts, nuts and washers placed in outdoor positions shall
be treated to prevent corrosion, by hot dip galvanizing, except high tensile steel
bolts and spring washers which shall be electro-galvanised / plated. Appropriate
precautions shall be taken to prevent electrolytic action between dissimilar metals.
Each bolt or stud shall project at least one thread but not more than three
threads through the nut, except when otherwise approved for terminal board studs
or relay stems. If bolts nuts are placed so that they are inaccessible by means of
ordinary spanners, special spanners shall be provided.
The length of the screwed portion of the bolts shall be such that no screw
thread may form part of a shear plane between members.
Taper washers shall be provided where necessary.
Protective washers of suitable material shall be provided front and back or
the securing screws.
2 No., anti-theft fasteners of steel on two diagonally opposite corners of the
tank shall be provided. All nuts & pins shall be adequately locked.
5.15. MOUNTING ARRANGEMENT :
The under base of all transformers shall be provided with two 75X40 mm
channels 460 mm long with holes to make them suitable for fixing on a platform or
plinth
5.16. OVERLOAD CAPACITY
The transformers shall be suitable for loading as per IS: 6600/ 1972
6. TESTS :
a) All the equipment offered shall be fully type tested by the bidder or his collaborator
as per the relevant standards including the additional type tests mentioned at
clause 6.2. The type test must have been conduced on a transformer of same
design. The Bidder shall furnish four sets of type test reports along with the offer.
Offers without type test reports will be treated as Non-responsive.
The type test certificates should not be more than three years old on the date of
bid opening.
b) Special tests other than type and routine tests, as agreed between
purchaser and Bidder shall also be carried out as per the relevant standards.
c) The requirements of site tests are also given in this clause.
6.1. ROUTINE TESTS:
6.1.1. Ratio, polarity and phase sequence.
6.1.2. No Load current and losses at service voltage and formal frequency.
Page 15 of 27
15
______________________________________________________________________
Page 16 of 27
16
______________________________________________________________________
6.3. TESTS AT SITE: The purchaser reserves the right to conduct all tests on
Transformer after arrival at site and the manufacturer shall guarantee test
certificate figures under actual service conditions.
6.4. ACCEPTANCE TESTS: The transformers shall be subjected to the following
routine/acceptance test in presence of purchaser’s representative at the place of
manufacture before dispatch without any extra charges. The testing shall be
carried out in accordance with IS: 1180 and IS: 2026 with latest amendments.
6.4.1. Checking of weights, dimensions, fitting and accessories, tank sheet
thickness, oil quality, material, finish and workmanship as per GTP/QA Plan
and contract drawings.
6.4.2. Physical verifications of core coil assembly and measurement of flux density
of one unit of each rating, in every inspection with reference to short circuit
test report.
6.4.3. All tests as specified in clause 6.1
6.4.4. One transformer per lot shall be tested at NABL accredited independent
laboratory for performance measurement at free of cost.
6.5. TOLERANCES: Unless otherwise specified herein the test value of
transformers supplied would be within the tolerance permitted in the relevant
standards. No positive tolerance is allowed on guaranteed 50% Load and 100%
Load losses.
7. INSPECTION:
7.1 STAGE INSPECTION
The purchaser's representative may carry out stage inspection of the transformers
during manufacturing / assembling stage. The purchaser shall have absolute right
to reject the raw material/component / sub assemblies or complete equipment not
found to be conforming to the requirement of specification or being of poor quality /
workmanship. The stage inspection will particularly include following tests / check
besides the general Routine tests to be conducted during manufacturing stages as
per manufacturer's standard practice.
a) Physical inspection / checking of winding insulating material, core material for
annealing and prime quality and other accessories /fitting of Transformer.
b) Measurement of Core area and flux density.
c) Verification of HV & L.V coils, conductor’s size, I.D., O.D., Axial length, Weight,
Insulation covering etc.
d) Measurement of thickness of tank plates (Top, bottom and sides) and to conduct
air pressure & vacuum tests as specified in the specification, to ensure the
adequate strength of the transformer tank body.
e) Sample testing of core material for checking specific loss and thickness of core
plates.
f) Visual and dimensional check during assembly stage of core.
g) Check for proper provisions of spacers and bracing outline drawing, provision for
all fittings, finishing etc. The purchaser at his option may collect the sample of the
following raw material / component for independent testing:
Page 17 of 27
17
______________________________________________________________________
a) CRGO Lamination - One specimen sheet of 300- 500 mm length and 50-75 mm
width ( for each lot)
b) HV Winding wire- 1250 mm length specimen for each type
c) LV Winding wire- 1250 mm length specimen for each type
d) Transformer oil - 2 samples of 5 Liters each
To facilitate stage inspection, the supplier should intimate complete schedule of
manufacturing programme of the transformers at least 15 days in advance to the
concerned purchasing authority. At least 25% of the transformers shall be offered
in the shape of finished core - coil assembly. The inspecting officers during the
course of stage inspection may seal these core-coil assemblies.
e) The manufacturing program shall not be interrupted in case purchaser's
representative does not reach within seven days of the date of intimation.
7.2 All tests and inspection shall be made at the place of manufacturer and
unless otherwise especially agreed upon the manufacturer and the
purchaser at the time of purchase. The manufacturer shall afford the
inspector representing the purchaser all reasonable facilities, without charge
to satisfy him that the material is being furnished in accordance with
specification.
