FH II - Vs - Ramset - Spatec Plus#SA SA#FH II-S Spatec Plus#gvz##C2025#carb#dry#ap Ap
FH II - Vs - Ramset - Spatec Plus#SA SA#FH II-S Spatec Plus#gvz##C2025#carb#dry#ap Ap
1.43.1.0
Database version
2016.12.21.10.48
Date
22.12.2016
Product
performance
comparison
versus
no data available Design under fire exposure acc. TR020 no data available
no data available Design under seismic actions acc. TR045, no data available
performance category C1
no data available Design under seismic actions acc. TR045, no data available
performance category C2
Temperature ranges
Product
performance
comparison
versus
FH II 10 S 40 6.08 -20.2% +25.2% 7.62 50 Spatec Plus M6 Concrete cone Steel failure
failure
FH II 12 S 60 11.18 +17.4% -14.8% 9.52 60 Spatec Plus M8 Concrete cone Pullout failure
failure
FH II 15 S 70 14.08 +0.0% +0.0% 14.08 70 Spatec Plus M10 Concrete cone Concrete cone
failure failure
FH II 18 S 80 17.21 +0.0% +0.0% 17.21 80 Spatec Plus M12 Concrete cone Concrete cone
failure failure
FH II 24 S 100 24.05 +0.0% +0.0% 24.05 100 Spatec Plus M16 Concrete cone Concrete cone
failure failure
FH II 28 S 125 33.61 +0.0% +0.0% 33.61 125 Spatec Plus M20 Concrete cone Concrete cone
failure failure
FH II 32 S 150 44.18 - XXXXXXXXXXXXXXXXXXXXXX Concrete cone
failure
FH II 10 S 40 3.57 +50.0% -33.3% 2.38 50 Spatec Plus M6 Pullout failure Pullout failure
FH II 12 S 60 5.71 +0.0% +0.0% 5.71 60 Spatec Plus M8 Pullout failure Pullout failure
FH II 15 S 70 7.62 +0.0% +0.0% 7.62 70 Spatec Plus M10 Pullout failure Pullout failure
FH II 18 S 80 11.90 -2.9% +3.0% 12.27 80 Spatec Plus M12 Pullout failure Concrete cone
failure
FH II 24 S 100 17.14 +0.0% +0.0% 17.14 100 Spatec Plus M16 Concrete cone Concrete cone
failure failure
FH II 28 S 125 23.96 +0.0% +0.0% 23.96 125 Spatec Plus M20 Concrete cone Concrete cone
failure failure
FH II 32 S 150 31.49 - XXXXXXXXXXXXXXXXXXXXXX Concrete cone
failure
FH II 12 S 60 18.86 +1.2% -1.2% 18.63 60 Spatec Plus M8 Steel failure Steel failure
FH II 15 S 70 28.17 +0.4% -0.4% 28.06 70 Spatec Plus M10 Pryout Steel failure
FH II 24 S 100 48.10 +0.0% +0.0% 48.10 100 Spatec Plus M16 Pryout Pryout
FH II 28 S 125 67.22 +0.0% +0.0% 67.22 125 Spatec Plus M20 Pryout Pryout
FH II 24 S 100 34.29 +0.0% +0.0% 34.29 100 Spatec Plus M16 Pryout Pryout
FH II 28 S 125 47.92 +0.0% +0.0% 47.92 125 Spatec Plus M20 Pryout Pryout
Valid for the smallest anchor size Valid for the smallest anchor size
Remarks
Spatec Plus
-
Design method ETAG 001, Annex C, Method A
Anchor loading The given permissible or recommended loads in this document do not consider any reduced
measures e.g. spacings or edge distances. It is assumed that the member thickness is much
enough that spalling will not occure.
For chemical anchors the cleaning of the drill hole must be done by means of the best possible
cleaning method which is given in the assessment.
Advantage fischer
Advantage Ramset
Identical values