The bidder shall give 15 days (for local supplies) and 30 days (in case of
foreign bidders) advance information to enable the purchaser to depute his
representative for witnessing acceptance routine tests.
The manufacturer shall provide all services to establish and maintain quality
of workman ship in his works and that of his sub-contractors to ensure the
mechanical/electrical performance of components, compliance with
drawings, identification and acceptability of all materials, parts and
equipment as per Nigam intends to purchase only High Quality material. For
this purpose stringent testing of the material can be done. Inspection can be
got done from third party Inspection agency or from Nigam’s own officers.
Nigam reserves the right of 100% testing of the transformers. The details of
source of material shall be supplied duly filled as per Annexure-III.
Page 18 of 27
18
______________________________________________________________________
Page 20 of 27
20
______________________________________________________________________
Page 21 of 27
21
______________________________________________________________________
ANNEXURE-1
Page 22 of 27
22
______________________________________________________________________
Page 23 of 27
23
______________________________________________________________________
Page 24 of 27
24
______________________________________________________________________
ANNEXURE-II
ADDITIONAL DETAILS
SI. No. Description
1. Core Grade
2. Core diameter ( mm)
3. Gross Core area (cm)
4. Net Core area (cm)
5. Flux density (Tesla)
6. Wt. of Core (kg.)
7. Loss per kg. of Core at the
Specified Flux density (Watts)
8. Core window height
9. Center to center distance of the core (mm)
10. No. of LV. Turns
11. No. of HV turns
12. Size of LV Conductor bare/ covered (mm)
13. Size of HV conductor bare/ covered (mm)
14. No. of parallels
15. Current density of LV winding amps/sq.mm.
16. Current density of HV winding amps/ sq.mm
17. Wt. of the LV winding for Transformer kg.
18. Wt. of the HV winding for Transformer kg.
19. No. of LV Coils/phase
20. No. of HV coils/phase
21. Height of LV Windings mm
22. Height of HV Windings mm
23. ID/OD of LV Winding mm
24. ID/OD of HV winding mm
25. Size of the duct in LV winding mm
26. Size of the duct in HV winding mm
27. Size of the duct between HV & LV mm
28. HV winding to LV winding clearance mm
29. HV winding to tank clearance mm
30. Calculated impedance %
31. HV to earth creepage distance mm
32. LV to earth creepage distance mm
Page 25 of 27
25
______________________________________________________________________
ANNEXURE-3
SOURCE OF MATERIALS/PLACES OF MANUFACTURE TESTING AND
INSPECTION
SI. No. Item Source of Material Place of Place of testing and Manufacture
inspection
1. Laminations
2. Aluminium Conductor
3. Insulated winding wires
4. Oil
5. Press Boards
6. Kraft Paper
7. MS Plated / Angles/ Channels
8. Gaskets
9. Bushing HV/ LV
10. Paints
Page 26 of 27
26
______________________________________________________________________
ACRONYMS
--------------------------------------------------------------------------------------------------------------
--
Reference Abbreviations Name and Asset
--------------------------------------------------------------------------------------------------------------
--
IEC International Electro Technical
Commission Bureau Central de la
Commission Electro Technique
International, Rue de verembe
Geneva, Switzerland.
Page 27 of 27
27
EErq Efurgr Ese-arcrr ffi fu+gsr ftarff
UTTT$. DI*ESTF ilTETiIfir BT.trI ATIBiTT TIGJ*H
s*
FOR
1. SCOPE:
2. STANDARDS:
3. CLIMATIC CONDITIONS:
The equipment is required to operate satisfactorily under the
following site conditions:
3.1 Max. Ambient Temperatrtre 60 0c
3.2 tvln. Amolent I emperature -5 0c
3.3 Max.Retatiffi lOOo/o
3.4
26%
3.5 Avgrage no. of rainv davs pei aniG Nearly 120 davs
3.6 Average annual rainfall 900 mm
3.7 {rvgrage numoer of clust storm days per annum 35
3.8 lsokeraunic level 45
3.9 _l4qx Wind pressure 195K9 / sq. meter
3.10 Altitude above mean sea level Less than 1000 meter
The 1 1KV switchgear panels shall comprise of 1 1KV Vacuum Type circuit
relay panel, instrument panel and instrument transformers (complete in breakers, control
suitable for indoor.use. The equipment shall be totally enclosed in all respect) etc.,
metal clad cubical, dust.
and vermin proof with necessary isolation arrangLment. Each panel shall be easily
extensible on either side and should be compl-ete with n".""".ry internal
connections, small wiring, L.T. fuses and supporting framework with
to secure it""pp",
floor' Each panel shall be provided with space h6ater, door switchbolts
with
to the
lamps and 15 -
Ampere power receptacle.
\f/ S\/
, "'t' .+ti, l'-.1J$,;figi;l:1;r3'1;$1t1:'1SS$;,*''
The vacuum type circuit breaker shall be tri! free and the breaker control shall be draw out
type. The VCBs shall be suitable for operation from 24 DC auxiliary supply. The operating
mechanism shall be motor operated spring charged type. There shall be provision (s) for
manual charging of closing spring and emergency hand trip. The motor used for the
purpose will be suitable for 240 V AC. All auxiliaries shall be supplied from AC and
arrangement shall be made for automatic switch over to DC in case of AC supply failure.
The operating mechanism shall works satisfactorily between 85 -110o/o of rated supply
voltage.
5.2INSTRUMENT PANELS:
Each unit shall have its own instrument panel provided at the top & complete with small
wiring connections from relays, instrument transformers, metering instruments, indicating
instruments, selector switches & circuit breaker control switch. All wiring shall be carried out
by using stranded single annealed copper conductor, insulated with poly vinyl chloride
insufation suitable for 650 V service and in accordance with lS: 732 - 1963. CT/PT circuits
shall use wire of not less than 2.s mm2 cross -
sectional area whereas
control/alarm/supervision circuit shall use wire of not than 1.5 mm2 cross - sectional area.
All wires will be continuous from one terminal to the other and also will have no T - Junction
enroute. The connections shall be securely made with the help of suitable connecting lugs
duly crimped on the copper conductor. The meters and relays shall be mounted in a
convenient position so as these are readily accessible for inspection or repair. The terminal
board provided in the instrument panel of VCBs will be made of molded dielectric having
brass studs, washers, holding nuts & locking nuts. All holding nuts shall be secured oy
locking nuts. The connection studs shall project 6 mm from the lock nut surface. No OTHER
TYPE OF TERMINAL BORAD lS ACCEPTABLE. The panels shall have a degree of
protection of lP - 4X. The leads from the metering CTs shall be directly terminated at TTB
and there from at the KWH meter with a provision to seal TTB and KWH meter. The said
. CT leads will be effectively concealed to prevent their tempering enroute as well as at TTB.
Similarly PT leads from secondary box of the PT to TTB & there from to energy meter,
including inter panel PT leads, will also be effectively concealed to prevent their tempering.
The mode and extent of concealing the metering leads of CTs & PTs, to prevent their
tempering (by unscrupulous operating personnel), will be discussed and mutually agreed
upon with the successful bibber (s). TTB, used on the instrument panel, should be suitable
for front connections.
Earthing of current free metallic parts or metallic bodies of the relays switches mounted on
the instrument panel and metal enclosed switchgear shall be done by a suitable sized
copper conductor. Eafth bus made of 25 X 3 mm bare copper flat will be extended through
entire length of 1'1KV switch-board with suitable provision to connect it to the sub-station
earth at the extremities. The earthing arrangement will meet with the requirements laid
down in lS:3427, read with its latest amendments.
The secondary voltage & current rating of the instrument transformers shall match with the
metering and protective equipment. The CTs shall have ratio & accuracy class as
mentioned in the schedule of requirement. The CTs shall be wound/ring type in accordance
with their ratings. The terminal boards, associated with REF CTs &Over Current / Earth
Fault Protection CTs will be of disconnecting type, having short circuiting facility & thus
facilitate secondary 1e..gting of concerned protective relay without disturbing the associated
small wiringf- Interchangeability of housing of CTs, from one panel to another, must be
ensured. A resin cast potential transformer of ratio (11000d3X110{3) volts, having 1q) VA
output per phase with accuracy class 0.5 as per tss: 3156 (part-il) - 196s, shalt be
provided on the incoming side of each panel set and shall be star - star connected. lt shall
be provided with HT ahd LT fuses. i
:Effi , l'trpl.r, $ ''ft-@['€@
r,H,& E#ffi ,f,lt$lffirlBl B![r. !frB*s r{I€drit
The neutral point, of star connected secondary windings of instrument transformers, shall
be earthed to the main earth bus referred to in concluding paragraph of clause 5.12.
Multiple earthing of any instrument transformers shall be avoided.
All the panels shall be provided with insulpted copper bus bar of 1200 Amps current rating
for all switches boards. These shall be cohnected in a separate moisture and vermin proof
sheet metal chamber. The bus - bar connection & insulator supports shall be mechanically
strong & rigidly supported so as to withstand the stresses, generated by vibrations, variation
in temperature and severe short circuits. The bus - bar should be in horizontal formations to
enable DHBVN to connect with existing Circuit Breaker Panel Board without any difficulty in
matching. The Adopter Panel, if required to match the loose panelwith the existing panels,
shall be prepared / fabricated as per site conditions by the Nigam at its own cost.
The bus - bar shall be supported on insulator at short intervals, keeping adequate clearance
between the bus bar and earth. The bus - bar chamber shall be provided with inspection
cover with gaskets & bus bar shutters. Provision shall be made for future extension of bus
bar & switch board.
The temperature rise, of current carrying parts, shall not exceed the permissible limits
above the ambient temperature as per relevant standards (latest edition).
These shall comply with latest version of lS: 2099 in all respects.
All disconnectors (isolators) of 11KV VCBs & interlocks between different pieces of
apparatus, provided for reasons of safety & for convenience of operation of switchgear,
shafl meet with the requirement of lS 3427 - 1969 read with its latest amendment.
Each 11 KV incoming VCBs shall be provided with cable boxes, complete with jointing kits
& sealing material for receiving 3 Core, 11 l(/ XLPE type outer PVC sheathed cable of size
630 mm" (Panel with CT ratio 900-450/5-5-5-5A for 12.5 MVA PTR,600-300/5-5-5-5 A for
.16MVA pTR). The outgoing 11KV VCBs, including 11KV capacitor controlling VCB, shall be
provided with cable boxes suitable to receive 3 Core, 11 KV XLPE type outer PVC
sheathed cables of size up to 300 mm' (Panel with CT ratio 400 - 200/5-5-5A). The 11 KV
station transformer VCB shall be provided with cable boxes (Epoxy Resin Type ) suitable to
receive 3 Core, 1 1KV XLPE type outer PVC sheathed cables of size up to 50 mm2 (Panel
with CT ratio 60-30/5-54). Each cable box shall have vertical entry from below. These cable
boxes shall be complete in all respects, including cable glands of requisite size. lt is clarified
that one jointing kiUcable box is required to connect one 11KV XLPE cable with one 11KV
VCBs. No separate (extra) jointing kit is required.
5.9 RELAYS:
All relays shall be numeric (with RS -Port & SCADA compatible) except the relays for DC
failure supervision alarm, annunciation scheme, shall be draw out type and mounted
"l"rm,
on the front of each circuit breaker control panel in a flush pattern case. All relays shall be
provided with testing facilities. In case the same cannot be provided within the relay, a
separate test block ind test plugs shall be provided. The relay adjustment devices shall be
easily accessible when the relays have been mounted-on the panels'
I
u',, .{11'. .;. Sfi;;|,' :f r:. lil.ii r", r rtii:;i:.1.il&,"''.
ffi ,€,enqr ,Efuqr. fiffi"fiq-p1'
S,f,.-,Sl[, Ert ' 8.l[4 vtf{frT- ryI"if,{U
The relays shall conform to the latest edition of lS: 3231. The relays shall not operate at a
current equal to or less than the setting. The minimum operating current shall not exceed
110% of the setting. The coils & CT circuit of the relay should be suitable to withstand the
minimum operating current continuously, in case the minimum operaiing current is around
110o/o. The relays covers and cases shall be dust tight, moisture and vermin proof.
Operation Indicators shall be provided oh all relays and on their immediate auxiliaries for
indication, regarding type of fault and phase involved. lt shall be possible to reset the
operation indicator, without opening the relays covers. All relays shall be tested at
manufacturer's works and test certificates got approved, before dispatch of material. The
bidder shall submit the descriptive and pictorial literature, in quadruplicate, in respect of
each relay proposed, along with the tender. All relays in the specification shall be suitable
for 24V DC auxiliary voltages.
The incoming feeder panel shall be provided with one alarm bell and alarm indicating
auxiliary relays. lt shall indicate tripping of circuit breaker, under fault conditions, with the
help of auto trip lamp and alarm. lt shall be complete with the indicating lamp and push
button switches for'Accepts" and "Resets" alarm.
.l
1KV switches panels, covered by this specification, shall be provided with the following
lamp indication:
position of the
For monitoring the trip circuit healthy conditions, both in open and close
circuit breakei t tto. irip circuit supervision relay is proposed. In casb of trip circuit being
by audio - visual annunciation' lt
faulty, the operation of ifris relay shall be accompanied
strati Oe possible to silence the buzzer by pressing the accept push button but the lamp
shall continue to glow till the fault has been attended'
Circuit breaker 'Close' & 'Open' lamps shall be wired so as to be on 240 V AC
under
'normal' condition.
The 11 KV lncoming VCB will be provided with a digital Voltmeter along with
a selector
switch. The selector switch shalJ facilitate the measurement of Phase - Phase and Phase -
Neutralvoltage, one by one. The static voltmeter shall be rated for 110 V (Phase - Phase
"A" classification with
Voltages). The instrument shall be static type of industrial grade
accuracy class 1.0 & shallconfirm to lS: 1248 (1968)'
ammeter, .rated
Each of the 11 KV VCB Panel will be provided with a suitably sealed digital
the CTs, shall be included
t* snrp (additional oLts; ir any, required to cover all the taps of
of phase currents' The
at the time of bidding) & a seletior switch, facilitating measurement
having accuracy class
instrument shall be oi it"tic type, industrial grade "A" classification,
1.0 & shall conform to lS: 1248 (1968)
with a three
Each of the 11 lry VCB, except the 11KV capacitor VCB, will be equipped
phage four wire static tri-vector meter (confirming to Technical specification no' s - 45 / SE
for 11 KV Feeders) &
, P & D / XEN / DD _ ||; Static cT / PT operated Tri-vector.Meter
suitable for three phase four wire unbalanced load conditions with accuracy
Mf 1.5 ".tO
h4v|ngRS-232,RS-485PortforDat4.-lonning/Data-Down|oadingfaci|ity.Thetri-
Ftr.q "Effi frry#" fir-q
rilffi fiffi:IIS I Brlttt: Ttftlf mqnti
vector meter shall be rated for 5 Amp CT secondary and 110/{3 V (phase to neutral),
available from 11 KV PT mounted on the incoming VCB.
Each of the 11KV VCB will be provided with a static power factor meter. The static PF
meter, having range of 0.5 lag - one - 0.5 lead, shall be of static type; suitable for use on
three phase three wire unbalanced system. lt shall be rated for 5A CT secondary & 110
Volts (Phase - Phase Voltage), having accuracy class 1.0 with digital display.
NOTE: Routine test certificates of all the indicating & integrating instruments will be
submitted along with the routine test certificates of 11 KV switchgear.
5.13 PADLOCK:
Padlock or some other arrangement of approved design shall be provided for locking the
equipment in 'OFF' position. All locks shall have two keys, in addition to the master key
which shall be provided for each panel set. Approved racks or cabinets, for accommodation
of padlocks and keys while in use, shall be provided along with each panel set and it shall
be suitably labeled and numbered for identification.
In addition to the auxiliary contacts required for normal operation, each circuit breaker shall
be provided with 2 NO & 2NC spare auxiliary contacts duly wired up to terminal block.
Suitable arrangement should be provided to make it possible for the Nigam to close 11 KV
VCB from the remote end, through a communication system to be provided by the Nigam,
in case the following conditions are satisfied.
#r
"
Suitable arrangement should be provided to make it possible for the Nigam to trip 11 KV
VCB from the remote end, through a communication system to be provided by the Nigam,
in case the breaker is on & certain preset conditions, to be decided later on.
6. PROTECTION SHEMES:
Each incoming panelshallbe provided with a single pole restricted earth fault relay, suitable
for 5 Amps C.T. Secondary, with a setting range of 10% to 4oo/o of 5 Amp (strictly in steps of
5%). The relay shall be housed in draw out flush pattern case.
The backup protection shall be in the form of combined over current and earth fault relay,
consisting of two over current & one earth fault unit which shall be triple pole having inverse
definite minimum time (l.D.M.T.) characteristics with a 3110 time current curve i.e. the relay
operating time shall be 3 Second at 10 times the plug setting with T.M.S = 1. The two outer
elements of the relay shall be arranged for over current protection and shall have a setting
range of 5O - 200o/o of 5 Amps, adjustable in suitable equal steps by means of plug boards
The central element shall be used for earth fault protection with a setting range of 20 - 80%
of 5 Amps, adjustable in suitable equal steps by means of a plug board. Each of the three
elements shall be fitted with shunt reinforcing unit with hand reset operation indicator.
Two nos. over current high set instantaneous elements, having setting range of 500 -
2000o/o of 5A and one no. earth fault high set instantaneous element, having setting range
of 200 -800% of 5A and adjustable in suitable steps, shall be wired in series with the IDMT
type over current and earth fault relay respectively . The high set instantaneous element
shall have low transient over reach with a high pickup / drop out ratio. The high set
instantaneous element shall be so wired so as to take this element (instantaneous) out of
circuit, if so desired by the Nigam, at any time during the operation of equipment.
The backup protection shall be in the form of combined over current and earth fault relay,
consisting of two over current & one earth fault unit which shall be triple pole having inverse
definite minimum time (l.D.M.T.) characteristics with a3l1O time current curve i.e. the relay
operating time shall be 3 Second at 10 times the plug setting with T.M,S = 1. The two outer
elements of the relay shall be arranged for over current protection and shall have a setting
range of S0 - of 5 Amps, adjustable in suitable equal steps by means of plug boards.
20oo/o
The central element shall be used for earth fault protection with a setting range o'f 20 - 8oo/o
of 5 Amps, adjustable in suitable equal steps by means of a plug board. Each of the three
elements shall be fitted with shunt reinforcing unit with hand reset operation indicator.
TWO nos. over current high set instantaneous elements, having setting range of 500 -
2ililgo/o of 5A and one no. earth fault high set instantaneous element,
having setting range
Of 200 -800% of 5A and adjustable in suitable sleps, shall be wired
in series with the IDMT
type over current and earth fault relay respectively . The high set instantaneous element
ihalt hav" low transient over reach w1h a high pickup / drop out ratio. The hig[ set
,element"(instantaneous) out of
instantaneous element shall be so wired so as to take thls
circuit, if so desired by thre Nigam, at any time during the operation of,equipment.
t getv
,-q,f.+ , E ltll &Efd 'fiffiqrry. 'frqlw
tm-+if,t, D#ffi,Se$-4{_rfi s[u $$tdq l{Gtu,
The backup protection shall be in the form of combined over current and earth fault relay,
consisting of two over current & one earth fault unit which shall be triple pole having inverse
definite minimum time (l.D.M.T.) characteristics with a3110 time current curve i.e. the relay
operating time shall be 3 Second at 10 times the plug setting with T.M.S = 1. The two outer
elements of the relay shall be arranged for over current protection and shall have a setting
range of 20 - 8Oo/o of 5 Amps, adjustable ifi suitable equal steps by means of plug boards.
The central element shall be used for earth fault protection with a setting range of 10 - 40%
of 5 Amps, adjustable in suitable equal steps by means of a plug board. Each of the three
elements shall be fifted with shunt reinforcing unit with hand reset operation indicator.
Two nos. over current high set instantaneous elements, having setting range of 200 - 800%
of 5A and one no. earlh fault high set instantaneous element, having setting range of 100 -
400o/o of 5A and adjustable in suitable steps, shall be wired in series with the IDMT type
over current and earth fault relay respectively . The high set insiantaneous element shall
have low transient over reach with a high pickup / drop out ratio. The high set instantaneous
element shall be so wired so as to take this element (instantaneous) out of circuit, if so
desired by the Nigam, at any time during the operation of equipment.
The 11KV capacitor control panel shall be provided with the following protection.
6.4.1 The backup protection shall be in the form of combined over current and earth fault
relay, consisting of two over current & one earth fault unit which shall be triple pole having
inverse definite minimum time (l.D.M.T.) characteristics with a 3l1O time current curve i.e.
the relay operating time shall be 3 Second at 10 times the plug setting with T.M.S = 1. The
two outer elements of the relay shall be arranged for over current protection and shall have
a setting range of 50 - 2OO% of 5 Amps, adjustable in suitable equal steps by means of plug
boards. The central element shall be used for earth fault protection with a setting range of
20 - 80o/o of 5 Amps, adjustable in suitable equal steps by means of a plug board. Each of
the three elements shall be fitted with shunt reinforcing unit with hand reset operation
indicator.
6.4.2For the protection of the bank against unbalancing, an inverse time Neutral Voltage
displacement relay having setting 5.4,7.5, 12.5 and 20 volts and suitable for 190 V AC
operation shall be provided. The relay will be fed from the open delta connected secondary
of residual voltage transformer (Discharge coil) and shall have suitable Setting range to
afford adequate protection to the capacitor bank against unbalancing.
6.4.3 For over voltage protection of the capacitor bank, over voltage relay; having setting
range of 110o/oIo 170%in steps of 10% & rated for 110 Volts A.C. supply, obtainable from
the secondary of 11KV Bus P.T's mounted on 1 1KV Incoming Panel shall be provided'
6.4.4 For under voltage protection of the capacitor bank, under voltage relay; having setting
range of 50% to g0*n steps of 10o/o & rated for 110 Volts A.C. supply, obtainable from the
sec-ondary of 1 1KV Bus P.T's mounted on 1 1KV Incoming Panel shall be provided.
6.4.5 1O minute adjustable timer contact shall be wired in series with the closing circuit so
as to ensure that the capacitor bank is fully discharged, once it has been switched OFF.
7. FREQUENCY OF OPERATION:
Mosly the VCB panels are expected to be used for feeding heavily concentrated load. As
such they are expected to be subjected to frequent tripping due to overload & earth fault.
Any specific design features, adopted or proposed to be provided, by the bidder in the
switchgear on this account should be indicated clearly in the tender.
t
wV
* r'r+:.r::i$:."r.,i-,jr., . . ..,:: ,::t*@.ii,;: - .,
8. TESTS:
with ls: 131 18 /1991 (Latest
All type tests & routine tests shall be carried out in accordance
version thereof).
ThePT,sandCT,sshal|besubjectedtoroutinetests,asspecifiedinthe|atestversionof
if so desired by the
relevant ISS in the presence of purchaser - authorized representative'
such as relays'
purchaser. The routine test cerlificates of the bought out component
switches, indicating instruments & KWH metering will also
be presented to DHBVN's
the same to the purchaser along with his
authorized inspecting officer who will forward
be got approval from
. inspection report for the main equipment. All test reports should
purchaser before dispatch of equipment'
*p#r*xvx
purchaser's comments. The modified drawings will be approved within 15 days of their
receipt. After receipt of approved drawings, a set of reproducible of approved drawings &
flve sets of all the approved drawings & operating manuals containing, erection, operJtion
&maintenance instructions per 11KV switchboard shall be supplied tobCwt / MM, DHBVN,
Hisar for use by various agencies of the purchaser. However, one set of drawing and
operating manual will be dispatched along with each 11KV switchboard. The ltfV
switchgear will not be fabricated without getting the drawing approved from the purchaser.
The bidder shall separately quote for a set of special tools, if so required, for erection and
maintenance of the switchgear panels.
Should the tender wish to deviate from the provisions of the specifications, either on
account of manufacturing practice or any other reasons, he shall draw attention to the
propoied point of deviation in the tender and submit such full information, drawing and
specification so that merits of his proposal may be fully understood. The specification shall
be held binding unless the deviations have been fully accepted as requested.
1 2. TRAINING FACILITIES:
These particulars shall be furnished strictly as per Annexure 'A' in duplicate. Any deviation
from this specification shall clearly be brought out separately.
The bidder shall state the place of manufacture, testing and name of the manufacturer of
the various items, included in his tender.
The make(s) of relays / other fitments may be restricted to, as depicted in Annexure 'C'.
16.INSPECTION:
lnspection of material and supervision of tests, in accordance with the relevant ISS (as
mentioned in clause 2 above), approved drawings and schedules shall be carried out by the
purchaser or his duly authorized representative. The material shall be inspected and tested
before dispatch by authorized representative of the Nigam. The manufacture shall provide
to the inspecting officer all reasonable facilities, without charge, to satisfy him that the
material is being furnished in accordance with the specifications.
The purchaser or his authorized representative shall have access, at all reasonable
time, to the manufacture's works to inspect and witness the tests of the equipment
manufactured.
The purchaser has the right to have the tests carried out, at cost of supplier, by an
independent Govt. Agency wherever there is a dispute regarding the quality of material
supplied. /
10
\,y \$/
px'/
6
r.qtr{ ,F..&Fu,T €,futolf, €r-ota
'uiT-{,t*, E+ffiF' r4Jtn$;f,fr BUr{ y{.rffrr l{rciln
23. GUARANTEEAA'ARRANTY:
Vr/ \-, {0 -/
n X9./
Y/
Supeiintendin g Engineer/P&D
Cum-Member Secretarv CSC
DHBVN Hisar.
12
6:tr{ ,E&LE-rr: ffffi frFqq1
FtIiit, D+ !g ,tiiff*fiir" 'B[ilt !ffifir fie*[
be rejected and bidder shall arrange to supply the replacement within thirty (30) days of
such detection at his cost including to & fro transportation. In addition to this penalty
@10% of cost of the inspected lot of material shall be imposed.
23. GUARANTEEMARRANTY:
days from the date of issue of notice in respect thereof; failing which, the purchaser
reserves the right to dispose of defective product in any manner considered fit by him
(Purchaser), at the sole risk and cost of the supplier. Any sale proceeds of the defective
product after meeting the expenses incurred on its custody, disposal handling etc., shall
however be credited to the supplier's account and set off against any outstanding dues of
the purchaser against the supplier. The warranty for 30/36 months shall be one time.
W
7
Supeiintending Engineer/P&D
Cum-Member Secretary CSC
DHBVN Hisar.
II
EIir +ft't{ eruq fudi ft-d'-{
tr l , iE :B,*{,.1, {ffiF trrqnii
ANNEXURE: A
SWITCHGEAR PANELS
A. CIRCUIT BREAKERS:
1. Maker's name and country of manufacture.
2.Type
3. Nominal system voltage
4. Highest system voltage
5. Frequency
6. Nominal current rating
6.1 At Ref. Ambient temp. as per relevant standard
6.2 At site conditions
1"3
VU
ffiffi EnEr 4fuff 1sfr-drclr flrq$ fu€or ft-drd ,ffi
lrrr*B E*fistr rr*cf*nr* B*,rr !f1s61s tre.*H 1.p.*ruttn
ffi
C RELAYS
1. Type and make
2. Time setting range
3. Other details like No. of auxiliary contacts
4. Standard to which conform
5. No. & Auxiliary contacts :
D BUS BAR
1. Material
2. Normalcurrent rating in amp.
3. Normalarea (mm )
4. Shape
5. Type of Insulation
E. VOLTAGE TRANSFORMER
1. Name of manufacture
2. Whether imported or indigenous
3. Manufacturer's type, normal amps and rupturing capacity for vacuum bottles used for
Incoming panel
4. -----------------do--- for outgoing panels
5. ------------------do--- for capacitor control panel
6. Degree of vacuum inside the vacuum interrupters
7. Short time rating of vacuum bottles
8. Number of full short circuit operations as per test duly 1 to 5 of IEC-56, which the vacuum
bottles offered can safely withstand
9. Whether the vacuum bottles used on incoming and outgoing panels are same or
different.
10. Whether the operating mechanism is imported or indigenous.
brv
^ o/ \- /
L4
,-tr , 'ffffi,'frtd@I. fu6ffi ffi,
:r {# r-fifl{g+WA glil.t r!tr-tti{ rier' #*iftwu
{,{'
ANNEXURE.B
SCHEDULE OF REQUITEMENT
,3.1No.3phasestar/starconnectedbusbartyperesincastdrawoutvo|tage
output per phase with
transiormer?t"ti"'iiloool.teyiir06/gl volts and 100 VA
per lS: abiO lpartlf f)-1965-complete in all respect with HT
and
ctass 1 O limiting
"t"rr""V "s
plugs and sockeis for HT& LT copper connectors' current
LT fuses,
""f"ti"fi
resistances.
a. 1 No. 230 V.AC. panel space heater'
b. 2 set of vermin and dust proof fitments'
c. '1 earthing set for earthing the breakers individually'
6. One No. single pole restricted E/F relay with setting of 10-40o/o of 5 Amps and complete
with a tuned 50c/s circuit.and stabilizing resistance mounted in draw-out type ilush
pattern case with a provision of inter-tripping the circuit breaker.
7. 4No. of230 volt A.C. indicating lampl with fittings to indicate breaker open, breaker
closed auto trip and spring charged.
a. 1 indicating lamp with fitting and push button switch to indicate trip healthy. Trip
Circuit supervision scheme and D.C. fail scheme as per foregoing specification.
8.8.4 P.T. leads should come direct from 11KV P.T. Secondary to avoid any
tempering in between. lset of triple pole combined O/C and E/F IDMTL relay with
two outer elements for O/Q protection having setting of 50-2OO% of 5 Amps and
central elements for EIF protection with setting range of 20-80o/o of 5 Amps mounted
in draw-out type flush pattern case. A set of triple pole combined over current & earth
fault instantaneous high set relays with two elements for over current protection
having a setting range of 500% to 2000o/o of 5 Amps and the central element for
earth fault protection having a setting range of 200Vo-800o/o of SAmps. The relay shall
have low transient over reach with a high pick up/drop off ratio. Relay will be
connected in series with the triple pole combined over current and earth fault relay
referred to above and shall be so wired as to take this element (instantaneous) out if
so desired by the purchaser at any time during operation of equipment.
8.9 3Nos. 230 Volts AC indicating lamps with fittings to indicate Breaker Open,
Breaker CLOSED and AUTO TRIP.
8.10 1No of.24 Volts DC indicating lamp with tittings and push button switch to
indicate TRIP CIRCUIT HEALTHY
10.0{ 1 No. Triple pole 400 Amps, 350 MVA, 11KV circuit breaker fitted with arc
control device, interlock arrangement, auxiliary switches, isolating contacts, alarm
contacts, emergency hand trip device, and mechanical ON & OFF indication and
under voltage release.
10.02 1 set of 1200 A bus bars.
10.03 lset of isolating plugs & sockets.
10.04 1 set of single-phase cluster type isolating contacts.
10.05 1 No. Trifurcating main cable box for reception of 3 core XLpE up to
mmz
185 size and complete with wiping glands and clamps.
10.06 3 Nos. CTs of ratio 200-100-50-/54 with 15 VA output burden of S P 10
accuracy for protection 1 No. 230 V AC panel Space heaters.
10.07 1 set vermin and dust proof fitment.
10.08 1 Instrument panel mounted on top and equipped as 6elow:-
10.08.01 1 No. suitably sealed CT operated static Ammeter of 5 Amp., with digital
display.
10.08.02 1 No. 3-way ON/OFF Ammeter selector switch.
10.08.03 3Nos. 230 VAC indicating lamps with fitting to indicate breaker open,
breaker closed and auto trip.
10.08.04 1No.24 VDC indicating lamps with fitting to indicate trip heatthy.
10.08.05 1 No. Breaker control Switch.
10.08.06 1 set of triple pole combined over current & earth fault IDMT relay with two
outer elements for O/C protection having sefting of 5O-200% of 5 AMPS, and central
elements for earth fault protection with setting range of 2O to 8oo/o of 5 amps
mounted in drawn out type flush pattern case.
10.08.07 One Set of inverse time Neutral (Voltage) displacement relay suitable for
190 V AC operations for protection of the bank against unbalancing.
10.08.08 One set of over voltage relay with setting range 110% to 170% along with
auxiliary transformers (for external mounting) having ratio 1211115 to 127 (in Steps
of 1 Volt) to be used for compensating the error of over voltage relay.
10.08.09One no. under Voltage Relay with setting range of 50o/o lo 90oh.
10.08.10 10 Minute adjustable timer to ensure that the capacitor bank is fully
discharged once it has been switched off before it can be switched ON again.
10.08.11 The capacitor controlling breaker should be suitable to meet all conditions
required for capacitor operation and should be suitable for controlling capacitive
current up to 400 Amps at 11 KV which is equivalent to 7.5 MVAR approx. 110V
supply shall be available from existing (11000/{3y(1104/3) Volts PT's.
1 Relays ALSTOM/EASUN
REYRO LLE/AB B/S I EM EN S/JVS
II
-W-W'
:E.-ffi €1,t. t ffi' 'fif- -s*rr €iEil
:tttf*n, Dffrgdlu. rtfiqlfitt Bel|.r atf-BAtr rue*ri
#**"$,?
18
1
INDEX
1 SCOPE
This specification covers the design, manufacture, assembly, testing at
manufacturer’s works, supply & delivery at site and performance
requirements of 9KV, (5KA) gapless zinc oxide, polymeric housed
station type outdoor surge arrestors as specified hereunder and in the
schedule of Quantity/ Price Schedule. Any equipment not specially
mentioned but required for satisfactory operation of surge arrestors in
the opinion of the tenderer must be included in the scope of bidder.
2 DEFINITIONS:-
3 SYSTEM PARAMETERS:-
The arrestors must be able to operate under the system parameters
mentioned in this specification as below:-
4 PRODUCT REQUIREMENTS:-
4.1 POLYMER HOUSING MATERIAL:-
The polymer material used for the arrestor must be tracking and
erosion resistant, stabilized against UV Radiations.
11KV
Creepage Length 300mm (Minimum)
Tensile Strength 1000 Nm (Minimum)
Cantelever Load 150Nm (Minimum)
Torsion 30Nm (Minimum)
11KV
Arrestor Max. Cont. Operating 8 KV rms
Voltage (Uc)
Arrestor Rated Voltage (Ur) 10KV rms
Nominal Discharge Current (In) 5 KA Peak
Long Duration Discharge Class 200A,2000µs
Max Residual Voltage (@ In) 26.1 KV Peak
Lightening Impulse 1,2/50µs 95 KV Peak
Withstand Voltage
Wet Power Frequency Withstand 38 KV rms
Voltage
4
4.4 ACCESSORIES:-
4.4.1 MOUNTING:-
Arrestors should be suitable for Vertical and Horizontal Mounting as
required.
4.4.2 TERMINALS:-
Terminals should be made of M10 Bolts to allow the connection of line
and ground leads.
5 TESTING:-
6 MARKING:-
Each arrestor shall be provided with a name plate bearing the
following information as a minimum, in English language:-
- Arrestor Type
- IEC Standard
- Continuous operating voltage Uc
- Rate Voltage Ur
- Nominal Discharge Current
- Rated Short Circuit Current
- Manufacturer’s Name or Trade Mark
- Year of Manufacturer
7 QUALITY ASSURANCE:-
The manufacturer should be certified in accordance with ISO 9001.
The supplier has to provide a copy of a valid certificate along with his
quote.
Relevant Manuals shall be presented upon request to purchaser/
utility.
9 COMPLETENESS OF EQUIPMENT
Any fitting, accessories or apparatus which may not have specifically
been mentioned in these specification but which are otherwise usual
or necessary in the equipment of similar plant shall be included in the
contract and shall be supplied by the contractor without extra
charges. All plants and equipment shall be complete in all details,
whether such details are mentioned in the specification or not.